Secondary Containment Testing Report Form
This form is intendedfor use by contractors performing p eriodic testing of UST secondary containment systems. Use the
appropriate pages of this form to report results for all components tested The completed form, written test procedures, and
printouts from tests(if applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: GO GO MM MART Date of Testing: 10-15-08
Facility Address: 3699 WILSON RD
Facility Contact: ALONDRA Phone: 835-8044
Date Local Agency Was Notified of Testing: 10/07/08
Name of Local Agency Inspector(fpresent during testing): Bakersfield Fire Dept.
2. TESTING CONTRACTOR INFORMATION
Company Name: Redwine Testing Services,Inc.
Technician Conducting Test: RUBEN BECERRA
Credentials: X CSLB Licensed Contractor ❑SWRCB Licensed Tank Tester
License Type: A HAZ License Number: 532878
Manufacturer Training
Manufacturer Component(s) Date Training Expires
Incon Incon TS-STS 02/14/2010
3. SUMMARY OF TEST RESULTS
Component Pass Fail Not Repairs Component Pass Fail Not Repairs
Tested Made Tested Made
87 ANNULAR X ❑ 0 ❑ 5-6 UDC X ❑ p ❑
87-2 ANNULAR X 0 ❑ 0 7-8 UDC X 0 ❑ 0
91 ANNULAR X ❑ 0 ❑ 87 FILL SUMP X ❑ ❑ ❑
W-O ANNULAR X ❑ ❑ ❑ 87-2 FILL SUMP X ❑ ❑ ❑
87 SECONDARY X ❑ ❑ ❑ 91 FILL SUMP X ❑ ❑ 0
87-2 SECONDARY X ❑ 0 0 W-O FILL SUMP X ❑ ❑ ❑
91 SECONDARY X 0 0 ❑ 87 SPILL BUCKET X 0 0 ❑
87 PIPING SUMP X ❑ ❑ ❑ 87 VPR BUCKET X 0 ❑ ❑
87-2 PIPING SUMP X 0 ❑ ❑ 87-2 SPILL BUCKET X ❑ ❑ ❑
91 PIPING SUMP X ❑ ❑ ❑ 87-2 VPR BUCKET X ❑ ❑ 0
1-2 UDC X ❑ ❑ ❑ 91 SPILL BUCKET X ❑ ❑ ❑
3-4 UDC X ❑ 0 0 91 VPR BUCKET X ❑ ❑ ❑
If hydrostatic testing was performed,describe what was done with the water after completion of tests:
Recycle and reused.
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
To the best of my knowledge,the fads stated in this ment are accurate and in full compliance with legal requirements
Technician's Signature: Date 10/15/08
IIIIIIIIIIIIIIIIIIII 46
I
SWRCB,,January 2002 Page of
4. TANK ANNULAR TESTING
Test Method Developed By: ❑Tank Manufacturer X Industry Standard ❑Professional Engineer
❑Other(Specify)
Test Method Used: ❑Pressure X Vacuum ❑Hydrostatic
❑Other(Spec)
Test Equipment Used: 4 in.Dial Gauge Equipment Resolution: .5%
Tank#87 Tank#87-2 Tank#91 Tank#W-O
Is Tank Exempt From Testing?' ❑Yes X No ❑Yes X No ❑Yes X No ❑Yes X No
Tank Capacity: 12K GALLON 12K GALLON 12K GALLON 500 GALLON
Tank Material: FIBERGLASS FIBERGLASS FIBERGLASS FIBERGLASS
Tank Manufacturer: XERXES XERXES XERXES XERXES
Product Stored: GASOLINE GASOLINE GASOLINE WASTE OIL
Wait time between applying
pressure/vacuum/water and 30 MIN 30 MIN 30 MIN 30 MIN
startin test:
Test Start Time: 10:00AM 10:00AM 11:OOAM 11:OOAM
Initial Reading(Rj): -10 HG -10 HG -10 HG -10 HG
Test End Time: 11:OOAM 11:OOAM 12:OOPM 12:OOPM
Final Reading(RF): -10 HG -10 HG -10 HG -10 HG
Test Duration: 1 HR 1 HR 1 HR 1 HR
Change in Reading(RF-Rj): NONE NONE NONE NONE
Pass/Fail Threshold or Criteria: PASS PASS PASS PASS
TestResult: X Pass°: d Fad X,:Pass. _❑Fail'; X Pass y ❑Fail X Pass; ❑Fa►1
Was sensor removed for testing? X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA
Was sensor properly replaced and X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes. ❑No ❑NA
verified functional after testis ?
Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests)
i
' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary
containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment
testing. {California Code of Regulations,Title 23,Section 2637(ax6))
SWRC&,January 2002 Page of
5. SECONDARY PIPE TESTING
Test Method Developed By: ❑Piping Manufacturer X Industry Standard ❑Professional Engineer
❑Other(Specify)
Test Method Used: X Pressure ❑Vacuum ❑Hydrostatic
❑Other(Specify)
Test Equipment Used: 4"Gauge Equipment Resolution: .5%
Boom
Piping Run#87 Piping Run#87-2 Piping Run#91 Piping Run#
Piping Material: FIBERGLASS FIBERGLASS FIBERGLASS
Piping Manufacturer: A.O.SMITH A.O. SMITH A.O. SMITH
Piping Diameter: 5" 5" 5"
Length of Piping Run: 30' 30' 30'
Product Stored: GASOLINE GASOLINE GASOLINE
Method and location of TEST PORT TEST PORT TEST PORT
piping-run isolation:
Wait time between applying
pressure/vacuum/water and 30 MIN 30 MIN 30 MIN
starting test:
Test Start Time: 10:OOAM 10:OOAM 11:OOAM
Initial Reading(Rj): 5 PSI 5 PSI 5 PSI
Test End Time: 11:OOAM 11:0OAM 12:OOPM
Final Reading(RF): 5 PSI 5 PSI 5 PSI
Test Duration: 1 HR 1 HR 1 HR
Change in Reading(RF-Ri): NONE NONE NONE
Pass/Fail Threshold or PASS PASS PASS
Criteria:
T�est'Result; X Pass:; 01 ail X Pass 'Fad == X Pass 0 Fail,r Pass:. ;Fail,
Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests)
,SWRCB,January 2002 Page of
6. PIPING SUMP TESTING
Test Method Developed By: ❑Sump Manufacturer X Industry Standard ❑Professional Engineer
❑Other(Spec)
Test Method Used: ❑Pressure ❑Vacuum X Hydrostatic
❑Other(Sped)
Test Equipment Used: Incon TS-STS Equipment Resolution: .000 in.
Sump#87 Sump#87-2 Sump#91 Sump#
Sump Diameter: 32" 32" 32"
Sump Depth: 61" 61" 61"
Sump Material: FIBERGLASS FIBERGLASS FIBERGLASS
Height from Tank Top to Top of 12" 12" 12"
Highest Piping Penetration:
Height from Tank Top to Lowest 20" 20" 20"
Electrical Penetration:
Condition of sump prior to testing: CLEAN CLEAN CLEAN
Portion of Sump Tested' 25% 25% 25%
Does turbine shut down when
sump sensor detects liquid(both X Yes ❑No DNA X Yes ❑No ❑NA X Yes ❑No ❑NA ❑Yes ❑No ❑NA
product and water)?*
Turbine shutdown response time 7 SEC 7 SEC 7 SEC
Is system programmed for fail-safe X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA ❑Yes ❑No ❑NA
shutdown?`
Was fail-safe verified to be X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA ❑Yes ❑No ❑NA
operational?*
Wait time between applying
pressure/vacuum/water and starting 30 MIN 30 MIN 30 MIN
test:
Test Start Time: 10:45AM/11:02AM 11:20AM/11:36AM 11:54AM/12:12PM
Initial Reading(R,): 2.5727"/2.5714" 4.1096"/4.1098" 2.4390"/2.4382"
Test End Time: 11:00AM/11:18AM 11:35AM111:51AM 12:09PM112:28PM
Final Reading(RF): 2.5713"/2.5711" 4.1099"/4.1099" 2.4384"/2.4386"
Test Duration: 15MIN/I5MIN 15MIN/15MIN I5MIN/I5MIN
Change in Reading(FF-RO: 0.0014"/0.0003" 0.0003"/0.0001" 0.0006"/0.0004"
Pass/Fail Threshold or Criteria: 0.002"/0.002" 0.002"/0.002" 0.002"/0.002"
Test Restiflt X `Pass ❑Fail X Pass ❑Fail X Pass C]Fail O Pass ❑1Fail
Was sensor removed for testing? X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA ❑Yes ❑No ❑NA
Was sensor properly replaced and X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA ❑Yes ❑No ❑NA
verified functional after testin ?
Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests)
' If the entire depth of the sump is not tested,specify how much was tested. If the answer to any of the questions indicated with an
asterisk(*)is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160)
-SWRCB,January 2002 Page of
7. UNDER-DISPENSER CONTAINMENT C TESTING
Test Method Developed By: ❑UDC Manufacturer X Industry Standard ❑Professional Engineer
❑Other(Specify)
Test Method Used: ❑Pressure ❑Vacuum X Hydrostatic
❑Other(Spec)
Test Equipment Used: Incon TS-STS Equipment Resolution: .000 in.
El I I'll 111110111111; —UDC#1-2 UDC#3-4 UDC#5-6 UDC#7-8
UDC Manufacturer: UNK UNK UNK UNK
UDC Material: FIBERGLASS FIBERGLASS FIBERGLASS FIBERGLASS
UDC Depth: 34" 34" 34" 34"
Height from UDC Bottom to Top 12" 12" 12" 12"
of Highest Piping Penetration:
Height from UDC Bottom to 12" 12" 12" 12"
Lowest Electrical Penetration:
Condition of UDC prior to CLEAN CLEAN CLEAN CLEAN
testing:
Portion of UDC Tested 50% 50% 50% 50%
Does turbine shut down when
UDC sensor detects liquid(both X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA
product and water)?*
Turbine shutdown response time 7 SEC 7 SEC 7 SEC 7 SEC
Is system programmed for fail- X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA
safe shutdown?*
Was fail-safe verified to be X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA
operational?*
Wait time between applying 30 MIN 30 MIN 30 MIN 30 MIN
pressure/vacuum/water and
starting test
Test Start Time: 1:07PM/1:45PM 1:07PM/1:45PM 2:05PM/2:22PM 2:05PM/2:22PM
Initial Reading(R O: 2.9119"/3.5401" 2.1855"/3.5100" 6.0013"/6.0016" 5.4304"/5.4292"
Test End Time: 1:22PMr2:00PM 1:22PM/2:OOPM 2:20PM/2:37PM 2:20PM/2:37PM
Final Reading(RF): 2.9111"/3.5382" 2.1855"/3.5100" 6.0015"/6.0014" 5.4292"/5.4295"
Test Duration: 15MIN/15MIN 15MIN/15MIN 15MIN/15MIN 15MIN/15MIN
Change in Reading(RF-RO: 0.0008"/0.0018" 0.0000"/0.0000" 0.0002"/0.0002" 0.0012"/0.0003"
Pass/Fail Threshold or Criteria: 0.002"/0.002" 0.002"/0.002" 0.002"/0.002" 0.002"/0.002"
TestResult` �` Xy.L'ass, '_C7 Fair X1'ass', 'C1 T a�1 X FPass ❑'Fgl X Pass ❑'Fail
-,
Was sensor removed for testing? X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA
Was sensor properly replaced and X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA
verified functional after testin ?
COMMents—(include information on repairs made prior to testing, and recommended follow-up for failed tests)
' If the entire depth of the UDC is not tested,specify how much was tested. If the answer to M of the questions indicated with an
asterisk(')is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160)
SWRCB;January 2002 Page of
8. FILL RISER CONTAINMENT SUMP TESTING
Facility is Not Equipped With Fill Riser Containment Sums ❑
Fill Riser Containment Sumps are Present,but were Not Tested ❑
Test Method Developed By: ❑Sump Manufacturer X Industry Standard ❑Professional Engineer
❑Other(Spec)
Test Method Used: ❑Pressure ❑Vacuum X Hydrostatic
❑Other(Sped)
Test Equipment Used: Incon TS-STS Equipment Resolution: .000 in.
Fill Sump#87-1 Fill Sump#87-2 Fill Sump#91 Fill Sum p#W-O
Sump Diameter: 32" 32" 32" 32"
Sump Depth, 61" 61" 61" 43"
Height from Tank Top to Top of 15" 15" 15" 15"
Highest Piping Penetration:
Height from Tank Top to Lowest 17" IT' 17" 17"
Electrical Penetration:
Condition of sump prior to CLEAN CLEAN CLEAN CLEAN
testing:
Portion of Sump Tested 25% 25% 25% 25%
Sump Material: FIBERGLASS FIBERGLASS FIBERGLASS FIBERGLASS
Wait time between applying 30 MIN 30 MIN 30 MIN 30 MIN
pressure/vacuum/water and
starting test:
Test Start Time: 1:07PM/1:45PM 12:30PM/12:49PM 12:30/12:45PM 2:39PM/2:56PM
Initial Reading(R{): 3.2696"/3.7811" 4.8232"/4.8225" 5.8579"/5.8577" 4.2570"/4.2569"
Test End Time: 1:22PM/2:0OPM 12:45PM/1:04PM 12:45PM/1:04PM 2:54PM/3:11PM
Final Reading(RF): 3.2699"/3.7814" 4.8227"/4.8230" 5.8580"/5.8582" 4.2569"/4.2566"
Test Duration: 15MIN/15MIN 15MIN/15MIN 15MIN/15MIN 15MIN/15MIN
Change in Reading(RF-&): 0.0003"/0.0003" 0.0005"10.0005" 0.0001"0.0005" 0.0001"/0.0003"
Pass/Fail Threshold or Criteria: 0.002"/0.002" 0.002"/0.002" 0.002"/0.002" 0.002"/0.002"
Test Result X`Pass _❑fail >XvPass ❑Fail, rX Passe ` ❑Eail ;X Pass ` 0 Fad'`
Is there a sensor in the sump? X Yes ❑No X Yes ❑No X Yes ❑No X Yes ❑No
Does the sensor alarm when
either product or water is X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes 0 No ❑NA
detected?
Was sensor removed for testing? X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA X Yes ❑No ❑NA
Was sensor properly replaced and rx e s ❑No ❑NAT X Yes ❑No ❑�N:A X Yes ❑No ❑NA X Yes ❑No ❑�NA
verified functional after testin ?
Comments--(include information on repairs made prior to testing, and recommended follow-up for failed tests)
SWRCB;January 2002 Page of
9. SPILL/OVERFILL CONTAINMENT BOXES
Facility is Not Equipped With Spill/Overfill Containment Boxes ❑
Spill/Overfill Containment Boxes are Present,but were Not Tested ❑
Test Method Developed By: ❑Spill Bucket Manufacturer X Industry Standard ❑Professional Engineer
❑Other(Spec)
Test Method Used: ❑Pressure ❑Vacuum X Hydrostatic
❑Other(Spec)
Test Equipment Used: Incon TS-STS Equipment Resolution: .000 in.
Spill Box#87-1 Spill Box#87-1 Spill Box#87-2 Spill Box#87-2
SPILL VAPOR SPILL VAPOR
Bucket Diameter:
Bucket Depth: 15" 15" 15" 15"
Wait time between applying
pressure/vacuum/water and 30 MIN 30 MIN 30 MIN 30 MIN
starting test:
Test Start Time: 10:45AMII 1:02AM 10:45AM/I 1:20AM 11:36AM/I 1:20AM 11:54AM/12:12PM
Initial Reading(R,): 3.9176"/3.9162" 3.2195"/4.2493" 2.4089"/2.4092" 4.8420"/4.8424"
Test End Time: I1:00AMI11:18AM 11:00AM/l 1:35AM 11:51AM/11:35AM 12:39PM/12:28PM
Final Reading(RF): 3.9160"/3.9162" 3.2209"/4.2502" 2.4088"/2.4096" 4.8423"/4.8420"
Test Duration: 15MIN/15MIN 15MIN/15MIN 15MIN/15MIN 15MIN/15MIN
Change in Reading(RF-R,): 0.0016"/0.0000" 0.0014"/0.0009" 0.0001"/0.0004" 0.0003"10.0004"
Pass/Fail Threshold or 0.002"/0.002" 0.002"/0.002" 0.002"/0.002" 0.002"/0.002"
Criteria:
Test Resiilti X Pas§. ❑Fail X`Pass 'Fad X:Pass ❑Fair X Pass. ❑MFail,
Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests)
SWRCB,January 2002 Page of
9. SPILL/OVERFELL CONTAINMENT BOXES
Facility is Not Equipped With Spill/Overfill Containment Boxes ❑
Spill/Overfill Containment Boxes are Present,but were Not Tested ❑
Test Method Developed By: ❑Spill Bucket Manufacturer X Industry Standard ❑Professional Engineer
❑Other(Spec)
Test Method Used: ❑Pressure ❑Vacuum X Hydrostatic
❑Other(Specify)
Test Equipment Used: Incon TS-STS Equipment Resolution: .000 in.
Spill Box#91 SPILL Spill Boa#91 VPR Spill Boa#W.O. Spill Box#
SPILL
Bucket Diameter: 11" 11" 11"
Bucket Depth: 15" 15" 15"
Wait time between applying
pressure/vacuum/water and 30 MIN 30 MIN 30 MIN
starting test:
Test Start Time: 11:54AM/12-.12PM 12:30PM/12:49PM 2:39PM/2:56PM
Initial Reading(R,): 3.6712"/3.670T' 6.3791"/6.3791" 3.1281"/3.1280".
Test End Time: 12:09PM/12:28PM 12:45PM/1:04PM 2:54PM/3:1 IPM
Final Reading(RF): 3:6706"/3.6711" 6.3790"/6.3787" 3.1281"/3.1282"
Test Duration: 15MIN/15MIN 15MIN/15MIN 15MIN/l5MIN
Change in Reading(RF-R,): 0.0006"/0.0004" 0.0001"/0.0004" 0.0000"/0.0002"
Pass/Fail Threshold or 0.002"10.002" 0.002"/0.002" 0.002"/0.002"
Criteria:
Test Result X Pass: ❑Faii Pass q'Fai l X Pass ❑Fail'. . : Pass
X (J.Fail
Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests)
GOGO MINI MART j GOGO MINI MART
._'.699 WILSON RD. I 3699 WILSON RD.
BAKERSFIELD MKERSFIELD
LOGO ;MINI MART GAGO MINI MART CALIFORNIA j CALIFORNIA
3699 WILSON RD, 3699 WILSON RD, 1-800-984-6266 1-500-984-6266
BAKERSFIELD SRK,ERSFIELD
CALIFORNIA ED 2008 �3 I r�
1E+�15r�_ 1: FPi 1015. 008 11:00 RM
1-800-984-6266 1-800-984-6266 �
SUMP LEAK TEST REPORT i SUMP LEAK TEST REPORT
10/15/2008 2.55 Pht 10/15/2008 3: 1.1 F't'i
SUMP LEAK TESL" REPORT LEAK I 87FILL 87STP
SUMP TEST
W��STP TEST STARTED 1:07 PM j TEST STARTED 10:45 AM
bJOSTP TEST STARTED 10/15/2008 I TEST STARTED 10/15/2008
1"ES1" STARTED ':39 PM BEGIN LEVEL 3.2696 IN j BEGIN LEVEL 2.5727 IN j
TEST STARTED 256 PM END TIME i:12 PPi END TIME 11:00 AM
TEST STARTED 10.2570 0s TEST STARTED I0/15/20o+ END DATE 10/15/2008 END DATE 10/15/200$
BEGIN 'FUEL 4.2570 IN BEGIN LEVEL 4.2569 IN i 9u 3
END TIME 2:54 Phi z, END LEVEL 3.26_ . IN END LEVEL 2.571,: IN
END �y 1 � END TIME •11 PM � LEAK THRESHOLD 0.002 11.4 LEAK THRESHOLD 0.002 IN �
ATE 60/15/2003 END DATE 10/15/200$
END LEUEL 4.2569 IN END LEVEL 4,2566 IN TEST RESULT PASSED TEST RESULT PASSED
LEAK THRESHOLD 0.002 IN LEAK THRESHOLD 0.002 IN
TEST RESULT PASSED TEST RESULT PASSEL? ry
1—� UDC 87SPILL !
TEST STARTED 1:07 PP1 TEST STARTED 10:45 AM
WOSPILL WOSPILL TEST STARTED 10/15/2008 TEST STARTED 10/15/2008
I
TEST STARTED 2:39 Ph1 BEGIN LEUEL 2.9119 IN BEGIN LEUEL 3.9176 IN
TEST STARTED 2:5+_ PP1
TEST STARTED 10/15/2008 TEST rr
END TIME 1:22 PP1 END TIME 11:x0 Rr9
TEST LEVEL ::;.1231 IN EST STARTED 10/15. 1008 END DATE 10/15/2a0L END DATE 10/15/2008 j
END TIME :54 Ft9 8E+3.IN LEUEL 3.1280 IN END LE_IJEL 2.9111 IN END LEUEL 3.91.60 IN
END TIME ':il PM LEAK THRESHOLD 0.001 IN LEAK THRESHOLD 0.002 IN �
END DATE 10/15/2008 END DATE 10/151'200;=; o S I
TEST RESULT ASSkD TEST RESULT PASSED
END LEVEL 3.1281 IN END LEUEL 3.1282 IN
LEAK THRESHOLD 0.002 IN LEAK THRESHOLD 0.002 IN
TEST RESULT, PASSED TEST RESULT PASSED 3-4 UDC 87VAPOR
TEST STARTED 1:07 PM TEST STARTED 10:45 AM
TEST STARTED 10/15/2008 TEST STARTED 10/15/2008 !
BEGIN LEUEL 2.1855 IN BEGIN LEVEL 3.2195 IN
END TIME 1:22 PM I END TIME 11:00 AM
END DATE 10/15/2008 END DATE 10/15/2008
END LEUEL 2.1355 IN END LEVEL 3.2209 IN
LEAK THRESHOLD 0.002 IN LEAK THRESHOLD 0.002 IN
TEST RESULT PASSED TEST RESULT PASSED !
I
I
i
LOGO MINI MART GOGO MINI MART LOGO MINI MART
3699 WILSON RD. 3699 WILSON RD. 3
699 WILSON RD.
BRKERSFIELD BAKERSFIELD BAKERSFIELD
CALIFORNIA CALIFORNIA CALIFORNIA
1-800-984-6266 1-800-984-6266
1-800-984-6266 GOr,O rgINI MART
10/15/2008 11:18 AM 10/15/2008 11:35 AM 10/15/2008 11:51 AM 3699 WILSON RD.
SUMP LEAK TEST REPORT SUMP LEAK TEST REPORT i�CCALIFO NIA
SUMP LEAK TEST REPORT CALIFORNIA "
F 1-800-984-6266
87STP TP
c c VIPSTP 10/15/2008
: c•:
20 Pm TEST STARTED 11:02 AM TEST STARTED 11:20 AM TEST STARTED 11:36 AM
TEST STARTED 10/15/2008 TEST STARTED 10/15/2008 TEST STARTED 10/15/2008 i SUMP LEAK TEST 'REPORT
BEGIN LEVEL 2.5714 IN BEGIN LEVEL 4.1096 IN
5-6 UDC
END TIME 11:18 AM END TIME 11:35 AM BEGIN LEVEL 4.1098 IN
END DATE 10/15/2008 END DATE 10/15/2008
END TIME, 11:51 'iP'f
END LEVEL ''.5711 IN END DATE 10/15/2008
LEAK THRESHOLD 0.002 IN Eh1D LEVEL 4.1099 Iti TEST STARTED
LEAK THRESHOLD 0.002 IN ENC? LEVEL 4.1R19'� IN 05 Phi
j LEAK THRESHOLD 0.002 IN �ESf STARTED 10/15/2008
TEST RESULT PASSED TEST RESULT PASSED TEST RESULT PASSED BEGIN LEVEL 6.0013 IN
END TIME 2:20 PM
87SPILL END DATE 10/15/2008
&SPILL (SPILL END LEVEL 6.0015 IN
LEAS: THRESHOLD 0.002 IN
TEST STARTED 11:02 AM TEST STARTED 11:20 AM TEST RESULT
TEST STARTED 10/15/2008 TEST STARTED 10/15/2008 TEST STARTED 11:36 AM TEST
BEGIN LEVEL 3.9162 IN I
BEGIN LEVEL 2.4092 IN j TEST STARTED 10/15/2008
END TIME 11:18 AM ! BEGIN LEVEL 2.4089 IN
END DATE 10/15/2008 END TIME 11:35 AM i END TIME 11:51 AM 7-8 UDC
END LEVEL 3.9162 IN END DATE 10/15/2008 END DATE 10/15/2008 n
END LEVEL 2.4096 IN END LEVEL 2.4088 IN TEST .STARTED 5
LEAK THRESHOLD 0.002 IN LEA THRESHOLD 0.002 IN TEST STARTED •0 Ph;
TEST RESULT PASSED PASSED LEAK THRESHOLD 0.002 IN BEGIN LEVEE 15/15/2008
TEST RESULT TEST RESULT PASSED 4304 IN
END TIME 2:20 PM
mom END DATE 10/15/2008
OR
87VRPOR I END LEVEL 5.4292 IN
XESHOL STARTED 11: I LEAK THRESHOLD 0.002 IN
D 10/ S TEST STARTED 11:20 AM TES ARTED / RM TEST RESULT PASSED
08 IN TEST STARTED 10/15/200f� TEST S TED /2008
11:18 AM BEGIN I-EVEL 4.2493 IN BEGIN LE 4.2505 IN
END TIME 11:35 AM END TIME 11:51 AM
10/15/2008 END DATE 10/15/2008
=.2185 IN END LEVEL 4.2502 IN I END DAT /15/2008
OL 002 IN LEAK THRESHOLU 0.002 IN END L 480 IN
ILED TEST RESULT PASSED LE ESELTOLD 0. IN
T RESULT FA
I
i
GOGO 1INI MART j LOGO MINI MART
3644 WILSON RD. I 3699 WILSON RD. � I
BAKERSFIELD BAKERSFIELD GOGO MINI MAR1'
G0G0 3
CALIFORNIA 699 WILSON RD.
MINI � CALIFORNIA ' -
3699 WILSON RD. � 1-800-984-6266 i 1-800-984-6266 {AKERSFIELD
BAKERSFIELD CALIFORNIA
CALIFORNIA 10/15/2008 2:00 PM 10/15/2008 12:46 Pri 1-800-984-6266
1-800-984-6266
SUMP LEAK TEST REPORT SUMP LEAK TEST REPORT 101`15/2008 1:04 PM
10/15./20 18 2:37 PM I
87FILL 91VAP0R SUMP LEAK TEST REPORT
SUMP LEAK TEST REPORT
TEST STARTED 1:45 PM + TEST STARTED 12:30 PM ,
91VPPOR
5-6 UDC I TEST STARTED 10/15/200,0 TEST STARTED 10/15/2008.
BEGIN LEVEL 3.7811 IN I BEGIN LEVEL 6.3791 IN I TEST STARTED 12:49 PM
TEST STARTED 2:2"? PM END TIME 2:00 Pt-1 END TIME 12:45 PM ► TEST STARTED 10/15/2008
TEST STARTED 10/15/200;:, END DATE 10/15/2008 =ND DATE 10/15/2068 BEGIN LEVEL 6,3791 IN
BEGIN LEVEL 6.0016 IN END LEVEL 3.7814 IN END LEVEL 6.3740 IN END TIME 1:04 PM
END TIME 2:37 PM LEAK THRESHOLD 0,002 IN ► LEAK THRESHOLD 0.002 IN END DATE 10/15/2008
END DATE 10/15/2008 TEST RESULT PASSED TEST RESULT PASSEL? i END LEVEL 6.3787 IN
END LEVEL 6.6014 IN
LEAK THRESHOLD 0.002 IN
LEAK THRESHOLD 0.002 IN TENT RESULT PASSED
TEST RESULT PASSED 1-2) UDC 91FILL
i
TEST STARTED 1:45 P01 i TEST STARTED 12:30 PM 91FILL
7-8 UDC i TEST STARTED 10/15/2008 TEST STARTED 10/15/2068
BEGIN LEVEL 3.5401 IN BEGIN LEVEL 5.8574 IN TEST STARTED 12:49 PM
TEST STARTED 2:22 PM END TIME 2:00 PM + END TIME 12:45 PM TEST STARTED 10/15/2008
TEST STARTED 18/15/2008 END DATE 10/15/2002. END DATE 10/15/2008 BEGIN LEVEL 5.8577 IN
BE+GIN LEVEL 5.4292 IN END LEVEL 3.5382 IN ► END LEVEL 5.8580 IN END TIME 1:04 PM
END TIME 237 PM LEAK THRESHOLD 0.0102 IN LEAK THRESHOLD 0.002 IN END DATE 10/15/2008
END DATE 10/15/2008 TEST RESULT PASSED TEST RESULT PASSED ? END LEVEL 5.8582 IN
END LEVEL 5.4295 IN LEAK THRESHOLD 0.0012 IN
LEAK. THRESHOLD 0.002 IN ! TEST RESULT PASSED
TEST RESULT PASSED ; 3-4 UDC WILL
TEST STARTED 1:45 PM TEST STARTED 12:30 PM ' FILL
TEST STARTED 10/15/2008 ' TEST STARTED 10/15/2008 ►
BEGIN LEVEL 3.5100 IN BEGIN LEVEL. 4.8232 IN TEST STARTED 12:49 PM
END TIME 2:00 PM END TIME 12:45 PM TEST STARTED 10/15-'2008
END DATE 10/15/2068 END DATE 10/15/2008 BEGIN LEVEL 4,8225 IN
END LEVEL 3.5100 IN END LEVEL 4.8227 IN END TIME 1:04 PM
LEAK THRESHOLD 0.092 IN LEAK THRESHOLD 0.062 IN END DATE 16/15/2068
TEST RESULT PASSED TEST RESULT PASSED END LEVEL 4.8236 IN
LEAK THRESHOLD 0.002 IN
► TEST RESULT PASSED
LOGO MINI MART LOGO MINI MART
3699 WILSON RD. 3599 WILSON RD.
BAKERSFIELD BAKERSFIELD
CALIFORNIA CALIFORNIA
1-800-984-5266 1-800-984-6266
10/15/2008 12:10 PP1 i 10/15•'2008 12:'28 PP1
SUMP LEAK TEST REPORT SUMP LEAK TEST REPORT
AIVAFOF,'
VAPOR
TEST STARTED 11:54 AM TEST STARTED 12:12 PM
TEST STARTED 10/15/2008 TEST STARTED 10/15/2008
BEGIN LEVEL 4.8420 IN BEGIN LEVEL 4.8424 IN
END TIME 12:09 PM END TIME 12:28 PM
END DATE 10/15/2008 END DATE 10/15/2008
END LEVEL 4.8423 IN ENb LEVEL 4.8420 IN
LEAK THRESHOLD 0.002 IN LEAK THRESHOLD 0.002 IN
TEST RESULT PASSED TEST RESULT PASSED
91STP 91STP
TEST STARTED 11:54 AN I TEST STARTED 12: 12 PM
TEST STARTED 10/15/2008 TEST STARTED 10/15/2008
BEGIN LEVEL 2.4390 IN BEGIN LEVEL 2.4302 IN
END TIME 12:09 PM END TIME 12:28 PM
END DATE 10/15/2008 END DATE 10/15/200"
END LEVEL 2.4384 IN END LEVEL 2.436 IN
LEAK THRESHOLD 0.002 IN LEAK THRESHOLD 0.002 IN
TEST RESULT PASSED TEST RESULT PASSED
91SPILL 91SPILL
I
TEST STARTED 11:54 AM TEST STARTED 12: 12 PM
TEST STARTED 10/15/2008 TEST STARTED 10/15/2008
BEGIN LEVEL 3.6712 IN BEGIN LEVEL 3.6707 IN
END TIME 12:09 PM END TIME 12:28 PM
END DATE 10/15/2008 END DATE 10/15/2008
END LEVEL 3.6706 IN END LEVEL 3.6711 IN
LEAK THRESHOLD 0.002 IN LEAK THRESHOLD 0.002 IN
TEST RESULT PASSED TEST RESULT PASSED
- I
MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State of California N,p
Authwrity Cited:Chapter 6 7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations V�
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each
monitoring astem control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator.
The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility Name: GO GO MINI MART Bldg.No.:
Site Address: 3699 WILSON RD City: BAKERSFIELD Zip: 93309
Facility Contact Person: ALONDRA Contact Phone No.: (661) 835-8044
Make/Model of Monitoring System: VR TLS 350 Date of Testing/Servicing: 10/15/2008
B. Inventory of Equipment Tested/Certified
Check the appropriate boxes to indicate specific ui ment.ins ted/serviced:
FCOgAnnular 87 Tank ID: 89
k Gauging Probe. Model: 847390-107 ®In-Tank Gauging Probe. Model: 847390-107
Space or Vault Sensor. Model: 794390-407 ®Annular Space or Vault Sensor. Model: 794390-407
Sump/Trench Sensor(s). Model: 794380-205 ®Piping Sump/Trench Sensor(s). Model: 794380-205
®Fill Sump Sensor(s). Model: 794380-205 ®Fill Sump Sensor(s). Model: 794380-205
-0-Me7chamcal'Line Uap�-r,vtcul—h tndel:_$.I-FXIV- —_®_Mechanical Line 1--k.Det-ctor--Model: RJ-FXIV
r_. _ - -
❑Electronic Line Leak Detector. Model: ❑Electronic Line Leak Detector. Model:
❑Tank Overfill/High-Level Sensor. Model: ❑Tank Overfill/High-Level Sensor. Model:
❑Other(specify equipment type and model in Section E on Page 2). ❑Other(specify equipment type and model in Section E on Page 2).
Tank ID: 91 Tank ID: WASTE OIL
Z In-Tank Gauging Probe. Model: 847390-107 ❑In-Tank Gauging Probe. Model:
Z Annular Space or Vault Sensor. Model: 794390-407 ®Annular Space or Vault Sensor. Model: 794390-420
Z Piping Sump/Trench Sensor(s). Model: 794380-208 ❑Piping Sump/Trench Sensor(s). Model:
Z Fill Sump Sensor(s). Model: 794380-208 ®Fill Sump Sensor(s). Model: 794380-205
Z Mechanical Line Leak Detector. Model: RJ-FXIV ❑Mechanical Line Leak Detector. Model:
❑Electronic Line Leak Detector. Model: ❑Electronic Line Leak Detector. Model:
❑Tank Overfill/High-Level Sensor. Model: ®Tank Overfill/High-Level Sensor. Model: 794380-205
❑Other(specify equipment type and model in Section E on Page 2). ❑Other(specify equipment type and model in Section E on Page 2).
Dispenser ID: 1-2 Dispenser ID: 3-4
Z Dispenser Containment Sensor(s). Model: 794380-205 ®Dispenser Containment Sensor(s). Model: 794380-205
®Shear Valve(s). Z Shear Valve(s).
❑Dispenser Containment Float(s)and Chain(s). ❑Dispenser Containment Float(s)and Chain(s).
Dispenser ID: 5-6 Dispenser ID: 7-8
Z Dispenser Containment Sensor(s). Model: 794380-205 Z Dispenser Containment Sensor(s). Model: 794380-205
Z Shear Valve(s). Z Shear Valve(s).
❑Dispenser Containment Float(s)and Chain(s). ❑Dispenser Containment Float(s)and Chain(s).
Dispenser ID: Dispenser ID:
❑Dispenser Containment Sensor(s). Model: ❑Dispenser Containment Sensor(s). Model:
❑Shear Valve(s). ❑Shear Valve(s).
❑Dispenser Containment Float(s)and Chain(s). ❑Dispenser Containment Float(s)and Chain(s).
*If the facility contains more tanks or dispensers,copy this form. Include information for every tank and dispenser at the facility.
C. Certification -I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers'
guidelines. Attached to this Certification is information (e g. manufacturers' checklists) necessary to verify that this information is
correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports,I have also
attached a copy of the report;(check all that apply): ®System set-up ®Alarm histo. -
Technician Name(print): RUBEN BECERRA Signature:
Certification No.: VR-A206421 ICC#5238591-UT License.No.: 532878 A-h
Testing Company Name: Redwine Testing Services, Inc. Phone No.:(661) 834-6993
Site Address: 3699 WILSON RD Date of Testing/Servicing: 10115/2008
Page 1 of 3
UN-036-1/4 www.unidocs.org Rev.01/26/06
S
Monitoring System Certification
D. Results of Testing/Servicing
Software Version Installed: 7.03
Complete the folio win checklist:
® Yes ❑ No* Is the audible alarm operational?
® Yes ❑ No* Is the visual alarm operational?
® Yes ❑ No* Were all sensors visually inspected, functionally tested,and confirmed operational?
® Yes ❑ No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will
not interfere with their proper operation?
❑ Yes ❑ No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem)
® N/A operational?
® Yes ❑ No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
❑ N/A monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate
positive shut-down? (Check all that apply) ® Sump/Trench Sensors; M Dispenser Containment Sensors.
Did you confirm positive shut-down due to leaks and sensor failure/disconnection? ®Yes; ❑No.
❑ Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e.; no
® NIA-rncchunical-overfill-prevention valve-is-installed),-is-the-overfill warning alarm visible and audible at the tank
fill point(s)and operating properly? If so,at what percent of tank capacity does the alarm trigger? 95%
❑ Yes* ® No Was any monitoring equipment replaced? If yes, identify specific sensors,probes,or other equipment replaced
and list the manufacturer name and model for all replacement parts in Section E,below.
El Yes* ❑ No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)
❑Product; ❑ Water. If yes,describe causes in Section E,below.
IS Yes ❑ No* Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports, if applicable
® Yes ❑ No* Is all monitoring equipment operational per manufacturer's specifications?
*In Section E below,describe how and when these deficiencies were or will be corrected.
E. Comments:
Page 2 of 3
UN-036—2/4 www.unidocs.org Rev.01/26/06
Monitoring System Certification
F. In-Tank Gauging/SIR Equipment: ® Check this box if tank gauging is used only for inventory control.
❑ Check this box if no tank gauging or SLR equipment is installed.
This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
® Yes ❑ No* Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
• Yes ❑ No* Were all tank gauging probes visually inspected for damage and residue buildup?
• Yes ❑ No* Was accuracy of system product level readings tested?
• Yes ❑ No* I Was accuracy of system water level readings tested?
• Yes ❑ No* Were all probes reinstalled properly?
• Yes ❑ No* Were all items on the equipment manufacturer's maintenance checklist completed?
*In the Section H,below,describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD): ❑ Check this box if LLDs are not installed.
Complete the follo ing checklist:
® Yes ❑ No* For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance?
❑ N/A (Check all that apply) Simulated leak rate: ®3 g.p.h.; [10.1 g.p.h; ❑ 0.2 g.p.h.
• Yes ❑ No* Were all LLDs confirmed operational and accurate within regulatory requirements?
• Yes ❑ No* Was the testing apparatus properly calibrated?
• Yes ❑ No* For mechanical LLDs,does the LLD restrict product flow if it detects a leak?
❑ N/A
❑ Yes ❑ No* For electronic LLDs,does the turbine automatically shut off if the LLD detects a leak?
® N/A
❑ Yes ❑ No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled
® N/A or disconnected?
❑ Yes ❑ No* For electronic LLDs;does the turbine automatically shut off if any portion of the monitoring system malfunctions
® N/A or fails a test?
❑ Yes ❑ No* For electronic LLDs,have all accessible wiring connections been visually inspected?
® N/A
® Yes ❑ No* Were all items on the equipment manufacturer's maintenance checklist completed?
*In the Section H,below,describe how and when these deficiencies were or will be corrected.
H. Comments:
Page 3 of 3
UN-036—1/4 www.unidocs.org Rev.01/26/06
MECHANICAL LEAK DETECTOR TEST
WORK SHEET
W/O# :
Facility Name: GO GO MINI MART
Facility Address: 3699 WILSON RD, BAKERSFIELD,CA. 93309
Product Line Type (Pressure, Suction, Gravity) PRESSURE
PRODUCT LEAK DETECTOR TYPE TEST TRIP PASS
SERIAL# BELOW PSI OR
3 GPM FAIL
87 L/D TYPE RJ-FXIV YES 12 PSI PASS
SERIAL# 116-056
89 L/D TYPE RJFXIV YES 11 PSI PASS
SERIAL# 116-056
91 L/D TYPE RJFXIV YES 12 PSI PASS
SERIAL# 116-056
L/D TYPE
SERIAL#
I certify the above tests were conducted on this date according to Red Jacket Pumps
field test apparatus testing procedure an limitations
The Mechanical Leak Detector Test pass / fail is determined by using a low flow
threshold trip rate of 3 gallon per hour or les at 10 PSI
I acknowledge that all data collected is true and correct to the best of my knowledge.
Tech: Ruben Becerra
Signature: �`/: -. ,= Date: 10115/2008
Monitoring System Certification
UST Monitoring Site Plan
Site Address: °i`F `i.k:t t
.' - ��r 4 . . . . . . . . . . . . . . .
i I
-- ... �R r._ .«,.� . +. . . . . . . . . . . . . . . . .
.
�( . . . . . . . . . . . : . : __._ .�. #. . . .. . . . . . . . . . . . . .
P
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . § .
. t . . . . . . . . . . . . . . . . . .
r
. . . . . . . . . . . . . . . . . . . ttl lv . . . . . . . . . . #.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . r-,b-- -— .
. . . . . . . . . . . . . . . . ' ryq
)}j/ •.1{1. .._ "
. . � . � •.���/.
.P
. . . . . . . . . . A. 9 . . . . . . . . . . . . /.
. . . . . . . . . . . 't. P . . . . . . . . . . . . . .
Q�S�Gt `
.. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . �`.�--"c3Cay.i.'<<'%X:.=� . . . . . . . . . . . .
y . . . . '.. .
. . . . . . . . . . . �1 . . . .
. . ... . . . . . . . erg. . . . .
. . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . , . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . .. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . .. . . . . . . . . . . . . . . . . . I . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . - - . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .... . . . . . . . . . . . . .
. . . . . . . . . . . . . .
Date map was drawn: to / t</r
Instructions
If you already have a diagram that shows all required information,you may include it,rather than this page,with your Monitoring System Certification. On
your site plan,show the general layout of tanks and piping. Clearly identify locations of the following equipment,if installed:monitoring system control
panels;sensors monitoring tank annular spaces,sumps,dispenser pans,spill containers,or other secondary containment areas;mechanical or electronic line
leak detectors;and in-tank liquid level probes(if used for leak detection). In the space provided,note the date this Site Plan was prepared.
Monitoring System Certification Page 4 of 4 12/07
I 2/21/07
1
I N-TANK S.z_! UP
SYSTEM SETUP T 1 :SUPREME
- - - - - - - - - - - - PRODUCT CODE 1
OCT 15, 2308 9:09 AM THERMAL COEFF : .000700
HP GO GO TANK DIAMETER 120.00
3369 WILSON RD TANK PROFILE 4 PTS
BAKERSFIE'-D CA 93309 90.0 INCH VOL 19894
SYSTEM UNITS
U.S 60.0 INCH VOL 6143
OCT 15, 2308 9:09 AM SY.�TEhI LANGUAGE 30.0 INCH VOL 2313
ENGLISH
HP GO GO FLOAT SI2:3: 4.0 INCHES
SYSTEM ;STATUS REPORT 3369 WILSON RD
- - BAKERSFIE:-D CA 93309 WATER WARNING 1 .0
T 1 :DELIU=RY NEEDED HIGH WATER LIMIT: 3.0
SHIFT TIM:= 1 DISABLED MAX OR LA:3EL VOL: 11849
SHIFT TIM: 2 : DISABLED OVERFILL 90%
SHIFT TIM:? 3 DISABLED 10664
HIGH PRODJCT 95%
PERIODIC TEST WARNINGS 11256
DISABLED DELIVERY :'_IMIT 15%
ANNUAL TEST WARNINGS 1777
DISABLED
LOW PRODUCT 600
SYSTEM SECURITY LEAK ALARM LIMIT: 8
SYSTEM SETUP CODE : 003000 SUDDEN LOSS LIMIT: 25
- - - _ _ - TANK TILT 0.50
OCT 1:5. 2308 9:09 AM
MANIFOLDE:D TANKS
Ttt: NONE
SYSTEM UNITS LEAK MIN ANNUAL 0
U.S.
SYSTEM LANGUAGE PERIODIC 'TEST TYPE
ENGLISH STANDARD
HP GO GO ANNUAL TEST FAIL
3369 WILSON RD ALARM DISABLED
BAKERSFIE:_D CA 93309 COMMUNICATIONS SETUP _ PERIOLiIG 'PEST FAIL
ALARM DISABLED
SHIFT TIME 1 DISABLED
SHIFT TIME 2 DISABLED PORT SETTINGS: GROS� TEST FAIL
SHIFT'TIME' 3 DISABLED ALARM DISABLED
PERIODIC 'PEST WARNINGS
NONE FOUND ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
DISABLED RS-232 SECURITY PER
ANNUAL TEST WARNINGS CODE : 003000 TANK TEST NOTIFY: OFF
DISABLED
SYSTEM SE,=:UR I TY TNK TST SIPHON BREAK:OFF
CODE 00D000 DELIVERY DELAY 3 MIN
RS-232 END OF MESSAGE
DISABLED
r
LEAK TEST METHOD
T 3:UNLLH.)ED 1 TEST WEEK:-Y ALL TANK
SUN
PRODUCT CODE 3
THERMAL COEFF : .000700 START TIM:-: 2:00 AM
TANK DIAM:2TER : 120.00 TEST RATE :0.20 OURS
SHR
T 2:UNLEADED 2 TANK PROFILE 4 PTS DURATION 2 HOUR
PRODUCT CODE 2 FU�L VOL 11849
THERMAL COEFF : .000700 90.0 INCH VOL 9894
TANK DIAMETER 120.00 60.0 INCH VOL 6143
TANK PROFILE 4 PTS 30.0 INCH VOL 2313
FU:'L VOL : 11849
90.0 IN,}H VOL 9894
60.0 INCH VOL .6143 FLOAT SIZE: 4.0 INCHES
30.0 INCH VOL 2313
WATER WARNING 1 .0
HIGH WATER LIMIT: 3.0
FLOAT SIZE: 4.0 INCHES
MAX OR LA:3EL VOL: 11849
WATER WARNING 1 .0 OVERFILL :-IMIT 900
HIGH WATER LIMIT: 3.0 10664
HIGH PRODUCT 95%
MAX OR LA:3EL VOL: 11849 11256 LINE LEAK DETECTOR SETUP
OVERFILL :'-IMIT 90% DELIVERY :'-IMIT 15% - - _ - - - - - - -
10664 1777
HIGH PRODJCT 958
11256 LOW PRODUCT 600
DELIVERY :-IMIT 15; LEAK ALARM LIMIT: 8
1777 SUDDEN LOSS LIMIT: 25
TANK TILT 0.00
LOW PRODUCT 600
LEAK ALARM LIMIT: 8 MANIFOLDED TANKS
SUDDEN LOSS LIMIT: 25 T#: NONE
TANK TILT 0.75
LEAK MIN ANNUAL 0
MANIFOLDED TANKS
T#: NONE PERIODIC 'PEST TYPE
QUICK LINE_LEAK TEST SETUP - -
LEAK MIN ANNUAL 0 TEST ON DATE : ALL LINES
PERIODIC TEST TYPE ANNUAL TE,3AALARMLDISABLED JAN 1 , :
START TIME DISABLED
QUICK PERIODIC 'PEST FAIL
TEST RATE :0..20 GAL/HR
ANNUAL TEST FAIL ALARM DISABLED
ALARM DISABLED
GROSS TEST FAIL
PERIODIC 'PEST FAIL ALARM DISABLED
ALARM DISABLED
ANN TEST AVERAGING: OFF
GROSS TEST FAIL PER TEST AVERAGING: OFF
ALARM DISABLED
TANK TEST NOTIFY: OFF
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF TNK TST SIPHON BREAK:OFF
TANK TEST NOTIFY: OFF DELIVERY :DELAY 3 MIN LINE LEAK LOCKOUT SETUP
TNK TST SIPHON BREAK:OFF LOCKOUT SCHEDULE
DELIVERY DELAY 3 MIN DAILY
START T I NI:E: DISABLED
STOP TIME DISABLED
Y
L14:87 TP ---------. -- —
TRI-STATE: (SINGLE FLOAT)
—- - - --- - - CATEGORY : STP SUMP
LIQUID tif., cUk SETUP
L15:87 ANNULAR
_ _ _ _ _ _ _ _ _
- - TRI-STATE (SINGLE FLOAT)
I. 1 :87 1 STP CATEGORY : ANNULAR SPACE.
TRI-STATE (SINGLE FLOAT) ALARM HISTORY REPORT
CATEGORY : STP SUMP
L16.87 F I:�L ----- SEN130R ALARM ----
L 2:WASTE OIL ANNULAR TRI-STATE (SINGLE FLOAT) STP�SUMP .TP
TRI-STATE (SINGLE FLOAT( CATEGORY PIPING SUMP FUEL ALARM
CATEGORY ANNULAR SPACE MAR 22r 2707 12:44 PM
L 3:WASTE OIL SUMP ---__
TRI-STATE (SINGLE FLOAT) - - -
CATEGORY PIPING SUMP
OUTPUT 1E.�A'Y S1r'I'UP
L 4:WASTE OIL HI LEVEL - -
TRI-STATE (SINGLE FLOAT)
CATEGORY OTHER SENSORS ALARM HIS'T'ORY REPORT
R 1 :SUPkE11E
TYPE: -- SENSOR ALARM --
L 1 :87 1 STP ___
STANDARD L 5:DISP 1-2 NORMALLY CLOSED STP SUMP
TRI-STATE (SINGLE FLOAT) FUEL. ALARIh
CATEGORY : DISPENSER PAN MAR 22. 2707 12:44 PM
IN-TANK A:�ARMS
T I :HIGH WATER ALARM
L 6:DISP 3-4 T 1 :LOW :?RODUCT ALARM
TRI-STATE (SINGLE FLOAT)
CATEGORY DISPENSER PAN
- R 2:87 2
TYPE:
L 7:DISP 5-6 STANDARD
TRI-STATE (SINGLE FLOAT) NORMALLY CLOSED ALARM: HISTORY REPORT
CATEGORY : DISPENSER PAN
I N-TAN}: A'"_ARMS
L 2:WASTEJOILAANNULAR-
T 2:HIGH WATER ALARM ANNULAR S:?ACE
L 8:DISP 7-8 T 2:1-OW :?RODUCT ALARM
TRI-STATE (SINGLE FLOAT)
CATEGORY : DISPENSER PAN
R 3:87 1
L 9:91 ANNULAR TYPE:
TRI-STATE (SINGLE FLOAT) STANDARD
CATEGORY : ANNULAR SPACE NORMALLY CLOSED
ALARM HISTORY REPORT
IN-TANK A,-ARMS ----- SENSOR ALARM -----
L10:91 FI _L T 3:HIGH WATER ALARM L 3:WASTE OIL SUMP
TRI-STATE (SINGLE FLOAT) T 3:LOW :?RODUCT ALARM PIPING SUMP
CATEGORY PIPING SUMP
L11 :91 ST:?
TRI-STATE (SINGLE FLOAT)
CATEGORY : STP SUMP LINE DISA3LE SETUP
L12:87 2 ANNULAR
TRI-STATE (SINGLE FLOAT) ALARM HISTORY'REPORT
CATEGORY : ANNULAR SPACE
SOFTWARE :REVISION LEVEL, ----- SENSOR ALARM -----
VERSION 7.03 L 4:WASTE OIL HI LEVEL
SOFTWARE# 349500-007-D OTHER SENSORS
L13:87 2 :=ILL CREATED - 94.08.24.10.26
TRI-STATE (SINGLE FLOAT)
CATEGORY PIPING SUMP NO SOFTWARE MODULE
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
r `
ALARM HISTORY REPORT
----- SENSOR ALARM -----
L 5:D1SP 1-2
DISPENSER PAN ALARM HIS'T'ORY REPORT
ALARM HISTORY REPORT SENSOR ALARM -----
----- SEN;DOR ALARM ----- L14:87 2 ,STP
1-10:91 FI: L STP SUMP
PIPING S UIHP
FUEL ALARM
FEB 3, 2308 5:53 AM
FUEL ALARM
ALARM HISI'ORY REPORT JAN 24, 2J08 11 :20 AM
SENSOR ALARM ----- FUEL ALARM
L 6:DISP 3-4 DEC 7, 2307 7:58 PM ALARM HISTORY REPORT
,DISPEN'tiER PAN
--- - SENSOR ALARM -----
L15:87 ANNULAR
ANNULAR S?ACE
ALARM HISTORY REPORT ALARM HISTORY REPORT
---- SENSOR ALARM ----- ----- SENSOR ALARM -----
L 7:DISP 5-6 L11 :91 ST:=
DISPENSER PAN STP SUMP ALARM HISTORY REPORT
FUEL ALARM ----- SEN;�OR ALARM -----
MAR 22. 2307 12:46 PM L15:87 ANNULAR
ANNULAR S?ACE
ALARM HISTORY REPORT
----- SENSOR ALARM -----
L 8:DISP 7-8 ALARM HISTORY REPORT
DISPENSER PAN ALARM HISTORY REPORT
FUEL ALARM ----- SENSOR ALARM -----
SEP 4. 2307 10: 17 AM ----- SENSOR ALARM -----
L.12:87 2 ANNULAR L16:87 Fl'-L
FUEL ALARM ANNULAR S?ACE PIPING SUIliP
SEP 3, 2307 12:49 PM
ALARM {•I I' TORY REPORT ALARM HISTORY REPORT
ALARM HISTORY REPORT ----- SENSOR ALARM ----- ----- SENSOR ALARM -----
L13:87 2 =ILL L16:87 FI:' L
----- SENSOR ALARM ----- PIPING SUMP PIPING SUMP
L 9:91 ANNULAR
ANNULAR S?ACE