HomeMy WebLinkAboutFMC RESULTS 2010 Pass MONITORING SYSTEM CERTIFICATION For Use By All Jurisdictions Within the State of California Authority Cited: Chapter 6 7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of this date. A. General Information IIIIIIIIIIIIIIIIIIII 07 Facility Name: #233 D &G Liquor IE Bldg.No.: Site Address: 2732 Brundage Lane City: Bakersfield Zip: 93304 Facility Contact Person: Omero Garcia Contact Phone No.: 661-393-7000 Make/Model of Monitoring System: Veeder-Root TLS 350 Date of Testing/Servicing: 8/16/2010 B. Inventory of Equipment Tested/Certified es Check the appropriate box to Indicate specific equipment inspected/servind: Tank ID: 12000 gal.Regular Tank ID: 12000 gal.Diesel [X] in-Tank Gauging Probe. Model:847390-107 [x] in-Tank Gauging Probe. Model:847390-107 ❑ Annular Space or Vault Probe. Model: ❑ Annular Space or Vault Sensor. Model: ❑ Piping Sump/Trench Sensor(s). Model: ❑ Piping Sump/Trench Sensor(s). Model: ❑ Fill Sump Sensor(s) Model: ❑ Fill Sump Sensor(s). Model: ❑ Mechanical Line Leak Detector. Model: ❑ Mechanical Line Leak Detector. Model: [X] Electronic Line Leak Detector. Model:WPLLD U Electronic Line Leak Detector. Model: WPLLD U Tank Overfill/High Level Sensor. Model:847390-107 U Tank Overfill/High Leval Sensor. Model: 847390-107 ❑ Other(specify equip.type and model in Sec. E on Pg.2) ❑ Other(specify equip.type and model in Sec. E on Pg.2) Tank iD: 12000 gal.Super Tank iD: [x] in-Tank Gauging Probe. Model:847390-107 ❑ in-Tank Gauging Probe. Model: ❑ Annular Space or Vault Sensor. Model: ❑ Annular Space or Vault Sensor. Model: ❑ Piping Sump/Trench Sensor(s). Model: ❑ Piping Sump/Trench Sensor(s). Model: ❑ Fill Sump Sensors(s). Model: ❑ Fill Sump Sensor(s). Model: [] Mechanical Line Leak Decector. Model: ❑ Mechanical Line Leak Detector. Model: [x] Electronic Line Leak Detector. Modei:WPLLD ❑ Electronic Line Leak Detector. Model: Lx] Tank Overfill/High Level Sensor. Model:847390-107 E] Tank Overfill/High Level Sensor.Model: E] Other(specify equip.type and model in Sec. E on Pg.2) ❑ Other(specify equip.typs and model in Sec. E on Pg.2) Dispenser iD: 1 &2 Dispenser ID: [x] Dispenser Containment Sensor(s). Model: 794390-208 ❑ Dispenser Containment Sensor(s). Model: [X] Shear Valve(s). ❑ Shear Valve(s). ❑ Dispenser Containment Float(s)and Chain(s). ❑ Dispenser Containment Float(s)and Chain(s) Dispenser ID: Dispenser iD: ❑ Dispenser Containment Sensor(s). Model: ❑ Dispenser Containment Sensor(s). Model: ❑ Shear Valve(s). ❑ Shear Valve(s). ❑ Dispenser Containment Float(s)and Chains(s). ❑ Dispenser Containment Float(s)and Chain(s). Dispenser ID: Dispenser ID: ❑ Dispenser Containment Sensor(s). Model: ❑ Dispenser Containment Sensor(s). Model: ❑ Shear Valve(s). ❑ Shear Valve(s). ❑ Dispenser Containment Float(s)and Chain(s) ❑ Dispenser Containment Float(s)and Chain(s). *if the facility contains more tanks or dispensers,copy this form. Include information for every tank and dispenser at the facility. C. Certification -1 certify that the equipment identified in this document was inspected/services in accordance with the manufacturers'guidlines.Attached to this Certification is information(e.g.manufacturers'checklist)necessary to varify that this information is correct and a plot plan showing the layout of monitoring equipment.For equipment capable of generating such reports,1 have attached a copy of the report; (check all that apply) x❑System Set-up x Al hi ory report Technician Name(print): Bryan A Self Signature: Certification No: 837501 License N. 804904 Testing Company Name: Confldence UST Services,Inc. Phone No: 800-339-9930 Site Address: 2732 Brundage Lane,Bakersfield,CA 93304 11111111111111111 O8 Date of Testing/Servicing: 8/16/2010 A Results of Testing/Servicing Software Version Installed: 14.04 Complete the following checklist: ❑ Yes [x-1 No* Is the audible alarm operational? gx Yes x e No* Is t Visua alarm operational? x Yes No* Were all sensors visually inspected,functionally tested,and confirmed operational? Yes ❑ No* Were all sensors installed at the lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment(e.g.modem) x N/A operational? x Yes ❑ No* For pressurized piping systems,does the turbine automatically shut down if the piping secondary ❑N/A containment monitoring system detects a leak,fails to operate,or is electrically disconnected? If yes: which sensors initate positive shut-down? ❑Sump/Trench Sensors U Dispenser Containment Sensors Did you confirm positive shut-down due to leaks and sensor failure/disconnected? U Yes; ❑ No; U Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device(i.e.no N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visual and audible at the tank fill point(s)and operating properly?If so,at what percent of tank capasity does the alarm trigger? 9p % ❑ Yes* U No Was any monitoring equipment replaced? If Yes, identify specific sensors,probes,or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E,below. ❑ Yes* E No Was liquid found inside any secondary containment systems designed as dry systems? ❑ Product; ❑ Water. If yes,describe causes in Section E,below. TX N * Was monitoring system set-up reviewed to ensure proper settings?Attach set-up reports, if applicable. E Yes I D No* I Is all monitoring equipment operational per manufacturer's specifications? *In Section E below,discribe how and when these deficiencies were or will be corrected. E. Comments: F. In-Tank Guaging/SIR Equipment: M Check this box if tank guaging is used only for inventory control. ❑ Check this box if tank guaging or SIR equipment is installed. This section must be completed if in-tank guaging equipment is used to perform leak detection monitoring. Complete the following checklist: [.1] Yes ❑ No* Has all input wiring been inspected for proper enter and termination,including testing for ground faults? x Yes No* Were all tank guaging probes visually inspected for damage and residue buildup? Ix Yes No* Was accuracy of system product level readings tested? x Yes No* Was accuracy of system water level readings tested? _[xl Yes No* Were all probes reinstalled properly? U Yes ❑ No*I Were all items on the equipment manufacturer's maintenance checklist completed? *In the Section H,below,describe how and when these deficiencies were or will be corrected. G. Line Leak Detectors (LLD): ❑Check this box if LLD's are not installed. Complete the following checklist: [x] Yes ❑ No* For equip. start-up or annual equipment certification,was a leak simulated to varify LLD performance? (Check all that apply) Simulated leik rate: [�]3 g.p.h.: ❑0.1 g.p.h.; ❑0.2 g.p.h.; x Yes No* Were all LLD's confirmed operational and accurate within regulatory requirments? x Yes No Was the testing apparatus properly calibrated? ❑ Yes No* For mac amca LLD's,does the LLD restrict product flow if it detects a leak? x N/A [x] Yes No* For electronic LLD's,does the turbine automatically shut off if the LLD detects a leak? ❑ N/A L] Yes No* For electronic LLD's,does the turbine automatically shut off if any portion of the monitoring system is ❑ N/A disabled or disconnected? [x Yes No* For electronic LLD's,does the turbine automatically shut off if any portion of the monitoring system ❑ N/A malfunction or fails a test? ❑ Yes No* For electronic LLD's,have all accessible wiring connections been visually inspected? ❑ N/A x Yes No Were all items on the equipment manufacturer's maintenance checklist completed? * In the section H,below,describe how and when these deficiencies were or will be corrected. H. Comments: D AND G 233 SYSTEM SETUP 2732 BRUNDAGE LN - - - - - - - - - - - - SAKERSFFiLD CA 9330 AUG 16, 2010 1'2:23 PM 661-326-1083 D AND G 233 2732 BRUNDAGE LN AUG 16. 2010 12:23 PM SYSTEM UNITS BAKERSFFILD CA 9330 U S 661-326-1083 SYSTEM LANGUAGE AUG 16, 2010 12:23 PM ,SYSTEM STATUS REPORT ENGLISH - - - - - - - - - - - - SYSTEM DATE:TIME FORMAT T 3:DELIVERY NEEDED MON DD YYYY HH:MM:SS xM SYSTEM,STATUS REPORT D AND G 233 - - - INVENTORY REPORT 2732 BRUNDAGE LN T 3:D)IVERY NEEDED BAKERSFFILD CA 9330 661-326-1083 T ! :UNLEADED INVENTORY REPORT VOLUME m 7070 GALS SHIFT TIME I : DISABLED ULLAGE - 4930 GALS SHIFT TIME 2 DISABLED 90% ULLAGE- 3730 GALS SHIFT TIME 3 DISABLED T ) :UNLEADED TC VOLUME - 6929 GALS SHIFT TIME 4 DISABLED VOLUME = 7070 GALS HEIGHT - 54.75 INCHES ULLAGE - 4930 GALS WATER VOL - 0 GALS TANK PER TST NEEDED WRN WRN 90% ULLAGE= 3730 GALS WATER = 0.00 INCHES DISABLED TST NEEDED DISABLED TC VOLUME - 6929 GALS TEMP . 88.4 DEG F DISABLED HEIGHT = 54.75 1NCHE5 WATER VOL 0 GALS - T 2:PREMIUM LINE RE-ENABLE METHOD WATER 0.00 INCHES VOLUME = 1963 GALS PASS LINE TEST TEMP 88,4 DEG F ULLAGE - 10037 GALS 90% ULLAGE= 8837 GALS LINE PER TST NEEDED WRN T 2:PREMIUM TC VOLUME - 1927 GALS DISABLED VOLUME = 1963 GALS HEIGHT - 21 .16 INCHES LINE ANN TST NEEDED WRN ULLAGE - 10037 GALS WATER VOL - 15 GALS DISABLED 90Y. ULLAGE= 8837 GALS WATER - 0.79 INCHES TC VOLUME - 1927 GALS TEMP - 85.6 DEG F PRINT TO VOLUMES HEIGHT = 1 . 16 INCHES ENABLED WATER VOL = 15 GALS T 3:DIESEL TEMP COMPENSATION TEMP 8 B ,..6 WATER = 5 INCHES VOLUME = 1199 GALS VALUE (DEG F > : 60.0 6 DEG F ULLAGE = 10801 GALS STICK HEIGHT OFFSET 90% ULLAGE- 9601 GALS DISABLED T 3:DIESEL v TC VOLUME = 1047 GALS ULLAGE: 9(r6 VOLUME = 1199`GALS HEIGHT = 15.01 INCHES ULLAGE , - 10801 GALS WATER VOL - 0 GALS H-PROTOCOL DATA FORMAT 90 ULLAGE= 9601 GALS WATER = 0.00 INCHES HEIGHT TC VOLUME - 1047 GALS TEMP = 88.0 DEG F PRECISION TEST DURATION HEIGHT = 15.01 INCHES HOURS: 12 WATER VOL - 0 GALS DAYLIGHT SAVING TIME WATER a 0.00 INCHES x X " R ENE) x h DISABLED TEMP a 88.0 DEG F RE-DIRECT LOCAL PRINTOUT DISABLED R END EURO PROTOCOL PREFIX S SYSTEM SECURITY CODE : 000000 MAINTENANCE HISTORY DISABLED TANK CHART SECURITY DISABLED CUSTOM ALARMS DISABLED MASS/DENSITY DISABLED 1 T 2:PREMIUM IN-TANK SETUP PRODUCT CODE 2 - - - - - - - - - - - - THERMAL COEFF : .000700 T ( :UNLEADED TANK DIAMETER 96.00 COMMUNICATIONS SETUP_ _ _ PRODUCT CODE I TANK PROFILE I PT - - - - - - - - - THERMAL COEFF : .000700 FULL VOL (2000 TANK DIAMETER 96.00 PORT 3ETT11Vt;°: TANK PROFILE t PT FLOAT SIZE: 4.0 IN. FULL VOL 12000 C-OMI-i BOARD : I (R5-232) WATER WARNING 2.0 BAUD RATE : 9600 FLOAT SIZE: 4.0 IN. HIGH WATER LIMIT: 3.0 PARITY NONE STOP BIT t STOP MAX OR LABEL VOL: 12000 DATA LENGTH: 8 DATA WATER WARNING 2.0 OVERFILL LIMIT 90. RS-232 SECURITY HIGH WATER LIMIT: 3.0 10800 CODE DISABLED MAX OR LABEL VOL: 12000 HIGH PRODUCT 11400 OVERFILL LIMIT 90% DELIVERY LIMIT 15% AUTO TRANSMIT SETTINGS. 10800 1800 HIGH PRODUCT 956 AUTO LEAK ALARM LIMIT 11400 LOW PRODUCT : 600 DISABLED DELIVERY LIMIT 15%6 LEAK ALARM LIMIT: 99 AUTO HIGH WATER LIMIT 1600 SUDDEN LOSS LIMIT: 99 DISABLED TANK TILT 0.00 AUTO OVERFILL LIMIT LOW PRODUCT 600 PROBE OFFSET 0.00 DISABLED LEAK ALARM L1111T: 99 AUTO LOW PRODUCT SUDDEN LOSS LIMIT: 99 DISABLED TANK TILT 0.00 SIPHON MANIFOLDED TANKS AUTO THEFT L1M17 PROBE OFFSET 0.00 TO: NONE DISABLED LINE MANtFOLDED TANKS AUTO DELIVERY START SIPHON MANIFOLDED TANKS To: NONE DISABLED Td: NONE AUTO DELIVERY END LINE MANIFOLDED TANKS LEAK MIN PERIODIC: In DISABLED Td: NONE AUTO EXTERNAL INPUT ON 120 AUTSO EXTERNAL. INPUT OFF LEAK MIN ANNUAL IV. LEAK MIN PERIODIC: lry DISABLED 120 t20 AUTO SENSOR FUEL ALARM DISABLED LEAK MIN ANNUAL 1%L AUTO SENSOR WATER ALARM 120 PERIODIC TEST TYPE DISABLED STANDARD AUTO SENSOR OUT ALARM ANNUAL TEST FAIL DISABLED PERIODIC TEST TYPE ALARM DISABLED STANDARD PERIODIC TESTS FAIL ANNUAL TEST FAIL ALARM DISABLED ALARM DISABLED GROSS TEST FAIL PERIODIC TEST FAIL ALARM DISABLED ALARM DISABLED RS-232 END 6F MESSAGE GROSS TEST FAIL ANN TEST AVERAGING: OFF DISABLED ALARM GISABLED PER TEST AVERAGING: OFF TANK TEST NOTIFY: OFF ANN TEST AVERAGING: OFF PER TEST AVERAGING: OFF TNK TST SIPHON SREAK:OFF TANK TEST NOTIFY: OFF DELIVERY DELAY 1 MIN PUMP THRESHOLD : 10.00%s TNK TST SIPHON BREAK:OFF DELIVERY DELAY 1 MIN PUMP THRESHOLD : 10.004 LIINE LEAK,LOCKOUT ;SETUP T 3:DIESEL LEAK 'TEST METHOD' LOCKOUT SCHEDULE - PRODUCT CODE 3 - - - _ DAILY: THERMAL COEFF .004500 TEST WEEKLY #iLL TANK START 'CIME-:, DISABLED TANK DIAMETER 96.00 SUN STOP TIME DISABLED TANK PROFILE I PT START TIME 2:00 A10 FULL VOL. : 12000 TEST RATE :u•.20 GAL'HR DURATION 2 HOURS FLOAT SIZE: 4.0 1N. TST EARLY STOP:DISABL:ED WATER WARNING 2.0 LEAK TEST REPORT FORMAT HIGH WATER LIMIT.: 3.0 NORMAL MAX OR LABEL VOL: 12000 OVERFILL LIMIT 90X. IOB00 HIGH PRODUCT 95 LIQUID. SENSOR SETUP 1.1400 - - - - - - - - DELIVERY LIMIT 1.5% 1800 L. 1 :D'ISP 1 - TRI-STATE•: (SINGLE FLOAT) LOW PRODUCT -600 CATEGORY ;. DISPENSER AN LEAK ALARM LIMIT: 99 lJPLLD LINE LEAK SETUP SUDDEN.LOSS LIMIT: 99 TANK TILT 0.00 - PROBE OFFSET 0.o0 W i :,DIESEL SIPHON MANIFOLDED TANKS LINE NONE LINE2LENGTH , 00. FEET LINE MANIFOLDED 'TANKS SHUTDOWN RATE.! 3:O GPH To' NONE T 3:DIESEL: DISPENSE, MODE.: LEAK. M I.N PERIODIC: !s: STANDARD 120 OUTPUT RELAY•SETUP PRESSURE OFFSET: 0.0P3i - - - - - - - LEAK M1N ANNUAL 11X 120 �°R .1,:'OVERF I,LL ALARM. TYPE;: STANDARD PERIODIC TEST TYPE NOR ALLY .OPEN STANDARD ANNUAL TEST FALL IN-TANK ALARMS ALARM DISABLED ALL.:'OVERF I LL ALARM .ALL:'kIGH PRODUCT;ALARM PERIODIC TEST FAIL -ALL:MAk PRODUCT ALARM ALARM DISABLED W 2:-UNLEADED GROSS TEST FAIL ALARM DISABLED TYP:2,0 .IN SCEEL LINE LENGTH,: '100-FEET ANN TEST AVERAGING: OFF SHUTDOWN RATE,: 3.0, GPH PER TEST AvERAOLNG: OFF T i :UNLEADED DISPENSE'MODE: TANK TEST NOTIFY: OFF STANDARD. ' TNK TST SIPHON BREAK:OFF PRESSURE' OF;FSET: O'.OPSt WPLLD L I NE. D'I SABLE .SETUP DELIVERY DELAY I MIN PUMP THRESHOLD 10.01 W 1 :DIESEL LIQUID SENSOR ALMS ALL:FUEL ALARM ALL:SENSOR •OUT.ALARM ALL':,SHORT .ALARM W 2:UNLEADED W 3:PREMI Lim. LIQUID SENSOR, ALMS NILL:FbEL ALARM TY,P:�2..0 IN, S'F_EEL ALL::SENSOR:OOT ALARM L I NE";LEiVGTH: 1:00','FEET, ALL-.SHORT ALARM SHUTDOWN'<RATE: .3.;0 GPm T 2:PREMI.UM W. 3:PREM I UII1 DISPENSE; "MODE' STANDARD- L l'dU I D',SEIS'Ei6R ALMS ALL,IFUEL ALARM PRESSURE- OFFSET'. O':OPS'l ALL::SENSOR' OUT`ALARM ALL;SHORT`AL:ARM ---- IN-TANK. ALARM ----- T 2:PREMIUM ALARM HISTORY REPORT INVALID FUEL LEVEL AUG 16. 2010 12:50 PM ALARM HISTORv REPORT ---- Iht-TANK ALARM ----- ---- IN-TANK ALARM ----- T 3:DlESEL T I :UNLEADED OVERFILL ALARM DELIVERY NEEDED JUL 31, 2010 6:56 PM AUG 4, 2010 3:42 PM ---- IN-TANK ALARM ----- T 2:PREM I UIM PROBE OUT AUG 16, 2010 12:50 PM hxxxEND END xrix i - IN-TANK ALARM ----- T 3:DIESEL PROBE OUT AUG 16, 2010 12:50 PM ALARM HISTORY REPORT ALARM HISTORY REPORT ---- 11,1-TANK ALARM ----- ----- SENSOR ALARM -' L I :DISP I T 2:PREMIUM DISPENSER PA14 D AND G 233 2732 BRUNDAGE LN LOW PRODUCT ALARM BAKERSFFILD CA 9330 AUG 7. 2010 5:25 PM 661-326-1063 INVALID FUEL LEVEL AUG 16. 2010 12:51 PM AUG 8, 2010 1 :58 PM DELIVERY NEEDED SYSTEM STATUS REPORT JUL 26, 2010 11 :42 AM x h END r R - - - - - - - - - - - T 2:LOW PRODUCT?ALARM T 2:SUDDEN LOSS ALARM T 2:INVALID FUEL LEVEL T 2:PROBE OUT T 2:DELIVERY NEEDED x END x h x x T 3:LOW PRODUCT ALARM T 3:SUDDEN LOSS ALARM T 3:lNVALID FUEL LEVEL T 3:PROBE OUT T 3:DELIVER'Y NEEDED D AND G 233 IN-TANK ALARM ----- 2732 BRUNDAGE LN D AND G 233 T ! :UNLEADED BAKERSFFILD CA 9330 2732 BRUNDAGE LN DELIVERY NEEDED 661-326-1083 BAKERSFFILD CA 9330 AUG 16, 2010 12:52 PM 661-326-1083 AUG 16. 2010 1 :03 PM AUG Ib, 2010 1:06 PM SYSTEIN STATUS REPORT - - - - - - - - - - - - SYSTEM STATUS REPORT T 2:SUDDEN LOSS ALARM - - - - - - - - - - - - ALL FUNCTIONS NORMAL. ---- 1N-TANV ALARM ----- T ) :UNLEADED PROBE OUT AUG 16, 2010 12:52 PM ---- IN-TANK ALARM ----- WPLLD LINE LEAK ALARM T 2:PREMIUM W I :DIESEL HIGH PRODUCT ALARM WPLLD SHUTDOWN ALM AUG 16. 2010 1 :07 PM ---- IN-TANK ALARM AUG 16. 2010 1 :05 PM ----- T ) :UNLEADED LOW TEMP WARNING AUG 16, 2010 12:153 PM ---- IN-TANK. ALARM ----- WPLLD LINE LEAK ALARM T 2:PREMIUM W 2:UNLEADED PROBE OUT WPLLD SHUTDOWN ALM AUG 16, 2010 1 :07 PM AUG 16. 2010 1 :05 PM T 3:DIESEL INVENTORY INCREASE INCREASE START AUG 16. 2010 12:50 PM T 3: 1NVALID FUEL LEVEL VOLUME 427 GALS HEIGHT n 7.41 INCHES WATER - 0.00 INCHES WPLLD LINE LEAK ALARM TEMP - 88.0 DEG F W 3;PREMIUM WPLLD SHUTDOWN AL11 AUG 16. 2010 1 :05 PM INCREASE END AUG 16. 2010 12:54 PM VOLUME a 5274 GALS HEIGHT - 43.43 INCHES WATER = 0.83 INCHES TEMP = 90.3 DEG F GROSS IIdC;REASE- 4847 ----- SENSOR ALARM ----- TC NET INCREASE- 4182 L I :DISP 1 DISPENSER PAN FUEL ALARM AUG 16, 2010 1 :05 PM D AND G 233 2732 BRUNDAt;E LN BAKERSFFILD GA 9330 661-326-1083 T 2:PREM I Ul,l AUC 16. 2010 1 :07 PM INVENTORY INCREASE INCREASE START ---- 1N-TANK ALARM ----- AUG 16, 2010 1 :08 Pfl SYSTEM STATUS REPORT T I :UNLEADED - - - - - - - - - - - - LOW TEMP WARNING 7 2:1NVALID FUEL LEVEL T 2:H1GH PRODUCT' ALARM AUG 16, 2010 1 :09 PM VOLUME = 679 GALS HEIGHT = 10.16 INCHES T 2:PROBE OUT WATER - 0.00 INCHES TEMP - 105.1 DEG F INCREASE END AUG 16, 2010 1:11 PM VOLUME = 1942 GALS ---- IN-TANK ALARM ----- HEIGHT - 21 .00 INCHES T 3:DIESEL WATER - 0.81 INCHES HIGH PRODUCT ALARM TEMP = 105.1 DEG F AUG 16. 2010 1 :10 PM -- 114-TANK ALARM ----- GROSS INCREASE 1263 INVALID FUEL LEVEL 2: UM TO NET INCREASE- 1223 I AUG 16. 2010 1 :00 F'M ---- IN-TANY ALARM ----- T 3:DIESEL PROBE OUT AUG 16. 2010 1 :10 PM ---- IN-TANK ALARM ----- T 2:PREMIUM -- 1N-TANK ALARM PRODUCT ALARM T -:DIESEL AUG lo. 2010 1 :06 Phl INVALID FUEL LEVEL AUG 16. 2010 1 :11 PM T I :UNLEADED INVENTORY INCREASE INCREASE START ---- IN-TANK ALARM ----- AUG 16. 2010 1 :08 PM T LIVERYI VOLUME - 5461 GALS ---- 1N-TANK ALARM -- DELIVERY NEEDED 10 1 HEIGHT - 44,61 INCHES T 3:DIESEL AUG 16. 2010 t :uti PM WATER ¢ 0.00 INCHES DELIVERY NEEDED TEMP - 104.9 DEG F AUG 16. 2010 1 :11 PM INCREASE END AUG 16. 2010 1 :l1 PP1 VOLUME - 11327 GALS HEIGHT - 85.90 INCHES ---- IN-TANK ALAFb%l ----- WATER - 0.00 INCHES T I :UNLEADED TEMP - 105.4 DEG F OVERFILL AUaRM AUG lb. 2010 1 :08 PM GROSS INCREASE- 5866 TO NET INCREASE= 5676 ---- IN-TA14Y. ALARM ----- T I :UNLEADED PROBE OUT AUG 16. 2010 1 :09 PM D AND C 233 2732 BRUNDAGE LN BAKERSFFILD CA 9330 D AND G 233 661-326-1083 2732 BRUNDAGE LN BAKERSFFILD CA 9330 AUG 16, 2D10 1 : 11 Phi 661-326-1083 WPLLD LINE LEAK ALARM AUG 16, 2010 1 :31 P1M W 3:PREIM I UM SYSTEM STATUS REPORT WPLLD SHUTDOWN ALM - - - _ _ _ - _ AUG 16. 2010 1:13 PM T 3:DELIVERY NEEDED SYSTEM STATUS REPORT T 3:DELIVERY 14EEDED ----- SENSOR ALARM ----- L I :DISP I DISPENSER PAN T 3:DIESEL SENSOR OUT ALARM " INVENTORY INCREASE AUG 16, 2010 1 : 13 PiM WPLLD LINE LEAK ALARM INCREASE START W 2:UNLEADED AUG 16, 2010 1 :09 PM GROSS LINE FAIL hl VOLUME . 5275 GALS AUG 16, 2010 2:02 P HEIGHT - 43.44 INCHES WATER a 0.84 114CHES TEMP o 105.4 DEC F D AND C 233 INCREASE END 2732 BRUNDAGE LN AUG 16, 2010 1 :12 PM BAKERSFFILD CA 9330 661-326-1083 VOLUME - 11289 GALS WPLLD LINE LEAK ALARM HEIGHT - 85.51 INCHES AUG 16, 2010 1 :13 PM W 2:UNLEADED WATER 1 .60 INCHES WPLLD SHUTDOWN ALM TEMP a 105.4 DEC F AUG 16. 2010 2:02 Ph SYSTEM STATUS REPORT GROSS INCREASE- 6014 T 3:DELIVERY NEEDED TC NET 1NCREASEa 4784 L I :SENSOR OUT ALARM W I :WPLLD SHUTDOWN ALM W 2:WPLLD SHUTDOWN ALM D A14D G 233 W 3:WPLLD SHUTDOWN ALM 2732 BRUNDAGE LN BAKERSFFILD CA 9330 661-326-1083 AUG 16. 2010 2:03 PM WPLLD LINE LEA}: ALARM W 1 :D1£SEL WPLLD SHUTDOWN ALM SYSTEM STATUS REPORT AUG 16. 2010 m3 PM - - - - - - - - - - - - T 3:DELIVERY NEEDED D AND G 233 W 2:GROSS L114E FAIL 2732 BRUNDAGE LN W 2:WPLLD SHUTDOWN ALM BAKERSFFILD CA 9330 661-326-1083 AUG 16, 2010 I :31 Ph{ WPLLD LINE LEAK ALARM W 2:UNLEADED WPLLD SHUTDOWN ALM SYSTEM STATUS REPORT AUG 16. 2010 1 :13 PM T 3:DELIVERY NEEDED - D AND G 233 D AND G 233 2732 BRUNDAGE LN 2732 BRUNDAGE LN BAKERSFFILD CA 9330 BAKERSFFILD CA 9330 661-326-1083 661-326-1083 AUG 16, 2010 2:14 PM AUG 16, 201 2:05 PM SYSTEM STATUS REPORT SYSTEM STATUS REPORT - - - - - - - - - - - - - - - - - - - - - - - - T 3:DELIVERY NEEDED T 3:DELIVERY NEEDED W 3:GROSS LINE FAIL W 2:GROSS LINE FAIL W 3:WPLLD SHUTDOWN ALM W 2:WPLLD SHUTDOWN ALM D AND G 233 WPLLD LIME LEAK ALARM 2732 BRUNDAGE LN W 3:PREMIUM BAKERSFFILD CA 9330 GROSS LINE FAIL 661-326-1083 AUG 16. 2010 2:13 PM AUG 16. 2010 2:22 PM SYSTEM STATUS REPORT - T 3:DELIVERY NEEDED WPLLD LINE LEAK ALARM W 3:PREMIUM WPLLD SHUTDOWN ALM AUG 16, 2010 2: 13 PM WPLLD LINE LEAK ALARM W I :DIESEL GROSS LINE FAIL AUG 16, 2010 2:26 PM D AND C 233 2732 BRUNDAGE LN BAKERSFFILD CA 9330 661-326-1083 AUG 16. 2010 2:14 PM SYSTEM STATUS REPORT WPLLD LINE LEAK ALARM - - - - - _ - - - - - - W [ :DIESEL T 3:DELIVERY NEEDED WPLLD SHUTDOWN ALM AUG 16. 2010 2:26 PM W 3:GROSS LINE FAIL W 3:WPLLD SHUTDOWN ALM D A14D G 233 2732 BRU14DAGE LN BAKERSFFILD CA 9330 661-326-1083 AUG 16. 2010 2:30 PM SYSTEM STATUS REPORT . - T 3:DELIVERY NEEDED SWRCB,January 2006 Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printouts from tests (f applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: #233 D and G I Date of Testing: 8/16/2010 Facility Address: 2732 Brundage Lane , Bakersfield,CA 93304 Facility Contact: Omero Garcia I Phone: 661-393-7000 Date Local Agency Was Notified of Testing : 7/23/10 Name of Local Agency Inspector(f present during testing): Erina Medina 2. TESTING CONTRACTOR INFORMATION Company Name: Confidence UST Services, Inc. Technician Conducting Test: Bryan A Self Credentials: X CSLB Contractor X ICC Service Tech. ❑ SWRCB Tank Tester ❑Other(Spec) License Number(s): CSLB#804904 ICC 98022804-UT 3. SPILL BUCKET TESTING INFORMATION Test Method Used: x Hydrostatic ❑Vacuum ❑Other Test Equipment Used: Lake Test Equipment Resolution: 0.0625" Identify Spill Bucket(By Tank 1 Regular 2 Diesel 3 Super 4 Number, Stored Product, etc. Bucket Installation Type: ❑Direct Bury ❑Direct Bury ❑ Direct Bury ❑ Direct Bury x Contained in Sump x Contained in Sump x Contained in Sump ❑Contained in Sum Bucket Diameter: 12.00" 12.00" 12.00" Bucket Depth: 13.50" 14.25" 14.25" Wait time between applying 5 min. 5 min. 5 min. vacuum/water and start of test: Test Start Time(Ti): 1:00pm 1:00pm 1:00pm Initial Reading(Rj): 11.00" 11.50" 11.001, Test End Time(TF): 2:00pm 2:00pm 2:00pm Final Reading(RF): 11.00" 11.50" 11.00" Test Duration(TF—T,): 1 hour I hour 1 hour Change in Reading(RF-Ri): 0.00" 0.00" 0.00" Pass/Fail Threshold or 0.0625" 0.0625" 0.0625" Criteria: Test Result: X Pass ❑Fail X Pass ❑Fail X Pass ❑Fail ❑ Pass ❑Fail Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) The repaular SB was pasing- but would not allow aas to drain back into tank and Needs to be replaced. CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true,accurate,and in full compliance with legal requirements. Technician's Signature:'&AA Date: 8/16/2010 State laws and regulations do not c require testing to be performed by a qualified contractor. However,local requirements may be more stringent.