HomeMy WebLinkAboutFMC 2011 RESULTS IIIIIIIIIIIIIIIIIIII 41 MONITORING SYSTEM CERTIFICATION
IE
For Use By All Jurisdictions Within the State of California
Authority Cited:Chapter 6.7, Health and Safety Code;Chapter 16, Division 3, Title 23, California Code of Regulations
This form must be used to document testing and servicing of monitoring equipment.A separate certification or report must be prepared for each monitoring
system control anel by the technician who performs the work. A Copy of this form must be provided to the tank system owner/operator.The
owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility Name: PENSKE BAKERSFIELD Bldg.No:
Site Address: 2929 E. BRUNDAGE LANE City: BAKERSFIELD Zip:
Facility Contact Person: Phone: Fax:
Make/Model of Monitoring System: VEEDER ROOT SIMPLICITY Date of Testing/Servicing: 2/10/2011
B. Inventory of Equipment Test/Certified
Check the appropriate boxes to indicatespecific equipment inspected/serviced:
Tank ID: DIESEL NORTH Tank ED: DIESEL SOUTH
hi-Tank Gauging Probe. Model: In-Tank Gauging Probe. Model:
Annular Space or Vault Sensor. Model: 301 T Annular Space or Vault Sensor. Model: 301
Piping Sump/Trench Sensor(s). Model: 352 Piping Sump/Trench Sensor(s). Model: 352
Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model: T Mechanical Line Leak Detector. Model: RED JACKET
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
Tank Overfill/High Level Sensor. Model: OPW Flaper Tank Overfill/High Level Sensor. Model: OPW Flaper
X Other(specify equipment type and model in Section E on Page 2) X Other(specify equipment type and model in Section E on Page 2)
Tank ID• Tank ED:
In-Tank Gauging Probe. Model: hi-Tank Gauging Probe. Model:
Annular Space or Vault Sensor. Model: Annular Space or Vault Sensor. Model:
Piping Sump/Trench Sensor(s). Model: Piping Sump/Trench Sensor(s). Model:
Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model: Mechanical Line Leak Detector. Model:
H Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
Tank Overfill/High Level Sensor. Model: Tank Overfill/High Level Sensor. Model:
E]Other(specify equipment type and model in Section E on Page 2) Other(specify equipment type and model in Section E on Page 2)
Dispenser ED: MASTER 1-2 Dispenser ID: SATELITE 1
Dispenser Containment Sensor(s). Model: 352 Dispenser Containment Sensor(s). Model: 322
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s)and Chain(s). Dispenser Containment Float(s)and Chain(s).
oft
Dispenser ID: SATELITE 2 Dispenser ID:
Dispenser Containment Sensor(s). Model: 322 Dispenser Containment Sensor(s). Model:
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s)and Chain(s). Dispenser Containment Float(s)and Chain(s).
Dispenser ID: DI Buser ID:
Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s), Mode
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s)and Chain(s). Dispenser Containment Float(s)and Chain(s). aw
•If the facility contains more thanks or dispensers,copy this form Include information for every tank and dispenser at the facility.
C.Certification-I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers'guidelines.
Attached to this Certification is information(e.g.manufacturers'checklists)necessary to verify that this information is correct and a Plot Plan showing
the layout of monitoring equipment. For any equipment capable of generating such reports,I have also attached a copy of the report;(check all that
apply): _X_System set-up X_Alarm History report
Technician Name(print): Gerardo Zuniga Signature:
Certification No.: B34891 License No 745065 A,B-Haz
Testing Company Name: Tank Specialists of California Ph el o.: (g09)273-0900
Facility Address: 560 Birch Street, Unit#3 Lake Elsinore, Ca Date of T,esfing/Servicing: 2/10/2011
Monitoring System Certification Page 1 of 3 03/01
PENSKE BAKERSFIELD Mont Cert 2-10-2011.)ds I IIIII�VIII III IIII 42
IE
D. Results of Testing/Servicing
PENSKE BAKERSFIELD
Software Version
Installed: 123.01 2/10/2011
Complete the following checklist:
X Yes No* Is the audible alarm operational?
X Yes No* Is the visual alarm operational?
]Yes No* Were all sensors visually inspected,functionally tested,and confirmed operational?
X Yes No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not
interfere with their proper operation?
LX Yes No* If alarms are relayed to a remote monitoring station,is all communications equipment(e.g.modem)operational?
N/A
X Yes No* Fore pressurized piping systems,does the turbine automatically shut down if the piping secondary containment monitoring system
N/A detects a leak,fails to operate,or is electrically disconnected? If yes:which sensors initiate positive shut-down?(Check all that
apply)_X_Sump/Trench Sensors _X_Dispenser Containment Sensors. Did you confirm positive shut-down due to leaks and
sensor failure/disconnection? X Yes No.
Yes No* For Tank systems that utilize the monitoring system as the primary tank overfill warning device(ie.,no mechanical
WN/A overfill prevention valve is installed),is the overfill warning alarm visible and audible at the tank fill point(s)and
operating properly?If so,at what percent of tank capacity does the alarm trigger? %
Yes X No Was any monitoring equipment replaced? If yes,identify specific sensors,probes,or other equipment replaced and
list the manufacturer name and model for all replacement parts in Section E,below.
Yes X No Was liquid found inside any secondary containment systems designed as dry systems?(Check all that apply)
Product; _Water. If yes,describe causes in Section E,below.
X Yes No* Was monitoring system set-up reviewed to ensure proper settings?Attached set up reports,if applicable.
X Yes No* Is all monitoring equipment operational per manufacturer's specifications?
* In Section E below,describe how and when these deficiencies were or will be corrected:
E.Comments:
There is also oil line low point sensor 420
Monitoring System Certification
Page 2 of 3 03/01
PENSKE BAKERSFIELD Mont Cart 2-102011.x1s
F.'fn=Tank Gauging/ SIR Equipment:
eX Check this box if tank gauging is used only for inventory control.
Check this box if no tank gauging or SIR equipment is installed.
Complete the following checklist:
Ex Yes E]No* Has all input wiring been inspected for proper entry and termination,including testing for ground faults?
❑x Yes E]No* Were all tank gauging probes visually inspected for damage and residue buildup?
aYes E]No* Was accuracy of system product level reading tested?
QYes []No* Was accuracy of system water level readings tested?
lEx Yes nNo* Were all probes reinstalled properly?
Eyes No* Were all items on the equipment manufacturer's maintenance checklist completed?
* In the Section H,Below,describe how and when these deficiencies were or will be corrected.
G.Line Leak Detectors(LLD):
Check this box if LLDs are not installed.
Complete the following checklist:
❑X Yes No* For equipment start-up or annual equipment certification,was a leak simulated to verify LLD performance?(Check
N/A all that apply) Simulated Leak rate: X_3 g.p.h. 0.1 g.p.h. 0.2 g.p.h.
X Yes No Were all LLDs confirmed operational and accurate within regulatory requirement?
X Yes No Was the testing apparatus properly calibrated?
X Yes No* For Mechanical LLDs,does the LLD restrict product flow if it detects a leak?
N/A
Yes No* For electronic LLDs,does the turbine automatically shut off if the LLD detects a leak?
X N/A
Yes No* For electronic LLDs,does the turbine automatically shut off if any portion of the monitoring system is disabled or
EX N/A disconnected?
Yes No* For electronic LLDs,does the turbine automatically shut off if any portion of the monitoring system malfunctions or
X N/A fails a test?
V Yes No* For electronic LLDs,have all accessible wiring connections been visually inspected?
N/A
s [-]No* Were all items on the equipment manufacturer's maintenance checklist completed?
* In Section H below,describe.how and when these deficiencies were or will be corrected:
H.Comments:
Monitoring System Certiflcation
Page 3 of 3 03/01
PENSKE BAKERSFIELD Mont Cent 2-10-2011.xls
Facility Name: PENSKE BAKERSFIELD Test Date: 2/10/2011
1. SPILL/OVERFILL CONTAINMENT BOXES
Facility is Not Equipped With Spill/Overfill Containment Boxes
Spill/Overfill Containment Boxes are Present,but were Not Tested
Test Method Developed By: Spill Bucket Manufacturer ❑ Industry Standard E] Professional Engineer
Other(Specify)
Test Method Used: ❑ Pressure Vacuum 1XI Hydrostatic
E] Other(Specify)
Test Equipment Used: INCON ui ment Resolution:
DSL.FILL IS.DSL FILL Sill Box# Spill Box# Spill Box#
Bucket Diameter: 12 IN. 12 IN.
Bucket Depth: 13 IN. 12 1/2 IN.
Wait time between applying
pressure/vacuum/water and
starting test:
Test Start Time: 10:54 AM AM
Initial Reading(R): 4.5531 IN. IN.
Test End Time: 11:09 AM AM
Final Reading(RF): 4.5525 IN. IN.
Test Duration: 15 MIN. 15 MIN.
Change in Reading(RF-R): 0.0006 IN. IN.
Pass/FaiI Threshold or Criteria: 0.002 IN. 0.002 IN.
Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests)
SOUTH FILL SPILL BUCKET FAILED DUE TO SPILL BUCKET NEED TO REPLACE DREICT BURY OPW SPILL
UST Monitoring Site Plan
Date: 2/10/2011
Site Location: PENSKE BAKERSFIELD
2929 E. BRUNDAGE
BAKERSFIELD ,CA 93307
SHOP ESO
VEEDER ROOT SIMPLICIT
SATELITE DISPENSER#2 OIL LINE
322 SENSOR 420 SENSOR
MASTER DISPENSER# 1-2
352 SENSOR
SATELITE DISPENSER# 1
322 SENSOR
ANNULAR SPACE PIPING SUMP
301 SENSOR
FILL SPILL BUCKE
352 SENSOR
NORTH DIESEL TANK
SIPHONE TANK
OPW DROP TUIAES WITH FLAPERS RED JACKET LINE LEAK
DETECTOR
SOUTH DIESEL TANK
PIPING SUMP
301 SENSOR 352 SENSOR
FILL SPILL BUCKET I ANNULAR SPACE
INSTRUCTIONS
If you already have a diagram that shows all required information,you may include it,rather than this page,with your Monitoring
System Certification. On your site plan,show the general layout of tanks and piping.Clearly identify locations of the following
equipment,if installed; monitoring system control panels;snesors monitoring tank annular spaces,sumps,dispenser pans,spill
containers,or other secondary containment areas;mechanical or electronic line leak detectors;and in-tank liquid level probes(if used
for leak detection). In the space provided,note the date this Site Plan was prepared.
Tank Specialists of California (888) 606-TANK
(#745065 A,B-HAZ)
Page 4
109755 ROLLING 140 SYSTEM SETUP RS-232 END OF MESSAGE
2929 E BRUNDAGE — — — — — — — — — — — — DISABLED
BAKERSFIELD. CA FEB 10, 2011 10:08 AM COMMUNICATIONS SETUP — —
80448302105001 — — — —
FEB 10, 2011 10:08 AM
SYSTEM UNITS PORT SETTINGS:
U.S. 1 (FXMOD)
SYSTEM LANGUAGE COMM BOARD
SYSTEM STATUS REPORT ENGLISH BAUD RATE 2400
ITY ODD
SYSTEM DATE/TIME FORMAT PAR
ALL FUNCTIONS NORMAL MON DD YYYY HH:MM:SS xM STOP BIT 1 STOP
DATA LENGTH: 7 DATA
109755 ROLLING 140 RS-232 SECURITY
2929 E BRUNDAGE CODE : DISABLETONE
BAKERSFIELD CA DIAL TYPE 1 RING
80448302105001 ANSWER ON
SHIFT TIME 1 5:45 AM ' MODEM SETUP STRING :
SHIFT TIME 2 DISABLED DIAL TONE INTERVAL: 32
SHIFT TIME 3 DISABLED i 2 (S—SAT )
109755 ROLLING 140 SHIFT TIME 4 DISABLED ! COMM BOARD 9600
2929 E BRUNDAGE BAUD RATE NONE
BAKERSFIELD CA TANK PER TST NEEDED WRN PARITY I STOP
80448302105001 DISABLED STOP HIT
TANK ANN TST NEEDED WRN DATA LENGTH:-8 DATA
FEB 10, 2011 10:08 AM DISABLED I RS-232 SECURITY
CODE : DISABLED
LINE RE—ENABLE METHOD DTR NORMAL STATE: HIGH
PASS LINE TEST I
SYSTEM— —STATUS REPORT 1 RECEIVER SETUP:
— — — — — — — — LINE PER TST NEEDED WRN
ALL FUNCTIONS NORMAL DISABLED
LINE ANN TST NEEDED WRN
INVENTORY REPORT DISABLED D 8:VEEDER ROOT (FMS)
PRINT TC VOLUMES RCVR TYPE: COMPUTER
T 1 :DIESEL 1 SOUTH ENABLED PORT NO. 2
VOLUME = 7161 GALS RETRY NO: 5
ULLAGE = 4266 GALS TEMP COMPENSATION RETRY DELAY: 5
90 ULLAGE= 3123 GALS VALUE (DEG F ) : 60.0 's CONFIRMATION REPORT: OFF
TC VOLUME = 7137 GALS STICK HEIGHT OFFSET
HEIGHT = 52.70 INCHES DISABLED
WATER VOL = 0 GALS
WATER = 0.00 INCHES H—PROTOCOL DATA FORMAT
TEMP = 67.1 DEG F HEIGHT
DAYLIGHT SAVING TIME
ENABLED i
T 2:DIESEL 2 NORTH START DATE !
VOLUME = 6636 GALS MAR WEEK 3 SUN
ULLAGE = 4791 GALS START TIME
90% ULLAGE= 3648 GALS 2:00 AM
TC VOLUME = 6615 GALS END DATE AUTO DIAL TIME SETUP:
HEIGHT = 49.51 INCHES NOV WEEK 1 SUN
WATER VOL = 0 GALS END TIME
WATER = 0.00 INCHES 2:00 AM D 8:VEEDER ROOT (FMS)
TEMP = 66.9 DEG F DIAL WEEKLY
RE—DIRECT LOCAL PRINTOUT WED 3:15 AM
DISABLED DIAL TIME
RECEIVER REPORTS:
EURO PROTOCOL PREFIX 1 1 :DIESEL 1 SOUTH
S PRODUCT CODE 1
THERMAL COEFF : .000450
TANK DIAMETER 90.00
TI'y
RS-232 FND OF MESSAGE
DISABLED' '
ALARM T 2:DIESEL 2 NORTH
AUTO DIAL ALAR
_ _ _ _ _ _ PRODUCT CODE 2
FLOAT SIZE: 4.0 IN. THERMAL COEFF : .000450
D 8:VEEDER ROOT (FMS) TANK DIAMETER 90.00
WATER WARNING 2.0 TANK PROFILE 4 PTS
IN-TANK ALARMS HIGH WATER LIMIT: 3.0 FULL VOL
11427
ALL:LEAK ALARM 67.5 INCH VOL 9435
ALL:HIGH WATER ALARM MAX OR LABEL VOL: 11594 45.0 INCH VOL 5888
ALL:OVERFILL ALARM OVERFILL LIMIT 891/0 22.5 INCH VOL 2289
ALL:LOW PRODUCT ALARM 10318
HIGH PRODUCT 94%
ALL:SUDDEN' LOSS ALARM 1094% FLOAT SIZE;
ALL:HIGH PRODUCT ALARM DELIVERY LIMIT 12% 4.0 IN.
ALL: INVALID FUEL LEVEL 1391 WATER WARNING
ALL:PROHE OUT 2.0
ALL:HIGH WATER WARNING LOW PRODUCT 1000 HIGH WATER LIMIT: 2.5
ALL:DELIVEOD NEEDED LEAK ALARM LIMIT: 25 MAX OR LABEL VOL: 11594
ALL:MflX PRODUCT ALARM SUDDEN LOSS LIMIT: 25 OVERFILL LIMIT
ALL:GROSS TEST FAIL 89%
TA
ALL:PERIODIC TEST FAIL TANK TILT 0.70 10318
ALL:ANNUAL TEST FAIL PROBE OFFSET 0.70 HIGH PRODUCT 94%
ALL:PER TST NEEDED WRN 10898
ALL:PER TST NEEDED ALM SIPHON MANIFOLDED TANKS DELIVERY LIMIT
12%
ALL:NO CSLD IDLE TIME 1391
ALL:CSLD INCR RATE WARN T#: NONE
ALL:ACCU_CHART CAL WARN LINE OANIFOLDED TANKS LOW PRODUCT 1000
ALL:RECON WARNING T#: NONE LEAK ALARM LIMIT: 25
SUDDEN LOSS LIMIT: 25
RLL:RECON ALARM TANK TILT
ALL:LOW TEMP WARNING LEAK MIN PERIODIC: 25% 1 .25
PROBE OFFSET
ALL:GROSS FAIL LINE TNK 2898 1 .25
LIQUID SENSOR ALMS LEAK MIN ANNUAL 25o SIPHON MANIFOLDED TANKS
ALL:FUEL ALARM 2898 T#: NONE
ALL:SENSOR OUT ALARM LINE MANIFOLDED TANKS
ALL:SHORT ALARM T#: NONE
ALL:WATER ALARM PERIODIC TEST TYPE
ALL:WATER OUT ALARM STANDARD
ALL:HIGH LIQUID ALARM LEAK MIN PERIODIC: 25%
ALL:LOW LIQUID ALARM ANNUAL TEST FAIL � 2898
ALL:LIQUID WARNING ALARM DISABLED
LEAK MIN ANNUAL
RECEIVER ALARMS PERIODIC TEST FAIL 2898
SERVICE REPORT WARN ALARM DISABLED
ALARM CLEAR WARNING GROSS TEST FAIL PERIODIC TEST TYPE
ALARM DISABLED STANDARD
ANN TEST AVERAGING: OFF ANNUAL TEST FAIL
PER TEST AVERAGING: OFF ALARM DISABLED
TANK TEST NOTIFY: OFF PERIODIC TEST FAIL
TNK TST SIPHON BREAK:OFF ALARM DISABLED
GROSS TEST FAIL
DELIVERY DELAY 5 MIN ALARM DISABLED
IN-TANK SETUP PUMP THRESHOLD : 10.00%
- _ - _ - - - - _ ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
T 1 :DIESEL 1 SOUTH TANK TEST NOTIFY: OFF
PRODUCT CODE 1
THERMAL COEFF : .000450 TNK TST SIPHON BREAK:OFF
TANK DIAMETER 90.00
TANK PROFILE 4 PTS DELIVERY DELAY
FULL VOL 11427 PUMP THRESHOLD 5 MITI
LD
67.5 INCH VOL 9435 : 10.00%
45.0 INCH VOL 5888
22.5 INCH VOL 2289
TEST WEEKLY : ALL TANK- OUTPUT RELAY SETUP
SAT - - - - - - - - - - - -- ----- SENSOR ALARM -----
START TIME : 10:00 PM L S:ANNULAR 1 TANK
TEST RATE :0.20 GAL/HR R 1 :ALARM ANNULAR SPACE
DURATION 2 HOURS TYPE: LOW LIQUID ALARM
STANDARD FEB 10, 2011 10:05 AM
TST EARLY STOP:DISABLED NORMALLY CLOSED
LEAK TEST REPORT FORMAT
ENHANCED IN-TANK ALARMS
ALL:HIGH WATER ALARM
T 1 :LOW PRODUCT ALARM
ALL:SUDDEN LOSS ALARM
ALL:GROSS TEST FAIL
LIQUID SENSOR ALMS ----- SENSOR ALARM -----
L 1 :FUEL ALARM L 6:STP SUMP 1 TANK
L 3:FUEL ALARM STP SUMP
L 4:FUEL ALARM FUEL ALARM
L 5:FUEL ALARM FEB 10, 2011 10: 10 AM
L 6:FUEL ALARM
LIQUID SENSOR SETUP L 7:FUEL ALARM
- - - - - - - - - - - - L 8:FUEL ALARM
ALL:SENSOR OUT ALARM
L 1 :SATELITE DISP PAN ALL:SHORT ALARM
DUAL FLT. HIGH VAPOR ALL:LOW LIQUID ALARM
CATEGORY : DISPENSER PAP! L 8:LIQUID WARNING
----- SENSOR ALARM -----
L 2:0IL LINE L 7:ANNULAR 2 TANK
TRI-STATE (SINGLE FLOAT) ANNULAR SPACE
CATEGORY : PIPING SUMP LOW LIQUID ALARM
FEB 10, 2011 10:10 AM
L 3:PIPING MID PAN
DUAL FLT. HIGH VAPOR
CATEGORY : DISPENSER FAN
RECONCILIATION SETUP
L 4:SATELITE DISP PAN S
DUAL FLT. HIGH VAPOR AUTOMATIC DAILY CLOSING
CATEGORY DISPENSER PAN TIME: 2:00 AM ----- SENSOR ALARM --
---
L 7:ANNULAR 2 TANK
PERIODIC RECONCILIATION ANNULAR SPACE
MODE: MONTHLY LOW LIQUID ALARM
L 5:ANNULAR 1 TANK FEB 10.2011-1'9:11 All
DUAL FLOAT HYDROSTATIC TEMP COMPENSATION
CATEGORY : ANNULAR SPACE STANDARD
BUS SLOT FUEL METER TANK
L 6:STP SUMP 1 TANK TANK MAP EMPTY
DUAL FLT. HIGH VAPOR
CATEGORY : STP SUMP
----- SENSOR ALARM -----
L 7:ANNULAR 2 TANK L B:STP SUMP 2 TANK
DUAL FLOAT HYDROSTATIC STP SUMP
CATEGORY : ANNULAR SPACE LIQUID WARNING
FEB10r 2011 10:11 AM
L 8:STP SUMP 2 TANK
----- SENSOR ALARM -----
L 3:PIPING MID PAN ----- SENSOR ALARM -----
DISPENS.ER -PAN L 8:STP SUMP 2 TANK
FUEL ALARM STP SUMP
FEB 10, 2011 10:13 AM SENSOR OUT ALARM
FEB 10, 2011 10: 16 AM ALARM HISTORY REPORT
-- SYSTEM ALARM --
PAPER OUT ---
JAN 19, 20
PRINTER 5:34 FM
IVTER ERROR
JAN 19, 2011 5:34 PM
BATTERY IS OFF
JAN 1 , 1996 8:00 AM
----- SENSOR ALARM -----
L 1 :SATELITE DISP PAN
DISPENSER PAN
SENSOR OUT ALARM
FEB 10, 2011 10: 16 All
* * END * n
----- SENSOR ALARM -----
L 2:011- LINE
PIPING SUMP
SENSOR OUT ALARM
SENSOR ALARM ----- FEB 10, 2011 10:16 All
L 1 :SATELITE DISP FAN
DISPENSER PAN ALARM HISTORY REPORT
FUEL ALARM
FEB 10, 2011 10: 14 AM IN-TANY•. ALARM -
T 1 :DIESEL 1 SOUTH
SETUP DATA WARNING
-- SENSOR ALARM ----- AUG 11 , 2009 11 :26 AM
L P PAN MID PAN
DISPENSER HIGH WATER ALARM
ENS OCT 2
SENSOR OUT ALARM OC 2009 10:44 AM
T 15,
FEB 10, 2011 10: 16 AM 2004 10:52 All
----- SENSOR ALARM ----- OCT 2, 2003 11 :18 AM
L 2:0IL LINE
PIPING SUMP OVERFILL ALARM
FUEL ALARM JUN 18, 2010 12: 19 PM
FEB 10, 2011 10: 15 AM FEB 10, 2010 10:49 All
JAN 29, 2010 4:40 PM
LOW PRODUCT ALARM
AUG 11 , 2009 11 :28 AM
-- SENSOR ALARM ----- JUN 13, 2009 10:37 AM
L 4:SATEL.ITE DISP PAN S JUL 22, 2008 5:47 PM
--_-- DISPENSER PAN HIGH PRODUCT
SENSOR OUT ALARM OCT 28, '.)00
ALARM AM
FEB 10, 2011 10: 16 AM FEB 22, X9 10:40
-- SENSOR ALARM DEC 26, `007 8:50 AM
L 5:ANNULAR 1 TANK 2006
ANNULAR SPACE 8:19 AM
ALID
SENSOR OUT ALARM INVALID FUEL LEVEL
FEB 10, 2011 10:16 AM OCT 2 15, 2004 10:40 AM
2003 11 : 15 All
----- SENSOR ALARM -----
L 6:STP SUMP 1 TANK
STP SUMP
SENSOR OUT ALARM
SENSOR ALARM -----
FEB 10, 2011 10: 16 AM
-----
L 7:ANNULAR 2 TANK
ANNULAR SPACE
SENSOR OUT ALARM
FEB 10, 2011 10:16 AM
INVALID FUEL LEVEL ALARM H 1 STORY xh1'QX 1
PROBE OUT OCT 9, 2009 9:31 AM SENSOR ALARM -----
DEC ' 9, 2009 4:42 PM JUN 13, 2009 9:22 AM L 2:0IL LINE
OCT 28, 2009 11 : 16 AM JUN 2, 2009 9:20 AM PIPING SUMP
OCT 28, 2009 11 :09 AM PROBE OUT SENSOR OUT ALARM
HIGH WATER WARNING DEC 9, 2009 4:38 PM FEB 10, 2011 10: 16 AM
OCT 28, 2009 10:44 AM OCT 28, 2009 10:28 AM FUEL ALARM
OCT 15, 2004 10:52 AM OCT 9, 2009 9:49 AM FEB 10, 2011 10: 15 AM
FEB 2, 2004 10:22 AM
HIGH WATER WARNING FUEL ALARM
DEC 9, 2009 4:46 PM JAN 13, 2011 11 :36 PM
DELIVERY NEEDED OCT 9, 2009 9:48 AM
AUG 11 , 2009 11 :28 AM OCT 9, 2009 7:38 AM
JUN 12, 2009 4:39 PM
JUN 2, 2009 7:51 AM
DELIVERY NEEDED
MAX PRODUCT ALARM JUN 12, 2009 2:39 PM
OCT 28, 2009 11 :06 AM JUN 1 , 2009 2:17 PM
OCT 28, 2009 10:40 AM MAR 10, 2009 5:04 PM
OCT 15, 2004 10:29 AM
MAX PRODUCT ALARM
OCT 9, 2009 9:39 AM * € END
LOW TEMP WARNING OCT 15, 2004 10:28 AM
OCT 15, 2004 10:29 All OCT 2, 2003 11 :13 AM
LOW TEMP WARNING
OCT 28, 2009 10:39 AM
OCT 8, 2009 3:05 PM
OCT 15, 2004 11 :02 AM
* END ALARM HISTORY REPORT
----- SENSOR ALARM -----
L 3:PIPING MID PAN
DISPENSER PAN
SENSOR OUT ALARM
* * END FEB 10, 2011 10: 16 AM
FUEL ALARM
FEB 10, 2011 10: 13 AM
SENSOR OUT ALARM
DEC 9, 2010 10:04 All
ALARM HISTORY REPORT
---- IN-TANK ALARM -----
T 2:DIESEL 2 NORTH
HIGH WATER ALARM ALARM HISTORY REPORT
OCT 9, 2009 9:48 AM
OCT 15, 2004 10:52 AM ----- SENSOR ALARM -----
OCT 2, 2003 11 : 18 AM L 1 :SATELITE DISP PAN
DISPENSER PAN * END x
OVERFILL ALARM SENSOR OUT ALARM
FEB 16, 2010 12:31 PM FEB 10, 2011 10: 16 AM
OCT 9, 2009 9:39 All
JUL 2, 2009 6:42 AM FUEL ALARM
FEB 10, 2011 10:14 AM
LOW PRODUCT ALARM
JUN 12, 2009 4:48 PM SENSOR OUT ALARM
JUN 2, 2009 8:23 All DEC 9, 2010 10:04 AM
JUL 22, 2008 2:07 PM
HIGH PRODUCT ALARM
OCT 9, 2009 9:39 AM ALARM HISTORY REPORT
FEB 22, 2007 8:36 AM
OCT 18, 2006 9:36 AM ----- SENSOR ALARM -----
L 4:SATELITE DISP PAN S
DISPENSER PAN
SENSOR OUT ALARM
FEB 10, 2011 10: 16 AM
FUEL ALARM
FEB 10, 2011 10:12 AM
FUEL ALARM
DEC 9, 2010 9:58 AM
ALARM HISTORY REPORT
----- SENSOR ALARM -----
ALARM HISTORY REPORT L 7:ANNULAR 2 TANK
ANNULAR SPACE
----- SENSOR ALARM ----- SENSOR OUT ALARM
L 5:ANNULAR 1 TANK FEB 10, 2011 10: 16 AM
ANNULAR SPACE LOW LIQUID ALARM
SENSOR OUT ALARM FEB 10, 2011 10: 11 AM
FEB 10, 2011 10: 16 AM
LOW LIQUID ALARM LOW LIQUID ALARM
FEB 10, 2011 10:09 All FEB 10, 2011 10: 10 AM
LOW LIQUID ALARM
DEC 9, 2010 9:54 AM
* END
* * END
ALARM HISTORY REPORT
----- SENSOR ALARM -----
ALARM HISTORY REPORT L B:STP SUMP 2 TANK
STP SUMP
-- SENSOR ALARM ----- SENSOR OUT ALARM
L 6:STP SUMP 1 TANK FEB 10, 2011 10:16 AM
STP SUMP LIQUID WARNING
SENSOR OUT ALARM FEB 10, 2011 10: 11 AM
FEB 10, 2011 10:16 AM
SENSOR OUT ALARM
FEB 10, 2011 10:1.
FUEL ALARM DEC 9, 2010 10:04 AM
0 AM
FUEL ALARM
DEC 9, 2010 9:56 AM
ri n END n
PENSKE BAKERSFIELD
2929 E, BRUNDAGE LANE
BAKERSFIELD CA 93307
02/10/2011 11:09 AM
SUMP LEAK TEST REPORT
NFILBKT
TEST STARTED 10:54 AM
TEST STARTED 02/10/2011
BEGIN LEVEL 4,5531 IN
END TIME 11:09 AM
END DATE 02/10/2011
END LEVEL 4.5525 IN
LEAK THRESHOLD 0,002 IN
TEST RESULT PASSED
PENSKE BAKERSFIELD
2929 E, BRUNDAGE LANE
BAKERSFIELD CA 93307
02/10/2011 11:24 AM
SUMP LEAK TEST REPORT
NFILBKT
TEST STARTED 11:09 AM
TEST STARTED 02/10/2011
BEGIN LEVEL 4,5525 IN
END TIME 11:24 AM
END DATE 02/10/2011
END LEVEL 4,5523 IN
LEAK THRESHOLD 0.002 IN_
TEST RESULT PASSED
WORK ORDER
Tank Specialists of California
e
560 Birch Street, Building #3 Lake Elsinore, CA 92530
(888) 606-TANK (8265) FAX (951) 245-2886 DATE
License#745065 A,B-HAZ
❑A.M.
❑
P.M.
BILL TO PHONE
ADDRESS TECHNICIAN
CITY LABORER
JOB NAME AND LOCATION
CONTACT NAME&#:
DESCRIPTION OF WORK
QUANTITY DESCRIPTION OF WORK PERFORMED
Z ZZ X5012 P/4fi5E_D t OP— cq"-r
3 s�NSo2 0, s�e9
3 o r s�.vso2 Pi4 ss .'00
ZO S�NSvlZ /0 -1�rP
�uca' 7
ADDITIONAL WORK REQUIRED -
s�-�
PARTS USED
HOURS LABOR AMOUNT TOTAL
TECHNICIAN @ MATERIALS
LABORER @ TOTAL
LABOR
I h e acknowledge the satisfactory TOTAL LABOR TAX
co e n of the ab=described work.
SIGNATURE y DATE COMPLETED TOTAL
TANK SPECIALISTS OF CALITORNIA
s YOUR PARTNER IN A GREENER ENVIRONMENT
r
February 23, 2011
Bakersfield Fire Prevention Services
Attn: Inspector-Ernie Medina
2101 "H" Street
Bakersfield, CA 93301
Re: Test Results
Please find attached test results for the following facilities housing fuel storage systems:
TSOC Client Name Results for this testing: Date of Test
Penske Truck Leasing Monitoring Certification 2/10/2011
2929 E. Brundage Lane
Bakersfield, CA 93307
Please note we will mail the original copies of these results to our customers for them to have on
site at their facility if you should need to review the results during your inspections.
If you have any questions or concerns, please give me a call.
Thank you,
TANK SPECIALISTS OF CALIFORNIA
George Aguilar
Testing and Maintenance Coordinator
WWW.TANK-SPECIALISTS.COM
LIC. #745065 A, 9-HAZ
P: (888) 606-TANK(8265) • F: (951) 245-2886 • 560 BIRCH STREET, BUILDING #3 • LAKE ELSINORE, CA 92530