Monitoring System Certification
For Use By All Jurisdictions Within the State of California
Authority Cited:Chapter 6.7, Health and Safety Code;Chapter 16, Division 3, Title 23, California Code of Regulations
This form must be used to document testing and servicing of monitoring equipment.A separate certification or report must be prepared for each
monitoring system control panel by the technician who performs the work.A copy of this form must be provided to the tank system owner/operator.The
owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facilit . Pacific Bell Telephone Co. dba AT&T California GEO PAR#SA114
Address: 3501 Columbus Ave. City: Bakersfield Zi : 93306
Facility Contact Person: Grant Armstrong Contact Phone No: 661-327-6903
Make/Model of Monitoring System: Veeder Root TLS-350 Service Date: 12/28/2010
B. Inventory of Equipment Tested/Certified IIIIIIIIIIIIIIIIIII
Check the appropriate boxes to Indicate specific equipment Inspected/serviced: 75
I
Tank ID: SA114AO01 Tank ID: SA114AO04
®In-Tank Gauging Probe Model:846391-399 ®In-Tank Gauging Probe Model:846390-199
®Annular Space or Vault Sensor Model:794380-303 ®Annular Space or Vault Sensor Model:794390-420
❑Piping Sump/Trench Sensor(s) Model: ❑Piping Sump/Trench Sensor(s) Model:
❑Fill Sump Sensor(s) Model: ❑Fill Sump Sensor(s) Model:
❑Mechanical Line Leak Detector Model: ❑Mechanical Line Leak Detector Model:
❑Electronic Line Leak Detector Model: ❑Electronic Line Leak Detector Model:
®Tank Overfill/High Level Sensor Model:790091-001 ®Tank Overfill/High Level Sensor Model:790091-001
❑Other(Specify equipment type and model in Section E on Page 2) ®Other(Specify equipment type and model in Section E on Page 2)
Tank ID: Tank ID:
❑In-Tank Gauging Probe Model: ❑In-Tank Gauging Probe Model:
❑Annular Space or Vault Sensor Model: ❑Annular Space or Vault Sensor Model:
❑Piping Sump/Trench Sensor(s) Model: ❑Piping Sump/Trench Sensor(s) Model:
❑Fill Sump Sensor(s) Model: ❑Fill Sump Sensor(s) Model:
❑Mechanical Line Leak Detector Model: ❑Mechanical Line Leak Detector Model:
❑Electronic Line Leak Detector Model: ❑Electronic Line Leak Detector Model:
❑Tank Overfill/High Level Sensor Model: ❑Tank Overfill/High Level Sensor Model:
❑Other(Specify equipment type and model in Section E on Page 2) ❑Other(Specify equipment type and model in Section E on Page 2)
Dispenser ID: Dispenser ID:
❑Dispenser Containment Sensor(s) Model: ❑Dispenser Containment Sensor(s) Model:
❑Shear Valve(s) ❑Shear Valve(s)
❑Dispenser Containment Float(s)and Chain(s) ❑Dispenser Containment Float(s)and Chain(s)
Dispenser ID: Dispenser ID:
❑Dispenser Containment Sensor(s) Model: ❑Dispenser Containment Sensor(s) Model:
❑Shear Valve(s) ❑Shear Valve(s)
❑Dispenser Containment Float(s)and Chain(s) ❑Dispenser Containment Float(s)and Chain(s)
Dispenser ID: Dispenser ID:
❑Dispenser Containment Sensor(s) Model: ❑Dispenser Containment Sensor(s) Model:
❑Shear Valve(s) ❑Shear Valve(s)
❑Dispenser Containment Float(s)and Chain(s) ❑Dispenser Containment Float(s)and Chain(s)
*If the facility contains more tanks or dispensers,copy this form.Include information for every tank and dispenser at the facility.
C. Certification-I certify that the equipment identified in this document was inspected/serviced in accordance with the
manufacturers'guidelines.Attached to this Certification is information(e.g. manufacturers'checklists)necessary to verify
that this information is correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of
generating such reports, I have also attached a copy of the report; (check all that apply):
®S tern set-up ®Alarm history report
Technician Name (Print): Paul McLane Si nature:
Certification No: A27638 I License No: 588098
Testing Company Name: TAIT ENVIRONMENTAL SERVICES Phone No: 714 560-8222
Testing Company Address: 2131 South Dupont Drive Anaheim CA 92806 Date of Testin /Servicin : 12/28/2010
Monitoring System Certification Page 1 of 4 IIIIIIIIIIIIIIIIIII 76 12/07
IE
Monitoring System Certification
Address: 3501 Columbus Ave. Bakersfield 93306 Service Date: 12/28/2010
D. Results of Testing/Servicing
Software Version Installed: 130.01
Complete the fol owing checklist:
•Yes ❑ No* Is the audible alarm operational?
•Yes ❑ No* Is the visual alarm operational?
•Yes ❑ No* Were all the sensors visually inspected, functionally tested, and cofirmed operational?
•Yes ❑ No* Were all sensors installed at lowest point of secondary containment and positioned so that other
equipment will not interfere with their proper operation?
M Yes ❑ No* If alarms are relayed to a remote monitoring station, is all communications equipment(e.g. modem)
operational?
❑ N/A
❑Yes ❑No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary
containment monitoring system detects a leak, fails to operate, or is electrically disconnected?
If yes:which sensors
initiate positive shut- ❑ Sump/Trench Sensors ❑ Dispenser Containment Sensors
® N/A down?:
Did you confirm positive shut-down due to leaks and sensor failure/disconnection? ❑ Yes ❑No
M Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no
mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the
❑ N/A tank fill point(s)and operating properly?If so, at what percent of tank capacity does the alarm trigger?:
90%
❑Yes* ® No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment
replaced and list the manufacturer name and model for all replacement parts in Section E below.
Was liquid found inside any secondary containment systems designed as dry systems?
❑Yes* ® No If yes, check the type(s)of liquid found and describe causes in Section E, below. ❑Product ❑Water
®Yes ❑ No* Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports, if applicable
®Yes ❑ No* Is all monitoring equipment operational per manufacturer's specifications?
*In Section E below,describe how and when these deficiencies were or will be corrected.
E. Comments
Other sensor from page 1.
L3 Generator 2 Floor sensor 794380-208-Certified
SA114A004 has an Overfill Prevention Valve installed in the drop tube.
Monitoring System Certification Page 2 of 4 12/07
Monitoring System Certification
Address: 3501 Columbus Ave. Bakersfield 93306 Service Date: 12/28/2010
F. In-Tank Gauging/SIR Equipment ❑Check this box if tank gauging is used only for inventory control
❑Check this box if no tank gauging or SIR Equipment is installed
This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring
Complete the fol owing checklist
•Yes ❑ No* Has all input wiring been inspected for proper entry and termination, including testing for ground
faults?
•Yes ❑ No* Were all tank gauging probes visually inspected for damage and residue buildup?
•Yes ❑ No* Was accuracy of system product level readings tested?
•Yes ❑ No* Was accuracy of system water level readings tested?
•Yes ❑No* Were all probes reinstalled properly?
•Yes ❑ No* Were all items on the equipment manufacturer's maintenance checklist completed?
* In the Section H below, describe how and when these deficiencies were or will be corrected
G. Line Leak Detectors (LLD): ®Check this box if LLDs are not installed
Complete the fol owing checklist
❑Yes ❑ No* For equipment start-up or annual equipment certification, was a leak simulated to verify LLD
performance?
❑ N/A Simulated Leak Rate(check all that apply) 1:13.0 g.p.h ❑0.1 g.p.h ❑0.2 g.p.h
❑Yes ❑ No* Were all LLDs confirmed operational and accurate within regulatory requirements?
❑Yes ❑ No* Was the testing apparatus properly calibrated?
❑Yes ❑ No* For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
❑ N/A
❑Yes ❑ No* For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
❑ N/A
❑Yes ❑ No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is
disabled or disconnected?
❑ N/A
❑Yes ❑ No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system
malfunctions or fails a test?
❑ N/A
❑Yes ❑ No* For electronic LLDs, have all accessible wiring connections been visually inspected?
❑ N/A
❑Yes ❑ No* Were all items on the equipment manufacturer's maintenance checklist completed?
* In the Section H below, describe how and when these deficiencies were or will be corrected
H. Comments
The monitoring system is operational at this time therefore no ground faults are present.
SA114A004 has an Overfill Prevention Valve installed in the drop tube.
Suction System.
Monitoring System Certification Page 3 of 4 12/07
Monitoring System Certification
Address: 3501 Columbus Ave. Bakersfield 93306 Service Date: 12/28/2010
UST monitoring Site Plan
. - . �+��v'r� �•,�, , _
�GFIV► y
yfk+i. o iK r. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7 9444 310 J4 3 7tfq?jeJ
As
T r /aiT
T - ar'iib'•rr' ilT6»gyp��o.jn . . , . . . . . . . . .
7
' . . . . . . . _ _ . . . . .
.No
. . . . . . . . . . . . . . _ . . .
. . . . . . . . . . . g , �..s�firry. _ . . , . . . . .
Date map was drawn: 12/28/2010
Instructions
If you already have a diagram that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification. On your site plan, show the general layout of tanks and piping.
Clearly identify locations of the following equipment, if installed: monitoring system control panels; sensors
monitoring tank annular spaces, sumps, dispenser pans, spill containers, or other secondary containment
areas; mechanical or electronic line leak detectors; and in-tank liquid level probes (if used for leak detection).
In the space provided, note the date this Site Plan was inspected.
Monitoring System Certification Page 4 of 4 12/07
SWRCB,January 2006
SPILL BUCKET TESTING REPORT FORM
This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printout from
tests(if applicable),should be provided to the facility owner/operator for submittal to the local regulatory agency.
1.FACILITY INFORMATION
Facili Name: Pacific Bell Telephone Co.dba AT&T California Date of Testing: 12/28/2010
Facili Address: 3501 Columbus Ave. Bakersfield CA 93306 GEO PAR#SAl 14
Facility Contact: Grant Armstrong Facility Phone:
Date Local Agency Was Notified of Testing: 12/23/2010
Name of Local Agency Inspector if present during testing): None
2.TESTING CONTRACTOR INFORMATION
Company Name: TAIT ENVIRONMENTAL SERVICES
Technician Conducting Test:Paul McLane
Credentials: ®CSLB Contractor ®ICC Service Tech ❑SWRCB Tank ❑Other(Specify)
Tester
License Number (s): A ASB HAZB C-10. 588098; 5238651-UT
3.SPILL BUCKET TESTING INFORMATION
Test Method Used ®Hydrostatic ❑Vacuum ❑Other
Test Equipment Used: MarkerNisual Tape Measure I Equipment Resolution: l/16"
Identify Spill Bucket(By Tank Number, 1 SA114A001 2 SAI 14AO04 3 4
Stored Product,etc)
❑Direct Bury ❑Direct Bury E]Direct Bury El Direct Bury
Bucket Installation Type ❑Contained in Sump ❑Contained in Sump El Contained in Sump ❑Contained in Sump
®On top of AST ®On top of AST [:]On to of AST ❑On top of AST
Bucket Diameter inches 12" 13"
Bucket Depth inches 15.5" 10"
Wait Time between applying 30 min 30 min
vacuum/water and start of test
Test Start Time: 9:30 am 9:30 am
Initial Reading Ri): 14" 10"
Test End Time: 10:30 am 10:30 am
Final Reading 14" 10"
Test Duration: 1 Hour 1 Hour
Chan a in Reading Rf-Ri : 0 110
Pass/Fail Threshold or Criteria: 0 1 0
Test Result Pass Pass
Comments:Removed test water from site. Took back to TES shop.
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true,accurate and in full compliance with legal requirements
Technician's Signature � a�_ Date 12/28/2010
El
I50301
JAN 4, 2011 10:22 AM
# 1:BKFDCAI3 SA114
I50302
JAN 4, 2011 10:22 AM
# 2:3501 COLUMBUS AVE
150303
JAN 4, 2011 10:22 AM
# 3:BAKERSFIELD,CA 93306
150304
JAN 4, 2011 10:22 AM
# 4:661-873-1204
IS1700
JAN 4, 2011 10:22 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
150F00
JAN 4, 2011 10:22 AM
MON DD YYYY HH:MM:SS xM
El
❑
110200
JAN 4, 2011 10:22 AM
BKFDCA13 SA114
3501 COLUMBUS AVE
BAKERSFIELD,CA 93306
661-873-1204
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 4 PROBE / G.T. 166764 164820
2 INTERSTITIAL BD 202494 201851
3 UNUSED 10234515 10165187
4 UNUSED 10167081 10131907
5 UNUSED 10146141 10130436
6 UNUSED 10154888 10114608
7 UNUSED 10136842 10134651
8 UNUSED 10140509 10114037
9 RELAY BOARD 15037 15029
10 COMBO I/O BOARD 9922 9923
11 UNUSED 10155822 10122347
12 UNUSED 15000000 10128296
13 UNUSED 10136031 10112161
14 UNUSED 10134374 10124082
15 UNUSED 10134794 10118923
16 UNUSED 10137467 10111656
COMM 1 FAXMODEM BOARD 40577 40546
COMM 2 UNUSED 10140095 10113347
COMM 3 UNUSED 10130865 10125706
COMM 4 UNUSED 10129869 10110142
COMM 5 UNUSED 10132033 10113917
COMM 6 UNUSED 10123375 10121250
160100
JAN 4, 2011 10:22 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 DIESEL TK#SA114A001 ON
2 DIESEL TK#SA114A004 ON
3 OFF
4 OFF
160200
JAN 4, 2011 10:22 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 DIESEL TK#SA114A001
2 DIESEL TK#SA114A004
3
4
160300
JAN 4, 2011 10:22 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 DIESEL TK#SA114A001 1
2 DIESEL TK#SA114A004 2
3 3
4 4
160400
JAN 4, 2011 10:22 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA114A001 2063
2 DIESEL TK#SA114A004 2601
3 0
4 0
I60700
JAN 4, 2011 10:22 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 DIESEL TK#SA114AO01 22.19
2 DIESEL TK#SA114A004 24.50
3 0.00
4 0.00
160900
JAN 4, 2011 10:22 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 DIESEL TK#SA114A001 0.000450
2 DIESEL TK#SA114A004 0.000450 .
3 0.000000
4 0.000000
161200
JAN 4, 2011 10:22 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 DIESEL TK#SA114A001 NONE NONE
2 DIESEL TK#SA114A004 NONE NONE
3 NONE NONE
4 NONE NONE
162100
JAN 4, 2011 10:22 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA114A001 1000
2 DIESEL TK#SA114A004 1000
3 0
4 0
❑
162200
JAN 4, 2011 10:22 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA114A001 1959
2 DIESEL TK#SA114A004 2661
3 0
4 0
162300
JAN 4, 2011 10:22 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA114A001 1856
2 DIESEL TK#SA114A004 2521
3 0
4 0
162400
JAN 4, 2011 10:23 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 DIESEL TK#SA114A001 2.0
2 DIESEL TK#SA114A004 2.0
Fl
D'
I62800
JAN 4, 2011 10:23 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA114A001 2063
2 DIESEL TK#SA114A004 2801
3 0
4 0
162900
JAN 4, 2011 10:23 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA114A001 990
2 DIESEL TK#SA114A004 1344
3 0
4 0
170300
JAN 4, 2011 10:23 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 TANK I ANNULAR TRI-STATE (SINGLE FLOAT)
2 TANK 2 ANNULAR TRI-STATE (SINGLE FLOAT)
3 GEN2 FLOOR SENSOR TRI-STATE (SINGLE FLOAT)
4 TRI-STATE (SINGLE FLOAT)
5 TRI-STATE (SINGLE FLOAT)
6 TRI-STATE (SINGLE FLOAT)
7 TRI-STATE (SINGLE FLOAT)
8 TRI-STATE (SINGLE FLOAT)
190200
JAN 4, 2011 10:23 AM
SOFTWARE REVISION LEVEL
VERSION 130.01
SOFTWARE# 346130-100-B
CREATED - 10.07.23.17.44
NO SOFTWARE MODULE
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
111100
JAN 4, 2011 10:23 AM
BKFDCAI3 SA114
3501 COLUMBUS AVE
BAKERSFIELD,CA 93306
661-873-1204
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 2 TANK DIESEL TK#SA114A004 SUDDEN LOSS ALARM CLEAR 12-28-10 11:09AM
D 1 OTHER CALL CENTER AUTODIAL FAILURE CLEAR 12-28-10 11:08AM
D 1 OTHER CALL CENTER AUTODIAL FAILURE ALARM 12-28-10 11:03AM
D 1 OTHER CALL CENTER AUTODIAL FAILURE CLEAR 12-28-10 11:03AM
T 1 TANK DIESEL TK#SA114A001 SUDDEN LOSS ALARM CLEAR 12-28-10 11:02AM
T 1 TANK DIESEL TK#SA114A001 LOW PRODUCT ALARM CLEAR 12-28-10 11:02AM
T 1 TANK DIESEL TK#SA114A001 HIGH WATER ALARM CLEAR 12-28-10 11:O1AM
T 1 TANK DIESEL TK#SA114AO01 LOW PRODUCT ALARM ALARM 12-28-10 11:O1AM
T 1 TANK DIESEL TK#SA114AO01 SUDDEN LOSS ALARM ALARM 12-28-10 11:O1AM
T 1 TANK DIESEL TK#SA114A001 HIGH WATER ALARM ALARM 12-28-10 10:55AM
T 1 TANK DIESEL TK#SA114A001 OVERFILL ALARM CLEAR 12-28-10 10:52AM
T 1 TANK DIESEL TK#SA114A001 OVERFILL ALARM ALARM 12-28-10 10:46AM
T 1 TANK DIESEL TK#SA114A001 SUDDEN LOSS ALARM CLEAR 12-28-10 10:46AM
T 1 TANK DIESEL TK#SA114A001 LOW PRODUCT ALARM CLEAR 12-28-10 10:45AM
T 1 TANK DIESEL TK#SA114A001 LOW PRODUCT ALARM ALARM 12-28-10 10:45AM
T 1 TANK DIESEL TK#SA114A001 SUDDEN LOSS ALARM ALARM 12-28-10 10:45AM
L 1 ANNULAR TANK 1 ANNULAR FUEL ALARM CLEAR 12-28-10 10:44AM
D 1 OTHER CALL CENTER AUTODIAL FAILURE ALARM 12-28-10 10:41AM
D 1 OTHER CALL CENTER AUTODIAL FAILURE CLEAR 12-28-10 10:41AM
L 1 ANNULAR TANK 1 ANNULAR FUEL ALARM ALARM 12-28-10 10:40AM
T 2 TANK DIESEL TK#SA114A004 LOW PRODUCT ALARM ALARM 12-28-10 10:27AM
T 2 TANK DIESEL TK#SA114AO04 HIGH WATER ALARM CLEAR 12-28-10 10:27AM
T 2 TANK DIESEL TK#SA114A004 SUDDEN LOSS ALARM ALARM 12-28-10 10:27AM
T 2 TANK DIESEL TK#SA114A004 HIGH WATER ALARM ALARM 12-28-10 10:22AM
T 2 TANK DIESEL TK#SA114A004 OVERFILL ALARM CLEAR 12-26-10 10:18AM
D 1 OTHER CALL CENTER AUTODIAL FAILURE ALARM 12-28-10 10:18AM
T 2 TANK DIESEL TK#SA114A004 OVERFILL ALARM ALARM 12-28-10 10:12AM
T 2 TANK DIESEL TK#SA114A004 LOW PRODUCT ALARM CLEAR 12-28-10 10:11AM
L 3 OTHER GEN2 FLOOR SENSOR FUEL ALARM CLEAR 12-28-10 10:09AM
L 3 OTHER GEN2 FLOOR SENSOR FUEL ALARM ALARM 12-28-10 10:04AM
L 2 ANNULAR TANK 2 ANNULAR FUEL ALARM CLEAR 12-28-10 10:03AM
L 2 ANNULAR TANK 2 ANNULAR FUEL ALARM ALARM 12-28-10 9:59AM
D 1 OTHER CALL CENTER AUTODIAL FAILURE CLEAR 12-09-10 12:57PM
D 1 OTHER CALL CENTER AUTODIAL FAILURE ALARM 12-09-10 12:57PM
T 2 TANK DIESEL TK#SA114A004 LOW PRODUCT ALARM ALARM 12-09-10 12:41PM
T 2 TANK DIESEL TK#SA114A004 LOW PRODUCT ALARM CLEAR 12-09-10 12:40PM
L 3 OTHER GEN2 FLOOR SENSOR FUEL ALARM CLEAR 12-09-10 12:33PM
L 3 OTHER GEN2 FLOOR SENSOR FUEL ALARM ALARM 12-09-10 12:33PM
L 3 OTHER GEN2 FLOOR SENSOR FUEL ALARM CLEAR 12-09-10 12:33PM
L 3 OTHER GEN2 FLOOR SENSOR FUEL ALARM ALARM 12-09-10 12:33PM
L 2 ANNULAR TANK 2 ANNULAR FUEL ALARM CLEAR 12-09-10 12:31PM
L 2 ANNULAR TANK 2 ANNULAR FUEL ALARM ALARM 12-09-10 12:31PM
I 1 INPUT GENERATOR RUN EXTERN INPUT ALARM CLEAR 12-09-10 12:23PM
I 1 INPUT GENERATOR RUN EXTERN INPUT ALARM ALARM 12-09-10 12:232M
1 1 INPUT GENERATOR RUN EXTERN INPUT ALARM CLEAR 12-09-10 11:57AM
I 1 INPUT GENERATOR RUN EXTERN INPUT ALARM ALARM 12-09-10 11:57AM
I 1 INPUT GENERATOR RUN EXTERN INPUT ALARM CLEAR 12-09-10 11:55AM
I 1 INPUT GENERATOR RUN EXTERN INPUT ALARM ALARM 12-09-10 11:55AM
1 1 INPUT GENERATOR RUN EXTERN INPUT ALARM CLEAR 12-09-10 11:55AM
I 1 INPUT GENERATOR RUN EXTERN INPUT ALARM ALARM 12-09-10 11:55AM
El
❑
I11200
JAN 4, 2011 10:23 AM
BKFDCAI3 SA114
3501 COLUMBUS AVE
BAKERSFIELD,CA 93306
661-873-1204
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 1 TANK DIESEL TK#SA114A001 DELIVERY NEEDED CLEAR 12-28-10 11:02AM
T 1 TANK DIESEL TK#SA114A001 INVALID FUEL LEVEL CLEAR 12-28-10 11:02AM
T 1'TANK DIESEL TK#SA114A001 INVALID FUEL LEVEL ALARM 12-28-10 11:02AM
T 1 TANK DIESEL TK#SA114A001 HIGH WATER WARNING CLEAR 12-28-10 11:O1AM
T 1 TANK DIESEL TK#SA114A001 DELIVERY NEEDED ALARM 12-28-10 11:O1AM
T 1 TANK DIESEL TK#SA114A001 HIGH WATER WARNING ALARM 12-28-10 10:55AM
T 1 TANK DIESEL TK#SA114A001 HIGH PRODUCT ALARM CLEAR 12-28-10 10:49AM
T 1 TANK DIESEL TK#SA114A001 HIGH PRODUCT ALARM ALARM 12-28-10 10:46AM
T 1 TANK DIESEL TK#SA114A001 DELIVERY NEEDED CLEAR 12-28-10 10:45AM
T 1 TANK DIESEL TK#SA114A001 DELIVERY NEEDED ALARM 12-28-10 10:45AM
T 2 TANK DIESEL TK#SA114A004 INVALID FUEL LEVEL ALARM 12-28-10 10:27AM
T 2 TANK DIESEL TK#SA114A004 HIGH WATER WARNING CLEAR 12-28-10 10:27AM
T 2 TANK DIESEL TK#SA114A004 DELIVERY NEEDED ALARM 12-28-10 1027AM
T 2 TANK DIESEL TK#SA114A004 HIGH WATER WARNING ALARM 12-28-10 10:22AM
T 2 TANK DIESEL TK#SA114A004 HIGH PRODUCT ALARM CLEAR 12-28-10 10:14AM
T 2 TANK DIESEL TK#SA114A004 HIGH PRODUCT ALARM ALARM 12-28-10 10:13AM
T 2 TANK DIESEL TK#SA114A004 DELIVERY NEEDED CLEAR 12-26-10 10:11AM
T 2 TANK DIESEL TK#SA114A004 INVALID FUEL LEVEL CLEAR 12-28-10 10:11AM
SYSTEM PRINTER ERROR CLEAR 12-27-10 11:16AM
SYSTEM PAPER OUT CLEAR 12-27-10 11:16AM
SYSTEM PAPER OUT ALARM 12-27-10 11:15AM
SYSTEM PRINTER ERROR ALARM 12-27-10 11:14AM
SYSTEM PRINTER ERROR CLEAR 12-27-10 11:13AM
SYSTEM PAPER OUT CLEAR 12-27-10 11:13AM
SYSTEM PRINTER ERROR ALARM 12-25-10 7:30AM
SYSTEM PAPER OUT ALARM 12-25-10 7:30AM
T 2 TANK DIESEL TK#SA114A004 INVALID FUEL LEVEL ALARM 12-09-10 12:412M
T 2 TANK DIESEL TK#SA114A004 DELIVERY NEEDED ALARM 12-09-10 12:41PM
T 2 TANK DIESEL TK#SA114A004 HIGH PRODUCT ALARM CLEAR 12-09-10 12:41PM
T 2 TANK DIESEL TK#SA114A004 HIGH PRODUCT ALARM ALARM 12-09-10 12:41PM
T 2 TANK DIESEL TK#SA114A004 INVALID FUEL LEVEL CLEAR 12-09-10 12:41PM
T 2 TANK DIESEL TK#SA114A004 DELIVERY NEEDED CLEAR 12-09-10 12:41PM
T 2 TANK DIESEL TK#SA114A004 DELIVERY NEEDED ALARM 12-09-10 10:42AM
T 2 TANK DIESEL TK#SA114A004 INVALID FUEL LEVEL ALARM 12-09-10 10:18AM
I20600
JAN 4, 2011 10:24 AM
BKFDCA13 SA114
3501 COLUMBUS AVE
BAKERSFIELD,CA 93306
661-673-1204
TANK ALARM HISTORY
TANK 1 DIESEL TK#SA114A001
HIGH WATER ALARM DEC 28, 2010 10:55 AM
OVERFILL ALARM DEC 28, 2010 10:46 AM
LOW PRODUCT ALARM DEC 28, 2010 11:01 AM
DEC 28, 2010 10:45 AM
SUDDEN LOSS ALARM DEC 28, 2010 11:01 AM
DEC 28, 2010 10:45 AM
HIGH PRODUCT ALARM DEC 28, 2010 10:46 AM
INVALID FUEL LEVEL DEC 28, 2010 11:02 AM
HIGH WATER WARNING DEC 28, 2010 10:55 AM
DELIVERY NEEDED DEC 28, 2010 11:01 AM
DEC 28, 2010 10:45 AM
TANK 2 DIESEL TK#SA114A004
HIGH WATER ALARM DEC 28, 2010 10:22 AM
OVERFILL ALARM DEC 28, 2010 10:12 AM
LOW PRODUCT ALARM DEC 28, 2010 10:27 AM
DEC 9, 2010 12:41 PM
DEC 9, 2010 10:42 AM
SUDDEN LOSS ALARM DEC 28, 2010 10:27 AM
HIGH PRODUCT ALARM DEC 28, 2010 10:13 AM
DEC 9, 2010 12:41 PM
INVALID FUEL LEVEL DEC 28, 2010 10:27 AM
DEC 9, 2010 12:41 PM
DEC 9, 2010 10:18 AM
HIGH WATER WARNING DEC 28, 2010 10:22 AM
DELIVERY NEEDED DEC 28, 2010 10:27 AM
DEC 9, 2010 12:41 PM
DEC 9, 2010 10:42 AM
I30200
JAN 4, 2011 10:24 AM
BKFDCA13 SA114
3501 COLUMBUS AVE
BAKERSFIELD,CA 93306
661-873-1204
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 TANK 1 ANNULAR
DEC 28, 2010 10:40 AM FUEL ALARM
2 TANK 2 ANNULAR
DEC 28, 2010 9:59 AM FUEL ALARM
DEC 9, 2010 12:31 PM FUEL ALARM
3 GEN2 FLOOR SENSOR
DEC 28, 2010 10:04 AM FUEL ALARM
DEC 9, 2010 12:33 PM FUEL ALARM
DEC 9, 2010 12:33 PM FUEL ALARM
TAI ■ 21�7 S. Dupcm✓rz,e, Anaheiu,, CA 92806
P: 1 d;5 6 '6 12 2 c n i
January 6, 2011
'%WIN
VIA FED EX 7942 9653 7201 JAN 1 1 2011
Kern County Environmental Health
2700 M St., Suite 300
Bakersfield, Ca. 93301 H SEMACES
Re: Monitoring System Certification
Spill Bucket Testing
Pacific Bell Telephone Co. dba AT&T California
3501 COLUMBUS AVE., BAKERSFIELD, CA
GEOPAR: SA114
To Whom It May Concern:
Enclosed are the results for the following tests completed on December 28,
2010:
■ Monitoring System Certification Report Form
■ Spill Bucket Testing Report Form
Please do not hesitate to call me if you have any questions.
V ours,
M tftt h Denison
Pr gram Manager
CA Itcd 588098 AZ lic,#045984 j NV 1.c# 0049666 i TX lic-4 CR0000041