HomeMy WebLinkAbout2010 FMC RESULTS MONITORING SYSTEM CERTIFICATION Pass
For Use By All Jurisdictions Within the State of California
Authority Cited: Chapter 6 7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be
prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided
to the tank system owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems
within 30 days of this date.
A. General Information IIIIIIIIIIIIIIIIIIII 01
Facility Name: #347 Fastrip#26 IE Bldg.No.:
Site Address: 2698 Oswell Street City: Bakersfield Zip: 93306
Facility Contact Person: Omero Garcia Contact Phone No.: 661-393-7000
Make/Model of Monitoring System: Gilbarco EMC Date of Testing/Servicing: 8/11/2010
B. Inventory of Equipment Tested/Certified
es
Check the appropriate box to care specific equipment innpecteWseniced:
Tank ID: 12000 gal.Regular 1 Tank ID: 12000 gal.Regular 2
[X] In-Tank Gauging Probe. Model:847390-107 [x] In-Tank Gauging Probe. Model:847390-107
[x] Annular Space or Vault Probe. Model:794390-420 [x] Annular Space or Vault Sensor. Model:794390-420
[x] Piping Sump/Trench Sensor(s). Model:794380-208 [x] Piping Sump/Trench Sensor(s). Model: 794380-208
❑ Fill Sump Sensor(s) Model: ❑ Fill Sump Sensor(s). Model:
[J Mechanical Line Leak Detector. Model:FX1V ❑ Mechanical Line Leak Detector. Model: NIA
❑ Electronic Line Leak Detector. Model: ❑ Electronic Line Leak Detector. Model:
U Tank Overfill/High Level Sensor. Model:847390-107 U Tank Overfill/High Leval Sensor. Model: 847390-107
❑ Other(specify equip.type and model in Sec. E on Pg.2) ❑ Other(specify equip.type and model in Sec. E on Pg.2)
Tank ID: 12000 gal.Super Tank ID: 12000 gal. Diesel
[x] In-Tank Gauging Probe. Model:847390-107 [x] In-Tank Gauging Probe. Model: 847390-107
[x] Annular Space or Vault Sensor. Model-794390-420 [x] Annular Space or Vault Sensor. Model: 794390420
[X] Piping Sump/Trench Sensor(s). Model:794380-208 [x] Piping Sump/Trench Sensor(s). Model: 794380-208
❑ Fill Sump Sensors(s). Model: ❑ Fill Sump Sensor(s). Model:
[xx] Mechanical Line Leak Decector. Model:FX1V [x] Mechanical Line Leak Detector. Model: FX1DV
❑ Electronic Line Leak Detector. Model: ❑ Electronic Line Leak Detector. Model:
[x] Tank Overfill/High Level Sensor. Model:847390-107 U Tank Overfill/High Level Sensor.Model:847390-107
❑ Other(specify equip.type and model in Sec. E on Pg.2) ❑ Other(specify equip,typs and model in Sec. E on Pg.2)
Dispenser ID: 1 &2 Dispenser ID: 3&4
Ex-1 Dispenser Containment Sensor(s). Model: 794380-208 [x] Dispenser Containment Sensor(s). Model: 794380-208
[X] Shear Valve(s). [x] Shear Valve(s).
❑ Dispenser Containment Float(s)and Chain(s). ❑ Dispenser Containment Float(s)and Chain(s)
Dispenser ID: 5&6 Dispenser ID: 7&8
[x] Dispenser Containment Sensor(s). Model: 794380-208 [x] Dispenser Containment Sensor(s). Model: 794380-208
[x] Shear Valve(s). U Shear Valve(s).
❑ Dispenser Containment Float(s)and Chains(s). ❑ Dispenser Containment Float(s)and Chain(s).
Dispenser ID: North Transition Sump Dispenser ID: South Transition Sump
[x1 Dispenser Containment Sensor(s). Model: 794380-208 [X] Dispenser Containment Sensor(s). Model: 794380-208
❑ Shear Valve(s). ❑ Shear Valve(s).
❑ Dispenser Containment Float(s)and Chain(s) ❑ Dispenser Containment Float(s)and Chain(s).
If the facility contains more tanks or dispensers,copy this form. Include information for every tank and dispenser at the facility.
C. Certification -I certify that the equipment identified in this document was inspected/services in accordance with the
manufacturers'guidlines.Attached to this Certification is information(e.g.manufacturers'checklist)necessary to varify that
this information is correct and a plot plan showing the layout of monitoring equipment.For equipment capable of enerating
such reports,I have attached a copy of the report; (check all that apply) ❑x S tem Set-up [x]Al his ry report
Technician Name(print): Bryan A Self Signature: l/`-
Certification No: 837501 License No:8049
Testing Company Name: Confidence UST Services,Inc. Phone No: 800-339-9930
Site Address: 2698 Oswell Street,Bakersfield,CA 93306 IIIIIIIIIIIIIIIIIIII _Date of Testing/Servicing: 8111/2010
02
IE
D.Results of Testing/Servicing
Software Version Installed: 327.04
Complete the following checklist:
L] Yes ❑ No* Is the audible alarm operational?
• Yes No* Is the Visual alarm operational?
• Yes No* Were all sensors visually inspected.
x Yes ❑ No* Were all sensors installed at the lowest point of secondary containment and positioned so that other
equipment will not interfere with their proper operation?
Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment(e.g.modem)
Hx N/A operational?
[XI Yes ❑ No* For pressurized piping systems,does the turbine automatically shut down if the piping secondary
❑N/A containment monitoring system detects a leak,fails to operate, or is electrically disconnected?If yes:
which sensors initate positive shut-down? E Sump/Trench Sensors[x]Dispenser Containment Sensors
Did you confirm positive shut-down due to leaks and sensor failure/disconnected? ❑ Yes; L] No;
❑ Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device(i.e.no
L]N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visual and audible at
the tank fill point(s)and operating properly?If so,at what percent of tank capasity does the alarm
trigger? 9p %
❑ Yes* U No Was any monitoring equipment rep ace ? If Yes, identify specific sensors,probes, or other equipment
replaced and list the manufacturer name and model for all replacement parts in Section E, below.
❑ Yes* X No Was liquid found inside any secondary containment systems designed as dry systems?
❑Product; ❑ Water. If yes,describe causes in Section E,below.
x * I Was monitoring system set-up reviewed to ensure proper settings?
*In Section E below,describe how and when these deficiencies were or will be corrected.
E. Comments:
r
F. In-Tank Guaging/SIR Equipment: ❑ Check this box if tank guaging is used only for inventory control.
❑ Check this box if tank guaging or SIR equipment is installed.
This section must be completed if in-tank guaging equipment is used to perform leak detection monitoring.
Complete the following checklist:
Fxj Yes ❑ No* Has all input wiring been inspected for proper enter and term ination,including testing for ground faults?
x Yes 7 No* Were all tank guaging probes visually inspected for damage and residue buildup?
x Yes No* Was accuracy of system product level readings tested?
x Yes No* Was accuracy of system water level readings tested?
L[x] Yes No* Were all probes reinstalled properly?
L] Yes ❑ No* Were all items on the equipment manufacturer's maintenance checklist completed?
* In the Section H,below,describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD): ❑ Check this box if LLD's are not installed.
Complete the following checklist:
Lx] Yes ❑ No* For equip. start-up or annual equipment certification,,was a leak simulated to varify LLD performance?
(Check all that apply) Simulated leak rate: [X]3 g.p.h.: 00.1 g.p.h.; 00.2 g.p.h.;
[X] Yes No* Were all LLD's confirmed operational and accurate within regulatory requirments?
x Yes No* Was the testing apparatus properly calibrated?
Yes No* For machanical LLD's,does the LLD restrict product ow if it detects a leak?
N/A
❑ Yes No* For electronic LLD's,does the turbine automatically shut off if the LLD detects a leak?
Cx] N/A
❑ Yes No* For electronic LLD's, does the turbine automatically shut off if any portion of the monitoring system is
[x] N/A disabled or disconnected?
❑ Yes No* For electronic LLD's,does the turbine automatically shut off if any portion of the monitoring system
[X] N/A malfunction or fails a test?
❑ Yes D No* For electronic LLD's,have all accessible wiring connections been visually inspected?
[X] N/A
x Yes No Were all items on the equipment manufacturer's maintenance checklist completed?
* In the section H,below,describe how and when these deficiencies were or will be corrected.
H. Comments:
FASTRIP 347 COMMUNICATIONS SETUP
2698 OSWELL ST. SYSTEM SETUP - - - - - - - - - - - -
BAK.ERSFIELD.CA93306 -AUG 11. 2010 9:11
661-872-8781
PORT SETTINGS:
AUG 11 , 2010 9: 10 AM
SYSTEM UNITS COMM BOARD : 1 (ED1M )
RS-232 SECURITY
U.S. CODE : DISABLED
SYSTEM STATUS REPORT SYSTEM LANGUAGE
ENGLISH COMM BOARD 2 (RS-232)
ALL FUNCTIONS NORMAL SYSTEM DATE/TIME FORMAT BAUD RATE 9600
MON DD YYYY HH:MM:SS xM PARITY NONE
INVENTORY REPORT FASTRIP 347 STOP BIT — 1 STOP
2698 OSWELL ST. DATA LENGTH: 8 DATA SCURITY
T 1 :UNL 1 BAKERSFIELD.CA93306 -ODES: DISABLED
VOLUME - 8349 GALS 661-872-8781
ULLAGE = 3651 GALS COMM BOARD 3 (RS-232)
90% ULLAGE= 2451 GALS SHIFT TIME 1 6:00 AM BAUD RATE 9600
TC VOLUME = 8235 GALS SHIFT TIME 2 DISABLED PARITY NONE
HEIGHT = 63.01 INCHES SHIFT TIME 3 DISABLED STOP BIT 1 STOP
WATER VOL = 0 GALS SHIFT TIME 4 DISABLED DATA LENGTH: 8 DATA
WATER - 0.00 INCHES TANK PER TST NEEDED WRN RS-232 SECURITY
TEMP = 79.5 DEG F DISABLED CODE : DISABLED
TANK ANN TST NEEDED WRN
T 2:DIESEL DISABLED AUTO TRANSMIT SETTINGS:
VOLUME = 6580 GALS LINE RE-ENABLE METHOD
ULLAGE = 5420 GALS PASS LINE TEST AUTO LEAK ALARM LIMIT
90% ULLAGE= 4'220 GALS i DISABLED
TC VOLUME = 6492 GALS AUTO HIGH WATER LIMIT
HEIGHT = 51 .65 INCHES LINE PER TST NEEDED WRN DISABLED
WATER VOL = 21 GALS DISABLED AUTO OVERFILL LIMIT
WATER = 0.99 INCHES LINE ANN TST NEEDED WRN DISABLED
TEMP = 89.6 DEG F DISABLED AUTO LOW PRODUCT
PRINT TC VOLUMES DISABLED
ENABLED AUTO THEFT LIMIT
T 3:PNL DISABLED
VOLUME x 6460 GALS AUTO DELIVERY START
ULLAGE _ .5540 GALS TEMP COMPENSATION DISABLED
90°5 ULLAGE= 4340 GALS VALUE (DEG F ) : 60.0 AUTO DELIVERY END
TG VOLUME_ 6338 GALS STICK HEIGHT OFFSET DISABLED
HEIGHT - = O::_(3'9_INCHES DISABLED AUTO EXTERNAL INPUT ON
WATER VOL = 0 GALS ULLAGE: 90% DISABLED
WATER = 0.00 INC_,HES AUTO EXTERNAL INPUT OFF
TEMP = 87.0 DEG F H-PROTOCOL DATA FORMAT DISABLED
HEIGHT AUTO SENSOR FUEL ALARM
DAYLIGHT SAVING TIME DISABLED
T 4:UNL 2 ENABLED AUTO SENSOR WATER ALARM
VOLUME = 6815 GALS START DATE DISABLED
ULLAGE = 5185 GALS MAR WEEK 2 SUN AUTO SENSOR OUT ALARM
90% ULLA(:'E= 3985 GALS START TIME DISABLED
TC VOLUME = 6729 GALS 2:00 AM
HEIGHT = 53.13 INCHES END DATEEK 1 SUN
WATER VOL = 63 GALS END TIME
WATER = 2.07 INCHES 2:00 AM
TEMP = 77.8 DEG F
RE-DIRECT LOCAL PRINTOUT
x * n END * * * DISABLED
E RS-232 END OF MESSAGE
URO PROTOCOL PREFIX
S
DISABLED
SYSTEM SECURITY
CODE : 000000
MAINTENANCE HISTORY
DISABLED
TANK CHART SECURITY
DISABLED
CUSTOM ALARMS
DISABLED
MASS/DENSITY
DISABLED
T 2:D1ESEL T 3:PNL
IN SETUP PRODUCT CODE 2 PRODUCT CODE 3
THERMAL COEFF : .000450 THERMAL COEFF : .000700
TANK. DIAMETER 96.00 TANK DIAMETER 96.00
T 1 :UNL 1 TANK PROFILE 1 PT TANK PROFILE VOL : 12000
PRODUCT CODE 1 FULL VOL 12000
THERMAL COEFF : .000700
TANK DIAMETER 96.00
TANK PROFILE 1 PT FLOAT SIZE: 4.0 IN. FLOAT SIZE: 4.0 1N.
FULL VOL 12000 WATER WARNING 2.0 WATER WARNING = 2.0
HIGH WATER LIMIT: 3.0 HIGH WATER LIMIT: 3.0
FLOAT SIZE: 4.0 IN. MAX OR LABEL VOL: 12000 MAX OR LABEL VOL: 12000
MATER WARNING �,p OVERFILL LIMIT 90% OVERFILL LIMIT 10800
HIGH WATER LIMIT: 3.0 HIGH PRODUCT 1080 HIGH PRODUCT 95%
MAX OR LABEL VOL: 12000 11400
OVERFILL LIMIT 90% DELIVER! LIMIT 11450 DELIVERY LIMIT 1800
10800 1800
HIGH PRODUCT 95% LOW PRODUCT 1200 LOW PRODUCT 1200
11400 LEAK ALARM LIMIT: 99 LEAK ALARM LIMIT: 99
DELIVERY LIMIT 15% SUDDEN LOSS LIMIT: 99 SUDDEN LOSS LIMIT: 99
1600 TANK TILT 0.00
TANK TILT 0.00 PROBE OFFSET 0.00
LOW PRODUCT 1200 PROBE OFFSET 0.00
LEAK ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 99 SIPHON MANIFOLDED TANKS SIPHON MANIFOLDED TANKS
TANK TILT 0.00 Tit: NONE Tit: NONE
PROBE OFFSET 0.00 LINE MANIFOLDED TANKS LINE MANIFOLDED TANKS
Tit: NONE Tit: NONE
SIPHON 11AN I FOLIiED TANKS
Tit: NONE LEAK MIN PERIODIC: I% LEAK MIN PERIODIC: 1%
LINE MANIFOLDED TANKS 120 120
Ttt: NONE PERIODIC TEST TYPE PERIODIC TEST TYPE
STANDARD STANDARD
LEAK MIN PERIODIC: I% PERIODIC TEST FAIL PERIODIC: TEST FAIL
120 ALARM DISABLED ALARM DISABLED
PERIODIC TEST TYPE
STANDARD GROSS TEST FAIL GROSS TEST FAIL
PERIODIC TEST FAIL ALARM DISABLED ALARM DISABLED
ALARM DISABLED PER TEST AVERAGING: OFF PER TEST AVERAGING: OFF
GROSS TEST FAIL TANK TEST NOTIFY: OFF TANK TEST NOTIFY: OFF
ALARM DISABLED
PER TEST AVERAGING: .'.:.OFF TNK TST SIPHON BREAK:OFF TNK TST SIPHON BREAK:OFF
TANK TEST NOTIFY: OFF DELIVERY DELAY 1 MIN PUMPVT THRESHOLD 10.00%
' PUMP THRESHOLD 10.00%
TNY TST SIPHON BREAK:OFF
DELIVERY DELAY 1 MIN
PUMP THRESHOLD 10,00%
T 4:UNL 2 LIQUID SENSOR SETUP
PRODUCT CODE 4 PUMP SENSOR SETUP
THERMAL COEFF : .000700 - - - - - - - - - - - - _ _ _ _ _ _
TANK DIAMETER 96.00 L 1 :UNL 1 STP - - _ - -
TANK PROFILE PT TRI-STATE (SINGLE FLOAT) S 1 :UNL 1
FULL LE LL VOL 12000 CATEGORY STP SUMP TANK 0: 1
DISPENSE MODE:
FLOAT SIZE: 4.0 IN. STANDARD
L 2:UNL 1 ANN L
S 2:pN
WATER WARNING 2.0 TRI-STATE (SINGLE FLOAT) TANK N 3
HIGH WATER LIMIT: 3.0 CATEGORY ANNULAR SPACE DISPENSE MODE:
MAX OR LABEL VOL: 12000 STANDARD
OVERFILL LIMIT 90% L 3:DSL STP
10800 TRI-STATE( SINGLE FLOAT)
114400
HIGH PRODUCT 95% CATEGORY : STP SUMP
DELIVERY LIMIT 15%
1800 L 4:DSL ANN
LOW PRODUCT 1200 TRI-STATE (SINGLE FLOAT)
LEAK ALARM LIMIT: 99 CATEGORY : ANNULAR SPACE
SUDDEN LOSS LIMIT: 99
TANK TILT 0.00 OUTPUT RELAY SETUP
PROBE OFFSET 0.00 L 6:PNL ANN - - - - - - - - - - - "
TRI-STATE (SINGLE FLOAT) R 1 :UNL 1
SIPHON MANIFOLD£D TANKS CATEGORY ANNULAR SPACE IN TYPE:
LINE NONE S PUMP CONTROL OUTPUT
L NAN I FOLDED TANK, ri: 1
T#: NONE
L 7:UNL 2 STP TANK
PERIODIC: E ( FLOAT)
LEAK MIN 1 CATEGORY : STP SUMP
LIQUID SE 1VSOR ALMS
L 1 :FUEL ALARM
PEkIOUIC TEST TYPE 120 L 7:FUEL ALARM
STANDARD L B:UNL 2 ANN L 9:FUEL ALARM
TRI-STATE (SINGLE FLOAT) L11 :FUEL ALARM '
PERIODIC TEST FAIL CATEGORY ANNULAR SPACE L12:FUEL ALARM
ALARM DISABLED L 1 :SENSOR OUT ALARM
GROSS TEST FAIL L 7:SENSOR OUT ALARM
ALARM DISABLED L 9:DISP 1-2 L 9:SENSOR OUT ALARM
TRI-STATE (SINGLE FLOAT) LIO:SENSOR OUT ALARM
PER TEST AVERAGING: OFF CATEGORY : DISPENSER PAN L11 :SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L I :SHORT ALARM
TANK TEST NOTIFY: OFF L 7:SHORT ALARM
L10:DISP 3-4 L 9:SHORT ALARM
TIVK TST SIPHON bREF,k;_:OFF TRI-STATE (SINGLE FLOAT) L 10:SHORT ALARM
DELIVERY DELAY 1 MIN CATEGORY : DISPENSER PAN L11 :SHORT ALARM
PUMP THRESHOLD 10.00%
L12:SHORT ALARM
ISD SITE ALARMS
LII :DISP 5-6 ISD GROSS PRES FAIL
TRI-STATE (SINGLE FLOAT) ISD DEGRD LEAK FAIL
CATEGORY : DISPENSER PAM
ISD VP PRES FAIL
ISD VP STATUS FAIL
L12:DISP 7-8 ISD HOSE ALARMS
TRI-STATE (SINGLE FLOAT) ALL:GROSS COLLECT FAIL
CATEGORY : DISPENSER PAN ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
LEAK TEST METHOD
TEST ON DATE. : ALL TANK L13:TRANS SUMP NO.
FEB 6, 2007 TRI-STATE (SINGLE FLOAT)
START TIME : DISABLED CATEGORY DISPENSER PAN
TEST RATE :0.20 GAL;HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED L14:TRANS SUMP SO.
TRI-STATE (SINGLE FLOAT)
LEAK TEST REPORT FORMAT CATEGORY DISPENSER PAN
NORMAL
L15:PNL STP
TRI-STATE (SINGLE FLOAT)
CATEGORY STP SUMP
TYPE:
PUMP CONTROL OUTPUT SMARTSENS7R SETUP EVR/ISD SETUP
TANK #: 3 - - - - - - - - - - - -
s 1 :PS 3-4 EVk TYPE: VACUUM ASSIST
LIQUID SENSOR ALMS CATEGORY VAPOR PRESSURE VACUUM ASSIST TYPE
L 9:FUEL ALARM ,. HEALY VAC
2:
L10:FUEL ALARM s FM 1-2
Lll :FUEL ALARM CATEGORY AIR FLOW METER NOZZLE A/L RANGE
L12:FUEL ALARM s 3:FM 3-4 MAX: 1 .15 MIN: 0.95
L15:FUE ALARM CATEGORY AIR FLOW METER
L 9:SEN.�Ok OUT ALARM VAPOR PROCESSOR TYPE
L10:SENSOR OUT ALARM NO VAPOR PROCESSOR
Lll :SENSOR OUT ALARM s 4:Ft°I 5-6
L12:SENSOR OUT ALARM CATEGORY AIR FLOW METER
L15:SENSOR OUT ALARM ANALYSIS TIMES
L 9:SHORT ALARM s 5:FIJI 7-8 TIME: 10:00 AM ALARM CATEGORY AIR FLOW METER
Lll :SHORT ALARM DELAY MINUTES: 1
L12:SHORT ALARM
L15:SHORT ALARM ACCEPT HIGH ORVR:
ISD SITE ALARMS
DISABLED
ISD GROSS PRES FAIL ISD HOSE TABLE
ISD DEGRD PRES FAIL ID FP FL HL AA RR
ISD VAPOR LEAK FAIL -------•--_.--------------
ISD VP PRES FAIL O1 O1 01 02 01 UU
ISD VP STATUS FAIL 02 02 02 02 01 UU
ISD HOSE ALARMS 03 03 03 02 02 UU
ALL:GROSS COLLECT FAIL 04 04 04 02 02 UU
05 05 05 02 03 UU
ALL:DEGRD COLLECT FAIL
06 06 06 02 03 UU
ALL:FLOW COLLECT FAIL
07 07 07 02 04 UU
R 3:DSL 08 08 08 02 04 UU
TYPE:
STANDARD ISD AIRFLOW METER MAP
NORMALLY CLOSED ID SERIAL NUM LABEL
TANK #: 2 1 8424 FM 1-2
2 7356 FM 3-4
LIQUID SENSOR ALMS 3 8425 FM 5-6
4 8313 FM 7-8
L 3:FUEL ALARM
L 9:FUEL ALARM
Lll :FUEL ALARM ISD FUEL. GRADE HOSE MAP
L13:FUEL ALARM 1 2 3 4
L14:FUEL ALARM FP MHH MHH MHH MHH AA
L 3:SENSOR OUT ALARM -
L 9:SENSOR OUT ALARM 01 201 301 901 5 U- 1
L11 :SENSOR OUT ALARM 02 202 302 902 5 U 1 {'
L13:SENSOR OUT ALARM 03 203 303 903 U U 2
L14:SENSOR OUT ALARM 04 204 304 904 U U 2
L 3:SHORT ALARM 05 205 305 905 5 U 3
L 9:SHORT ALARM 06 206 306 906 5 U 3
L11 :SHORT ALARM 07 207 307 907 U U 4
L13:SHORT ALARM 08 208 308 908 U U 4
L14:SHORT ALARM
R 5:OVERFILL LABEL TABLE
TYPE: - -------------------
STANDARD 1 : UNASSIGNED
NORMALLY OPEN 2: BLENDS
TANK #: NONE 4: REGULAR
4: MID GRADE
5: PREMIUM
IN-TANK ALARMS 6: GOLD 7: BRONZE
ALL:OVERFILL ALARM 8: SILVER
ALL:HIGH PRODUCT ALARM 9: BLEND2
ALL:MAX PRODUCT ALARM 10: BLEND4
PMC SETUP
PROCESSOR CONTROL LEVEL:
NONE
SOFTWARE REVISION LEVEL ALARM HISTORY REPORT -
VERSION 327.04 ALARM HISTORY REPORT
SOFTWARE# :346327-100-E ---- IN-TANK ALARM -----
CREATED - 07.02.06. 10.28 T 2:DIESEL ---- IN-TANK ALARM -----
S-MODULE# 330160-004-a T 4:UNL 2
SYSTEM FEATURES: LOW PRODUCT ALARM
PERIODIC' IN-TANK TESTS AUG 11 , 2010 9:01 AM OVERFILL ALARM
ANNUAL 1N-TANK TESTS AUG 14, 2009 10:10 AM JUL 11, 2010 11 :31 PM
ISD AUG 14, 2009 9:43 AM JUN 8, 2010 11 :17 PM
PHO HIGH PRODUCT ALARM MAY 18, 2010 1 :56 AM
AUG 14, 2009 10:08 AM LOW PRODUCT ALARM
INVALID FUEL LEVEL MAR 9. 2010 7:29 PH
AUG 14. 2009 10:10 AM SUDDEN LOSS ALARM
PROBE OUT MAY 8, 2009 6:11 AM
AUG 11. 2010 9:01 AM MAY 7, 2009 6:43 PM
AUG 14, 2009 10:09 AM HIGH PRODUCT ALARM
ALARM HISTORY REPORT AUG 14, 2009 9:43 AM AUG 14. 2009 10:14 AM
JUL 16, 2009 5:26 AM
---- IN-TANK ALARM DELIVERY NEEDED DEC 31 , 2008 3:53 AM
AUG 11 .. 2010 9:01
T 1 :UNL 1 AUG 10, 2010 5:118 AAM M PROBE OUT
2010 9:04 AM
NOV 22
JUL 26. 2010 6:09 PM AUG ,
22
HIGH WATER ALARM 2009 7: 16 PM
NOV 23. 2009 2:47 Ire NOV 22., 2009 7:12 PM
HIGH WATER WARNING
OVERFILL ALARM AUG 11. 2010 9: 12 AM
JUN 15, 2010 5: 11 PM
JUN 4, 2010 12:30 AM
DEC 15. 2009 8:34 PM DELIVERY NEEDED
LOW PRODUCT ALARM MAR 19, 2010 1 :05 PM
JUN 25, '2010 5:40 PM MAR 9, 2010. 3:32 PM
FEB 5, 2010 3:45 PM
JUN 19, 2010 11 :32 All
JUN 12, 2010 10:34 PM * x * i END * x MAX PRODUCT ALARM
SUDDEN LOSS ALARM DEC 31 , 2008 3:55 Af'I
JUL 3. 2010 10: 12 PM
APR 6, 2010 9:59 PM LOW TEMP WARNING
JAN 31 , 2010 5:00 AM AUG 14, 2009 10:14 r4l
HIGH PRODUCT ALARM
AUG 14, 2009 10:10 AM
DEC 31 , 2008 4:02 All
INVALID FUEL LEVEL
AUG 11 , 2010 9:03 AM ALARM HISTORY REPORT
JUN 25, 2010 7:59 PM
JUN 19, 2010 1 :56 Pill ---- IN-TANK ALARM -----
PROBE OUT T 3:PNL >f * END
AUG 11 , 2010 9:02 AM
NOV 23, 2009 2:51 PM HIGH PRODUCT ALARM
NOV 23, 2009 2:40 PM AUG 14, 2009 10:06 AM
HIGH WATER WARNING PROBE OUT
NOV 23, 2009 2:47 1-r1 AUG 11 , 2010 9:00 AM
AUG 14, 2009 10:07 All
AUG 14, 2009 9:44 AM
DELIVERY NEEDED
JUN 25, 2010 4:00 PH
JUN 19, 2010 8: 18 All DELIVERY NEEDED
JUN 12, 2010 6:18 PM APR 6, 2010 3:31 PM
MAR 19, 2010 10:20 AM
JAN 29, 2010 10:30 PM
LOW TEMP WARNING
NOV 23, 2009 2:52 PM
AUG 14. 2009 10:12 AM
x * x * x END x X * X
x END
--. IN-TANK ALARM ----- ALARM HISTORY REPORT ALARM HISTORY REPORT
T 4:UNL 2
HIGH WATER WARNING ----- SENSOR ALARM ----- ----- SENSOR ALARM -----
AUG 11 , 2010 9:12 AM L 3:DSL STP L 6:PNL ANN
STP SUMP, ANNULAR SPACE.
FUEL ALARM SENSOR OUT ALARM
JUL 1, 2010 2:52 AM AUG 14, 2009 10:18 AM
FUEL ALARM FUEL ALARM
JUN 8, 2010 9:02 PM AUG 14, 2009 10:03 AM
FUEL ALARM
ALARM HISTORY REPORT MAY 18, 2010 4:09 AM
----- SENSOR ALARM ----=
L I :UNL" 1 STP
STP SUMP
FUEL ALARM
JUL 23, 2010 8:26 PM
* END * * x
FUEL ALARM
JUL 5, 2010 6:18 PM
SENSOR OUT ALARM * * * * END
AUG 14, 2009 10: 18 AM
ALARM HISTORY REPORT
----- SENSOR ALARM -----
* * * * END * * * * ;� ALARM HISTORY REPORT L 7:UNL 2 STP
STP SUMP
-- SENSOR ALARM ----- FUEL ARM
M 2:27 AM
L 4:DSL ANN JUL
ANNULAR SPACE
SENSOR OUT ALARM FUEL ALARM
AUG 14, 2009 10: 18 AM JUN 16, 2010 7:32 AM
FUEL ALARM FUEL ALARM
AUG 14, 2009 10:03 AM MAY 26, 2010 11 :53 AM
ALARM HISTORY REPORT
----- SENSOR ALARM -----
L 2:UNL 1 ANN
ANNULAR SPACE
SENSOR OUT ALARM
AUG 14, 2009 10:18 AM
FUEL ALARM * * * * * END END
* * * * * * * S * * * *
AUG 141 2009 10:04 AM
* * * * END * * ALARM HISTORY REPORT ALARM. HISTORY REPORT
----- SENSOR ALARM ----- ----- SENSOR ALARM -----
L 5: L B:UNL 2 ANN
OTHER SENSORS ANNULAR SPACE
SENSOR OUT ALARM
AUG 14, 2009 10:18 AM
FUEL ALARM
AUG 14, 2009 10:04 AM
* END * * x x x
END x x x x x
F M H I STORY REPORT SENSOk ALARM ----- ALARM HISTORY REPORT ALARM HISTORY REPORT
DISP 1-2 -- SENSOR ALARM ----- ----- SENSOR ALARM ENSER PAN I - L14:TRANS SUMP SO.
SENSOR OUT ALARM L11 :DISE 5-6
AUG 14. 2009 10:18 AM DISPENSER PAN DISPENSER PAN
SENSOR OUT ALARM FUEL ALARM
FUEL ALARM AUG 14. 2009 10:18 AM SEP 9, 2009 1 :21 PM
AUG 14.. 2009 10:00 AM FUEL ALARM SENOR OUT ALARM
AUG 14. 2009 10:00 AM AUG 27, 2009 11 :46 AM
FUEL ALARM
AUG 27, 2009 11 :42 AM
END --
* * * END
* * END
ALARM HISTORY REPORT
-- SENSOR ALARM ----- ALARM HISTORY REPORT
L 9:DISP 1-2 ----- SENSOR ALARM -----
DISPENSER PAN L12:DISP 7-8 ALARM HISTORY REPORT
SENSOR OUT ALARM DISPENSER PAN
AUG 14. 2009 10:18 AM SENSOR OUT ALARM ----- SENSOR ALARM -----
FUEL ALARM AUG 14. 2009 10:18 AM L15:PNL STP
AUG 14, 2009 10:00 AM STP SUMP
FUEL ALARM FUEL ALARM
AUG 14. 2009 10:01 AM JUN 15. 2010 6:13 AM
FUEL ALARM
APR 22. 2010 1 :54 AM
FUEL ALARM
APR 21, 2010 5:39 PM
* * * * END * * x
* * * x END
* MEND * *
ALARM HISTORY REPORT
----- SENSOR ALARM ----- ALARM HISTORY REPORT
L10:DISP 3-4 ----- SENSOR ALARM -----
DISPENSER PAN L13:TRANS SUMP NO.
SENSOR OUT ALARM DISPENSER PAN
AUG 14, 2009 10:18 AM FUEL ALARM
FUEL ALARM SEP 9, 2009 1 :24 PM FASTRIP 347
2698 OSWELL ST.
AUG 14, 2009 9:59 AM SENSOR OUT ALARM BAKERSFIELD,CA93306
AUG 28, 2009 8:04 AM 661-872-8781
SENSOR OUT ALARM AUG 11, 2010 9:13 AM
AUG 28, 2009 8:01 AM
- SYSTEM-STATUS REPORT- _
T 4:HIGH WATER WARNING
* END
END * x
----- SENSOR ALARM -----
L15:PNL STP ----- SENSOR-ALARM ----- ---- IN-TANK ALARM -----
STP SUMP L11 :DISP 5-6 - T 3:PNL
FUEL ALARM DISPENSER PAN HIGH PRODUCT ALARM
AUG 11 . 2010 9:14 AM FUEL ALARM AUG 11, 2010 9:22 AM
AUG 11, 2010 9:19 AM
----- SENSOR ALARM ----- ---- IN-TANK ALARM -----
L 3:DSL STP ----- SENSOR ALARM ----- T 3:PNL
STP SUMP L12:DISP 7-8 PROBE OUT
FUEL ALARM DISPENSER PAN AUG 11, 2010 9:23 AM
AUG 11, 2010 9:15 AM FUEL ALARM
AUG 11 . 2010 9:19 AM
---- IN-TANK ALARM -----
----- SENSOR ALARM ----- T 3:PNL
L 1 :UNL 1 STP ----- SENSOR ALARM ----- LOW TEMP WARNING
STP SUMP L 6:PNL ANN AUG 11. 2010 9:23 AM
FUEL ALARM ANNULAR SPACE
AUG 11. 2010 9: 15 AM FUEL ALARM
AUG 11 . 2010 9:20 AM
----- SENSOR ALARM -----
L13:TRANS SUMP NO.
----- SENSOR ALARM ----- DISPENSER PAN
L 7:UNL 2 STP ----- SENSOR ALARM ----- FUEL ALARM
STP SUMP L 4:DSL ANN AUG 11 , 2010 9:28 AM
FUEL ALARM ANNULAR SPACE
AUG 11, 2010 9: 16 AM FUEL ALARM
AUG 111 2010 9:21 AM
----- SENSOR ALARM -----
L14:TRANS SUMP SO-
----- SENSOR ALARM, ----- DISPENSER PAN
L10:DISP 3-4 ----- SENSOR ALARM ----- FUEL ALARM
DISPENSER PAN L 2:UNL 1 ANN AUG 11, 2010 9:30 AM
FUEL ALARM ANNULAR SPACE
AUG 11, 2010 9:17 AM FUEL ALARM
AUG 11 . 2010 9:21 AM
Il
---- IN-TANK ALARM -----
-- SENSOR ALARM -- _ T 2:DIESEL HIGH PRODUCT ALARM
L 9:DISP 1-2 ----- SENSOR ALARM ----- AUG 11. 2010 9:31 AM
DISPENSER PAN L 8:UNL 2 ANN
FUEL ALARM ANNULAR SPACE
AUG 11 , 2010 9:18 AM FUEL ALARM
AUG 11, 2010 9:22 AM
---- IN-TANK ALARM -----
T 2:DIESEL
PROBE OUT
AUG 11. 2010 '9:32 AM
1
---- IN-TANK ALARM ----- -- -- --- - — -- --- -—
T 1 :UNL ! ---- IN-TANK ALARM -----
T OBE O 2
HIGH PRODUCT ALARM
AUG 11 , 2010 9:33 AM PROBE OUT -- SENSOR ALARM -----
j AUG 11 , 2010 9:35 AM L12:DISP 7-B
DISPENSER PAN
SENSOR OUT ALARM
AUG 11, 2010 9:36 AM
-- IN-TANK ALARM ----- FASTRIP 347
T 1 :UNL 1 2698 OSWELL ST.
PROBE OUT BAKERSFIELD.CA93306
AUG 11, 2010 9:33 AM 661-872-8781 ----- SENSOR ALARM -----
AUG 11, 2010 9:35 AM L14:TRANS SUMP 80.
DISPENSER PAN
SENSOR OUT ALARM
AUG 11. 2010 9:36 AM
SYSTEM STATUS REPORT
-
T 4:PROBE OUT
---- IN-TANK ALARM -----
T 1 :UNL 1
LOW TEMP WARNING
AUG 11 . 2010 9;34 AM
----- SENSOR ALARM -----
L15:PNL STP
STP SUMP
SENSOR OUT ALARM
AUG 11, 2010 9:36 AM
----- SENSOR ALARM -----
L 9:DISP 1-2
T 2:DIESEL DISPENSER PAN
INVENTORY INCREASE SENSOR OUT ALARM
flUG 11. 2010 9:36 AM
INCREASE START
AUG 11, 2010 9:31 AM
FASTRIP 347
VOLUME = 6579 GALS 2698 OSWELL ST.
HEIGHT = 51 .64 INCHES BAKERSFIELD,CA93306
WATER = 0.96 INCHES 661-872-8781
TEMP o 93.2 DEC F
,{ -- SENSOR ALARM ----- AUG 11 , 2010 9:36 AM
INCREASE END L10:DISP 3-4
AUG 11, 2010 9:34 AM DISPENSER PAN
VOLUME = 11145 GALS SENSOR OUT ALARM - -
84.11 INCHES SYSTEM STATUS REPORT
HEIGHT AUG 11, 2010 . 9:36 AM '
WATER a 0.75. INCHES L10:SENSOR OUT ALARM
TEMP 92.8 DEG F L11 :SENS6R OUT ALARM
GROSS INCREASE- 4566 L12:SENSOR OUT ALARM
TC NET INCREASE- 4499 L13:SENSOR OUT ALARM
- SENSOR ALARM ----- L14:SENSOR OUT ALARM
L13:TRANS SUMP NO. L15:SENSOR OUT ALARM
DISPENSER PAN
SENSOR OUT ALARM
AUG 11, 2010 9:36 AM
---- IN-TANK ALARM -----
T 4:UNL 2
HIGH PRODUCT ALARM
AUG 11. 2010 9:34 AM
----- SENSOR ALARM -----
L11 :DISP 5-6
DISPENSER PAN
SENSOR OUT ALARM
AUG 11. 2010 9:36 AM
T 1 :UNL 1
INVENTORY INCREASE
INCREASE START
AUG 11. 2010 9:32 AM
VOLUME = 7878 GALS
HEIGHT - 59.93 INCHES
WATER - 1 .43 INCHES
TEMP - 84.3 DEG F
INCREASE END
AUG 11, 2010 9:36 AM
VOLUME = 9439 GALS
HEIGHT - 70.46 INCHES
WATER = 0.00 INCHES
TEMP = 85:4 DEG F
GROSS INCREASE- 1561
TC NET INCREASE- 1527
T 4:UNL 2
INVENTORY INCREASE
INCREASE START
AUG 11, 2010 9:34 AM
VOLUME - 5499 GALS
HEIGHT = 44.85 INCHES
WATER - 0.00 INCHES
TEMP = 78.0 DEG F
INCREASE END
AUG 11, 2010 9:38 AM
VOLUME - 9666 GALS
HEIGHT - 72.08 INCHES
WATER . 1 .02 INCHES
TEMP = 74.2 DEG F
GROSS INCREASE- 4167
TC NET INCREASE- 4140
SWRCB,January 2006
Spill Bucket Testing Report Form
This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and
printouts from tests(if applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: 4347 Fastrip#26 Date of Testing: 8/11/2010
Facility Address: 2698 Oswell Street,Bakersfield,CA 93306
Facility Contact: Omero Garcia I Phone: 661-393-7000
Date Local Agency Was Notified of Testing: 7/23/2010
Name of Local Agency Inspector(f present during testing): Ernie Medina
2. TESTING CONTRACTOR INFORMATION
Company Name: Confidence UST Services, Inc.
Technician Conducting Test: Bryan A Self
Credentials: X CSLB Contractor X ICC Service Tech. ❑SWRCB Tank Tester ❑Other(Spec)
License Number(s): CSLB#804904 ICC 98022804-UT
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: x Hydrostatic ❑Vacuum ❑Other
Test Equipment Used: Lake Test Equipment Resolution: 0.0625"
Identify Spill Bucket(By Tank 1 Regular 1 2 Regular 2 3 Super 4 Diesel
Number, Stored Product, etc.
Bucket Installation Type: ❑ Direct Bury ❑ Direct Bury ❑Direct Bury ❑Direct Bury
x Contained in Sump x Contained in Sump x Contained in Sump x Contained in Sum
Bucket Diameter: 12.00" 12.00" 12.00" 12.00"
Bucket Depth: 14.00" 13.75" 14.00" 14.00"
Wait time between applying 5 min. 5 min. 5 min. 5 min.
vacuum/water and start of test:
Test Start Time(Tj): 9:00am 9:00am 9:00am 9:00am
Initial Reading(Rj): 10.75" 11.50" 11.00" 10.50"
Test End Time(TF): 10:00am 10:00am 10:00am I0:00am
Final Reading(RF): 10.75" 11.50" 11.00" 10.50"
Test Duration(TF—Ti): 1 hour 1 hour I hour 1 hour
Change in Reading(RF-R,): 0.00" 0.00" 0.00" 0.00"
Pass/Fail Threshold or 0.0625" 0.0625" 0.0625" 0.0625"
Criteria:
Test Result: X Pass ❑Fail X Pass ❑Fail X Pass ❑Fail X Pass ❑Fail
Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true,accurate,and in full compliance with legal requirements.
Technician's Signature: Date: 8/11/2010
State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.