HomeMy WebLinkAbout2011 FMC RESULTS Appendix VI
(Copies of Monitoring System Certification form and UST Monitoring Plot Plan available at http://www.waterboards.ca.gov)
Monitoring System Certification
For Use By All Jurisdictions Within the State of California
Authority Cited:Chapter 6.7, Health and Safety Code;Chapter 16, Division 3, Title 23, California Code of Regulations
This form must be used to document testing and servicing of monitoring equipment.A separate certification or report must be prepared for each
monitoring system control panel by the technician who performs the work.A copy of this form must be provided to the tank system owner/operator.The
owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility: Pacific Bell Telephone Co. dba AT&T Califomia GEO PAR#SA098
Address: 3221 S. "H" STREET City: BAKERSFIELD Zip: 93304
Facility Contact Person: Grant Armstrong Contact Phone No: 661-327-6903
Make/Model of Monitoring System: TLS 350 Service Date: 01/20/2011
B. Inventory of Equipment Tested/Certified IIIIIIIIIIIIIIIIIIII 23
Check the appropriate boxes to indicate specific equipment Inspected/serviced: IE
Tank ID: SA0980001 Tank ID:
®In-Tank Gauging Probe Model:847390-107 ❑In-Tank Gauging Probe Model:
®Annular Space or Vault Sensor Model:794390-420 ❑Annular Space or Vault Sensor Model:
®Piping Sump/Trench Sensor(s) Model:794380-208 ❑Piping Sump/Trench Sensor(s) Model:
®Fill Sump Sensor(s) Model:794380-208 ❑Fill Sump Sensor(s) Model:
❑Mechanical Line Leak Detector Model: ❑Mechanical Line Leak Detector Model:
❑Electronic Line Leak Detector Model: ❑Electronic Line Leak Detector Model:
®Tank Overfill/High Level Sensor Model:790091-001 ❑Tank Overfill/High Level Sensor Model:
®Other(Specify equipment type and model in Section E on Page 2) ❑Other(Specify equipment type and model in Section E on Page 2)
Tank ID: Tank ID:
❑In-Tank Gauging Probe Model: ❑In-Tank Gauging Probe Model:
❑Annular Space or Vault Sensor Model: ❑Annular Space or Vault Sensor Model:
❑Piping Sump/Trench Sensor(s) Model: ❑Piping Sump/Trench Sensor(s) Model:
❑Fill Sump Sensor(s) Model: ❑Fill Sump Sensor(s) Model:
❑Mechanical Line Leak Detector Model: ❑Mechanical Line Leak Detector Model:
❑Electronic Line Leak Detector Model: ❑Electronic Line Leak Detector Model:
❑Tank Overfill 1 High Level Sensor Model: ❑Tank Overfill/High Level Sensor Model:
❑Other(Specify equipment type and model in Section E on Page 2) ❑Other(Specify equipment type and model in Section E on Page 2)
Dispenser ID: Dispenser ID. .
❑Dispenser Containment Sensor(s) Model: ❑Dispenser Containment Sensor(s) Model:
❑Shear Valve(s) ❑Shear Valve(s)
❑Dispenser Containment Float(s)and Chain(s) ❑Dispenser Containment Float(s)and Chain(s)
Dispenser ID: Dispenser ID:
❑Dispenser Containment Sensor(s) Model: ❑Dispenser Containment Sensor(s) Model:
❑Shear Valve(s) ❑Shear Valve(s)
❑Dispenser Containment Float(s)and Chain(s) ❑Dispenser Containment Float(s)and Chain(s)
Dispenser ID: Dispenser ID:
❑Dispenser Containment Sensor(s) Model: ❑Dispenser Containment Sensor(s) Model:
❑Shear Valve(s) ❑Shear Valve(s)
❑Dispenser Containment Float(s)and Chain(s) ❑Dispenser Containment Float(s)and Chain(s)
*If the facility contains more tanks or dispensers,copy this form.Include information for every tank and dispenser at the facility.
C. Certification-I certify that the equipment identified in this document was inspected/serviced In accordance with the
manufacturers'guidelines.Attached to this Certification is informatlon (e.g.manufacturers'checklists)necessary to verify
that this information is correct and a Plot Plan showing the layout of monitoring equipment.For any equipment capable of
generating such reports,1 have also attached a copy of the report; (check all that apply):
Sy set-up ®Alarm history report
Technician Name (Print): R. Harrebomee Si nature:
Certification No: A24768 I License No: 588098
Testing Company Name: TAIT ENVIRONMENTAL SERVICES Phone No: 714 560-8222
Testing Company Address: 2131 South Dupont Drive Anaheim CA 92806 Date of Testing/Servicing: 01/20/2011
Monitoring System Certification Page 1 of 4 12/07
1 IIIIIIIIIIIIIIIIIIII 24 2/21/07
IE
Monitoring System Certification
Address: 3221 S. "H"STREET BAKERSFIELD 93304 Service Date: 01/20/2011
D. Results of Testing/Servicing
Software Version Installed: 324.01
Complete the foll owina checklist:
•Yes ❑No* Is the audible alarm operational?
•Yes ❑ No* Is the visual alarm operational?
•Yes ❑ No* Were all the sensors visually inspected,functionally tested, and cofirmed operational?
•Yes ❑ No* Were all sensors installed at lowest point of secondary containment and positioned so that other
e ui ment will not interfere with their proper operation?
®Yes ❑ No* If alarms are relayed to a remote monitoring station, is all communications equipment(e.g. modem)
operational?
❑ N/A
❑Yes ❑ No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary
containment monitoring system detects a leak, fails to operate, or is electrically disconnected?
If yes:which sensors
initiate positive shut- ❑ Sump/Trench Sensors ❑ Dispenser Containment Sensors
®N/A down?:
Did you confirm positive shut-down due to leaks and sensor failure/disconnection? ❑ Yes ❑No
❑Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device(i.e. no
mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the
® N/A tank fill point(s)and operating properly?If so, at what percent of tank capacity does the alarm trigger?:
❑Yes* M No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment
replaced and list the manufacturer name and model for all replacement parts in Section E below.
Was liquid found inside any secondary containment systems designed as dry systems?
El Yes* ® No If yes,check the type(s)of liquid found and describe causes in Section E,below. ❑Product ❑ Water
•Yes ❑ No* lWas monitoring system set-up reviewed to ensure proper settings?Attach set up reports, if applicable
•Yes ❑ No* I Is all monitoring equipment operational per manufacturer's specifications?
*In Section E below,describe how and when these deficiencies were or will be corrected.
E. Comments
Other Sensors from page 1:
Transition Sump Sensor 794380-208 Certified.
Piping Pan Sensor 794390-420 Certified.
An Overfill Prevention Valve is installed in the Drop Tube.
Monitoring System Certification Page 2 of 4 12/07
2 2/21/07
Monitoring System Certification
Address: 3221 S. "H"STREET BAKERSFIELD 93304 Service Date: 01/20/2011
F. In-Tank Gauging/SIR Equipment ®Check this box if tank gauging is used only for inventory control
❑Check this box if no tank gauging or SIR Equipment is installed
This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring
Complete the fol owinci checklist
❑Yes ❑ No* Has all input wiring been inspected for proper entry and termination, including testing for ground
faults?
❑Yes ❑ No* Were all tank gauging probes visually inspected for damage and residue buildup?
❑Yes ❑ No* Was accuracy of system product level readings tested?
❑Yes ❑ No* Was accuracy of system water level readings tested?
❑Yes ❑ No* Were all probes reinstalled properly?
❑Yes ❑ No* lWere all items on the equipment manufacturer's maintenance checklist completed?
* In the Section H below, describe how and when these deficiencies were or will be corrected
G. Line Leak Detectors (LLD): ®Check this box if LLDs are not installed
Complete the fol owina checklist
❑Yes ❑No* For equipment start-up or annual equipment certification,was a leak simulated to verify LLD
performance?
❑ N/A Simulated Leak Rate(check all that apply) ❑3.0 g.p.h ❑0.1 g.p.h ❑0.2 g.p.h
❑Yes ❑ No* Were all LLDs confirmed operational and accurate within regulatory requirements?
❑Yes ❑ No* Was the testing apparatus properly calibrated?
❑Yes ❑ No* For mechanical LLDs, does the LLD restrict product Flow if it detects a leak?
❑ N/A
❑Yes ❑ No* For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
❑ N/A
❑Yes. ❑ No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is
disabled or disconnected?
❑ N/A
❑Yes ❑ No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system
malfunctions or fails a test?
❑ N/A
❑Yes ❑ No* For electronic LLDs, have all accessible wiring connections been visually inspected?
❑ N/A
❑Yes ❑ No* Were all items on the equipment manufacturer's maintenance checklist completed?
*In the Section H below, describe how and when these deficiencies were or will be corrected
H. Comments
Suction System.
Monitoring System Certification Page 3 of 4 12107
3 2/21/07
Monitoring System Certification
Address: 3221 S. "H"STREET BAKERSFIELD 93304 Service Date: 01/20/2011
UST monitoring Site Plan
clt&t Monitoring Plan Site Map
Drawing NOT to Scale
Business Name: Pacific Bell Telephone Co. dba AT&T Cal. (SA098)
Plpkp FWSWVW+
sump wl
I
+ i i : � AnnuM Sensor
+
Tranl$w Sump 9K UST Oiesel
AW Sena +
f _.:.. Fuel Um
VW Rlser �- I 1
�r P �. --OwU AW.
Li
L.
Erohe Room
TLS 360nI'Fk. AT&T building
N
E
S
Date map was drawn: 01/20/2011
Instructions
If you already have a diagram that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification. On your site plan, show the general layout of tanks and piping.
Clearly identify locations of the following equipment, if installed: monitoring system control panels; sensors
monitoring tank annular spaces, sumps, dispenser pans, spill containers, or other secondary containment
areas; mechanical or electronic line leak detectors; and in-tank liquid level probes (if used for leak detection).
In the space provided, note the date this Site Plan was inspected.
Monitoring System Certification Page 4 of 4 12/07
4 2/21/07
SWRCB,January 2006
SPILL BUCKET TESTING REPORT FORM
This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printout from
tests(if applicable),should be provided to the facility owner/operator for submittal to the local regulatory agency.
1.FACILITY INFORMATION
Facility Name: Pacific Bell Telephone Co.dba AT&T California Date of Testing:01/20/2011
Facility Address: 3221 S. "H"STREET BAKERSFIELD CA 93304 GEO PAR#SA098
Facility Contact:Grant Armstrong Facility Phone: 661-327-6903
Date Local Agency Was Notified of Testing:01/04/2011
Name of Local Agency Inspector if present during testing): Esther Duran
2.TESTING CONTRACTOR INFORMATION
Company Name:TAIT ENVIRONMENTAL SERVICES
Technician Conducting Test:R.Harrebomee
Credentials: ®CSLB Contractor ®ICC Service Tech ❑SWRCB Tank ❑Other(Specify)
Tester
License Number (s):A ASB HAZB C-10; 588098• ICC#5252138-UT
3.SPILL BUCKET TESTING INFORMATION
Test Method Used ®Hydrostatic ❑Vacuum ❑Other
Test Equipment Used:Tape Measure E ui ment Resolution: 1/16"
Identify Spill Bucket(By Tank Number, 1 SA098UO01 2 3 4
Stored Product,etc)
❑Direct Bury ❑Direct Bury El Direct Bury E]Direct Bury
Bucket Installation Type ®Contained in Sump ❑Contained in Sump ❑Contained in Sump ❑Contained in Sump
❑On top of AST ❑On top of AST ❑On top of AST ❑On top of AST
Bucket Diameter inches 11"
Bucket Depth inches 14"
Wait Time between applying 30 Min
vacuum/water and start of test
Test Start Time: 9:30 am
Initial Reading Ri): 9"
Test End Time: 10:30 am
Final Reading 9"
Test Duration: 1 Hour
Chan a in Reading Rf-Ri : 0
Pass/Fail Threshold or Criteria: 0
Test Result Pass
Comments:Test water removed from site and taken to the shop.
CERTIFICATION OF TE HNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the infor ai ed in this report is true,accurate and in full compliance with legal requirements
Technician's Signature " Date 01/20/2011
JAN 26, 2011 12:54 PM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA098U001 4784
2 4784
3 0
4 0
162300
JAN 26, 2011 12:54 PM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA098U001 4532
2 4532
3 0
4 0
162400
JAN 26, 2011 12:54 PM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 DIESEL TK#SA098U001 2.0
162800
JAN 26,2011 12:54 PM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA098U001 6016
2 5036
3 0
4 0
162900
JAN 26, 2011 12:54 PM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA098U001 3000
2 3525
3 0
4 0
170300
JAN 26, 2011 12:54 PM
LIQUID TYPE
SENSOR LOCATION TYPE
1 ANNULAR SPACE SENSOR TRI-STATE (SINGLE FLOAT)
2 FILL SUMP SENSOR TRI-STATE (SINGLE FLOAT)
3 PIPING SUMP SENSOR TRI-STATE (SINGLE FLOAT)
4 TRANSITION SUMP TRI-STATE (SINGLE FLOAT)
5 PIPING PAN TRI-STATE (SINGLE FLOAT)
6 ANNULAR SPACE TRI-STATE (SINGLE FLOAT)
7 TRI-STATE (SINGLE FLOAT)
8 TRI-STATE (SINGLE FLOAT)
I90200
JAN 26, 2011 12:54 PM
SOFTWARE REVISION LEVEL
VERSION 324.01
SOFTWARE# 346324-100-B
CREATED - 03.11.10.17.15
S-MODULE# 330160-002-A
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
CSLD
I11100
JAN 26, 2011 12:54 PM
BKFDCA14 SA098
I50301
JAN 26, 2011 12:53 PM
# 1:BKFDCAI4 SA098
❑
I50302
JAN 26, 2011 12:53 PM
# 2:3221 S. H ST.
Fl
I50303
JAN 26, 2011 12:53 PM
# 3:BAKERSFIELD,CA 93304
150304
JAN 26, 2011 12:53 PM
# 4:661-832-8370
I51700
JAN 26, 2011 12:53 PM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
150F00
JAN 26, 2011 12:53 PM
MON DD YYYY HH:MM:SS xM
I10200
JAN 26, 2011 12:53 PM
BKFDCA14 SA098
3221 S. H ST.
BAKERSFIELD,CA 93304
661-832-8370
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 4 PROBE / G.T. 163785 162052
2 INTERSTITIAL BD 200879 199688
3 UNUSED 10306571 10231829
4 UNUSED 10265262 10212271
5 UNUSED 10261818 1021.6914
6 UNUSED 10249310 10213220
7 UNUSED 10253984 10208478
8 UNUSED 10247323 10219759
9 RELAY BOARD 14983 14995
10 UNUSED 10251789 10224040
11 UNUSED 10242063 10211496
12 UNUSED 10251033 10213511
13 UNUSED 10239736 10218469
14 UNUSED 10246737 10206814
15 UNUSED 10242820 10219339
16 UNUSED 10238506 10214301
COMM 1 FAXMODEM BOARD 40172 40120
COMM 2 UNUSED 10240833 10214419
COMM 3 UNUSED 10246661 10215427
COMM 4 UNUSED 10237503 10218884
COMM 5 UNUSED 10242385 10206616
COMM 6 UNUSED 10240341 10218311
I60100
JAN 26, 2011 12:53 PM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 DIESEL TK#SA098U001 ON
2 OFF
3 OFF
4 OFF
160200
JAN 26, 2011 .12:53 PM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 DIESEL TK#SA098U001
2
3
4
160300
JAN 26, 2011 12:53 PM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 DIESEL TK#SA098U001 1
2 2
3 3
4 4
160400
JAN 26, 2011 12:53 PM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA098U001 6016
2 5036
3 0
4 0
I60700
JAN 26, 2011 12:54 PM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 DIESEL TK#SA098U001 95.75
2 92.00
3 0.00
4 0.00
160900
JAN 26, 2011 12:54 PM
TANK THERMAL COEFFICIENT
. TANK PRODUCT LABEL
1 DIESEL TK#SA098U001 0.000450
2 0.000450
3 0.000000
4 0.000000
161200
JAN 26, 2011 12:54 PM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 DIESEL TK#SA098U001 NONE NONE
2 NONE NONE
3 NONE NONE
4 NONE NONE
Fl
162100
JAN 26, 2011 12:54 PM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA098U001 2000
2 3000
3 0
4 0
162200
3221 S. H ST.
BAKERSFIELD,CA 93304
661-832-8370
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 1 TANK DIESEL TK#SA098U001 PROBE OUT CLEAR 1-20-11 10:18AM
T 1 TANK DIESEL TK#SA098U001 PROBE OUT ALARM 1-20-11 10:14AM
T 1 TANK DIESEL TK#SA098U001 HIGH WATER ALARM CLEAR 1-20-11 9:50AM
T 1 TANK DIESEL TK#SA098U001 PROBE OUT CLEAR 1-20-11 9:49AM
T 1 TANK DIESEL TK#SA098U001 PROBE OUT ALARM 1-20-11 9:48AM
T 1 TANK DIESEL TK#SA098U001 HIGH WATER ALARM ALARM 1-20-11 9:47AM
T 1 TANK DIESEL TK#SA098U001 PROBE OUT CLEAR 1-20-11 9:43AM
T 1 TANK DIESEL TK#SA098U001 OVERFILL ALARM CLEAR 1-20-11 9:42AM
T 1 TANK DIESEL TK#SA098U001 PROBE OUT ALARM 1-20-11 9:42AM
T 1 TANK DIESEL TK#SA098U001 OVERFILL ALARM ALARM 1-20-11 9:41AM
T 1 TANK DIESEL TK#SA098U001 LOW PRODUCT ALARM CLEAR 1-20-11 9:35AM
T 1 TANK DIESEL TK#SA098U001 LOW PRODUCT ALARM ALARM 1-20-11 9:35AM
T 1 TANK DIESEL TK#SA098U001 PROBE OUT CLEAR 1-20-11 9:35AM
T 1 TANK DIESEL TK#SA098U001 PROBE OUT ALARM 1-20-11 9:34AM
L 5 PIPE PIPING PAN FUEL ALARM CLEAR 1-20-11 9:30AM
L 5 PIPE PIPING PAN FUEL ALARM ALARM 1-20-11 9:27AM
L 4 PIPE TRANSITION SUMP FUEL ALARM CLEAR 1-20-11 9:26AM
L 4 PIPE TRANSITION SUMP FUEL ALARM ALARM 1-20-11 9:22AM
L 4 PIPE TRANSITION SUMP FUEL ALARM CLEAR 1-20-11 9:22AM
L 4 PIPE TRANSITION SUMP FUEL ALARM ALARM 1-20-11 9:22AM
L 3 PIPE PIPING SUMP SENSOR FUEL ALARM CLEAR 1-20-11 9:21AM
L 3 PIPE PIPING SUMP SENSOR FUEL ALARM ALARM 1-20-11 9:17AM
L 2 OTHER FILL SUMP SENSOR FUEL ALARM CLEAR 1-20-11 9:17AM
L 2 OTHER FILL SUMP SENSOR FUEL ALARM ALARM 1-20-11 9:13AM
L 1 ANNULAR ANNULAR SPACE SENSOR FUEL ALARM CLEAR 1-20-11 9:12AM
L 1 ANNULAR ANNULAR SPACE SENSOR FUEL ALARM ALARM 1-20-11 9:09AM
L 3 PIPE PIPING SUMP SENSOR FUEL ALARM CLEAR 6-30-10 7:56AM
L 3 PIPE PIPING SUMP SENSOR FUEL ALARM ALARM 6-28-10 9:36AM
T 1 TANK DIESEL TK#SA098U001 PROBE OUT CLEAR 1-29-10 9:37AM
T 1 TANK DIESEL TK#SA098U001 OVERFILL ALARM CLEAR 1-29-10 9:37AM
T 1 TANK DIESEL TK#SA098U001 PROBE OUT ALARM 1-29-10 9:37AM
T 1 TANK DIESEL TK#SA098U001 OVERFILL ALARM ALARM 1-29-10 9:36AM
L 5 PIPE PIPING PAN FUEL ALARM CLEAR 1-29-10 9:34AM
L 5 PIPE PIPING PAN FUEL ALARM ALARM 1-29-10 9:30AM
L 4 PIPE TRANSITION SUMP FUEL ALARM CLEAR 1-29-10 9:29AM
L 4 PIPE TRANSITION SUMP FUEL ALARM ALARM 1-29-10 9:23AM
L 3 PIPE PIPING SUMP SENSOR FUEL ALARM CLEAR 1-29-10 9:21AM
L 3 PIPE PIPING SUMP SENSOR FUEL ALARM ALARM 1-29-10 9:11AM
L 2 OTHER FILL SUMP SENSOR FUEL ALARM CLEAR 1-29-10 9:10AM
L 2 OTHER FILL SUMP SENSOR FUEL ALARM ALARM 1-29-10 9:05AM
L 1 ANNULAR ANNULAR SPACE SENSOR FUEL ALARM CLEAR 1-29-10 9:04AM
L 1 ANNULAR ANNULAR SPACE SENSOR FUEL ALARM ALARM 1-29-10 8:59AM
T 1 TANK DIESEL TK#SA098U001 HIGH WATER ALARM CLEAR 1-29-10 8:41AM
T 1 TANK DIESEL TK#SA098U001 HIGH WATER ALARM ALARM 1-29-10 8:40AM
T 1 TANK DIESEL TK#SA098U001 PROBE OUT CLEAR 1-29-10 8:37AM
T 1 TANK DIESEL TK#SA098U001 PROBE OUT ALARM 1-29-10 8:35AM
L 1 ANNULAR ANNULAR SPACE SENSOR FUEL ALARM CLEAR 12-08-09 8:59AM
L 1 ANNULAR ANNULAR SPACE SENSOR FUEL ALARM ALARM 12-08-09 8:57AM
L 3 PIPE PIPING SUMP SENSOR FUEL ALARM CLEAR 11-13-09 7:53AM
L 3 PIPE PIPING SUMP SENSOR FUEL ALARM ALARM 11-13-09 7:52AM
0
111200
JAN 26, 2011 12:55 PM
BKFDCA14 SA098
3221 S. H ST.
BAKERSFIELD,CA 93304
661-832-8370
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 1 TANK DIESEL TK#SA098U001 LOW TEMP WARNING CLEAR 1-20-11 10:18AM
T 1 TANK DIESEL TK#SA098U001 LOW TEMP WARNING ALARM 1-20-11 10:18AM
T 1 TANK DIESEL TK#SA098U001 LOW TEMP WARNING CLEAR 1-20-11 9:51AM
T 1 TANK DIESEL TK#SA098U001 LOW TEMP WARNING ALARM 1-20-11 9:50AM
T 1 TANK DIESEL TK#SA098U001 HIGH WATER WARNING CLEAR 1-20-11 9:50AM
T 1 TANK DIESEL TK#SA098U001 HIGH WATER WARNING ALARM 1-20-11 9:47AM
T 1 TANK DIESEL TK#SA098U001 DELIVERY NEEDED CLEAR 1-20-11 9:35AM
T 1 TANK DIESEL TK#SA098U001 INVALID FUEL LEVEL CLEAR 1-20-11 9:35AM
T 1 TANK DIESEL TK#SA098U001 DELIVERY NEEDED ALARM 1-20-11 9:35AM
T 1 TANK DIESEL TK#SA098U001 INVALID FUEL LEVEL ALARM 1-20-11 9:35AM
T 1 TANK DIESEL TK#SA098U001 LOW TEMP WARNING CLEAR 1-29-10 9:40AM
T 1 TANK DIESEL TK#SA098U001 LOW TEMP WARNING ALARM 1-29-10 9:38AM
T 1 TANK DIESEL TK#SA098U001 HIGH PRODUCT ALARM CLEAR 1-29-10 9:38AM
T 1 TANK DIESEL TK#SA098U001 HIGH PRODUCT ALARM ALARM 1-29-10 9:35AM
T 1 TANK DIESEL TK#SA098U001 HIGH WATER WARNING CLEAR 1-29-10 8:41AM
T 1 TANK DIESEL TK#SA098U001 HIGH WATER WARNING ALARM 1-29-10 8:40AM
SYSTEM PRINTER ERROR CLEAR 1-07-10 7:51AM
SYSTEM PAPER OUT CLEAR 1-07-10 7:51AM
SYSTEM PRINTER ERROR ALARM 1-07-10 7:30AM
SYSTEM PAPER OUT ALARM 1-07-10 7:30AM
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING CLEAR 9-28-09 11:27AM
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING ALARM 9-28-09 11:26AM
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING CLEAR 9-28-09 11:26AM
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING ALARM 9-28-09 11:25AM
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING CLEAR 9-28-09 11:15AM
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING ALARM 9-28-09 11:14AM
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING CLEAR 9-28-09 11:14AM
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING ALARM 9-28-09 11:14AM
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING CLEAR 9-28-09 11:14AM
SYSTEM PRINTER ERROR CLEAR 9-28-09 11:09AM
SYSTEM PAPER OUT CLEAR 9-28-09 11:09AM
SYSTEM PRINTER ERROR ALARM 9-28-09 11:09AM
SYSTEM PAPER OUT ALARM 9-28-09 11:09AM
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING ALARM 9-28-09 11:09AM
SYSTEM PRINTER ERROR CLEAR 9-28-09 11:09AM
SYSTEM PRINTER ERROR ALARM 9-28-09 11:09AM
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING CLEAR 9-28-09 11:07AM
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING ALARM 9-28-09 11:04AM
L 6 OTHER ANNULAR SPACE SETUP DATA WARNING CLEAR 9-28-09 10:58AM
L 6 OTHER ANNULAR SPACE SETUP DATA WARNING ALARM 9-28-09 10:53AM
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING CLEAR 9-28-09 10:48AM
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING ALARM 9-28-09 10:46AM
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING CLEAR 9-28-09 10:45AM
L 1 ANNULAR ANNULAR SPACE SENSOR SETUP DATA WARNING ALARM 9-28-09 10:44AM
SYSTEM PRINTER ERROR CLEAR 7-06-09 9:45AM
SYSTEM PAPER OUT CLEAR 7-06-09 9:45AM
SYSTEM PRINTER ERROR ALARM 7-06-09 9:44AM
SYSTEM PAPER OUT ALARM 7-06-09 9:44AM
SYSTEM PRINTER ERROR CLEAR 2-19-09 10:58AM
SYSTEM PRINTER ERROR ALARM 2-19-09 10:58AM
120600
JAN 26, 2011 12:55 PM
BKFDCA14 SA098
3221 S. H ST.
BAKERSFIELD,CA 93304
661-832-8370
TANK ALARM HISTORY
TANK 1 DIESEL TK#SA098U001
SETUP DATA WARNING APR 26, 2004 3:45 PM
LEAK ALARM JUN 2, 2006 9:35 AM
HIGH WATER ALARM JAN 20, 2011 9:47 AM
JAN 29, 2010 8:40 AM
OVERFILL ALARM JAN 20, 2011 9:41 AM
JAN 29, 2010 9:36 AM
FEB 19, 2009 9:49 AM
LOW PRODUCT ALARM JAN 20, 2011 9:35 AM
FEB 19, 2009 9:48 AM
APR 13, 2005 10:14 AM
SUDDEN LOSS ALARM JUN 2, 2006 9:04 AM
HIGH PRODUCT ALARM JAN 29, 2010 9:35 AM
MAR 29, 2006 11:48 AM
APR 13, 2005 10:14 AM
INVALID FUEL LEVEL JAN 20, 2011 9:35 AM
FEB 19, 2009 9:48 AM
APR 13, 2005 10:13 AM
PROBE OUT JAN 20, 2011 10:14 AM
JAN 20, 2011 9:48 AM
JAN 20, 2011 9:42 AM
HIGH WATER WARNING JAN 20, 2011 9:47 AM
JAN 29, 2010 8:40 AM
DELIVERY NEEDED JAN 20, 2011 9:35 AM
FEB 19, 2009 9:48 AM
MAY 11, 2006 1:42 PM
MAX PRODUCT ALARM MAR 29, 2006 11:48 AM
PERIODIC TEST FAIL JUN 14, 2006 1:38 AM
JUN 3, 2006 9:55 AM
MAY 11, 2006 7:55 AM
CSLD INCR RATE WARN NOV 9, 2004 11:34 AM
OCT 23, 2004 10:39 AM
LOW TEMP WARNING JAN 20, 2011 10:18 AM
JAN 20, 2011 9:50 AM
JAN 29, 2010 9:38 AM
I30200
JAN 26, 2011 12:56 PM
BKFDCA14 SA098
3221 S. H ST.
BAKERSFIELD,CA 93304
661-832-8370
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 ANNULAR SPACE SENSOR
JAN 20, 2011 9:09 AM FUEL ALARM
JAN 29, 2010 8:59 AM FUEL ALARM
DEC 8, 2009 8:57 AM FUEL ALARM
2 FILL SUMP SENSOR
JAN 20, 2011 9:13 AM FUEL ALARM
JAN 29, 2010 9:05 AM FUEL ALARM
FEB 19, 2009 9:40 AM FUEL ALARM
3 PIPING SUMP SENSOR
JAN 20, 2011 9:17 AM FUEL ALARM
JUN 28, 2010 9:36 AM FUEL ALARM
JAN 29, 2010 9:11 AM FUEL ALARM
4 TRANSITION SUMP
JAN 20, 2011 9:22 AM FUEL ALARM
JAN 20, 2011 9:22 AM FUEL ALARM
JAN 29, 2010 9:23 AM FUEL ALARM
5 PIPING PAN
JAN 20, 2011 9:27 AM FUEL ALARM
JAN 29, 2010 9:30 AM FUEL ALARM
FEB 19, 2009 9:09 AM FUEL ALARM
El
f
TAIT
RISING 10 rrte a+[nueiraa 2181 S. Dup,nm Drive,.Anoheim, CA 92806
p:71d;S60r8%'L^< tv•.,rr.toit.com
January 27, 2011
VIA FED EX: 7967 0484 8100
Bakersfield Fire Department
2101 H Street
Bakersfield CA 93301
Re: Monitoring System Certification
Spill Bucket Testing
Pacific Bell Telephone Co. dba AT&T California
3221 S. H STREET, BAKERSFIELD, CA
GEOPAR: SA098
To Whom It May Concern:
Enclosed are the results for the following tests completed on January 20, 2011:
• Monitoring System Certification Report Form
• Spill Bucket Testing Report Form
Please do not hesitate to call me if you have any questions.
'IgheTr I o rs,
enison
ram Manager
CA 11cd 588098 i AZ link 0959841 NV link 0049666 1 TX Itck CR0000041