HomeMy WebLinkAbout3601 STOCKDALE HWY (2) MONITORING SYSTEM CERTIFICATION For Use By All Jurisdictions Within the State of California Authority Cited:Chapter 6.7,Health and Safety Code;Chapter 16, Division 3 Title 23, California Code of Regulations This form must be used to document testing and servicing of monitoring equipment. If more than one monitoring system control panel is installed at the facility,a separate certification or report must be Prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date. A General Information Facility Name: 7-ELEVEN#17721,MKT 2368 City: BAKERSFIELD CA Zip:93309 Site Address: 3601 STOCKDALE HIGHWAY Contact Phone No: 834-3093 Date of Testing/Service: 02/07/2011 Facility Contact Person: Manager Make/Model of Monitoring System:TLS350 Work Order Number: 3181091 IIIIIIIIIIIIINIIIII 1 I 53 B.Inventory of Equipment Tested/Certified IE Check the appropriate boxes to indicate specific equipment inspected/serviced Tank ID: 87 Tank ID: 87 X In-Tank Gauging Probe. Model: MAG PROBE X In-Tank Gauging Probe. Model: MAG PROBE Annular Space or Vault Sensor. Model: Annular Space or Vault Sensor. Model: X Piping Sump/Trench Sensor(s). Model: 208 Piping Sump/Trench Sensor(s). Model: 208 X Fill Sump Sensor(s). Model: 208 208 Fill Sump Sensor(s). Model: X Mechanical Line Leak Detector. Model: FX1V X Mechanical Line Leak Detector. Model: LD2000 Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model: X Tank Overfill/High-Level Sensor. Model: ATG Tank OverfilVHigh-Level Sensor. Model: ATG Other(specify equipment type and model in Section E on page 2). Other(specify equipment type and model in Section E on page 2). Tank ID: Tank ID: In-Tank Gauging Probe. Model: MAG PROBE In-Tank Gauging Probe. Model: Annular Space or Vault Sensor. Model: Annular Space or Vault Sensor. Model: X Piping Sump/french Sensor(s). Model: 208 Piping Sump/Trench Sensor(s). Model: X Fill Sump Sensor(s). Model: 208 Fill Sump Sensor(s). Model: X Mechanical Line Leak Detector. Model: LD2000 Mechanical Line Leak Detector. Model: Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model: Tank Overfill/High-Level Sensor. Model: ATG Tank Overfill/High-Level Sensor. Model: Other(specify equipment type and model in Section E on page 2). Others ci ( pe fy equipment type and model in Section E on page 2). Dispenser : 1/2 Dispenser ID: 3/4 ®Dispenser Containment Sensor(s) Model:208 _X-1 Dispenser Containment Sensors) Model: 208 RI Shear Valve(s). X Shear Valve(s) ❑Dispenser Containment Float(s)and Chain(s). 7 Dispenser Containment Float(s)and Chain(s). Dispenser ID: Dispenser ID: F]Dispenser Containment Sensor(s) Model: Dispenser Containment Sensor(s). Model: ❑ Shear Valve(s). Shear Valve(s). Dispenser Containment Float(s)and Chain(s). Dispenser Containment Float(s)and Chain(s). Dispenser ID: Dispenser ID: ❑ Dispenser Containment Sensor(s) Model: Dispenser Containment Sensor(s). Model: Shear Valve(s). Shear Valve(s). Dispenser Containment Float(s)and Chain(s). Dispenser Containment Float(s)and Chain(s). .If the facility contains more tanks or dispensers,copy this form.Include information for every tank and dispenser at the facility. C. Certification I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers'guidelines. Attached to this certification is information(e.g manufacturers'checklists)necessary to verify that this information is correct. and a Site Plan showing the layout of monitoring equipment.For any equipment capable of generating such reports,I have also attached a copy of the(Check all that apply): �X System set-up X❑Alarm history report Technician Name(print): ROBERT ALLEN Signature: Certification No.: A20125 License.No.: 743160(Class'A'General Enginering Contractor License) Testing Company Name:Tanknology Phone No.: (800)800-4633 Site Address: 11000 N.MoPac Expressway,suite 500,Austin,TX 78759 Date of Testing/Servicing: 02/07/2011 Monitoring System Certification Page 1 of 3 I IIIIIII VIII III IIII 54 Based on CA form dated 03/08 IE Monitoring System Certification Site Address 3601 STOCKDALE HIGHWAY Date of Testing/Service: 02/07/2011 D. Results of Testing/Servicing Software Version Installed: 329.02 Complete the following checklist: X Yes No• Is the audible alarm operational? Q Yes No• Is the visual alarm operational? 0 Yes No• Were all sensors visually inspected,functionally tested,and confirmed operational? ❑ Yes E]No Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not • interfere with their proper operation? x Yes No• NIA If alarms are relayed to a remote monitoring station,is all communications equipment(e.g.modem)operational? For pressurized piping systems,does the turbine automatically shut down if the piping secondary containment ❑ Yes No• ❑N/A monitoring system detects a leak,fails to operate,or is electrically disconnected?If yes:which sensors initiate positive shut-down?(check all that apply) ❑x Sump/Trench Sensors; ❑x Dispenser Containment Sensors. Did you confirm positive shut-down due to leaks and sensor failure/disconnection? ❑x Yes Ej No ❑X Yes ❑No• N/A For tank systems that utilize the monitoring system as the primary tank overfill waming device(i.e.:no mechanical overfill prevention valve is installed),is the overfill warning alarm visible and audible at the tank fill points(s)and operating properly? If so,at what percent of tank capacity does the alarm trigger? ❑ Yes' ❑x No Was any monitoring equipment replaced?If yes,identify specific sensors,probes,or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E,below. Mx Yes' ❑No Was liquid found inside any secondary containment systems designed as dry systems?(check all that apply) []Product; ❑x Water. If yes,describe causes in Section E,below. ❑X Yes ❑No• Was monitoring system set-up reviewed to ensure proper settings?Attach set-up reports,if applicable. ❑X Yes ❑No• Is all monitoring equipment operational per manufacturers'specifications? *In Section E below,describe how and when these defrciences were or will be corrected. E. Comments: of water removea from 91 STP sump. Page 2 of 3 Based on CA form dated 03/08 Monitoring System Certification Site Address: 3601 STOCKDALE HIGHWAY Date of Testing/Service: 02/07/2011 F. In-Tank Gauging /SIR Equipment ❑ Check this box if tank gauging is used only for inventory control. ❑ Check this box if no tank gauging or SIR equipment is installed. Check this box if no tank gauging or SIR equipment is installed. This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring. Complete the following checklist: ❑X Yes ❑No' Has all input wiring been inspected for proper entry and termination,including testing for ground faults? 0 Yes ❑No' Were all tank gauging probes visually inspected for damage and residue buildup? ❑X Yes ❑No' Was accuracy of system product level readings tested? ❑X Yes ❑No. Was accuracy of system water level readings tested? X Yes ❑No' Were all probes reinstalled properly? QYes ❑No• Were all items on the equipment manufacturers'maintenance checklist completed? "In the Section H,below,describe how and when these deficiencies were or will be corrected. G. Line Leak Detectors (LLD) : ❑ Check this box if LLDs are not installed. Complete the following checklist: For equipment start-up or annual equipment certification,was a leak simulated to verify LLD performance? Q Yes E]No' [:j N/A (Check all that apply)Simulated leak rate: X❑ 3 g.p.h ❑0.1 g.p.h ❑0.2 g.p.h M Yes ❑No• Were all LLDs confirmed operational and accurate within regulatory requirements? X Yes ❑No' Was the testing apparatus properly calibrated? ❑X Yes ❑No• ❑N/A For mechanical LLDs,does the LLD restrict product flow if it detects a leak? ❑Yes ❑No• El N/A For electronic LLDs,does the turbine automatically shut off if the LLD detects a leak? ❑Yes ❑No• X❑N/A For electronic LLDs,does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? ❑Yes ❑No• ❑X N/A For electronic LLDs,does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a test? ❑Yes ❑No' Q N/A For electronic LLDs,have all accessible wiring connections been visually inspected? 0 Yes ❑No' Were all items on the equipment manufacturers'maintenance checklist completed? "In the Section H,below,describe how and when these deficiencies were or will be corrected. H. Comments: Page 3 of 3 Based on CA form dated 03/08 SWRCB,January 2002 Page 1. Secondary Containment Testing Report Form This form is intended for use by contractors performing periodic testing of UST secondary containment systems. Use the appropriate pages of this form to report results for all components tested. The completed form, written test procedures, and printouts from tests(if applicable),should be provided to the facility owner/operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: 7-ELEVEN #17721, MKT 2368 Date of Testing: 02/07/2011 Facility Address: 3601 STOCKDALE HIGHWAY BAKERSFIELD, CA, 93309 Facility Contact: Manager Phone: (661) 834-3093 Date Local Agency Was Notified of Testing Name of Local Agency Inspector(if present during testing): Ernie Medina 2. TESTING CONTRACTOR INFORMATION Company Name: TANKNOLOGY, INC. Technician Conducting Test: ROBERT ALLEN Credentials: CSLB Licensed Contractor SWRCB Licensed Tank Tester License Type: A License Number: 743160 Manufacturer Training Manufacturer Component(s) Date Training Expires Incon STS 05/19/2011 3. SUMMARY OF TEST RESULTS Not Repairs Not Repair Component Pass Fail Tested Made Component Pass Fail Tested Made Spill Box 1 REG FILL El ❑ ❑ ❑ ❑ ❑ ❑ ❑ Spill Box 1 REG FILL a ❑ ❑ ❑ El ❑ ❑ ❑ Spill Box 1 REG VAPOR a ❑ ❑ ❑ ❑ ❑ ❑ ❑ Spill Box 1 REG VAPOR Efl ❑ ❑ El ❑ ❑ ❑ ❑ Spill Box 2 REG FILL ❑ ❑ ❑ ❑ ❑ ❑ ❑ Spill Box 2 REG FILL X ❑ ❑ ❑ ❑ ❑ ❑ ❑ Spill Box 2 REG VAPOR FRI ❑ ❑ ❑ ❑ ❑ ❑ ❑ Spill Box 2 REG VAPOR FRI ❑ ❑ ❑ ❑ 0 ❑ ❑ Spill Box 3 PRE FILL a ❑ ❑ ❑ ❑ ❑ ❑ ❑ Spill Box 3 PRE FILL ❑ El ❑ ❑ ❑ ❑ ❑ Spill Box 3 PRE VAPOR X ❑ ❑ ❑ ❑ ❑ ❑ Spill Box 3 PRE VAPOR E ❑ ❑ ❑ ❑ ❑ ❑ If hydrostatic testing was performed,describe what was done with the water after completion of tests: Test water removed sameday CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING To the best of my knowledge, the facts stated in this document are accurate and in full compliance with legal requirements Technician's Signature: Date: 02/07/2011 SWRCB,January 2006 9. Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printouts from tests(if applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: 7-ELEVEN #17721, MKT 2368 1 DateofTesting: 02/07/2011 Facility Address: 3601 STOCKDALE HIGHWAY BAKERSFIELD, CA, 93309 Facility Contact: Manager Phone: (661) 834-3093 Date Local Agency Was Notified of Testing: Name of Local Agency Inspector(if present during testing): Ernie Medina 2. TESTING CONTRACTOR INFORMATION Company Name: TANKNOLOGY, INC. Technician Conducting Test: ROBERT ALLEN Credentials): a CSLB Contractor E ICC Service Tech. ❑SWRCB Tank Tester El Other(Specify)A License Number: 743160 3. SPILL BUCKET TESTING INFORMATION Test Method Used: X❑ Hydrostatic ❑ Vacuum ❑ Other Test Equipment Used, Incon Equipment Resolution: .0020 Identify Spill Bucket(By Tank 1 1 REG FILL Z 1 REG FILL 3 1 REG VAPOR 4 1 REG VAPOR Number, Stored Product, etc) Bucket Installation Type: XO Direct Bury XD Direct Bury X❑Direct Bury ❑X Direct Bury ❑Contained in Sump ❑Contained in Sump ❑ Contained in Sump ❑Contained in Sump Bucket Diameter: 1111 1111 1111 11" Bucket Depth: 1311 1311 1311 1311 Wait time between applying 15min 15min 15min 15min vacuum/water and starting test: Test Start Time(TI ); 11:57am 12:14pm 11:57am 12:14pm Initial Reading(RI ): 5.1461 5.1466 5.1734 5.1731 Test End Time(TF 12:13pm 12:30pm 12:13pm 12:30pm Final Reading(RF ): 5.1466 5.1467 5.1732 5.1729 Test Duration: 15min 15min 15min 15min Change in Reading(R F-R1 ): .0005 .0 0 01 .0002 .0 0 0 2 Pass/Fail Threshold or .0020 .0 0 2 0 .0020 .0 0 2 0 Criteria: Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true,accurate,and in full compliance with legal requirements. Technician's Signature: Date: 02/07/2011 State laws and regulations do not currently require testing to be performed by a qualified contractor.However,local requirements SWRCB,January 2006 9. Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printouts from tests(if applicable),should be provided to the facility owner/operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: 7-ELEVEN #17721, MKT 2368 Date of Testing: 02/07/2011 Facility Address: 3601 STOCKDALE HIGHWAY BAKERSFIELD, CA, 93309 Facility Contact: Manager Phone: (6 61) 8 3 4-3 0 9 3 Date Local Agency Was Notified of Testing: Name of Local Agency Inspector(if present during testing): Ernie Medina 2. TESTING CONTRACTOR INFORMATION Company Name: TANKNOLOGY, INC. Technician Conducting Test: ROBERT ALLEN Credentials X❑CSLB Contractor ❑x ICC Service Tech. ❑SWRCB Tank Tester E Other(Specify)A License Number: 743160 3. SPILL BUCKET TESTING INFORMATION Test Method Used: ❑x Hydrostatic ❑ Vacuum ❑ Other Test Equipment Used: Incon Equipment Resolution: .0020 Identify Spill Bucket(By Tank 2 REG FILL Z 2 REG FILL 3 2 REG VAPOR 4 2 REG VAPOR Number, Stored Product, etc) X❑ Bucket Installation Type: Direct Bury X❑Direct Bury X❑Direct Bury ❑X Direct Bury ❑Contained in Sump ❑Contained in Sump ❑Contained in Sump ❑ Contained in Sump Bucket Diameter: 1111 1111 1111 1111 Bucket Depth: 1311 1311 1311 1311 Wait time between applying 15min 15min 15min 15min vacuum/water and starting test: Test Start Time(TI ): 11:57am 12:14pm 11:57am 12 :14pm Initial Reading(RI ): 4.6701 4 .6694 4.1260 4.1259 Test End Time TF ): 12:13pm 12:30pm 12 :13pm 12:30pm Final Reading(R F ): 4.6695 4.6 6 9 3 4.1260 4.1260 Test Duration: 15min 15min 15min 15min Change in Reading(R F-R I .0006 .0 0 01 0 .0001 Pass/Fail Threshold or 0020 .0020 .0020 .0020 Criteria: t ai ® a ai Comments - (include information on repairs made prior to testing, and recommended follow-up for jailed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true,accurate,and in full compliance with legal requirements. Technician's Signature: Date: 02/07/2011 I State laws and regulations do not currently require testing to be performed by a qualified contractor.However,local requirements SWRCB,January 2006 9. Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printouts from tests(if applicable),should be provided to the facility owner/operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: 7-ELEVEN ##17721, MKT 2368 Date of Testing: 02/07/2011 Facility Address: 3601 STOCKDALE HIGHWAY BAKERSFIELD, CA, 93309 Facility Contact: Manager Phone: (661) 834-3093 Date Local Agency Was Notified of Testing: Name of Local Agency Inspector(if present during testing): Ernie Medina 2. TESTING CONTRACTOR INFORMATION Company Name: TANKNOLOGY, INC. Technician Conducting Test: ROBERT ALLEN Credentials): CSLB Contractor [�]ICC Service Tech. ❑SWRCB Tank Tester Other(Specify)A License Number: 7 4 316 0 3. SPILL BUCKET TESTING INFORMATION Test Method Used: a Hydrostatic ❑ Vacuum ❑ Other Test Equipment Used: Incon Equipment Resolution: .0020 Identify Spill Bucket(By Tank 3 PRE FILL 2 3 PRE FILL 3 3 PRE VAPOR 4 3 PRE VAPOR Number, Stored Product, etc) Bucket Installation Type: ❑Direct Bury ❑Direct Bury ]Direct Bury 0 Direct Bury ❑Contained in Sump ❑Contained in Sump ❑Contained in Sump ❑Contained in Sump Bucket Diameter: 11" 11" 1111 1111 Bucket Depth: 1311 1311 1311 1311 Wait time between applying 15min 15min 15min 15min vacuum/water and starting test: Test Start Time(TI ): 12:50pm 1:0 5p 12 :50pm 1:0 5p Initial Reading(RI ): 4.0135 4.0133 4.9967 4.9970 Test End'Time(TF ): 1:0 5pm 1:2 Opm 1:05pm 1:2 Opm Final Reading(RF ): 4.0131 4.0130 4.9971 4.9969 Test Duration: 15min 15min 15min 15min Change in Reading(R F-RI ): .0004 .0003 .0004 .0001 Pass/Fail Threshold or .0020 .0 0 2 0 .0020 .0 0 2 0 Criteria: C3U •. ® SS a >w ® a N Comments- (include information on repairs made prior to testing, and recommended follow-up for failed tests) CERTIFICATION OF TECffi0CI4,N RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true,accurate,and in full compliance with legal requirements. Technician's Signature: Date: 02/07/2011 I State laws and regulations do not currently require testing to be performed by a qualified contractor.However,local requirements SITE DIAGRAM TanknokWy 8501 N MOPAC EXPRESSWAY,SUITE 400 AUSTIN,TEXAS 78759 (512)451-6334 FAX(512)459-1459 TEST DATE:02/07/11 WORK ORDER NUMBER3181091 CLIENT:7-ELEVEN, INC. SITE: 7-ELEVEN #17721, MKT 2368 So. REAL RD Direct Bury FiliNapor Buckets Nis 0 ,0 0 0 � T2 ;rl T1 � 3 O OA 7-11 #17721 4 3601 Stockdale Hwy L2 REG REG Bakersfield, CA 93309 STP L4 STP L3 661.834.3093 • Permit#S-2123-1-10 1 2 ESO L1 T3 STP ) OO PREM Overfill TLS 10( A Alarm ___EQ VEN CP L5 CAS DUMP- STER BREAKERS Printed 02123/2011 08:04 ACRAMER Work Order: 3181091 Oy(y)&6NY)TT'AgEbea-Veda 1-6252M Emergency Shut Off(ESO) & Dispenser Emergency Shutoff Valve (ESV) ANNUAL'TBST RECORD IACATTONS AND TEST DATA Teams Deft Lewdw rum ?- I S6oss iF: qb&'ID fk AAtheers O C a qey- Q46r�.., sic c.t �mer�e>a Sb4rt Off(F OI Tgstinn a in aaoordw=with"990 Vmlor l.,euer C3 21-OS)Aod',from Vale ra's Reiail ass Pot of aMMI amViimm awdn&this rCp=MUdiW tescd he slit off swit=b&clded on thi3*5bCIL listed blow: y stmt off 0M) IMN Provide j lrt Nswntenm=log it DM 09W: D®oenser F.M=09X ShHtoff VSbM(F-M Testing Beam On Z.-I-yl in aoomlmwe with NFPA 30A this reprCSMtfffffttMed&e > � of the Dispenser Emergency Shutoff VALVE(5)(ESV)1 in tine:mpply lines at the base of each individual island type dispenser bN iCMW on the di PM below.Each device(#)_ iet all, -,yauld autumWicaUy cdo. lisocd below: .�._.._ Dlsp. �[�ucy Shat Ott IfTio,Provide bl �v aw Pl.eemaa o�. amt V 0 0 p Tanknology Inc. 11000N.MoPac Expressway, Suite 500,Austin,Texas 78759 Work Order: 3181091 ALARM HISTORY REPORT ---- IN-TANK ALARM{ ---..- T I :REGULAR UL TANK 1 HIGH WATER ALARM FEB 7. 2011 9:40 AM OVERFILL ALARM FEB 7, 2011 9:5'"3 AM 235067 7-11 17721 LOLL PRODUCT ALARM 3601 STOCKDALE: HWY FEB 7, 2011 9:37 Am BAKERSFIELD,CA. 80749954505001 HIGH PRODUCT ALARM FEB 7. 2011 11 :53 AM FED 7. 2011 9:53 AM INVALID FUEL LEVEL FEB 7. 2011 9:37 AM SYSTEM STATUS REPORT PROBE OUT - - - - FEB 7, 2011 9:54 Ail SERVICE NOTICE FEB 7. 2011 9:37 AM P 5:HLARMI CLEAR WARNING HIGH WATER WARNING FEB 7. 2011 9:40 AM ALARM HISTORY RFPORT DELIVERY NEEDED ---- IN-TANK ALARM -- FEB 7, 2011 9:37 AM --- T 3:PREMIUM LOW TEMP WARNING HIGH WATER ALARM FEB 7. 2011 9:54 AM FEB 7, 2011 9:41 k, FEB 7. 2011 9:37 AM 235067 7-11 17721 OVERFILL ALARM 3601 STOC:KDALE HWY FEB 7, 2011 9:57 AM BAY.ERSFIELDXA. LOW PRODUCT ALARM 807499545050UI FED 7, 2011 9:38 AM FEB 7. 2011 I1 :53 AM ALARM HISTOR:' REPORT HIGH PRODUt'T ALARM ----- IN-TANK ALARM ----- FEB 7, 2011 9:58 N1 SYSTEM STATUS REPORT T 2:REGULER UL TANK. 2 INVALID FUEL LEVEL - - - - - - - - - - - - FEB 7, 2011 9:38 AM SERV 1 CE NOT I CE HIGH WATER ALARMI PROBE OUT FEB 7. 2011 9:37 AMI D 5:ALARM CLEAR WARNING, FEB 7, 2021 9:59 AMI OVERFILL. ALARM FEB 7. 2011 9:38 All FEB 9 7, 2011 9: AM HIGH WATER WARNING AUG flUG 29, 010 3:339 AM FEB 7, 2011 9:41 Ai LOW PRODUCT ALARM FEB 7, 2011 9:34 AM DELIVERY NEEDED HIGH PRODUCT ALARM FEB 7, 2011 9:38 AM FEB 7. 2011 9:51 AM JAN 28, 2011 5:43 PM INVALID FUEL LEVEL ALARM HI$TOP.Y kEP<-)FT FEB 7. 2011 9:34 All PROBE OUT -- SYSTEM ALARMI ----- FEB 7. 2011 9:52 AM PAPER OUT FEB 7. 2011 9:34 AM JAN 21 , 2011 8:36 AM PRINTER ERROR HIGH WATER WARNING JAN 21, 2011 6::36 AM FEB 7. 2011 9:37 AM CLOSE SHIFT PE�NDIN, -FEB 2, 2011 7:00 AM CLOSE DAIL1 PENDING DELIVERY NEEDED FEB 7, 2011 6:00 AM FEB 7, 2011 9:34 AM SERVICE NOTICE FEB 7, 2011 8:55 AM LOW TEMP WARNING FEB 7. 2011 9:52 AM Tanknology Inc. 11000N.MoPac Expressway,Suite 500,Austin,Texas 78759 Work Order: 3181091 ALARM HISTORY REPORT ----- SENSOR ALARM ----- L 1 :DISP PAN 1-2 DISPENSER PAN SENSOR OUT ALARM FEB 7. 2011 10:12 AIM FUEL ALARM FEB 7. 2011 10:09 AM FUEL ALARM AUG 2. 2010 9:09 AM ALARM HISTORY REPORT ----- SENSOR ALARM ----- L 4:RUL 2 TURBINE xxxXx END xx * x x SO SENSOR OUT ALARM FEB 7. 2011 10:12 AM FUEL ALARM FEB 7. 2011 10:10 AN FUEL ALARM AUG 2, 2010 9:07 41 ALARM HISTORY REPORT ----- SENSOR ALARM ----- L 2:DISP PAN 3-4 DISPENSER PAN SENSOR OUT ALARM FEB 7, 2011 10:12 AM * x x * x END x x x x FUEL ALARM FEB 7. 2011 10:09 AM FUEL ALARM AUG 2, 2010 9:09 AM ALARM HISTORY REPORT ----- SENOR ALARM ----- L 5:PUL TURBINE STP SUMP �± x A x END « x x x -i SENSOR OUT ALARM FEB 7. 2011 10:12 AM FUEL ALARM FEB 7, 2011 10:11 AM FUEL ALAR11 FEB 7, 2011 10:11 AM ALARM HISTORY REPORT ----- SENSOR ALARM ----- L 3:RUL 1 TURBINE STP SUMP SENSOR OUT ALARM FEB 7. 2011 10:12' AM FUEL ALARM FEB 7, 2011 10:10 AM FUEL ALARM AUG 2. 2010 9:9B AM Tanknology Inc. 11000 N.MoPac Expressway,Suite 500,Austin,Texas 78759 Work Order: 3181091 SYSTEM SETUP FEB 7, 2011 8:55 Am SYSTEM UN ITS U.S. SYSTEM LANGUAGE ENtiLISH 235067 7-11 17721 SYSTEM DATE.-TIME Fr-RMAT 3601 STOCKDALE HWY MON DD YYYY HH:1111:SS w:M BAKERSF171D,CA. 60749954505001 235067 7-11 17721 RE-DIRECT LOCAL PRINTOUT 3601 STOCKDALE HWY DISABLED FEB 7, 2011 8:53 AM 60744954505001 EURO PROTOCOL PREFIX S SHIFT TIME 1 : 7:00 AM SYSTEM STATUS REPORT SHIFT TIME 2 DISABLED - SHIFT TIME 3 D I;CABLED SYSTEM SECURITY TY ALL FUNCTIO14S 14ORMAL SHIFT TIME 4 DISABLED CODE : SECURI SHIFT BIR PRINTOUTS ENABLED DAILY BIR PRINTOUTS TANK CHART SE4,URITY ENABLED DISABLED TICKETED DELIVERY DISABLED TANK PER TST NEEDED LJRN CUSTOM ALARMS DISABLED DISABLED ----- SYSTEM ALARM ----- TANK ANN TST NEEDED WRN SERVICE NOTICE DISABLED FEB 7, 2011 8:55 AM SERVICE NOTICE LINE RE-ENABLE METHOD ENABLED PASS LINE TEST DELIVERY OVERRIDE DISABLED LINE PER T ST NEEDED WRN DISABLED ISO 3166 COUNTRY ANN TST NEEDED WRN CODE: DISABLED PRINT TC VOLUMES SOFTWARE REVISION LEVEL ENABLED Mi"2S,'DENS I TY VERSION 329.02 DISABLED SOFTWARE# 346329-100-C TEMP COMPENSATION CREATED - 09.07.01 .16.29 VALUE (DEG F is 60.0 STICK HEIGHT OFFSET S-MODULEO 330160-162-A ENABLED SYSTEM FEATURES: ULLAGE: 90% PERIODIC IN-TANK. TESTS ANNUAL IN-TANK TESTS H-PROTOCOL DATA FORMAT CSLD HEIGHT BIR DAYLIGHT SAVING TIME PLLD ENABLED 0.10 AUTO START DATE 0.20 REPETITIV MAR WEEK 3 SUN WPLLD START TIME 0.10 AUTO 2:00 AM 0.20 REPETITIV END DATE NOV WEEK 2 SUN END TIME 2:00 AM Tanknology Inc. 11000 N.MoPac Expressway,Suite 500,Austin,Texas 78759 Work Order: 3181091 COMMUNICATIONS SETUP PORT SETT I NCB: COMM BOARD : I (EDIM ) RS-232 SECURITY CODE : DISABLED 00i'IM BOARD : 2 (ED I M RS-232 SECURITY CODE : D I S-4--BLED COh1M BOARD : 3 (S-SAT ) AUTO DIAL TIME SETUP: BAUD RATE : 9600 PARITY : NONE D 5:FQ FMS STOP BIT : 2 STOP DIAL ON DATE DATA LEW.;TH: a DATA SEP 26, 2008 RS-232 SECURITY DIAL TIME : DISABLED CODE : DISABLED RECEIVER REPORTS: DTR NORMAL STATE: HIGH COMM LARD 5 (RS-4a5) ALL:DELIVY DENSITY WARN BAUD RATE 2400 PARITY : EVEN LIQUID SENSOR ALMS STOP HIT : 1 STOP ALL:FUEL ALARM DATA LENGTH: 7 DATA ALL:SENSOR OUT ALARM R9-232 SECURITY ALL:SHORT ALARM CODE : DISABLED ALL:WATER ALARM COMM 230ARD 6 (IHTCOhIM) ALL:WATER OUT ALARM RATE 1200 ALL:HIGH LIQUID ALARM BAUD ODD ALL:LOW LIQUID ALARM PARITY WARNING STOP BIT I STOP ALL:LIrdUILi DATA LENGTH: 7 DATA RS-232 END OF MESSAGE RECEIVER ALARMS RS-232 SECURITY DISABLED SERVICE REPORT WARN CODE : DISABLED ALARM CLEAR WARNING AUTO DIAL ALARM SETUP DELIVERY REPORT WRN AUTO TRANSMIT SETTINGS: - COMM SIDE DIM ALM AUTO LEAP: ALARM LIMIT D 5:FQ FMS ALL:DISABLED DIM ALARM ALL:COMMUNICATION ALARM DISABLED IN-TANK ALARNIS ALL:TRANSACTION ALARM AUTO HIGH WATER LIMIT ALL:LEAK ALARM DISABLED ALL:HIGH WATER ALARM RECONCILIATION ALM AUTO OVERFILL LIMIT ALL:OVERFILL ALARM ALL:PROD THRESHOLD ALM DISABLED ALL:LOW PRODUCT ALARM ALL:CLOSE SHIFT WARNING AUTO LOW PRODUCT AL.:SUDDEN LOSS ALARM ALL:CLOSE DAILY WARNING DISABLED ALL:HIGH PRODUCT ALARM AUTO THEFT LIMIT ALL:INVALID FUEL LEVEL PMC ALARMS DISABLED ALL:PROBE OUT VP EMISSIONS WARN AUTO DELIVERY START ALL:HIGH WATER WARNING VP EMISSIONS FAIL DISABLED ALL:DELIVERY NEEDED VP PRESSURE WARN AUTO DELIVERY END ALL:MHX PRODUCT AL,*M VP PRESSURE FAIL DISABLED VP DUTY CYCLE WARN AUTO EXTERNAL INPUT ON ALL:GROSS TEST FAIL DISABLED AC.I..:P>rk I OD]C• TEST FAIL VP DUTY CYCLE FAIL AUTO EXTERNAL INPUT OFF ALL:ANNUAL TEST FAIL PMC SETUP FAIL ALL:PER TST NEEDED WRN PMC SENSOR FAULT DISABLED AUTO LESOk FUEL ALARM ALL:ANN TST NEEDED WRN ALL:PER TST NEEDED ALM DISABLED AUTO SENSOR WATER ALARM ALL:ANN TST NEEDED ALM ALL:TANK TEST ikvTIVE DISABLED AUTO SENOR OUT ALARM ALL:NO CSLD IDLE TIME DISABLED ALL:TANK SIPHON BREAK ALL:CSLD ]NCR RATE WARN ALL:ACCU_CHART CAL WARN ALL:RECON WARNING ALL:RECON ALARM ALL:LOW TEMP WARNING RECEIVER SETUP: ALL:MISSING TICKET WARN ALL:GROSS FAIL LINE TNK D 5:FG FMS C10.90,3.96'3001 RCVR TYPE: COMPUTER PORT NO: 3 RETRY NO: 5 RETRY DELAY: 5 CONFIRMATION REPORT: OFF Tanknology Inc. 11000 N.MoPac Expressway,Suite 500,Austin,Texas 78759 Work Order: 3181091 T 2:REGULAR UL Ti=1NK 2 PRODUCT CODE 2 THERMAL COEFF : .000700 TANK DIAMETER 94.00 TANK PROFILE 20 PTS FULL VOL 10028 89,3 INCH VOL 9818 84.6 INCH VOL 9475 79.9 INCH VOL 9050 75.2 INCH VOL 8563 70.5 INCH VOL : 8028 65.8 INCH VOL 7459 61 .1 INCH VOL 6863 56.4 INCH VOL : 6247 51 .7 INCH VOL 5618 47.0 INCH VOL 4984 42.3 INCH VOL 4346 IN-TANK SETUP 37.6 INCH VOL 3722 32.9 INCH VOL 3107 - - - - - - - - - - - - 28.2 INCH VOL 2514 T 1 :REGULAR UL TAN}: 1 23.5 INCH VOL 1947 PRODUCT CODE 1 14.8 INCH VOL 1418 THERMAL COEFF : .000700 14.1 INCH VOL 937 TANK DIAMETER 94.00 .4 INCH VOL 494 SIPHON MANIFOLDED TAPIKS 4 4.7 INCH VOL 1B7 TANK PROFILE 20 PTS FULL VOL 10028 TO: METER DATA : YES 89.3 INCH VOL 9818 LINE MANIFOLDED TANKS END FACTOR: NONE 84.6 INCH VOL 9475 T4: NONE CAL UPDATE: NEVER 79.9 INCH VOL 9050 75.2 INCH VOL 8563 LEAK MIN PERIODIC: 244 FLOAT SIZE: 4.0 IN. 70.5 INCH VOL : 13028 2505 65.B INCH VOL 7459 WATER WARNING 1 .0 61 .1 INCH VOL : 6863 LEAK MIN ANNUAL 49'i HIGH WATER LIMIT: 1 .5 56.4 1NCH VOL : 6247 5010 51 .7 INCH VOL 5618 MAX OR LABEL VOL: 10020 47.0 INCH VOL 4984 OVERFILL LIMIT 90% 42.3 INCH VOL : 4:346 PERIODIC TEST T`VPE 9018 37.6 INCH VOL 3722 STANDARD HIGH PRODUCT 95% 32.9 INCH VOL 3107 9519 28.2 INCH VOL : 2514 ANNUAL TEST FAIL DELIVERY LIMIT 14% 23.5 INCH VOL 1947 nLARM DISABLED 1503 1B.8 INCH VOL 1418 14.1 INCH VOL : 937 PERIODIC TEST FAIL LOW PRODUCT 900 9.4 INCH VOL 494 A ALA IT: 15 4.7 INCH VOL 187 ALARM ENABLED LEAK ALARM LIMIT: METER DATA : YES SUDDEN LOSS LIMIT: 40 GROSS TEST END FACTOR: NONE FAIL TANK TILT 0.32 END UPDATE: NEVER ALARM ENABLED PROBE OFFSET 0.00 ANN TEST AVERAGING: OFF FLOAT SIZE: 4.0 IN. PER TEST AVERAGING: OFF SIPHON MANIFOLDED TANKS TO: NONE WATER WARNING 1 .0 TANK TEST NOT1F':': OFF LINE MANIFOLDED TANKS HIGH WATER LIMIT; 1 .5 TO: NONE TNK TST SIPHON 6FE/=t}C:OFF MAX OR LABEL VOL: 10020 DELIVERY DELAY 3 MIN LEAK MIN PERIODIC: 24% OVERFILL LIMIT 90`r, STICK OFFSET 0.00 2505 9018 PUMP THRE-HC!LD 10.00°%. HIGH PRODUCT 953s LEAK MIN ANNUAL : 493; 9519 5010 DELIVERY LIMIT 14% 1503 LOW PRODUCT 900 PERIODIC TEST TYPE LEAK ALARM LIMIT: 15 STANDARD SUDDEN LOSS LIMIT: 40 ANNUAL TEST FAIL TANK TILT 0.99 ALARM DISABLED PROBE OFFSET 0.00 PERIODIC TEST FAIL ALARM ENABLED GROSS TEST FAIL ALARM ENABLED ANN TEST AVERAGING: OFF PER TEST AVERAGING: OFF TANK TEST NOTIFY: OFF TNK TST SIPHON BREAK:OFF DELIVERY DELAY 3 MIN RT T(`X OFFSET n nn Tanknology Inc. 11000 N.MoPac Expressway,Suite 500,Austin,Texas 78759 Work Order: 3181091 T 3:PREMIU01 OUTPUT RELAY SETUP PRODUCT CODE 3 - - - - - - - - - - - - THERMAL C:OEFF : .000700 TANK DIAMETER 92.00 R ( :OVERFILL TANK PROFILE 1 PT TYPE: FULL VOL 10020 LEAK TEST METHOD STANDARD METER DATA YES - - - - - _ _ NORMALLY OPEN END FACTOR: NONE TEST C:SLD ALL TANK CAL UPDATE: NEVER Pd a 99y CLIMATE FACTOR:MODERATE IN-TANK ALARMS ALL:OVERF[LL ALARM FLOAT SIZE: 4.0 IN. REPORT ONLY: ALL:HIGH PRODUCT ALARM WATER WARNING 1 .0 DISABLED ALL:MAX PRODUCT ALARM HIGH WATER LIMIT: 1 .5 TST EARLY ST;)P:DISABLED TYPE: 1 MAX OR LABEL VOL: 10020 LEAK TEST REPORT FORMAT STANDARD OVERFILL LIMIT 90%G ENHANCED NORMALLY CLOSED 9018 HIGH PRODUCT 95: 9519 LIQUID SENSOR ALMS DELIVERY LIMIT 15%. L ! :FUEL ALARM 1503 L 2:FUEL ALARM L 3:FUEL ALARM LOW PRODUCT 900 L I :SENSOR OUT ALARM LEAK ALARM LIMIT: 15 L 2:SENSOR OUT ALARM SUDDEN LOSS LIMIT: 40 L 3:SENSOR OUT ALARM TANK TILT 0.17 L ! :SHORT ALARM PROBE OFFSET 0.00 L 2:SHORT ALARM LIQUID SENSOR SETUP L 3:SHORT ALARM SIPHON MANIFOLDED TANKS - R 3:RUL 2 TA: NONE L I :DISP PAN 1-2 TYPE: LINE MANIFOLDED TANKS TRI-STATE (SINGLE FLOAT) STANDARD T#: NONE CATEGORY : DISPENSER PAN NORMALLY CLOSED LEAK MIN PERIODIC: 25% LIQUID SENSOR ALMS 2505 L 2:DISP PAN 3-4 L ! :FUEL ALARM TRI-STATE (SINGLE FLOAT) L 2'FUEL ALARM LEAK. MIN ANNUAL 50% CATEGORY : DISPENSER PAN L 4:FUEL ALARM 5010 L 1 :SENSOR OUT ALARM L 2:SENSOR OUT ALARM L 4:SENSOR OUT ALARM PERIODIC TEST TYPE L 3:RUL I TURBINE L ! :SHORT ALARM STANDARD TRI-STATE %SINGLE FLOAT) L 2:SHORT ALARM CATEGORY STP SUMP L 4:SHORT ALARM ANNUM.. TEST FAIL ALARM DISABLED R 4:PUL L 4:RUL 2 TURBINE TYPE: PERIODIC TEST FAIL TRI-STATE (SINGLE FLOAT) STANDARD ALARM ENABLED CATEGORY STP SUMP NORMALLY CLOSED GROSS TEST FAIL ALARM ENABLED L 5:PUL TURBINE LIQUID SENSOR ALMS TRI-STATE (SINGLE FLOAT) L ! :FUEL ALARM L 2:FUEL ALARM ANN TEST AVERAGING: OFF CATEGORY STP SUMP PER TEST AVERAGING: OFF L 5: SEENSOALARM ALARM TANK TEST NOTIFY: OFF L 2:SENSOR OUT ALARM L 5:SENSOR OUT ALARM TNK TST SIPHON BREAK:OFF L 2:SHORT ALARM DELIVERY DELAY 3 MIN L 5:SHORT ALARM STICK OFFSET 0.00 PUMP THRESHOLD 10.00% Tanknology Inc. 11000 N.MoPac Expressway, Suite 500,Austin,Texas 78759 Work Order: 3181091 i RECONCILIATION SETUP EDIM 1 : ED 111 2: AUTOMATIC DAILY (,LOS I N(; TIME: 6:00 AM AUTO SHIFT 01 CLOSING TIME: DISABLED AUTO SHIFT #2 CLOSING TIME: DISABLED AUTO SHIFT 03 CLOSING TIME: DISABLED AUTO SHIFT 04 CLOSING TIME: 7:00 AM PERIODIC RECONCILIATION MODE: MONTHLY ALARM: ENABLED ALARM THRESHOLD: 1.00 ALARM OFFSET: 130 TEMP COMPENSATION STANDARD METER CALIBRATION OFFSET: 0.000% BUS SLOT FUEL METER TANY - 3 2 1 2 1 3 2 1 3 3 3 2 2 2 1 3 2 2 3 3 3 2 3 2 2 3 2 3 3 3 3 2 4 2 2 3 2 4 3 3 PIlC SETUP PMC VERSION; 01 .02 VAPOR PROCESSOR TYPE NONE PROCESSOR CONTROL LEVEL: NONE Tanknology Inc. 11000 N.MoPac Expressway,Suite 500,Austin,Texas 78759 Work Order: 3181091 7-11 17721 3601 STOCKDALE HWY 7-11 17721 BAKERSFIELD 3601 STOCKDALE HWY CALIFORNIA BAKERSFIELD 3181091 CALIFORNIA 3181091 02/07/2011 12:13 PM 02/07/2011 12:30 PM SUMP LEAK TEST REPORT SUMP LEAK TEST REPORT 87FIH 87FILL TEST STARTED 11:57 AM TEST STARTED 02/07/2011 TEST STARTED 12:14 PM BEGIN LEVEL 5,1461 IN TEST STARTED 02/07/2011 END TIME 12:13 PM BEGIN LEVEL 5,1466 IN END DATE 02/07/2011 END TIME 12:30 PM END LEVEL 5,1466 IN END DATE 02/07/2011 LEAK THRESHOLD 0.002 IN END LEVEL 5,1467 IN TEST RESULT PASSED LEAK THRESHOLD 0,002 IN TEST RESULT PASSED 87VWM 87VAPOR TEST STARTED 11:57 AM TEST STARTED 02/07/2011 TEST STARTED 12:14 PM BEGIN LEVEL 5,1734 IN TEST STARTED 02/07/2011 END TIME 12:13 PM BEGIN LEVEL 5,1731 IN END DATE 02/07/2011 END TIME 12:30 PM END LEVEL 5.1732 IN END DATE 02/07/2011 LEAK THRESHOLD 0.002 IN END LEVEL 5.1729 Its TEST RESULT PASSED LEAK THRESHOLD 0,002 IN TEST RESULT PASSED 87FILL 87FILL TEST STARTED 11:57 AM TEST STARTED 02/07/2011 TEST STARTED 12:14 PM BEGIN LEVEL 4,6701 IN TEST STARTED 02/07/2011 END TIME 12:13 PM BEGIN LEVEL 4.6694 IN END DATE 02/07/2011 END TIME 12:30 PM END LEVEL 4.6695 IN END DATE 02/07/2011 LEAK THRESHOLD 0.002 IN END LEVEL 4,8693 IN TEST RESULT PASSED LEAK THRESHOLD 0,002 IN TEST RESULT PASSED 87VAPOR 87VAPOR TEST STARTED 11:57 AM TEST STARTED 02/07/2011 TEST STARTED 12:14 PM BEGIN LEVEL 4,1260 IN TEST STARTED 02/07/2011 END TIME 12:13 PM BEGIN LEVEL 4.1259 IN END DATE 02/07/2011 END TIME 12:30 PM END LEVEL 4,1260 IN END DATE 02/07/2011 LEAK THRESHOLD 0,002 IN END LEVEL 4,1260 IN TEST RESULT PASSED LEAK THRESHOLD 0.002 IH TEST RESULT PASSED Tanknology Inc. 11000N.MoPac Expressway,Suite 500,Austin,Texas 78759 Work Order: 3181091 r 7-11 17721 7-11 17721 3601 STOCKDALE HWY 3601 MCKDALE HWY BAKERSFIELD BAKERSFIELD CALIFORNIA CALIFORNIA 3181091 3181091 02/07/2011 1:21 PM 02/07/2011 1:05 PM SUMP LEAK TEST REPORT SUMP LEAK TEST REPORT 91FILL 91FILL TEST STARTED 1:05 PM TEST STARTED 12:50 PM TEST STARTED 02/07/2011 TEST STARTED 02/07/2011 BEGIN LEVEL &,0133 IN BEGIN LEVEL 4,0135 IN END TIME 1:20 PM END TIME 1:05 PM END DATE 02/07/2011 END DATE 02/07/2011 END LEVEL 4,0130 IN END LEVEL 410131 IN LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0,002 IN TEST RESULT PASSED TEST RESULT PASSED 91VAPOR 91VAPOR TEST STARTED 1:05 PM TEST STARTED 12:50 PM TEST STARTED 02/07/2011 TEST STARTED 02/07/2011 BEGIN LEVEL 4,9970 IN BEGIN LEVEL 4,9967 IN END TIME 1:20 PM END TIME 1:05 PM END DATE 02107/2011 END DATE 02/07/2011 END LEVEL 4,9969 IN END LEVEL 4.9971 IN LEAK TAF&40LD 0,002 IN LEAK THRESHOLD 0,002 IN TEST RESULT PASSED TEST RESULT PASSED Tanknology Inc. 11000 N.MoPac Expressway,Suite 500,Austin,Texas 78759 _JL ; T` anknology 11000 N. MoPac Expressway,Suite 500 Austin,Texas 78759 Phone: (512)451-6334 Fax: (512)459-1459 Date Printed and Mailed: 02/23/2011 BAKERSFIELD FIRE DEPARTMENT OFFICE OF ENVIRONMENTAL SERVICES INSPECTOR CRAIG PERKINS 1501 TRUXTUN AVE. BAKERSFIELD, CA. 93301 Test Date: 02/07/2011 Order Number: 3181091 Dear Regulator, Enclosed are the results of recent testing performed at the following facility: 7-ELEVEN #17721, MKT 2368 3601 STOCKDALE HIGHWAY BAKERSFIELD, CA. 93309 Testing performed: Impact Valve Leak detector tests Monitor Certification Secondary Containment-Spill Container Sincerely, 21b amyr � Dawn Kohlmeyer Manager, Field Reporting X17 TANKNOLOGY CERTIFICATE OF TESTING 8501 N MOPAC EXPRESSWAY,SUITE 400 AUSTIN,TEXAS 78759 TELEPHONE(512)451-6334 FAX(512)459-1459 PURPOSE: COMPLIANCE TEST RESULT SUMMARY REPORT TEST DATE: 02/07/11 WORK ORDER NUMBER: 3181091 CUSTOMER PO: CLIENT: 7-ELEVEN,INC. SITE:7-ELEVEN#17721,MKT 2368 P.O.BOX 711 3601 STOCKDALE HIGHWAY DALLAS,TX 75221 BAKERSFIELD,CA 93309 Manager (972)828-7908 (661)834-3093 TEST TYPE: TLD-1 Product Pipe Ti htness Test Results LIN LINE LIN N IMP'AC D RODUCT TYPE TEST MATE L FIN RATE gph V YE B D A B D F NCTiO SOUTH UL 1 REGULAR DW.FLEX PRESSURE Y NORTH UL 2 REGULAR DIN FLEX PRESSURE Y T3 PREM 3 PREMIUM DW FLEX PRESSURE Y Existina Line Leak Detector Test %TLNG LEAK DE1TEi,CT�_ EXIS N 1L CTOR Ip UFACTUR R MODEL# SEF! ULT MANUFACTURE MODE SE=R SOUTH UL 1 VAPORLESS MLD Unreadable P NORTH UL 2 RED JACKET FX1V 1899 P T3 PREM 3 VAPORLESS LD2000 0404422 P New Replacement Line Leak Detector Test UFA R MOp # UL M ACTOR MADE I SE RES For owner detailed report information,visit www.tanlrnology.com and select On-Line Reports-WRAP,or contact your local Tanknology office. Tester Name:ROBERT ALLEN Technician Certification Number:3637843760 Printed 02/23/201108:04 ACRAMER INDIVIDUAL TANK INFORMATION AND TEST RESULTS Mr Tian TEST DATE: 02/07/11 8501 N MOPAC EXPRESSWAY,SUITE 400 WORK ORDER NUMBER: 3181091 AUSTIN,TEXAS 78759(512)451-6334 CLIENT: 7-ELEVEN, INC. SITE: 7-ELEVEN #17721, MKT 2368 INNOtAN II�FGR A O T Tank ID: SOUTH UL 1 Tank manifolded: NO Bottom to top fill in inches: 128.0 Product: REGULAR Vent manifolded: YES Bottom to grade in inches: 134.0 Capacity in gallons: 10,020 Vapor recovery manifolded: YES Fill pipe length in inches: 32.0 Diameter in inches: 92.00 Overfill protection: YES Fill pipe diameter in inches: 4.0 Length in inches: 353 Overspill protection: YES Stage I vapor recovery: DUAL Material: STEEL Installed: ATG and CP Stage II vapor recovery: ASSIST CP installed on: COMMENTS TEST ESULTS es Met 029e eth PSI at tank bottom: New/passed Failed/replaced New/passed Failed/replaced Fluid level in inches: L.D.#1 L.D.#1 L.D.#2 L.D.#2 UFT/OFT: Make: VAPORLESS Fluid volume in gallons: Model: KLD Tank water level in inches: S/N: U=eadable Test time: NOT Open time in sec: 4.00 Number of thermisters: TESTED Holding psi: 23 NOT Specific gravity: Resiliency cc: 80 TESTED Water table depth in inches: Test leak rate ml/m: 189.0 Determined by(method): Metering psi: 9 Leak rate in gph: Calib. leak in gph: 3.00 Result: Results: PASS COMMENTS COMMENTS G TE T RE3 B :NONB LI ST RESU ty - Test time: Ullage volume: Material: Dw FLEX Ullage pressure: Diameter(in): 1.5 Results: Length(ft): 50.0 Test psi: DATA FOR UTS-4T ONLY: Bleedback cc: Time of test 1: Test time(min): Temperature: NOT Start time: NOT NOT NOT NOT Flow rate(cfh): TESTED End time: TESTED TESTED TESTED TESTED Time of test 2: Final gph: Temperature: Result: Flow rate(cfh): Pump type: PRESSURE Time of test 3: Pump make: RED JACKET Temperature: Flow rate(cfh): Impact Valves Operational: YES COMMENTS COMMENTS Printed 02/23/2011 08:04 ACRAMER I INDIVIDUAL TANK INFORMATION AND TEST RESULTS `r Tar*rwlogy TEST DATE: 02/07/11 8501 N MOPAC EXPRESSWAY,SUITE 400 WORK ORDER NUMBER: 3181091 AUSTIN,TEXAS 78759(512)451-6334 CLIENT: 7-ELEVEN, INC. SITE: 7-ELEVEN #17721, MKT 2368 �f$INFORMAtION Tank ID: NORTH DL 2 Tank manifolded: NO Bottom to top fill in inches: 126.0 Product: REGULAR Vent manifolded: YES Bottom to grade in inches: 132.0 Capacity in gallons: 10,020 Vapor recovery manifolded: YES Fill pipe length in inches: 30.0 Diameter in inches: 92.00 Overfill protection: YES Fill pipe diameter in inches: 4.0 Length in inches: 353 Overspill protection: YES Stage I vapor recovery: DUAL Material: STEEL Installed: ATG and CP Stage II vapor recovery: ASSIST CP installed on: COMMENTS T R S L T e d: NE ETE S SU e m od PSI at tank bottom: New/passed Failed/replaced New/passed Failed/replaced Fluid level in inches: L.D.#1 L.D.#1 L.D.#2 L.D.#2 UFT/OFT: Make: RED JACKET Fluid volume in gallons: Model: Pxiv Tank water level in inches: S/N: 1899 Test time: NOT Open time in sec: 2.00 Number of thermisters: TESTED Holding psi: 24 NOT Specific gravity: Resiliency cc: 40 TESTED Water table depth in inches: Test leak rate ml/m: 189.0 Determined by(method): Metering psi: is Leak rate in gph: Calib. leak in gph: 3.00 Result: Results: PASS COMMENTS COMMENTS U GE TES RESU TS 161 0 O L1W ST RESU type: Test time: Ullage volume: Material: DW FLEX Ullage pressure: Diameter(in): 1.5 Results: Length(ft): 50.0 Test psi: DATA FOR UTS-4T ONLY: Bleedback cc: Time of test 1: Test time(min): Temperature: NOT Start time: NOT NOT NOT NOT Flow rate(cfh): TESTED End time: TESTED TESTED TESTED TESTED Time of test 2: Final gph: Temperature: Result: Flow rate(cfh): Pump type: PRESSURE Time of test 3: Pump make: RED JACKET Temperature: Flow rate(cfh): Impact Valves Operational: YES COMMENTS COMMENTS Printed 02/23/2011 08:04 ACRAMER INDIVIDUAL TANK INFORMATION AND TEST RESULTS i Ta TEST DATE: 02/07/11 8501 N MOPAC EXPRESSWAY,SUITE 400 WORK ORDER NUMBER: 3181091 AUSTIN,TEXAS 78759(512)451-6334 CLIENT: 7-ELEVEN, INC. SITE: 7-ELEVEN #17721, MKT 2368 AN INF•.RICA-1 Tank ID: T3 PREM 3 Tank manifolded: No Bottom to top fill in inches: 126.0 Product: PREMIUM Vent manifolded: YES Bottom to grade in inches: 132.0 Capacity in gallons: 10,020 Vapor recovery manifolded: YES Fill pipe length in inches: 30.0 Diameter in inches: 92.00 Overfill protection: YES Fill pipe diameter in inches: 4.0 Length in inches: 323 Overspill protection: YES Stage I vapor recovery: DUAL Material: LINED Installed: ATC and CP Stage II vapor recovery: ASSIST CP installed on: COMMENTS OAR WTIBIJRCSUjTS e O O 4 Tit SU etho PSI at tank bottom: New/passed Failed/replaced New/passed Failed/replaced Fluid level in inches: L.D.#1 L.D.#1 L.D.#2 L.D.#2 LIFT/OFT: Make: VAPORLESS Fluid volume in gallons: Model: LD2000 Tank water level in inches: S/N; 0404*22 Test time: NOT Open time in sec: 5.50 Number of thermisters: TESTED Holding psi: 21 NOT Specific gravity: Resiliency cc: 70 TESTED Water table depth in inches: Test leak rate ml/m: 189.0 Determined by(method): Metering psi: 15 Leak rate in gph: Calib. leak in gph: 3.00 Result: Results: PASS COMMENTS COMMENTS UL 8 •d NONE LIN TEST RESC] T3 T Test time: Ullage volume: Material: DW FLEX FLEX Ullage pressure: Diameter(in): 2.0 2.0 Results: Length(ft): 25.0 35.0 Test psi: DATA FOR UTS-4T ONLY: Bleedback cc: Time of test 1: Test time(min): Temperature: NOT Start time: NOT NOT NOT NOT Flow rate(cfh): TESTED End time: TESTED TESTED TESTED TESTED Time of test 2: Final gph: Temperature: Result: Flow rate(cfh): Pump type: PRESSURE Time of test 3: Pump make: RED JACKET Temperature: Flow rate(cfh): Impact Valves Operational: YES COMMENTS COMMENTS LI I -- [1 Printed 02/23/2011 08:04 ACRAMER