HomeMy WebLinkAbout2011 LINE TEST IN 01
IE i
RICH ENVIRONMENTAL
5643 BROOKS CT. - BAKERSFIELD, CA 93308
OFFICE(661)326-8402 FAX(661)326-8934
ACURITE TM PIPELINE TESTER
PRECISION PRODUCT LINE TEST
TEST RESULTS
DATE 01-12-11
BILLING SITE: WESTCHESTER MOBIL SITE WESTCHESTER MOBIL
3200 F STREET 3200 F STREET
BAKERSFIELD,CA 93304 BAKERFIELD,CA 93304
PRODUCT PRODUCT MECHANICAL
PRODUCTS LINE TEST LEAK DETECTORS
UNL-87 -.005-PASS N/A
COMMENTS
A PRECISION TEST WAS PERFORMED ON PRODUCT LINES AT THE ABOVE LOCATION
USING THE ACURITE TM PIPELINE TESTER.I HAVE REVIEWED THE DATA PRODUCED IN
CONJUNCTION WITH AES PROTOCOL,AND THEREFORE SATISFIES ALL REQUIREMENTS
FOR SUCH TESTING AS SET FORTH BY NFPA-329-92 AND USE 40 CFR PART 280.
THE RESULTS OF TESTING ARE SHOWN ON THE FOLLOWING PAGE.INCLUDED WITH
THE REPORT ARE REPRODUCTION OF DATA COMPLIED DURING THE TEST WHICH FORMED
THE BASIS FOR THESE CONCLUSION. THIS INFORMATION IS STORED IN A PERMANENT
FILE IF FUTURE VERIFICATION OF TEST RESULTS IS NEEDED.
I DECLARE UNDER PENALTY OF PERJURY THAT I AM A LICENSED TANK TESTER IN
THE STATE OF CALIFONIA AND THAT THE INFORMATION CONTAINED IN THIS
REPORT IS TRUE AND CORRECT TO THE BEST OF MY KNOWLEDGE.
TEST CERTIFIED BY
RICH PHILLIPS
CERT#91-1071
02
IE
RICH ENNUONMENTAL
5643 BROOKS CT.BAKERSFIELD,CA.93308
OFFICE(661)392-8687 FAX(661)392-0621
ACURITE TM PWMM TESTER
/ TEST RESULTS WORK-SHEET
DATE:�/ ,L?!/ _ W/O#:
FACILITY NAME: G✓���G1~J �' !'�°X3
FACILITY ADDRESS: _3�'e v �= J"r
L-,4 any
PRODUCT LINE TYPE: FIBERGLASS �LASTIC (CIRCLE ONE)
SYSTEM TYPE: SS SUCTION GRAVITY (CIRCLE ONE)
TURBINE MANUFACTURER:
PRODUCT START TIME END TIME TEST VOLUME RESULTS
GRADE INITIAL FINAL PRESSURE RATE PASS
READING READING
00:00/GPH 00:00/GPH (P.S.I.) (G.P.H.) OR
FAIL
oa
1 CERTIFY THAT THE ABOVE LINE TESTS WERE CONDUCTED ACCORDING TO THE
EQUIPMENT MANUFACTURERS PROCEDURES. THE TEST RESULTS AS LISTED IS TRUE AND
ACCURITE TO THE BEST OF MV KNOWLEDGE.
THE TEST PASS/FAIL STATUS IS DETERMINED USING A THRESHOLD OF 190 ML PER HOUR,
(0.05 G.P.H. RATE AT 1 h TIMES OPERATING PRESSURE,OR 50 P.S.I.WHICH EVER IS GREATER.
TECHNICIAN: STATE LICENSE#:
SIGNATURE: MFG.CERTIFICATION#: 9