HomeMy WebLinkAboutSB-989 RESULTS 2010 IIII III VIII III IIII 19 IE SWRCB,January 2002 Page 1 of 5 Secondary Containment Testing Report Form This form is intended for use,by contractors performing periodic testing of UST secondary containments systems. Use the appropriate pages of this form to report results for all components tested. The completed form, written test procedures,and printout from tests(if applicable),should be provided to the facility owner/operator for submittal to the local regulatory agency. 1.FACILITY INFORMATION Facility:Pacific Bell Telephone Co.dba AT&T California Service Date: 10/06/2010 Facility Address:3221 S."H"STREET BAKERSFIELD:CA 93304 GEO PAR#SA098 Facility Contact:Grant ArmstrongFacili Phone: Date Local Agency Was Notified of Testing:09/27/2010 Test T :36 Month Name of Local Agency Inspector if present during testing): Esther Duran 2.TESTING CONTRACTOR INFORMATION Company Name:Tait Environmental Services Technician Providing Test:Scott Johnson Credentials ®CSLB Licensed Contractor ❑SWRCB Licensed Tank Tester ®ICC UST Service Technician License Type:A B ASB C-10 HAZ ILicense Number:588098 Manufacturer Training Manufacturer Component(s) Date Training Expires I.C.C.Service Tech #5252040-UT 11/24/2011 Franklin Fuelinjz Incon TS-STS #9788143701 11/25/2011 3.SUMMARY OF TEST RESULTS Component Pass Fail Not Repairs Component Pass Fail Not Repairs Tested Made I Tested Made SA098U001 Annular ® ❑ ❑ Q ❑ ❑ ❑ SA098U001 Fill Sump ® ❑ ❑ ❑ ❑ ❑ SA098U001 Piping Sump ® ❑ ❑ ❑ ❑ ❑ SA09S0001 Vent Secondary ® ❑ ❑ IQ I ❑ ❑ 1❑ SA098U001 Supply Secondary ® ❑ ❑ ❑ 1❑ ❑ SA098U001 Return Secondary ® ❑ ❑ ED ❑ I❑ ❑ ❑ ❑ ❑ ED ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ 00 ❑ ❑ ❑ ❑ 10 ❑ ❑ ❑ El IEJ I ELI] +R 11 ]F1 I F-I I F-1 If hydrostatic testing was performed,describe what was done with the water after completion of tests: Water was pumped into water trailer and returned to Tait shop. CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING To the best of my knowledge,the facts stated in this document are accurate and in full compliance with legal requirements Technician's Signature 1 Date 10/06/2010 IIIIIIII/IIIIIIIIIII 20 IE SWRCB,January 2002 4.TANK ANNULAR TESTING Test Method Developed by ❑ Tank Manufacturer E Industry Standard ❑ Professional Engineer ❑ Other(Specify) Test Method Used ❑ Pressure ® Vacuum ❑ Hydrostatic ❑ Other(Specify) Test Equipment Used:4"dial Guage Equipment Resolution: .2 Tank#SA098U00I Tank# Tank# Tank# Annular Is Tank Exempt From Testing?(1) ❑ Yes ® No ❑ Yes ❑No ❑ Yes ❑ No ❑ Yes ❑ No Tank Capacity: 6,000 Tank Material: Steel-Clad Tank Manufacturer: Modern Welding Product Stored: Diesel Wait Time between applying 15 min pressure/vacuum/water and starting test: Test Start Time: 11:00 AM Initial Reading(Ri): -10 HG Test End Time: 12:00 AM Final Reading(Rf): -10 HG Test Duration: 1 Hour Change in Reading(Rf-Ri): 0 Pass/Fail Threshold or Criteria: 0 Test Result ® Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail Was Sensor Removed for Testing? ® Yes ❑ No [DNA ❑ Ycs ❑ No ❑ NA El Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA Was Sensor properly replaced and verified functional after testing? ❑ Yes ® No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA Comments include any information on repairs made prior to testing,and recommended follow-up for failed tests Sensor was reinstalled to lowest point but not tested. (1)Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary containment,such as sysrtems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment testing. {California Code of Regulations,Title 23,Section 2637(a)(6)) SWRCB,January 2002 Page 3 of 5 5.SECONDARY PIPE TESTING Test Method Developed by ❑Piping Manufacturer ® Industry Standard ❑ Professional Engineer ❑Other(Specify) Test Method Used ®Pressure ❑ Vacuum ❑ Hydrostatic ❑ Other(Specify) Test Equipment Used:4"Dial Guage Equipment Resolution: .) Piping Run# Piping Run# Piping Run# Piping Run# SA0980001 Supply SA098UO01 Return SA098UO01 Vent Piping Material: Poly Poly Fiberglass Piping Manufacturer: Western Fiberglass Western Fiberglass A.O.Smith Piping Diameter: 1" 1 1/2" 3" Length of Piping Run: 35' 35' 35' Product Stored: Diesel Diesel Diesel Method and location of piping-run Test Boot in Sump Test Boot in Sump Test Boot in Sump isolation: Wait Time between applying 15 min 15 min 15 min pressure/vacuum/water and starting test: Test Start Time: 11:00 AM 11:00 AM 11:00 AM Initial Reading(Ri): 5 PSI 5 PSI 5 PSI Test End Time: 12:00 PM 12:00 PM 12:00 PM Final Reading(Rf): 5 PSI 5 PSI 5 PSI Test Duration: 1 Hour 1 Hour 1 Hour Change in Reading(Rf-Ri): 0 0 0 Pass/Fail Threshold or Criteria: 0 0 0 Test Result ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ❑ Pass ❑ Fail Comments include any information on repairs made prior to testing,and recommended follow-up for failed tests SWRCB,January 2002 Page 4 of 5 6.PIPING SUMP TESTING Test Method Developed by ❑ Sump Manufacturer ® Industry Standard ❑ Professional Engineer ❑ Other(Specify) Test Method Used ❑ Pressure ❑ Vacuum ® Hydrostatic ❑ Other(Specify) Test Equipment Used: Incon TS-STS Equipment Resolution: .0006 Sump#SA098U001 Sump# Sump# Sump# Piping Sump Diameter 48" Sump Depth 50" Sump Material Fiberglass Height from Tank Top to Top of 22" Highest Piping Penetration Height from Tank Top to Lowest 10" Electrical Penetration Condition of sump prior to testing Good/Clean Portion of Sump Tested(1) 2"Above Penetration Does turbine shut down when sump sensor detects liquid(both ❑ Yes ❑ No RNA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA product and water)?* Turbine shutdown response time N/A Is sytem programmed for fail-safe ❑ Yes ❑ No RNA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA shutdown?* Was fail-safe verified to be ❑ Yes ❑ No RNA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA operational?* Wait time between applying pressure/vacuum/water and starting 15 min test Test Start Time 11:07 11:22 Initial Reading Ri) 4.3294 4.3291 Test End Time 11:22 11:38 Final Reading R 4.3291 4.3291 Test Duration 15 min 15 min Change in Reading Rf-Ri .0003 .0000 Pass/Fail Threshold or Criteria .002 Test Result N Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail Was sensor removed for testing? ® Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA Was sensor properly replaced and ❑ Yes ® No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA verified functional after testing?_ Comments include any information on repairs made prior to testing,and recommended follow-up for failed tests Sensor Reinstalled to lowest point in sump,but not tested. (1)If the entire depth of the sump is not tested,specify how much was tested.If the answer to any of the questions indicated with an asterisk(*)is"NO"or"NA",the entire sump must be tested.(See SWRCB LG-160) SWRCB,January 2002 M Page 5 of 5 8.FILL RISER CONTAINMENT SUMP TESTING Facility is Not Equipped With Fill Riser Containment Sumps ❑ Fill Riser Containment Sumps are Present,but were Not Tested ❑ Test Method Developed by ❑ Sump Manufacturer ® Industry Standard ❑ Professional Engineer ❑ Other(Specify) Test Method Used ❑ Pressure ❑ Vacuum ® Hydrostatic ❑ Other(Specify) Test Equipment Used:Incon TS-STS Equipment Resolution: .0006 Fill Sump# Fill Sump# Fill Sump# Fill Sump# SA098UG01 Sump Diameter: 48" Sump Depth: 51" Height from Tank Top to Top of N/A Highest Piping Penetration: Height from Tank Top to Lowest 12" Electrical Penetration: Condition of sum rior to testing: Good/Clean Portion of Sump Tested: 2"Above penetration Sump Material: Fiberglass Wait time between applying 15 min pressure/vacuum/water and starting test: Test Start Time: 11:07 11:22 Initial Reading i : 4.4075 4.4075 Test End Time: 11:22 11:38 Final Reading(R f): 4.4075 4.4075 Test Duration: 15 min 15 min Change in Reading Rf-Ri : .0000 .0000 Pass/Fail Threshold or Criteria: .002 Test Result: ® Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail Is there a sensor in the sump? ® Yes ❑ No ❑ Yes ❑ No ❑ Yes ❑ No ❑ Yes ❑ No Does the sensor alarm when either ❑ Yes ® No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA product or water is detected? Was sensor removed for testing? ® Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA Was sensor properly replaced and ❑ Yes ® No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA verified functional after testin ? Comments include any information on repairs made prior to testing,and recommended follow-up for failed tests Sensor was reinstalled to lowest point in sump,but not tested. AT-T 3221-H, STREET- - - __._. ..-- - - AT-T BAKERSFIELD CALIFORNIA 3221 H. -STREET - BAKERSFIELD 10/06/2010 11:22 AM CALIFORNIA SUMP LEAK TEST REPORT 10/06/2010 11:38 AM FILL SUMP LEAK TEST REPORT TEST STARTED 11:07 AM FILL TEST STARTED 10/06/2010 BEGIN LEVEL 4,4075 IN TEST STARTED 11:22 AM END TIME 11:22 AM TEST STARTED 10/06/2010 END DATE 10/06/2010 BEGIN LEVEL 4,4075 IN END LEVEL 4,4075 IN END TIME 11:38 AM LEAK THRESHOLD 0,002 IN END DATE 10/06/2010 TEST RESULT PASSED END LEVEL 4,4075 IN _,_LEAK,THRESHOLD 0,002 IN TEST RESULT PASSED PIPING TEST STARTED 11:07 AM PIPING TEST STARTED 10/06/2010 BEGIN LEVEL 4,3294 IN TEST STARTED 11:22 AM END TIME 11:22 AM TEST STARTED 10/06/2010 END DATE 10/06/2010 BEGIN LEVEL 4,3291 IN END LEVEL 4,3291 IN END TIME 11:38 AM LEAK THRESHOLD 0,002 IN END DATE 10/06/2010 TEST RESULT PASSED END LEVEL 4,3291 IN LEAK THRESHOLD 0,002 IN TEST RESULT PASSED TEST DATE: 10/6/10 CLIENT: SA098 3221 South H Street,Bakersfield PAGE_L_OFA_ . r TAI T 4131146 TO TN!CNALL[NOl 2131 S. Dupont Drive, Anaheim,CA 92806 P:71 415 6018 2 22 www.tait.com October 14, 2010 VIA FED EX: 7940 1310 8691 - - Bakersfield Fire Department 2101 H Street Bakersfield CA 93301 Re: Secondary Containment Testing Pacific Bell Telephone Co. dba AT&T California 3221 S. H STREET, BAKERSFIELD, CA GEOPAR: SA098 To Whom It May Concern: Enclosed are the results for the following tests completed on October 6th, 2010: ■ Secondary Containment Testing Report Form Please do not hesitate to call me if you have any questions. je Phew Yours, . Denison Program Manager CA Iic#588098!AZ 11c#095984 1 NV Iic#0049666 1 TX lick CR0000041