MONITORING SYSTEM CERTIFICATION o
For Use By Alf Jurisdictions Within the State of Califom/a
Authority Cited:Chapter 6.7, Health and Safety Code;Chapter 16, Division 3, Title 23, Califomla Code of Regulations
This form must be used to document testing and servicing of monitoring equipment.A separate certification or report must be prepared for each
monitoring system control panel by the technician who performs the work. A Copy of this form must be provided to the tank system owner(operator.The
owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility Name: Penske-Bakersfield Bldg.No:
Site Address: 2929 E. Brundage City: Bakersfield zip:
Facility Contact Person: Phone: Fax:
Make/Model of Monitoring System: Veeder-Root Simplicity Date of Testing/Servicing: 12.19.07
B. Inventory of Equipment Test/Certified
Check the appropriate boxes to indicate specific equipment ins ted/serviced:
Tank ID: Dsl. #1 Tank TD; new oil
X In-Tank Gauging el: In-Tank Gauging o e. Mo
X Annular Space or Vault Sensor. Model: V-R 309 x Annular Space or Vault Sensor. Model: 420
x Piping Sump/Trench Sensor(s). Model: V-R 352 Piping Sump/Trench Sensor(s). Model:
Fig Sump Sensor(s). Model: Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector, Model: Mechanical Line Leah Detector. Model:
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
X Tank Overfill/High Level Sensor. Model: OPW Tank Overfill/high Level Sensor. Model:
Other(specify equipment type and model in Section E on Page 2) HOther(specify equipment type and model in Section E on Page 2)
MAnnular nk ID: Dsl. #2 Tank ID:In-Tank Gauging Pro . Model: M In-Tank Gauging Pro M Space or Vault Sensor. Model: V-R 309 Annular Space or Vault Sensor.
Model:
x Piping Sump/Trench Sensor(s). Model: V-R 352 Piping Sump/Trench Sensor(s). Model:
Fill Sump Sensor(s). Model: Fell Sump Sensor(s). Model:
Mechanical Line Leak Detector, Model: Mechanical line Leak Detector. Model:
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
x Tank Overfill/High Level Sensor. Model: OPW ;Tank Overfill/High Level Sensor. Model:
Other(specify equipment type and model in Section E on Page 2) Other(specify equipment type and model in Section E on Page 2)
Dispenser ID: dsl. Master user ID:- dsl. Sat. 1
X Dispenser Containment Sensor(s). Model: 352 X Dispenser Containment Sensor(s). Model: V- 322
x Shear Valve(s). x Shear Valve(s).
Dispenser Containment Float(s)and Chain(s). Dispenser Containment Float(s)and Chain(s).
user ID: dsl. Sat.2 Di enser ID:
x IDispenser Containment Sensor(s). Model: 322 Dispenser Containment Sensor(s).
• Shear Valve(s). Shear Valve(s).
Dispenser Containment Floats)and Chain(s). Dispenser Contain=nt Float(s)and Chain(s).
Dispenser ID: Dispenser ID:
Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model:
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s)and Chain(s). Dispenser Containment Float(s)and Chain(s).
,JE
*If the facility contains more thanks or dispensers,copy this form. Include Information for every tank and dispenser at the facility.
C,Certificatiion-I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers'guidelines.
Attached to this Certification is information(e.g.manufacturers'cbecklists)necessary to verify that this information is correct and a Plot Plan showing
the layout of monitoring equipment. For any equipment capable of generating such reports,I have also attached a copy of the report Reck all that
apply): X System set-up X Alarm History report
Technician Name(print): Dave Walker nature:
r
Certification No.: A32030 745065 AB-Haz
Testing Company Name: Tank Specialists of California + pltneTo.:_ (951)245-2800
Facility Address: 560 Birch St. bldg.#3 Lake Elsinore,Cai;.92530 Date of Testing/Servicing: 12.19.07
Monitoring System Certification Page 1 of 3 ,;; ; �",:,._;� :,:, ,r:: 03101
Penske-Bakersfield mon.cart 01-09-M.xls I�IIIII VIII III IIII 22
1 E
D. Results of Testing/Servicing
Penske-Bakersfield
Software Version
Installed: 123.01 12.19.07
Corn lete the following checklist:
x Yes No* Ils the audible alarm operational?
x Yes No* Is the visual alarm operational?
x Yes No* Were all sensors visually inspected,functionally tested,and confirmed operational?
x Yes No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not
interfere with their proper operation?
Yes No* If alarms are relayed to a remote monitoring station,is all communications equipment(e.g.modem)operational?
Hx N/A
x Yes No* Fore pressurized piping systems,does the turbine automatically shut down if the piping secondary containment
HNIA monitoring system detects a leak,fails to operate,or is electrically disconnected? If yes:which sensors initiate
positive shut-down?(Check all that apply)X Sump/Trench Sensors X Dispenser Containment Sensors. Did you
confirm positive shut-down due to leaks and sensor failure/disconnection? X Yes _No.
Yes No* For Tank systems that utilize the monitoring system as the primary tank overfill warning device(ie.,no mechanical
Hx N/A overfill prevention valve is installed),is the overfill warning alarm visible and audible at the tank fill point(s)and
operating properly?If so,at what percent of tank capacity does the alarm trigger? _%
Yes x No Was any monitoring equipment replaced? If yes,identify specific sensors,probes,or other equipment replaced and
list the manufacturer name and model for all replacement parts in Section E,below.
Yes x No Was liquid found inside any secondary containment systems designed as dry systems?(Check all that apply) _
Product; —Water. If yes,describe causes in Section E,below.
Ix Yes No* Was monitoring system set-up reviewed to ensure proper settings?Attached set up reports,if applicable.
E]yes No* 11s all monitoring equipment operational per manufacturer's specifications?
* In Section E below,describe how and when these deficiencies were or will be corrected:
1 .Comments:
Monitoring System Certification
Page 2 of 3 03101
Penske-Bakersfteid mon.cert 01-08-08.)ds
F. Iln-Tank Ganging/SIR Equipment: Penske-Bakersfield
nCheck this box if tank gauging is used only for inventory control 12.19.07
Check this box if no tank gauging or SIR equipment is installed.
Complete the following checklist:
EYes E]No* Has all input wiring been inspected for proper entry and termination,including testing for ground faults?
Dyes []No* Were all tank gauging probes visually inspected for damage and residue buildup?
EYes []No* Was accuracy of system product level reading tested?
EYes E]No* Was accuracy of system water level readings tested?
Eyes FlNo* Were all probes reinstalled properly?
Eyes No* Were all items on the equipment manufacturer's maintenance checklist completed?
* In the Section H,Below,describe how and when these deficiencies;were or will be corrected-
G.Line Leak Detectors(LLD):
Check this box if LLDs are not installed.
Complete the following checklist:
®Yes No* For equipment start-up or annual equipment certification,was a leak simulated to verify LLD performance?(Check
N/A all that apply) Simulated Leak rate: X 3 g.p.h. _0.1 g.p.h. _0.2 g p.h.
x Yes No Were all LLDs confirmed operational and accurate within regulatory requirement?
[j]yes No Was the testing apparatus properly calibrated?
Eyes No* For Mechanical LLDs,does the LLD restrict product flow if it detects a leak?
N/A
Yes No* For electronic LLDs,does the turbine automatically shut off if the LLD detects a leak?
Hx N/A
Yes No* For electronic LLDs,does the turbine automatically shut off if any portion of the monitoring system is disabled or
x N/A disconnected?
Yes No* For electronic LLDs,does the turbine automatically shut off if any portion of the monitoring system malfunctions or
da N/A fails a test?
Xes No* For electronic LLDs,have all accessible wiring connections been visually inspected?
x N/A
[Ayes No* Were all items on the equipment manufacturer's maintenance checklist completed?
* In Section H below,describe how and when these deficiencies were or will be corrected:
H.Comments:
Monitoring System Certification
Page 3 of 3 03/01
Penske-Bakersfield mon.oert.01.09-06.)ds
UST Monitoring Site ]Plan
Date: 12.19.07
Site Location: Penske-Bakersfield
2929 E. Brundage
Bakersfield 0
04 Nt
sA
P +k�
n
1..1 IIJE
MWML
INSTRUCTIONS
tf you aiready have a diagram that shows all required information,you may include it,rather than this page,with your Monitoring
System Certification. On your site plan,show the general layout of tanks and piping.Clearly identify locations of the following
equipment,if installed; monitoring system control panels;snesors monitoring tank annular spaces,sumps,dispenser pans,spill
containers,or other secondary containment areas;mechanical or electronic line leak detectors;and in-tank liquid level probes(if used
for leak detection). In the space provided,note the date this Site Plan was prepared.
Tank SpeciaLsts of California (888) 606-TANK
(#745065 AB-HAZ)
Page 4
U.S.
YSTEM LANGUAGE
ENGLISH
SYSTEM DATF✓TIME FORMAT
ION DD YYYY HH:MMISS XM
09755 ROLLING 140
?929 E BRUNDAGE RS-232 END OF MESSAGE
3AKERSFIELD CA DISABLED
30448302105001
AUTO DIAL ALARM SETUP
38IFTTIME 1 : 5:45 AM _ _ - - - - - - - - - -
3HIFT TIME 2 : DISABLED
SHIFT TIME 3 : DISABLED COMMUNICATIONS SETUP D B:VEEDER ROOT (FMS)
SHIFT TIME 4 : DISABLED - -- - - - - - - - - - -
IN-TANK ALARMS
TANK PER TST NEEDED WRN ALL:LEAK ALARM
DISABLED PORT SETTINGS: ALL:HIGH WATER ALARM
TANK ANN TST NEEDED WRN ALL:OVERFILL ALARM
COMM BOARD 1 tFXMOD)
DISABLED ALL:LOW PRODUCT ALARM
BAUD RATE 2400 ALL:SUDDEN LOSS ALARM
LINE RE-ENABLE METHOD PARITY BIT ODD ALL:HIGH PRODUCT ALARM
PASS LINE PEST DATA LENGTH: 7 DATA ALL :PROBEIOO UT LEVEL
LINE PER TST NEEDED WRN RS-232 SECURITY ALL:HIGH WATER WARNING
DISABLED CODE : DISABLED ALL:DELIVERY NEEDED
LINE ANN TST NEEDED WRN DIAL TYPE TONE ALL:MAK PRODUCT ALARM
DISABLED ANSWER ON 1 RING ALL-GROSS TEST FAIL
MODEM SETUP STRING ALL:PERIODIC TEST FAIL
PRINT TC VOLUMES DIAL TONE INTERVAL: 32 ALL:PERUA�T£ETDED WWRN
ENABLED ALL:PER TST NEEDED ALM
TEMP COMPENSATION COMM BOARD 2 (S-SAT ) ALL:NO CSLD IDLE TIME
60.0
VALUE (DEG F ) : BAUD RATE 9600 ALL:CSLD INCR RATE WARN
STICK HEIGHT OFFSET PARITY NONE ALL:ACCU_CHART CAL WARN
DISABLED STOP BIT 1 STOP ALL:RECON WARNING
DATA LENGTH: B DATA ALL:RECON ALARM
H-PROTOCOL DATA FORMAT RS-232 SECURITY ALL:LOW TEMP WARNING
HEIGHT CODE : DISABLED ALL:GROSS FAIL LINE TNK
DAYLIGHT SAVING TIME DTR NORMAL STATE: HIGH
ENABLED LIQUID SENSOR ALMS
START DATE ALL:FUEL ALARM
MAR WEEK 2 SUN RECEIVER SETUP: ALL:SENSOR OUT ALARM
START TIME 'ALL:SHORT ALARM
2:00 AM ALL:WATER ALARM
END DATE D 8:VEEDER ROOT (FMS) ALL:WATER OUT ALARM
NOV WEEK 1 SUN C3
END TIME RCVR TYPE: COMPUTER ALL:HIGH LIQUID ALARM
2:00 AM PORT N0: 1 ALL:LOW LIQUID ALARM
RETRY NO: 5 ALL:LIQUID WARNING
RE-DIRECT LOCAL. PRINTOUT RETRY DELAY: 5
DISABLED CONFIRMATION REPORT: OFF RECEIVER ALARMS
SERVICE REPORT WARN
EURO PROTOCOL PREFIX ALARM CLEAR WARNING
S
SYSTEM OEC000TY
CODE
CUSTOM ALARM LABELS
DISABLED
IN-TANK SETUP- - _ _ _ T 2:DIESEL 2 NORTH
PRODUCT CODE 2
T 1 :DIESEL 1 SOUTH THERMAL. COEFF : .000450 LEAK TEST METHOD
PRODUCT CODE 1 TANK DIAMETER 96.00 - _ _ _ _ - - -PRODUCT COEFF : .000450 TANK PROFILE 4 PTS TEST WEEKLY ALL TANG
DIAMETER 96.00 FULL VOL 11594 SAT
TANK
TANK DIAMETE 4 PTS 72.0 INCH VOL 10562 START TIME : t0:00 PM
FULL VOL 11594 48.0 INCH VOL 6177 TEST RATE :0.20 GAL,-HR
72.0 INCH VOL : 16577 24.0 INCH VOL 2394 DURATION : 2 HOURS
48.0 INCH VOL : TST EARLY STOP:DISABLED
24.0 INCH VOL 2394
FLOAT SIZE: 4.0 IN. ,
4.0 IN. WATER WARNING 2.0 LEAK TEST REPORT FORMAT
FLOAT SIZE: HIGH WATER LIMIT: 2.5 ENHANCED
WATER WARNING : 2.0
HIGH WATER LIMIT: 3.0 MAX'OR LABEL VOL: 11594
OVERFILL LIMIT 89%t
MATS OR LABEL VOL.: 11594 10318
OVERFILL LIMIT 89% HIGH PRODUCT 9 4y
10318 10898
HIGH PRODUCT 94%5 DELIVERY LIMIT 12%
10898 1391
DELIVERY LIMIT 12%
1391 LOW PRODUCT 1000
LEAK ALARM LIMIT: 25
LOW PRODUCT : 1000 SUDDEN LOSS LIMIT: 25
LEAK ALARM LIMIT: 25 TANK TILT 1 .25
'
SUDDEN LOSS LIMIT: 0.25 PROBE OFFSET 1.25 LIQUID SENSOR SETUP
TANK TILT 0.70 - - - - - - - - - - - -
PROBE OFFSET SIPHON MANIFOLDED TANKS
L 1 :SATELITE DISP PAN
Tit: 01 DUAL FLT, HIGH VAPOR
SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS CATEGORY : DISPENSER PAN
TO: 02
LINE MANIFOLDED TANKS
TO: NONE LEAK MIN PERIODIC: 25%
• 2898 L 2:0IL LINE
TRI-STATE (SINGLE FLOAT)
LEAK MIN PERIODIC: 2898 LEAK MIN ANNUAL 255 CATEGORY : PIPING SUMP
2898
LEAK MIN ANNUAL 2855B L 3:PIPING MID PAN
PERIODIC TEST TYPE DUAL FLT. HIGH VAPOR
STANDARD CATEGORY : DISPENSER PAN
PERIODIC TEST TYPE
TTANDARD ANNUAL TEST FAIL
ALARM DISABLED L 4:SATELITE DISP PAN S
ANNUAL TEST FAIL DUAL FLT. HIGH VAPOR
ALARM DISABLED PERIODIC TEST ARM FAIDISAHLED CATEGORY : DISPENSER PAN
PERIODIC TEST FAIL
ALARM DISABLED GROSS TEST FAIL ALARM DISABLED
L 5:ANNULAR 1 TANK
GROSS TEST FAIL DUAL FLOAT HYDROSTATIC
ALARM DISABLED PER TEST AVERRAGING: OFF CATEGORY : ANNULAR SPACE
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF TANK TEST NOTIFY: OFF
L 6:STP SUMP 1 TANK
TANK TEST NOTIFY: OFF TNK TST SIPHON BREAK:OFF DUAL FLT. HIGH VAPOR
CATEGORY STP SUMP DELAY 5 MIN TNK TST SIPHON BREAK:OFF DELIVERY
UMPV _THRESHOLD 10.00%6
DELIVERY DELAY 5 MIN L 7:ANNULAR 2 TANK
PUMP THRESHOLD : 10.00% DUAL FLOAT HYDROSTATIC
CATEGORY : ANNULAR SPACE
L B:STP SUMP 2 TANK
DUAL FLT. DISCRIMINATING
CATEGORY : STP SUMP
"--"" ""
—
ur ALARM HISTORY REPORT
_ _ — — — — — — — — — ALARM HISTORY REPORT
----- SENSOR ALARM -----
R 1 :ALARM ---- SENSOR ALARM ----- L 3:PIPING MID PAN
TYPE' L 1 :SATELITE DISP PAN DISPENSER PAN
STANDARD •DISPENSER PAN FUEL ALARM
NORMALLY CLOSED FUEL ALARM JAN 9, 2006 7:53 AM
JAN 9, 2006 8:05 AM
IN—TANK ALARMS FUEL ALARM
ALL:LEAK ALARM FUEL ALARM JAN 6, 2005 9:55 AM
ALL:HIGH WATER ALARM JAN 6. 20Q5 9:59 AM
T 1 :LOW PRODUCT ALARM SENSOR OUT ALARM
SENSOR OUT ALARM OCT 15. 2Q04 10:22 AM
ALL:SUDDEN LOSS ALARM
ALL:GROSS TEST FAIL OCT 15, 2004 10:22 AM
LIQUID SENSOR ALMS
L 1 :FUEL ALARM
L 3:FUEL ALARM
L 4:FUEL ALARM
L 6:FUEL ALARM
L B:FUEL ALARM
ALL:SENSOR OUT ALARM
ALL:SHORT ALARM
L7:HIGHL.IQUIDALARM * * * END * * * * * # * END �t
L 7:LOW LIQUID ALARM
L 1 :LIQUID WARNING
L 3:LIQUID WARNING
L 4:LIQUID WARNING
L 6:LIQUID WARNING
L B:LIBUID WARNING
RECONCILIATION SETUP _ —
— — — ALARM HISTORY REPORT ALARM HISTORY REPORT
AUTOMATIC DAILY CLOSING _____ SENSOR ALARM ----- -- SENSOR ALARM -----
TIME: 2:00 L-4:SATELITE DISP PAN S
L 2:0IL LINE DISPENSER PAN
PERIODIC RECONCILIATION PIPING SUMP FUEL ALARM
MONTHLY FUEL. ALARM JAN 9, 2006 7:52 AM
MODE: MAY. 2, 2006 3:30 AM
TEMP COMPENSATION FUEL ALARM
STANDARD FUEL ALARM JAN 6, 2005 10:03 AM
JAN 19, 2006 10:16 AM
BUS SLOT FUEL METER TANK FUEL ALARM SENSOR OUT ALARM
TANK MAP EMPTY
JAN 13, 2006 1 :12 PM OCT 15, 2004 10:22 AM
—
END �e
SOFTWARE REVISION LEVEL
VERSION 123.01
SOFTWARE# 346123-100—B
CREATED — 02.06.21 .13.00
NO SOFWE MODULE
SYSTEMTFEATURES:
ANNUAL IINITANKNTESTS
ALARM HISTORY REPORT
----- SENSOR ALARM -----
L 5:ANNULAR 1 TANK
ANNULAR SPACE
LOW LIQUID ALARM
NOV 8, 2007 4:25 PM
LOW LIQUID ALARM
ALARM HISTORY REPORT NOV G. 2007 4:15 PM
-- SYSTEM ALARM ----- LOW LIQUID ALARM
PAPER OUT NOV B. 2007 3:19 PM
DEC 19, 2007 7:09 AM
DIIT MTFD vvvnp
ALARM HISTORY REPORT - -- SENSOR ALARM
L I :SATELITE DISP PAN -
----- SENSOR ALARM ----- DISPENSER PAN
L 6:STP SUMP 1 TANK ----- SENSOR ALARM -'--- FUEL ALARM
STP SUMP L 6:STP SUMP 1 TANK DEC 19, 2007 11 :04 AM
FUEL ALARM STP SUMP
JAN 9, 2006 7:45 AM FUEL ALARM
FUEL ALARM DEC 19, 2007 10:53 AM
JAN 6, 2005 9:50 AM
SENSOR OUT ALARM
OCT 15, 2004 10:22 AM
----- SENSOR ALARM --
L 2:011, LINE
-
-- SENSOR ALARM ----- PIPING
FUEL ALARM RM
L B:STP SUMP 2 TANK DEC 19, 2007 11 :10 AM
STP SUMP
HIGH LIQUID ALARM
DEC 19, 2007 10:55 AM
* * SEND * * *
----- SENSOR ALARM -----
L 2:OI1. LINE
----- SENSOR ALARM PIPING SUMP
L 5:ANNULAR 1 TANK SENSOR OUT ALARM
ANNULAR SPACE DEC 19, 2007 11 :13 AM
ALARM HISTORY REPORT LOW LIQUID ALARM
DEC 19, 2007 11 :01 AM
----- SENSOR ALARM -----
L 7:ANNULAR 2 TANK
ANNULAR SPACE
LOW LIQUID ALARM
APR 11. 2007 11 :01 AM
LOW LIQUID ALARM SENSOR ALARM -----
JAN 13, 2007 7:37 AM
-- DISPENSER SENSOR ALARM ----- :PIPI MID PAN
LOW LIQUID ALARM L 7:ANNULAR 2 TANK DISPENSER R G PAN
JAN 8, 2007 12:04 PM ANNULAR SPACE SENSOR OUT ALARM
LOW LIQUID ALARM DEC 19, 2007 11 :13 AM
DEC 19, 2007 11 :02 AM
* * * END -- SENSOR ALARM -----
-- SENSOR ALARM ----- L 4: ELITE DISP PAN S
L-4:SATELITE DISP PAN S DISPENSER PAN
DISPENSER PAN SENSOR OUT ALARM
FUEL ALARM DEC 19. 2007 11 :13 AM
DEC 19, 2007 11 :03 AM
ALARM HISTORY REPORT
----- SENSOR ALARM -----
----- SENSOR ALARM -----
L S:STP SUMP 2 TANK ----- SENSOR ALARM ----- L ANNULAR SPA 1 TANK
STP SUMP L 3:PIPING MID PAN ANNULAR SPACE
SENSOR O
HIGH LIQUID ALARM DISPENSER PAN OUT ALARM
JAN 9, 2006 7:50 AM FUEL ALARM DEC 19. 2007 11 :13 AM
HIGH LIQUID ALARM DEC 19, 2007 11:03 AM _
JAN 6, 2005 9:49 AM
SENSOR OUT ALARM
OCT 15, 2004 10:22 AM
----- SENSOR ALARM -----
L 6:STP SUMP 1 TANK
STP SUMP
SENSOR OUT ALARM
DEC 19, 2007 11 :13 AM
----- SENSOR ALARM -----
L 7:ANNULAR 2 TANK
ANNULAR SPACE
SENSOR OUT ALARM
DEC 19, 2007 11 :13 AM
-- SENSOR ALARM -----
L 9:STP SUMP 2 TANK
STP SUMP
SENSOR OUT ALARM
DEC 1'9. 2007 11 :13 AM
-- SENSOR ALARM -----
L I :SATELITE DISP PAN
DISPENSER PAN
SENSOR OUT ALARM
DEC 19, 2007 11 :13 AM
Facility Name: Penske-Bakersfield Test Date: 12.19.07
1. SPILL/OVERFELL CONTAINMENT BOXES
Facility is Not Equipped With SpilUOverfill Containment Boxes
Spill/Overfill Containment Boxes are Present,but were Not Tested
Test Method Developed By: E] Spill Bucket Manufacturer Qx Industry Standard ❑ Professional Engineer
Other(Specify)
M Test Method Used: Pressure Vacuum Q Hydrostatic
Other(Specify)
Test Equipment Used: incon ui ment Resolution:
� test t jcisi.Sy.Fill test 1 jdslmas.rffltest2 jdsLsy.fiute6t2 I Spill Box#
Bucket Diameter: 12" 12" 12" 12"
Bucket Depth: 15" 15" 15" 15"
Wait time between applying
pressure/vacuum/water and
startin test: 60 mins. 60 miss. 60 mires. 60 mins.
Test Start Time: 11:45 AM 11:45 AM 12:01 PM 12:01 PM
Initial Reading(R): 3.7548" 3.8142" 3.7543" 3.8138"
Test End Time: 12:00 PM 12:00 PM 12:16 PM 12:16 P
Final Reading(RF): 3.7544" 3.8138" 3.7539" 3.8131"
Test Duration: 15 rains. 15 mins. 15 mins. 15 mins.
Change in Reading(RF-RD: 0.00NII 0.0004" 0.0004" 0.0007"
Pass/FO Threshold or Criteria: 0.002" 0.002" 0.002" 0.002"
COmmentS—(include information on repairs made prior to testing,and recommended follow-up for failed tests)
PENSKE TRUCK LEASING
2929 E. BRUNDAGE LN.
BAKERSFIELD
CA 93307
12/19/2007 12:00 PM
SUMP LEAK TEST REPORT
DSL FIL
TEST STARTED 11145 AM
TEST STARTED 12/1912007
BEGIN LEVEL 3.7548 IN
END TIME 12:00 PM
END DATE 12/19/2007
END LEVEL 3.7544 IN
LEAK THRESHOLD 0.002 IN
TEST RESULT PASSED
SYPHFIL
TEST STARTED 11:45 AM
TEST STARTED 12,119/2007
BEGIN LEVEL 3.5142 IN
END TIME 12:00 PM
END DATE 12/19/2007
END LEVEL 3.8138 IN
LEAK THRESHOLD 0.002 IN
TEST RESULT PASSED
PENSKE TRUCK LEASING
2929 E. BRUNDAGE LN.
BAKERSFIELD
CA 93307
12/19/2007 12:16 PM
SUMP LEAK TEST REPORT
DSL FIL
TEST STARTED 12:01 PM
TEST STARTED 12/19/2007
BEGIN LEVEL 3.7543 IN
END TIME 12:16 PM
END DRTE 12/19/2087
END LEVEL 3.7539 IN
LEAK THRESHOLD 0.002 IN
TEST RESULT PASSED
SYPHF I L
TEST STARTED 12101 PM
TEST STARTED 12/19/1007
BEGIN LEVEL 3.8138 IN
END TIME 12:16 PM
END DATE 12/19/20+07
END LEVEL 3.8131 IN
LEAK THRESHOLD 9.002 IN
TEST RESULT PASSED