Secondary Containment Testing Report Form
This form is intended for use by contractors performing periodic testing of UST secondary containment systems. Use the
appropriate pages of thisform to report results for all components tested The completed form, written test procedures, and
printouts from tests(f applicable),should be provided to the facility owner/operator for submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: Fastrip#781 Date of Testing: 2/28/11
Facility Address: 4013 South H St.Bakersfield,CA
Facility Contact: Jamieson Hill Phone: 1-661-393-7000
Date Local Agency Was Notified of Testing: February 23,2011
Name of Local Agency Inspector(fpresent during testing):
2. TESTING CONTRACTOR INFORMATION
Company Name: Sunset Mechanical
Technician Condu ' g Test: Scott Olinger
Credentials: CSLB Licensed Contractor ❑SWRCB Licensed Tank Tester
License Type: C-36 C-10 License Number. 589517
Manufacturer Training
Manufacturer Component(s) Date Training Expires
Incon TS-STS Inspection Equipment 1/18/13
Veeder Root Monitoring System 1/15/12
ICC Cal UST Service Tech 1/18%13
3. SUMMARY OF TEST RESULTS
Component Pass Fail Not Repairs Component Pass Fait Not Repairs
Tested Made Tested Made
UDC 1-2 ❑ ❑ ❑ PIPING RUN#1 ❑ ❑ ❑
UDC 3-4 ❑ ❑ ❑ PIPING RUN#2 ❑ ❑ ❑
UDC 5-6 ❑ ❑ ❑ PIPING RUN#3 ❑ ❑ ❑
UDC 7-8 ❑ ❑ ❑ PIPING RUN#4 ❑ ❑ ❑
STP#1 ❑ ❑ TRAN#1 ❑ ❑
STP#2 ❑ ❑ ❑ TR.AN#2 9' ❑ ❑
STP#3 ❑ ❑ ❑ SPILL#1 ❑ ❑ ❑
STP#4 ❑ ❑ ❑ SPILL#2 (1 ❑ ❑ ❑
FILL#1 ❑ ❑ ❑ SPILL#3 Et ❑ ❑ ❑
FILL#2 ❑ p ❑ SPILL#4 ❑ ❑ ❑
FILL#3 ❑ ❑ ❑ V SPILL#1 ❑ ❑ ❑
FILL#4 ❑ ❑ ❑ V SPILL#2 ❑ ❑ ❑
If hydrostatic testing was performed,describe what was done with the water after completion of tests:
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
To the best of my knowledge,the fa in this document are accurate and in full compliance with legal requirements
Technician's Signature: Date: 3/1/11
IIIIIII IIIII III IIII 66
IE
SWRCB,January 2002 Page of
Secondary Containment Testing Report Form
Thu form is intendedfor use by contractors performingperia&c testing of USTsecondary containment systems. Use the
appropriate pages of thisform to report results for all components tested The completed form,written test procedures, and
printouts from tests(rf applicable),should be provided to the facility owner/operator for submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: Fastrip#781 Date of Testing: 2/28/11
Facility Address: 4013 South H St Bakersfield,CA
Facility Contact: Jamieson Hill Phone: 1-661-393-7000
Date Local Agency Was Notified of Testing: February 23,2011
Name of Local Agency Inspector.(ifpresent during testing):
2. TESTING CONTRACTOR INFORMATION
Company Name: Sunset Mechanical
Technician Conducting Test: Scott Olinger
Credentials: ❑CSLB Licensed Contractor ❑SWRCB Licensed Tank Tester
License Type: C-36 C-10 License Number. 589517
Manufacturer Training
Manufacturer Component(s) Date Training Expires
Incon TS-STS Inspection Equipment 1/18/13
Veeder Root Monitoring System 1/15/12
ICC Cal UST Service Tech 1/18/13
3. SUMMARY OF TEST RESULTS
Component Pass Fail Not Repairs Component Pass Fail Not Repairs
Tested Made Tested Made
V SPILL#3 ❑ ❑ ❑ ❑ ❑ ❑ ❑
V SPILL#4 ❑ ❑ ❑ 0 0 0 0
ANN SPACE 1 ❑ ❑ 1 0 0 0 0 ❑
ANN SPACE 2 ❑ ❑ ❑ ❑ ❑ ❑ ❑
ANN SPACE 3 ❑ ❑ ❑ ❑ ❑ ❑ ❑
ANN SPACE 4 ❑ ❑ ❑ ❑ ❑ ❑ ❑
0 0 ❑ 0 ❑ 0 ❑ 0
0 ❑ 0 0 0 ❑ 0 0
0 0 0 0 0 0 0 0
0 0 ❑ 0 ❑ ❑ ❑ ❑
❑ 0 0 ❑ 0 0 0 ❑
❑ ❑ 1 ❑ 1 ❑ ❑ 0 0 0
If hydrostatic testing was performed,describe what was done with the water after completion of tests:
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
To the best of my knowledge,the ads s ted in this document are accurate and in full compliance with legal requirements
Technician's Signature Date: 3/1/11
SWRCB,January 2002 Page_of
4.4 TANK ANNULAR TESTING
Test Method Developed By: M Tank Manufacturer ❑Industry Standard ❑Professional Engineer
❑Other(Specify)
Test Method Used: ❑Pressure itVacuum. ❑Hydrostatic
❑Other(Specify)
Test Equipment Used.4"GEL FILLED GAUGE W/CERTS Equipment Resolution:0-30
Tank#1 Tank#2 Tank#3 Tank#
Is Tank Exempt From Testing?' ❑Yes ❑NO ❑Yes ONo ❑Yes ONo ❑Yes ❑No
Tank Capacity- 12,000 12,000 12,000 12,000
Tank Material: GLASS ISTEEL GLASS/STEEL GLASS/STEEL GLASS/STEEL
Tank Manufacturer. JOOR JOOR JOOR JOOR
Product Stored: UNL UNL PREM UNL
Wait time between applying
pressure/vacuum/water and 10 MIN 10 A41N 10 MIN 10 MIN
startin g test:
Test Start Time: 9:10 9:10 10:10 10:10
Initial Reading(R�: 10 14G 10 14G 12 HG 12 HG
Test End Time: 10:10 10:10 11:10 11:10
Final Reading(RF): 10 HG 10 HG 12 HG 12 HG
Test Duration: I HR I HR 1 H I HR
Change in Reading(RF-Ra- 0 0. 0 0
Pass/FailThreshold or Criteria: 0 0 0 0
"Test Result - :-Apiss OFafl &(Pass,-.-ahii Pass ❑Fail Pass O-Fail.
Was sensor removed for testing? dYes ❑No ❑NA es ❑No ❑NA //Yes ONo [INA �(Yes ❑No 11 NA
Was sensor properly replaced and dyes ❑No ❑NA 9//Yes ONo ONA Ges ❑No ❑NA ff es ❑No ❑NA
Lverified functional after testin g? I
Comments—(include information on repairs made prior to testing and recommended follow-up for failed tau)
Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary
containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment
testing. (California Code of Regulations,Title 23,Section 2637(a)(6)}
SWRCB,January 2002 Page_of
5. SECONDARY PIPE TESTING
Test Method Developed By Nf Piping Manufacturer ❑Industry Standard ❑Professional Engineer
❑Other(Specify)
Test Method Used: ❑Pressure ❑Vacuum 9Hydrostatic
❑Other(Specify)
Test Equipment Used:INCON TS-STS - Equipment Resolution: 0.0000
tr
_Z Piping Run 2 Piping Run#4
Piping Run#I Piping Run#3
Piping Material: FIBERGLASS FIBERGLASS FIBERGLASS FIBERGLASS
Piping Manufacturer- AO SMITH AO SMITH AO SMITH AO SMITH
Piping Diameter. 312 3" 312 3"
Length of Piping Run: 110, 120' 130' 140'
Product Stored: LTNL UNL PREM DIESEL
Method and location of TEST BOOT AT ST? TEST BOOT AT STP TEST BOOT AT
iping-run isolation STP TEST BOOT AT STP
p :
Wait time between applying
pressure/vacuum/water and 20 MIN 20 MIN 20 MIN 20 UN
starting test:
Test Start Time: 8:28 8:28 8:28 8:28
Initial Reading M): 3.2836 4.5585 4.6217 4.9323
Test End Time: 8:43 8:43 8:43 8:43
Final Reading(RF): 3.2834 4.5585 4.6217 4.9323
Test Duration: 15 MIN 15 NEN 15 MIN 15 NUN
Change in Reading(RF-R4): .0002 0 0 0
Pass/Fail Threshold or .002 .002 .002 .002
Criteria:
U(Pass, ...O:Fait ;
Test Result: Fail.'
Comments—(include information on repairs made prior to testing; and recommended follow-up for failed tests)
SWRCB,January 2002 Page_of
6. PIPING SUMP TESTING
Test Method Developed By: ❑Sump Manufacturer ❑Industry Standard ❑Professional Engineer
❑Other(Specify)
Test Method Used. ❑Pressure ❑Vacuum ❑Hydrostatic
0 Other(Specify)
Test Equipment Used:INCON TS-STS Equipment Resolution:0.0000
SUMP Diameter. 18"x24" 18"x24"
Sump Depth: 31" 31"
Sump Material: FIBERGLASS FIBERGLASS
Height from Tank Top to Top of 12"
Highest Piping'Penetration:
Height from Tank Top to Lowest
Electrical Penetration: 8" 8"
Condition of sump prior to testing: DRY DRY
Portion of Sump Tested' 14" 14"
Does turbine shut down when
sump sensor detects liquid(both ❑Yes ❑No AA ❑Yes ❑No AA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA
product and water)?*
Turbine,shutdown response time
Is system programmed for fail-safe ❑Yes ❑No I/NA ❑Yes ❑No
shutdown?* AA 0 Yes ❑No ❑NA 0 Yes ❑No ❑NA
Was fail-safe verified to be 0 Yes ❑No AA 0 Yes 0 No O/NA
operationall
D Yes ❑No ❑NA ❑Yes ONo [INA
*
Wait time between applying
pressure/vacuum/water and starting 10 MW Ohm
test
Test Start Time: 12:49 12:49
Initial Reading.(RO: 4.1601 4.0597
Test End Time- 1:04 1:04
Final Reading(RF): 4.1601 4.0594
Test Duration: 15 MIN 15 NUN
Change in Reading(RF44): 0 .0003
Pass/Fail Threshold or Criteria: .002 .002
Test ResWt~ Pass ::' �O
ss OFiff
Was sensor removed for testing? ❑Yes ONo YNA ❑Yes ONo dNA ❑Yes ONo DNA ❑Yes ONo DNA
Was sensor properly replaced and
verified functional after testing? D Yes ❑No AA D Yes ❑No O/NA 0 Yes ❑No DNA 0 Yes 11 No ❑NA
Comments—(mclude information on repairs made prior to testing; and recommended follow-up for failed tests)
Replace all hose clamps.
If the entire depth of the sump is not tested,specify how much was tested. If the answer to any of the questions indicated with an
asterisk(•)is"NO"or"NA",the entire sump must be tested, (See SWRCB LG-160)
SWRCB,January 2002 Page_of
6. PIPING SUMP TESTING
Test Method Developed By: Sump Manufacturer ❑Industry Standard ❑Professional Engineer
❑Other(Specify) If
Test Method Used: 13 Pressure ❑Vacuum Hydrostatic
❑Other(Specify)
Test Equipment Used INCON TS-STS :LEquipment Resolution:0.0000
UO
SUMP#1 STP SUMP#2 STP SUMP#3 STP :SUMP#4STP
Sump Diameter: 48" 48" 48" 48"
Sump Depth: 54" 55" 54" 56"
Sump Material: FIBERGLASS FIBERGLASS FIBERGLASS FIBERGLASS
Height from Tank Top to Top of 15" 16" 15" 16"
Highest Piping Penetration:
Height from Tank Top to Lowest 19" 19" 19" 20"
Electrical Penetration:
Condition of sump prior to testing- DRY DRY DRY DRY
Portion of Sump Tested' 18" 18" 18" is"
Does turbine shut down when
sump sensor detects*liquid(both C�Yes ❑No ❑NA IYes ❑No [INA Q(Yes ❑No DNA YYes ❑No ❑NA
product and water)?
Turbine shutdown response time 30 SEC 30 SEC 30 SEC 30 SEC
Is system programmed for fail-safe S(Yes "D No DNA YYes ❑No DNA 9�Yes ❑No 0 NA es ONo DNA
shutdown?*
Was fail-safe verified to be U(Yes ❑No ❑NA I/Yes ONo DNA Q/Yes 0 No 0 NA Xes ❑No DNA
op erational?*
Wait time between applying
pressurelvacuum/water and starting 10 MIN 10 NON 10 MIN 10 NM
test:
Test Start Time: 12:11 10:18 10:18 10:18
Initial Reading(R j): 5.6405 5.4795 6.6855 6.7314
Test End Time: 12:26 10:33 10:33 10:33
Final Reading(RF): 5.6403 5.47% 6.6854 6.7311
Test Duration: 15 MIN 15 MIN 15 MW 15 NUN
Change in Reading(RF-R4): OM .0001 .0001 .0003
Pass/Fail Threshold or Criteria: M .002 .002 M,
7
Pass jonil-
.xesfR&u1t: P"s -01a 7
Was sensor removed for testing? 9 Yes D No ❑NA Q(Yes ❑No DNA Yes 0 No DNA G/Yes ❑No (INA
Was sensor properly replaced and Wyes ❑No [=INAYes ONo DNA &s ❑No DNA As ❑No DNA
verified functional after testing!
Comments—(include information on repairs made prior to testing: and recommended follow-up for failed tests)
STP#I Install 2-3"repair boots and 3-1"repair boots.
If the entire depth of the sump is not tested,specify how much was tested. If the answer to any of the questions indicated with an
asterisk(*)is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160)
SWRCB,January 2002 Page_of
7. !MER-DISPENSER CONTAINMENT(UDC)TESTING
Test Method Developed By YUDC Manufacturer ❑Industry Standard 0 Professional Engineer
❑Other(Specify)
Test Method Used: 0 Pressure 0 Vacuum YHydrostatic
0 Other(Spec)
Test Equipment Used: INCON TS-STS Equipment Resolution: 0.0000
,Li
_UDC#3-4 UDC#!5-6 UDC#7-8
UDC Manufacturer: AM CON AM CON AM CON AM CON
UDC Material: FIBERGLASS FIBERGLASS- FIBERGLASS FIBERGLASS
UDC Depth: 32" 329' 3211 32"
Height from UDC Bottom to Top 12" 12" 12" 1211
of Highest Piping Penetration:
Height from UDC Bottom to 8" 8" 8" 81,
Lowest Electrical Penetration:
Condition of UDC prior to DRY DRY DRY DRY
testing:
Portion of UDC Tested 14" 14" 14" 14"
Does turbine shut down when
UDC sensor detects liquid(both G7`Yes ❑No ❑NA Q�es ❑No DNA 5/Yes ❑No DNA [/Yes 0 No ❑NA
product and water)?.
Turbine shutdown response time 30 SEC 30 SEC 30 SEC 30 SEC
Is system programmed for fail- 6/yes 0 No ❑NA Yes 0 No DNA Yes 0 No DNA EI/Yes DNo DNA
safe shutdown?* 4
Was fail-safe verified to be �Yes D No ❑NA —dy—es ❑No DNA Yes 0 No [INA 6/yes 0 No' 0 NA
operational?*
Wait time between applying 20 KIN 20 MIN 20 MIN 20 MIN
pressure/vacuum/water and
starting test
Test Start Time: 8:11 8:11 8:11 8:11
Initial Reading 3-2835 4.5579 4.6215 4.9319
Test End Time: 8:26 8:26 8:26 8:26
Final Reading(RF): 3.2836 4.5585 4.6217 4.9323
Test Duration: 15 NUN 15 MIN 15 MIN 15 MIN
Change in Reading(RF-": .0001 .0006 .0002 .0004
Pass/Fail Threshold or Criteria: .002 .002 .002
Test Results d-pass 0 Fail Pass ..; 0 Fail Pass - ❑Fail- Pass ❑Fail
Was sensor removed for testing? Yes 0 No ❑WA M Yes ❑No ❑NA dYes 6No DNA ffYes ❑No 0 NA
Was sensor properly replaced and [/Yes DNo DNA JYes ❑No DNA WYes 0 No ❑NA Yes DNo DNA
verified functional after testing?
Comments—(include information on repairs made prior to testing, and recommended fol ow-up forfailed tests)
If the entire depth of the UDC is not tested,specify how much was tested. If the answer to any of the questions indicated with an
asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160)
SWRCB,January 2002 Page of
8. FILL RISER CONTAINMENT SUMP TESTING
Facility is Not Equipped With Fill Riser Containment Sumps ❑
Fill Riser Containment Sumps are Prescnt,but were Not Tested 0-
Test Method Developed By: I Sump Manufacturer ❑Industry Standard ❑Professional Engineer
❑Other(Specify) I
Test Method Used: ❑Pressure ❑Vacuum &Aiydrostatic
❑Other(Specify)
Test Equipment Used:MON TS-STS Equipment Resolution:0.0000
Fill Sump#1 Fill Sump#2 Fill Sump#3 Fill Sump#4
Sump Diameter. 42" 42" 42" 42"
Sump Depth: 58" 5T' 54" 55"
Height from Tank Top to Top of N/A N/A N/A N/A
Highqt Piping Penetration:
Height from Tank Top to Lowest N/A N/A N/A N/A
Electrical Penetration:
Condition of sump prior to 6"WATER DRY DRY DRY
testing.
Portion of Sump Tested 12" 12" IT, 12"
Sump Material: FIBERGLASS FIBERGLASS FIBERGLASS FIBERGLASS
Wait time between applying 10 MIN 10 MIN 10 MIN 10 MIN
pressure/vacuum/water and
starting test
Test Start Time: 10:18 12:11 12:43 12:11
Initial Reading(R4): 4.8410 15189 4.0756 3.4420
Test End Time: 10:33 12-26 1:04 12:26
Final Reading(1kF): 4.8405 3.5185 4.0757 3.4417
Test Duration: 15 MIN 15 MIN 15 MIN 15 MIN
Change in Reading(RF-P.4): .0005 .0004 .0001 .0003
Pass/Fail Threshold or Criteria: 002 .002 002 .002
❑.Fail- Ef,-Pm , b*ail, Pass . IJ*Ail.. pisi yawl.
Is there a sensor in the sump? ❑Yes No ❑Yes VNo ❑Yes No (I Yes No
Does the sensor alarm when
either product or water is ❑Yes ❑No dNA ❑Yes 11 No E(NA ❑Ycs ❑No U(NA OYes ONo R(NA
detected?
Was sensor removed for testing? 0 Yes ❑No 041A ❑Yes ❑No ENA 0 Yes ❑No ft 1 ❑Yes ❑No 9KA
Was sensor properly replaced and ❑Yes ❑No C(NA ❑Yes ❑No 9/NA ❑Yes ❑No O/NA ❑Yes ❑No
verified functional after testing9 I I
Comments—(include information on repairs made pv,*to leabg and recommended follow-up for failed tests)
SWRCB,January 2002 Page_of
9. SPHAJOVERFILL CONTAINMENT BOXES
Facility is Not Equi ed With Spill/Overfill Containment Boxes ❑
Spill/Overfill Containment Boxes are Lr=t,but were Not Tested ❑
Test Method Developed By: ffSpill Bucket Manufacturer ❑Industry Standard ❑Professional Engineer
❑Other(Specify)
Test Method Used. ❑Pressure ❑Vacuum 2rHydrostatic
❑Other(Specify)
Test Equipment Used:- INCON TS-STS Equipment Resolution:0.0000
Split Box#V1 Spur Box#V2 SpiR Box W3 SpiR Box#V4
Bucket Diameter. 12" 12" 12" 12"
Bucket Depth: 15" 15" 15" 15"
Wait time between applying
pressurelvacuum/water and 10 MIN 10 PAIN 10 MIN 10 MIN
starting test
Test Start Time: 1:27 1:27 2:28 2:28
Initial Reading(Ri): 5.9042 4.9882 2.3896 1.7887
Test End Time: 1:42 1:42 2:44 2:44
Final Reading(RF): 5.9042 4.9882 2.3892 1.7880
Test Duration: 15 NUN 15 NffN 15 MIN 15 MIN
Change in Reading(RF-R): 0 0 .0004 -0007
Pass/Fail Threshold or -002 .002 .002 .002
Criteria: 4
.Test Result: ❑.Mf I Pass ` Fail Pass Fail
Comments—(include information on repairs made prior to pqMn ollow-Vfarfafled tests)
g, and recommendedf
SWRCB,January 2002 Page_of
9. SPMUOVERFILL CONTAINMENT BOXES
Facility is Not Equipped With Spill/Overfill Containment Boxes ❑
Spill/Overfill Containment Boxes are Msent,but were Not Tested ❑
Test Method Developed By: 11 Spill Bucket Manufacturer ❑Industry Standard ❑Professional Engineer
❑Other(Specify) 4
Test Method Used- ❑Pressure ❑Vacuum WHydrostatic
❑Other(Specify)
Test Equipment Used:INCON TS-STS Equipment Resolution:UNO
fit.' °3. '�
#1 Spin Box#2
. ....... Spill Box#3
spin Box Spin Box#4
Bucket Diameter. 12" 12" 12" 12"
Bucket Depth: 15" 15" 15" 15"
Wait time between applying
pressure/vacuum/water and 10 MIN 10 MIN 10 N41N 10 MIN
starting test:
Test Start Time: 1:27 1:27 2:28 2:28
Initial Reading(Ri): 3.2708 3.3163 0.9097 2.3363
Test End Time-. 1:42 1.-42 2:44 2-44
Final Reading(RF). 32708 33158 0.9092 2.3358
Test Duration: 15 MIN 15 MIN 15 MIN 15 NEN
Change in Reading(RF-Rj): 0 .0005 .0005 .0005
Pass/Fail Threshold or .002 .002 .002 .002
Criteria:
Test ItQStilt Pass ;:O.Faff efpass 0. Vl6;iss:, C�1,Fail
—(include information on repairs made prior to testin&and recommendedfollow-up for failed tests)
FASTRIP 781 FASTRIP 781
4013 S H ST 4013 S H ST
BAKERSFIELD CA BAKERSFIELD CA
SUNSET CONST SUNSET CONST
1-800-984-6266 FASTRIP 781 1-800-984-6266
4013
03/01/2011 2:44 PM BAKER S H ST
SFIELD CA
BAKE R B 03/01/2011 11:15 AM
SUNSET CONST
SUMP LEAK TEST REPORT 1-800-984-6266 SUMP LEAK TEST REPORT
SPILL3 03/01/2011 2:28 PM STP 2
TEST STARTED 2:28 PM SUMP LEAK TEST REPORT TEST STARTED 10:59 AM
TEST STARTED 03/01/2011 TEST STARTED 03/01/2011
BEGIN LEVEL 0.9097 IN SPILL3 BEGIN LEVEL 5,4796 IN.
END TIME 2:44 PM END TIME 11:14 AM
END DATE 03/01/2011 TEST STARTED 2:12 PH END DATE 03/01/2011
END LEVEL 0,9092 IN TEST STARTEC► 03/01/2011 END LEVEL 5,4786 IN
LEAK THRESHOLD 0,002 IN BEGIN LEVEL 0.9093 IN LEAK THRESHOLD 0.002 IN
TEST RESULT PASSED END TIME 2:28 PM TEST RESULT PASSED
END DATE 03/01/2011
USPILL3 END LEVEL 0.9096 IN
LEAK THRESHOLD 0.002 IN STP 3
TEST RESULT PASSED
TEST STARTED 2:28 PM TEST STARTED 10:59 AM
TEST STARTED 03/01/2011 TEST STARTED 03/01/2011
BEGIN LEVEL 2.3896 IN VSPILL3 BEGIN LEVEL 6.6843 IN
END TIME 2:44 PM END TIME. 11:14 AM
END DATE 03/01/2011 TEST STARTED 2:12 PM END DATE 03/0.1/2011
END LEVEL _ 2.3$92 IN TEST STARTED 03/01/2011 END LEVEL 6,6833 IN
LEAK THRESHOLD 0.002 IN LEAK THRESHOLD 0,002 IN
i
TEST RESULT pp BEGIN LEVEL 2,3893 IN
END TIME 2:28 PM TEST RESULT PASSED
END DATE 03/01/2011
SPILL4 END LEVEL 2,3895 IN
LEAK THRESHOLD 0,002 IN FILL 2
TEST RESULT PASSED
TEST STARTED 2:28 PM TEST STARTED 10:59 AM
TEST STARTED 03/01/2011 TEST STARTED 03101/2011
BEGIN LEVEL 2,3363 IN SPILL4 BEGIN LEVEL 4.0727 IN
END TIME 2:44 PM - END TIME 11:14 AM
END DATE 03/01/2011 TEST STARTED 2:12 PH END.DATE 03/01/2011
END LEVEL 2,3358 IN TEST STARTED .03/01/2011 END LEVEL 4,0726 IN
LEAK THRESHOLD 0.002 IN BEGIN LEVEL 2.3359-IN LEAK THRESHOLD 0.002 IN
TEST RESULT PASSED END TIME 2:28 PM TEST RESULT PASSED
END DATE 03/01/2011
USPILL4 END LEVEL 2.3361 IN STP 4
LEAK THRESHOLD 0.002 IN
TEST RESULT PASSED
TEST STARTED 2:28 PH .ST STARTED 10:59 AM
TEST STARTED 03/01/2011 EST STARTED 03/01/2011
BEGIN LEVEL 1.7887 IN VSPILL4 °FGIN LEVEL 6.7300 IN
END TIME 2:44 PM NO TIME 11:14 AM
END DATE 03/01/2011 TEST STARTED 2:12 PM Q DATE 03/01/2011
END LEVEL 1.7880 IN TEST STARTED 03/01/2011 `1 LEVEL 6.7286 IN -
LEAK THRESHOLD 0,002 IN BEGIN LEVEL 1,7885 IN THRESHOLD 0.002 IN
TEST RESULT PASSED END TIME 2:28 PH RESULT PASSED
END DATE 03/01/2011
END LPL 1.7887 IN
LEAK THRESHOLD 0.002 IN
TEST RESULT PASSED
03/01/2011 1:10 PM FASTRIP 781
4013 S H ST
SUMP LEVEL REPORT BAKERSFIELD CA
- SUNSET CONST
1-800-984-6266
SUMP SPILL1 3,273 IN
SUMP VSPILLI 5.905 IN 03/01/2011 1:42 PM
FASTRIP 781 SUMP SPILL2 3,318 IN i
4013 S H ST
BAKERSFIELD CA SUMP VSPILL2 4,989 IN SUMP LEAK TEST REPORT !
SUNSET CONST FASTRIP 781 SPILLI
1-800-984-6266 4013 S H-ST -
BAKERSFIELD CA TEST STARTED 1:27 PM
03/01/2011 12:47 PM SUNSET CONST TEST STARTED 03/01/2011
1-800-984-6266 BEGIN LEVEL 3.2708 IN
SUMP LEAK TEST REPORT END TIME
1:42 PM
03/01/2011 1:26 PM END DATE 03/01/2011
TRANSI END LEVEL 3,2708 IN
SUMP LEAK TEST REPORT LEAK THRESHOLD 0.002 IN
TEST STARTED 12:32 PM TEST RESULT PASSED
TEST STARTED 03/01/2011 SPILLI
BEGIN LEVEL 5.3327 IN
END TIME 12:47 PM TEST STARTED 1:10 PM VSPILLI
END DATE 03/01/2011 TEST STARTED 03/01/2011
END LEVEL 5,3332 IN BEGIN LEVEL 3.2719 IN TEST STARTED 1:27 PM
LEAK THRESHOLD 0.002 IN END TIME 1:25 PM TEST STARTED 03/01/2011
TEST RESULT PASSED END DATE 03/01/2011 BEGIN LEVEL 5.9042 IN
END LEVEL 312708 IN END TIME 1,42 PM
LEAK THRESHOLD 0,002 IN END DATE 03/01/2011
FILL 3 TEST RESULT PASSED END LEVEL 5.9042 IN
LEAK THRESHOLD 0.002 IN
TEST STARTED 12:32 PM TEST RESULT PASSED
TEST STARTED 03/01/2011 VSPILLI
BEGIN LEVEL 4,0877 IN
END TIME 12:47 PM TEST STARTED 1:10 PM SPIN
END DATE 03/01/2011 TEST STARTED 03/01/2011
END LEVEL 410880 IN BEGIN LEVEL 5.9046 IN TEST STARTED 1:27 PM
LEAK THRESHOLD 0.002 IN END TIME 1:25 PM TEST STARTED 03/01/2011
TEST RESULT PASSED END DATE 03/01/2011 BEGIN LEVEL 3,3163 IN
END LEVEL 5.9041 IN END TIME 1:42 PM
LEAK THRESHOLD 0,002 IN END DATE 03/01/2011
TRANS2 TEST RESULT PASSED END LEVEL 3.3158 IN
LEAK THRESHOLD 0.002 IN
TEST STARTED 12:32 PM TEST RESULT PASSED
TEST STARTED 03/01/2011 SPILL2
BEGIN LEVEL 4.3750 IN
END TIME 12:47 PM TEST STARTED 1:10 PM VSPILL2
END DATE 03/01/2011 TEST STARTED 03/01/2011
END LEVEL 4.3744 IN BEGIN LEVEL 3,3172 IN TEST STARTED 1:27 PM
LEAK THRESHOLD 0.002 IN END TIME 1:25 PM TEST STARTED 03/01/2011
TEST RESULT PASSED . END DATE 03/01/2011 BEGIN LEVEL 4.9882 IN
END LEVEL 3.3162 IN END TIME 1:42 PM
LEAK THRESHOLD 0.002 IN END DATE 03/01/2011
TEST RESULT PASSED END LEVEL 4.9882 IN
- LEAK THRESHOLD 0.002 IN
TEST RESULT PASSED
VSPILL2
TEST STARTED 1:10 PM
TEST STARTED 03/01/2011
BEGIN LEVEL 4.9887 IN -
END TIME 1:25 PM
END DATE 03101/2011
END LEVEL 4.9883 IN
rmaimir iii
4013 S H ST SUNbL I l.UNS 1
BAKERSFIELD CA 1-800-984-6266
SUNSET CONST 03/01/2011 11:49 AM
1-800-984-6266
03/01/2011 12:27 PM SUMP LEVEL REPORT
FASTRIP 781
SUMP LEAK TEST REPORT 4013 S H ST
SUMP STP 1 5,537 IN BAKERSFIELD CA
STP 1 SUMP.FILL 3 3,314 IN SUNSET CONST
SUMP FILL 2.._ 3;517_IN- .. 1-800-984-6266
TEST STARTED 12:11 PM SUMP FILL 4 3,442 IN
TEST STARTED 03/01/2011
03/01/2011 1:04 PM
BEGIN LEVEL 5,6405 IN FASTRIP 781
END TIME 12:26 PM 4013 S H ST SUMP LEAK TEST REPORT
END DATE 03/01/2011 BAKERSFIELD CA
END LEVEL x.'403 IN SUNSET CONST TRANSI
1-800-984-6266
LEAK THRESHOLD o.002 IN
TEST STARTED 12:49 PM
TEST RESULT PASSED 03/01/2011 12:08 PM TEST STARTED 03/01/2011
BEGIN LEVEL 4, 1601 IN
FILL 3 SUMP LEAK TEST REPORT END TIME 1:04 PM
END DATE 03/01/2011
TEST STARTED 12:11 PM STP 1 END LEVEL 4.1601 IN
TEST STARTED 03/'01/2011 LEAN THRESHOLD 0,002 IN
BEGIN LEVEL 13119 IN TEST STARTED 11:52 AM TEST RESULT PASSED
END TIME 12:26 PM TEST STARTED 03/01/2011
END DATE 03/01/2011 BEGIN LEVEL 5,6401 IN
END LEVEL 3.3099 IN END TIME 12:07 PM FILL 3
LEAK THRESHOLD 0,-002 IN END DATE 03101/2011
TEST RESULT FAILED END LEVEL 5,6404 IN TEST STARTED 12:49 PM
LEAK THRESHOLD 0,002 IN TEST STARTED 03/01/2011
TEST RESULT PASSED BEGIN LEVEL 4,0756 IN
END TIME 1:04 PM
Fill 2 END DATE . 03/01/2011
TEST STARTED 12:11 PM FILL 3 END LEVEL 4,0757 IN
TEST STARTED 03/01/2011 LEAK THRESHOLD 0,002 IN
BEGIN LEVEL 3.5189 IN TEST STARTED 11:52 AM TEST RESULT PASSED
END TIME 12:26 PM TEST STARTED 03/01/2011
END DATE 03/01/2011 BEGIN LEVEL 3,3133 IN
END LEVEL 3,5185 IN END TIME 12:07 PM TRANS2
LEAK THRESHOLD 0,002 IN
END DATE 03/01/2011
TEST RESULT PASSED END LEVEL 3,3131 _IN TEST STARTED 12:49 PM
LEAK.THRESHOLD 0,002 IN TEST STARTED 03/01/2011
TEST RESULT PASSED BEGIN LEVEL 4,0597 IN
END TIME 1:04 PM
FILL 4 END DATE 03/01/2011
TEST STARTED 12:11 PM FILL 2 END LEVEL 4,0594 IN
TEST STARTED 03/0112011 LEAK THRESHOLD 0,002 IN
BEGIN LEVEL 3,4420 IN TEST STARTED 11:52 AM TEST RESULT PASSED
END TIME 12:25 PM TEST STARTED -03/01/2011
END DATE 03/01/2011 BEGIN LEVEL 3,5184 IN
END LEVEL 3,4417 IN END TIME 12:07 PM
LEAK THRESHOLD 0,002 IN END DATE 03/01/2011
TEST RESULT PASSED END LEVEL 3,5189 IN -
LEAK THRESHOLD 0,002 IN
TEST RESULT PASSED
FILL 4
TEST STARTED . 11:52 AM
TEST STARTED 03/01/2011
BEGIN LEVEL 3,4419 IN
rH�iK1r ttf7 FASTRIP 781 FASTRIP 781
4013SHST 4013SHST 4013SHST
BAKERSFIELD CA BAKERSFIELD CA IiAKERSFIELD CA
SUNSET CONST SUNSET CONST SUNSET CONST
1-800-984-6266 1-800-984-6266 1-80D-984-6266
03/0112011 8143 AM 03/01/2011 $:2fi AM 03/01/2011 10:33 AM
SUMP LEAK TEST REPORT SUMP LEAK TEST REPORT
SUMP LEAK TEST REPORT
UDC 1-2 UDC 1-2 STP 2
TEST STARTED 8:28 AM TEST STARTED 8:11 AM TEST STARTED 10:18 AM
TEST STARTED 0310112011 TEST STARTED 03/01/2011 TEST STARTED 03/01/2011
BEGIN LEVEL 3,2836 IN BEGIN LEVEL 3,2835 IN BEGIN LEVEL 5,4795 IN
END TIME 8:43 AM END TIME 8:26 AM END TIME 10:33 AM
END DATE 03/01/2011 END DATE 03/01/2011 END DATE 03/01/2011
END LEVEL 3,2834 IN END LEVEL 3,2836 IN END LEVEL 5,4796 IN
LEAK THRESHOLD 0,002 IN LEAH THRESHOLD 0,002 IN LEAK THRESHOLD 0,002 IN
TEST RESULT PASSED TEST RESULT PASSED TEST RESULT PASSED
UDC 3-4 UDC 3-4 STP 3
TEST STARTED 8:28 AM TEST STARTED 8:11 AM
TEST STARTED 03/01/2011 TEST STARTED 03/01/2011 TEST STARTED 10:18 AM
BEGIN LEVEL 4,5585 IN BEGIN LEVEL 4,5579 IN TEST STARTED 03/01(2011
BEGIN LEVEL 6,6855 IN
END TIME 8:43 AM END TIME 8:26 AM END TIME 10:33 AM
END DATE 03/01/2011 END DATE 03/01/2011 END DATE 03/01/2011
END LEVEL 4,5585 IN END LEVEL 4,5585 IN END LEVEL 6,6854 IN
LEAK THRESHOLD 0.002 IN LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0,002 IN
TEST RESULT PASSED TEST RESULT PASSED TEST RESULT PASSED
UDC 5-6 UDC 5-6
FILL 1
TEST STARTED 8:28 AM TEST STARTED 8:11 AM
TEST STARTED 03/01/2011 TEST STARTED 03/01/2011 TEST STARTED 10:18/2 011
AM
TEST STARTED 03/01/2
BEGIN LEVEL 4,6217 IN BEGIN LEVEL 4,6215 IN
BEGIN LEVEL 4,8410 IN
END TIME 8:43 AM END TIME 8:26 AM END TIME 10:33 AM
END DATE 03/01/2011 END DATE 03/01/2011 END DATE 03/01/2011
END LEVEL 4.6216 IN END LEVEL 4,6217 IN END LEVEL 4,8405 IN
LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0.002 IN
TEST RESULT PASSED TEST RESULT PASSED TEST RESULT PASSED
UDC 7-8 UDC 7-8
STP 4
TEST STARTED 8:28 AM TEST STARTED 8:11 AM TEST STARTED 10:18 AM
TEST STARTED 03/01/2011 TEST STARTED 03/01/2011 TEST STARTED 03/01/2011
BEGIN LEVEL 4,9323 IN BEGIN LEVEL 4,9319 IN BEGIN LEVEL 6,7314 IN
END TIME 8:43 AM END TIME 8:26 AM END TIME 10:33 AM
END DATE 03/01/2011 END DATE 03/01/2011 END DATE , 03/01/2011
END LEVEL 4,9323 IN END LEVEL 4,9323 IPJ
END LEVEL 6,7311 IP1
LEAK THRESHOLD 0.002 IN - LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0,002 IN
TEST RESULT PASSED TEST RESULT PASSED
-.--------."-- " _ __ TEST RESULT PASSED
FASTRIP 781
4013SHST
BAKERSFIELD CA
SUNSET CONST
1-800-984-6266
03/01/2011 9:36 AM
SUMP LEAK TEST REPORT
TRANSI
TEST STARTED 9:20 AM
TEST STARTED 03/01/2011
BEGIN LEVEL 18832 IN
END TIME 1 9:36 AM
END DATE 03/01/2011'
END-LEVEL 3,7334 IN
FASTRIP 781 LEAK:THRESHOLD 0,002 IN
4013 S H ST TEST RESULT FAILED
BAKERSFIELD CA
SUNSET CONST STP 1
1-800-984-6266
03/01/2011 TEST STARTED 9:20 AM
10:13 All TEST STARTED 03/01/2011
BEGIN LEVEL 4,1630 IN
SUMP LEVEL REPORT END TIME 9:36 AM
END DATE 03/01/2011
SUMP STP 2 040 LEVEL 4,0681 IN 5,479 IN SUMP STP 3 6,47 IN LEAK THRESHOLD 0,002 IN
SW FILL i TEST RESULT FAILED
4.841. IM
STP q
-6, 731 IN
- _ FILL 1
TEST STARTED 9:20 AM
TEST STARTED 03/01/2011
BEGIN LEVEL 3,3061 IN
END TIME . 9:36 AM
END DATE 03/01/2011
END LEVEL 3.3057 IN
LEAK THRESHOLD 0.002 IN
TEST RESULT PASSED
TRANS2
TEST STARTED 9:20 AM
TEST STARTED 03/01/2011
BEGIN LEVEL 5,8813 IN
END TIME 9:36 AM
END DATE 03/01/2011 _
END LEVEL 5.8167 IN
LEAK THRESHOLD 0,002 IN
TEST RESULT FAILED
SWRCB,January 2002 Page of
Secondary Containment Testing Report Form
This form is intended for use by contractors performing periodic testing of UST secondary containment systems. Use the
appropriate pages of thisform to report results for all components tested The completed form,written test procedures, and
printouts from tests(f applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: Fastrip#721 Date of Testing: 2/28/11
Facility Address: 4013 South H St.Bakersfield,CA
Facility Contact: Jamieson Hill Phone: 1-661-393-7000
Date Local Agency Was Notified of Testing: February 23,2011
Name of Local Agency Inspector(i(present during testing):
2. TESTING CONTRACTOR INFORMATION
Company Name: Sunset Mechanical
Technician Condu ' g Test: Scott Olinger
Credentials: 14 CSLB Licensed Contractor D SWRCB Licensed Tank Tester
License Type. C-36 C-10 License Number. 589517
Manufacturer Training
Manufacturer Component(s) Date Training Expires
Incon TS-STS Inspection Equipment 1/18/13
Veeder Root Monitoring System 1/15/12
ICC Cal UST Service Tech 1/18/13
3. SUMMARY OF TEST RESULTS
Component Pass Fail Not Repairs Component Pass Fail Not Repairs
Tested Made Tested Made
UDC 9& 10 ❑ El PIPING RUN#1 El ❑ ❑
UDC 11 & 12 ❑ ❑ ❑ PIPING RUN#2 ❑ ❑ ❑
UDC 13 & 14 p' ❑ ❑ ❑ PIPING RUN#3 ❑ ❑ ❑
UDC 15 & 16 [d ❑ ❑ ❑ ANN SPACE#1 ❑ ❑ ❑
UDC 17& 18 ❑ ❑ ❑ ANN SPACE#2 ❑ ❑ ❑
UDC 19&20 ❑ ❑ ❑ ANN SPACE#3 Ef ❑ ❑ ❑
STP #1 ❑ ❑ ❑ SPILL#1 ❑ ❑ ❑
STP#2 ❑ ❑ ❑ SPILL#2 ❑ ❑ ❑
STP#3 if j ❑ ❑ ❑ SPILL#3 ❑ ❑ ❑
FILL#1 ❑ ❑ V SPILL#1 ❑ ❑ ❑
FILL#2 ❑ ❑ V SPILL#2 ❑ ❑
FILL#3 p ❑ V SPILL#3 Pf ❑ ❑ ❑
If hydrostatic testing was performed,describe what was done with the water after completion of tests:
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
To the best of my knowledge,the fa tated In this document are accurate and in full compliance with legal requirements
Technician's Signature: . Date: 2/28/11
SWRCB,January 2002 Page of
4. TANK ANNULAR TESTING
Test Method Developed By: 11 Tank Manufacturer ❑Industry Standard ❑Professional Engineer
❑Other(Spec)
Test Method Used: ❑Pressure i7vacuum, ❑Hydrostatic
❑Other(Spec)
Test Equipment Used:4"GEL FILLED GAUGE W/CERTS Equipment Resolution:0-30
n0l z Tank#1 Tank#2 Tank#3 Tank#
Is Tank Exempt From Testing?' ❑Yes No ❑Yes No ❑Yes o ❑Yes ❑No
Tank Capacity: 12,000 12,000 12,000
Tank Material: GLASS/STEEL GLASS/STEEL GLASS/STEEL
Tank Manufacturer: MODERN MODERN MODERN
Product Stored: UNL PREM DIESEL
Wait time between applying
pressure/vacuum/water and 10 MIN 10 MIN 10 MIN
starting test:
Test Start Time: 10:45 10:45 12:00
Initial Reading(RO: 10 HG 10 HG 10 HG
Test End Time: 11:45 11:45 1:00
Final Reading(RF): 10 HG 10 HG 10 HG
Test Duration: I HR l HR 1 HR
Change in Reading(RF-RO: 0 0 0
Pass/Fail Threshold or Criteria: 0 0 0
Test Result: Pass ..❑Fail - Pass 0 Fail 'Pass ,,.:d-Fail :0 Pass D Fail:
Was sensor removed for testing? Yes ❑No ❑NA 4Yes ❑No ❑NA es ❑No ❑NA ❑Yes ❑No ❑NA
Was sensor properly replaced and Yes ❑No ❑NA Yes ❑No ❑NA Yes ❑No ❑NA ❑Yes ❑No ❑NA
verified functional after testing?
Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests)
` Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary
containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment
testing. {California Code of Regulations,Title 23,Section 2637(a)(6))
SWRCB,January 2002 Page of
5. SECONDARY PIPE TESTING
Test Method Developed By: Piping Manufacturer ❑Industry Standard ❑Professional Engineer
❑Other(Spec)
Test Method Used: ssure ❑Vacuum ❑Hydrostatic
❑Other.(Specify)
Test Equipment Used:4"GEL FILLED GAUGE W/CERTS Equipment Resolution: 0-15
` Piping Run#1 Piping Run#2 Piping Run#3 Piping Run#
Piping Material: 3"FIBERGLASS 3"FIBERGLASS 3"FIBERGLASS
Piping Manufacturer: AO SMITH AO SMITH AO SMITH
Piping Diameter. 3" 3" 3"
Length of Piping Run: 150' 150' 150'
Product Stored: UNL PREM DIESEL
Method and location of TEST BOOT AT STP TEST BOOT AT STP TEST BOOT AT
piping-run isolation: &UDC &UDC STP&UDC
Wait time between applying
pressure/vacuum/water and 15 MIN 15 MIN 15 MIN
starting test:
Test Start Time: 9:45 9:45 9:45
Initial Reading(Rq): 5.1 5.2 5.2
Test End Time: 10:45 10:45 10:45
Final Reading(RF): 5.1 5.2 5.2
Test Duration: 1 HR 1 HR i HR
Change in Reading(RF-RO: 0 0 0
Pass/Fail Threshold or 0 0 0
Criteria:
Test Resalt. Pass D Fail P l7 ass ; Fad Pass',_. ❑.Fail ❑ Pass Fad
Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests)
SWRCB,January 2002 Page of
6. PIPING SUMP TESTING
Test Method Developed By: Sump Manufacturer ❑Industry Standard ❑Professional Engineer
❑Other(Spec)
Test Method Used: ❑Pressure ❑Vacuum ydrostatic
❑Other(Spec)
Test Equipment Used:INCON TS-STS Equipment Resolution:0.0000
.,
STP#1 STP#2 STP#3
Sump Diameter. 48" 48" 48"
Sump Depth: 52" 49" 48"
Sump Material: FIBERGLASS FIBERGLASS FIBERGLASS
Height from Tank Top to Top of 16" 16" 16"
Highest Piping Penetration:
Height from Tank Top to Lowest 14" 14" 14"
Electrical Penetration:
Condition of sump prior to testing: DRY DRY DRY
Portion of Sump Tested' 18" 18" 18"
Does turbine shut down when
sump sensor detects liquid(both i/Yes ❑No ❑NA &(Yes ❑No ❑NA &(Yes ❑No ❑NA ❑Yes ❑No ❑NA
product and water)?�
Turbine shutdown response time 20 SEC 20 SEC 20 SEC
Is system programmed for fail-safe 9/Yes ❑No ❑NA 0&es ❑No ❑NA I(Yes ❑No ❑NA ❑Yes ❑No ❑NA
shutdown?*
Was fail-safe verified to be i(Yes ❑No ❑NA [(Yes ❑No ❑NA C(Yes ❑No ❑NA ❑Yes ❑No ❑NA
op erational?*
Wait time between applying
pressure/vacuum/water and starting 15 MIN 15 MIN 15 MIN
test:
Test Start Time: 12:24 12:07 12:07
Initial Reading(R,): 5.6494 6.1177 5.9627
Test End Time: 12:39 12:22 12:22
Final Reading(RF): 5.6478 6.1176 5.9620
Test Duration: 15 MIN 15 MIN 15 MIN
Change in Reading(RF-114): .0016 .0001 .0007
Pass/Fail Threshold or Criteria: .002 .002 .002
"Test Result Pass O Fail; C�Pass ❑Fail CPass q Fall ❑ Pass, O F$il
Was sensor removed for testing? Yes ❑No ❑NA /Yes ❑No ❑NA Y ❑No 13 NA ❑Yes ❑No ❑NA
Was sensor properly replaced and 5/Yes ❑No ❑NA (Y Yes ❑No ❑NA Yes ❑No ❑NA ❑Yes ❑No ❑NA
verified functional after testing?
Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests)
'If the entire depth of the sump is not tested,specify how much was tested. If the answer to M of the questions indicated with an
asterisk(*)is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160)
SWRCB,January 2002 Page of
7. ER DISPENSER CONTAINMENT QTQ TESTING
Test Method Developed By: 96 UDC Manufacturer ❑Industry Standard ❑Professional Engineer
❑Other(Specify)
Test Method Used: ❑Pressure ❑Vacuum Hydrostatic
❑Other(Specify)
Test Equipment Used: INCON TS-STS Equipment Resolution: 0.0000
UDC#17-18 UDC#19-20 UDC# UDC#
UDC Manufacturer. ENVIRON ENVIRON
UDC Material: PLASTIC PLASTIC
UDC Depth: 30" 30"
Height from UDC Bottom to Top 10" 10"
of Highest Piping Penetration:
Height from UDC Bottom to 5" 5"
Lowest Electrical Penetration:
Condition of UDC prior to DRY DRY
testing:
Portion of UDC Tested 12" 12"
Does turbine shutdown when /
UDC sensor detects liquid(both pJ Yes ❑No ❑NA l Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA
product and water)?#
Turbine shutdown response time 20 SEC 20 SEC
Is system programmed for fail- dYes ❑No ❑NA es ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA
safe shutdown?*
Was fail-safe verified to be O/yes ❑No ❑NA As ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA
operational?*
Wait time between applying 10 MIN 10 MIN
pressure/vacuum/water and
starting test
Test Start Time: 11:31 10:13
Initial Reading 4.3998 4.5102
Test End Time: 11:46 10:28
Final Reading 4.3988 4.5086
Test Duration: 15 MIN 15 MIN
Change in Reading(Rr N: .0010 .0016
Pass/Fail Threshold or Criteria: .002 .002
TestiResidt- Pass -`.O Fail Pass .'.l7 Fail: !7 Pass, :l7 Fail ❑:Pass'':❑Fail ;:.
Was sensor removed md for testing? Yes ❑No ❑NA Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA
Was sensor properly replaced and yes ❑No ❑NA Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA
verified functional after testis ?
Comments—(include information on repairs made prior to testing; and recommended follow-rip for failed tests)
`If the entire depth of the UDC is not tested,specify how much was tested. If the answer to any of the questions indicated with an
asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160)
SWRCB,January 2002 Page of
7. UNDER-DISPENSER CONTAINMENT QT9 TESTING
Test Method Developed By: 211UDC Manufacturer ❑Industry Standard ❑Professional Engineer
❑Other(Specify)
Test Method Used: ❑Pressure ❑Vacuum Aydrostatic
❑Other(Specify)
Test Equipment Used: INCON TS-STS Equipment Resolution: 0.0000
�_UDC#9-10 UDC#11-12 UDC#13-14 UDC#15-16
UDC Manufacturer. ENVIRON ENVIRON ENVIRON ENVIRON
UDC Material: PLASTIC PLASTIC PLASTIC PLASTIC
UDC the 30" 30" 30" 30"
Height from UDC Bottom to Top 10" 10" 10" 10"
of Highest Piping Penetration:
Height from UDC Bottom to 5" 5" 5" 5"
Lowest Electrical Penetration:
Condition of UDC prior to DRY DRY DRY DRY
testing:
Portion of UDC Tested 12" 12" 12" 12"
Does turbine shut down when /
UDC sensor detects liquid(both 2(Yes ❑No ❑NA I Yes ❑No ❑NA Y'Yes ❑No ❑NA WI Yes ❑No ❑NA
product and water)?*
Turbine shutdown response time 20 SEC 20 SEC 20 SEC 20 SEC
Is system programmed for fail- p'Yes ❑No ❑NA
safe shutdown?* Yes ❑No DNA les 0 N DNA Yes 0 N DNA
Was fail-safe verified to be dYes ❑No ❑NA C//Yes ❑No ❑NA es ❑No ❑NA es ❑No ❑NA
operational?*
Wait time between applying 15 MIN 15 MIN 15 MIN 15 MIN
pressure/vacuum/water and
starting test
Test Start Time: 10:13 11:31 10:44 10:44
Initial Reading r): 5.5703 4.5602 3.3693 2.9415
Test End Time: 10:28 11:46 10:59 10:59
Final Reading(Rr): 5.5685 4.5592 3.3691 2.9412
Test Duration: 15 MIN 15 MIN 15 MIN 15 MIN
Change in Reading R1): .0018 .0010 .0002 .0003
Pass/Fail Threshold or Criteria: .002 .002 .002 .002
Test.Resnit- f:Pass . ❑Fail Pass:" O`Fail- Pass . ❑'Fail Psss ;0`Fad
Was sensor removed for testing? VYes ❑No ❑NA &Yes ❑No ❑NA Vfes ❑No ❑NA Yes ❑No ❑NA
Was sensor properly replaced and yes ❑No ❑NA R(Yes ❑No ❑NA es ❑No ❑NA
verified functional after te ? Yes ❑No ❑NA
stin
Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests)
'If the entire depth of the UDC is not tested,specify how much was tested. If the answer to M of the questions indicated with an
asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160)
SWRCB,January 2002 Page of
8. FILL RISER CONTAINMENT SUMP TESTING
Facility is Not Equipped With Fill Riser Containment Sumps ❑
Fill Riser Containment Sumps are Pres nt,but were Not Tested ❑
Test Method Developed By: Sump Manufacturer ❑Industry Standard ❑Professional Engineer
❑Other(Specify)
Test Method Used: ❑Pressure ❑Vacuum Hydrostatic
❑Other(Spec)
Test Equipment Used:INCON TS-STS Equipment Resolution:0.0000
Fill Sump#1 Fill Sump#2 Fill Sump#3 Fill Sume#4
Sump Diameter. 42" 42" 42"
Sump Depth: 48" 49" 48"
Height from Tank Top to Top of N/A N/A N/A
Highest Piping Penetration:
Height from Tank Top to Lowest N/A N/A N/A
Electrical Penetration:
Condition of sump prior to DRY DRY DRY
testing:
Portion of Sump Tested 12" 12" 12"
Sump Material: FIBERGLASS FIBERGLASS FIBERGLASS
Wait time between applying 10 MIN 10 MIN 10 MIN
pressure/vacuum/water and
starting test:
Test Start Time: 1:59 1:59 1:59
Initial Reading O: 1.3911 2.6514 5.8212
Test End Time: 2:14 2:14 2:14
Final Reading RF): 1.3919 2.6531 5.8197
Test Duration: 15 MIN 15 MIN 15 MIN
Change in Reading(RF-R): .008 .0017 .0015
Pass/Fail Threshold or Criteria: .002 .002 .002
''Te§t Result ,Pas s": ,0I Fail >. .;:Pass _-❑_Fail `Pass :Fail ❑:.Pass
Is there a sensor in the sump? ❑Yes ItNo ❑Yes No ❑Yes No ❑Yes ❑No
Does the sensor alarm when /� 1W NA either product or water is ❑Yes ❑No �7 NA ❑Yes ❑No fl NA ❑Yes ❑No P]NA ❑Yes ❑No ❑NA
detected?
Was sensor removed for testing? ❑Yes ❑No NA ❑Yes ❑No NA ❑Yes ❑No tAo-
Yes ❑No ❑NA
Was sensor properly replaced and ❑yes ❑No verified functional after testis ? NA ❑Yes ❑No ❑Yes ❑No Yes ❑No 0 N
Comments—(include information on repairs made prior to testing: and recommended follow-up for failed tests)
ALL FILL SUMPS WERE REGLASSED AND RETESTED ON 34-11.
SWRCB,January 2002 Page of
9. SPILIJOVERFILL CONTAIIKMENT BOXES
Facility is Not Equipped With Spill/Overfill Containment Boxes ❑
Spill/Overfill Containment Boxes are Present,but were Not Tested ❑
Test Method Developed By: Spill Bucket Manufacturer ❑Industry Standard ❑Professional Engineer
❑Other(Spec) Ic
Test Method Used: ❑Pressure ❑Vacuum Hydrostatic
❑Other(Spec)
Test Equipment Used:INCON TS-STS Equipment Resolution:0.0000
Spill Box#1 Spill Box#2 Spill Boa#3 Spill Bog#
Bucket Diameter: 12" 12" 12"
Bucket Depth: 12" 12" 12"
Wait time between applying
pressure/vacuum/water and 10 MIN 10 MIN 10 MIN
startin 9 test:
Test Start Time: 2:14 2:56 2:14
Initial Reading(RT): 4.2334 3.2804 5.7255
Test End Time: 2:29 3:11 2:29
Final Reading(RF): 4.2327 32799 5.7248
Test Duration: 15 MIN 15 MIN 15 MIN
Change in Reading(RF-&): .0007 .0005 .0007
Pass/Fail Threshold or .002 .002 .002
Criteria:
Test Result• Pass ❑.Fail Pass, 12Pass;:' ❑Fail ❑ Fass` q`Earl
Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests)
SWRCB,January 2002 Page of
9. SPILL/OVERFILL CONTAWWNT BOXES
Facility is Not E ui d With Spill/Overfill Containment Boxes ❑
Spill/Overfill Containment Boxes are Present,but were Not Tested ❑
Test Method Developed By: Rf Spill Bucket Manufacturer ❑Industry Standard ❑Professional Engineer
❑Other(Spec)
Test Method Used: ❑Pressure ❑Vacuum Hydrostatic
❑Other(Spec)
Test Equipment Used:INCON TS-STS Equipment Resolution:0.0000
T:: z 'K Spill Box#Vl Spill Box#V2 Spill Boa#V3 w Spill Boa#
Bucket Diameter: 12" 12" 12"
Bucket Depth: 12" 12" 12"
Wait time between applying
pressure/vacuum/water and 10 MIN 10 MIN 10 MIN
starting test:
Test Start Time: 2:14 1:59 2:14
Initial Reading 4.2400 4.6575 4.9048
Test End Time: 2:29 2:14 2:29
Final Reading(RF): 4.2393 4.6576 4.9039
Test Duration: 15 MIN 15 MIN 15 MIN
Change in Reading(RF-R): .0007 .0001 .0009
Pass/Fail Threshold or
002 .002 .002
Criteria:
Test Result::. Pass; ❑Fail Pass ❑Fail _ Pass .` ❑Fail O';Pass,, ❑Fait
Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests)
FASTRIP 721
FASTRIP 721 4013 SO H ST
4013 SO H ST BAKERSFIELD CA
BAKERSFIELD CA . SUNSET CONST
SUNSET CONST 1-800-984-6266
FASTRIP 721
1-800-984-6266
4013 SO H-ST 03/04/2011 2:14 PM
BAKERSFIELD CA
03/04/2011 2:30 PM
SUNSET CONST SUMP LEAK TEST REPORT
SUMP LEAK TEST REPORT 1-800-984 76266
FILL 1
FILL 1 02/28/2011 3:11 PM
TEST STARTED 1:59 PM
TEST STARTED 2:15 PM SUMP LEAK TEST REPORT TEST STARTED 03/04/2011
TEST STARTED 03/04/2011 BEGIN LEVEL 1.3911 IN
BEGIN LEVEL 1.3919 IN SPILL 2 END TIME 2:14 PM
END TIME 2:30 PM END DATE 03/04/2011
ND DATE 03/04/2011 TEST STARTED 2:56 PM END LEVEL 1.3919 IN
END
LEVEL 1,3923 IN TEST.STARTED 02/28/2011 LEAK THRESHOLD 0.002 IN
LEAK THRESHOLD 0.002 IN BEGIN LEVEL 3.2804 IN TEST RESULT PASSED
TEST RESULT PASSED END TIME 3:11 PM
END DATE 02/28/2011
END LEVEL 3,2799 IN FILL 2
FILL 2 LEAK THRESHOLD 0.002 IN
TEST RESULT PASSED TEST STARTED 1:59 PM
TEST STARTED 2:15 PH TEST STARTED 03/04/2011
TEST STARTED 03/04/2011 BEGIN LEVEL 2,6514 IN
BEGIN LEVEL 2,6531 IN END TIME 2:14 PM
END TIME 2:30 PM END DATE 03/04/2011
END DATE 03/04/2011 END LEVEL 2.6531 IN
END LEVEL 2.6537 IN LEAK THRESHOLD 0,002 IN
LEAK THRESHOLD 0.002 IN TEST RESULT PASSED,
TEST RESULT PASSED
FILL 3
FASTRIP 721
FILL 3 4013 SO H ST
TEST STARTED 1:59 PM
TEST STARTED 2:15 PM BAKERSFIELD CA TEST STARTED 03/04/2011
TEST STARTED 03/04/2011 SUNSET CONST BEGIN LEVEL 5.8212 IN
1-800-984-6266 - END TIME 2:14 PM
BEGIN LEVEL 5.8160 IN
END DATE 03/04/2011
ENO TIME 2:30 PM 02/28/2011 3:30 PM
END DATE 03/04/2011 END LEVEL 5.8197 IN
END LEVEL 5.8007 IN SUMP LEAK TEST-REPORT LEAK THRESHOLD 0,002 IN
LEAK THRESHOLD 0.002 IN TEST RESULT PASSED
TEST RESULT FAILED SPILL 2
TEST STARTED 3:14 PM
USPILL2
VSPILL2 TEST STARTED 02/28/2011
TEST STARTED 1:59 PM
BEGIN LEVEL 3,2799 IN
TEST STARTED 03/04/2011
TEST STARTED 2:15 PM END TIME 3:29 PM BEGIN LEVEL 4.6575 IN
TEST STARTED 03/04/2011
END DATE 02/28/2011 END TIME 2:14 PM
BEGIN LEVEL 4.6577 IN END LEVEL 3.2808 IP!
END TIME 2:30 PM LEAK THRESHOLD 0,002 IN END DATE 03/04/2011
END DATE 03/04/2011 TEST RESULT PASSED END LEVEL 4.6576 IN
END LEVEL 4.6577 IN LEAK THRESHOLD 0,002 IN
LEAK THRESHOLD 0,002 IN TEST RESULT PASSED
TEST RESULT PASSED -`
FASTRIP 721 FASTRIP 721
FASTRIP 721 4013 SO H ST
013 SO H ST 4013 SO H ST
4
4013S O14 CA BAKERSFIELD CA BAKERSFIELD CA
ST CONST SUNSET CONST SUNSET CONST
S
1UNSET 84-6266 1-800-984—m.. 1400-984-6266
02/28/2011 2:04 PM 02/28/2011 2:30 PM 02/28/2011 2:46 PM
SUMP LEAK TEST REPORT SUMP LEAK TEST REPORT SUMP LEAK TEST REPORT
S•P 1 SPILL 1 SPILL 1
1:49 PM TEST STARTED 2:14 PM TEST STARTED 2:30 PM
TEST STARTED TEST STARTED 02/28/2011 TEST STARTED 02/28/2011
TEST STARTED 02/28/2011 BEGIN LEVEL 4.2334 IN
BEGIN LEVEL BEGIN LEVEL 4,2318 IN
4
2:04 PM END TIME 2:29 PM END TIME 2:45 PM
END TIME END DATE 02!28/2411 END DATE 02/28/2011
END DATE 02/28/2011
END LEVEL 4,8880 IN END LEVEL 4,2327 IN END LEVEL 4.2318 IN
THRESHOLD .8890 IN LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0,002 IN
LEAK
TEST RESULT PASSED T
TEST RESULT PASSED TES RESULT PASSED
FILL 1 VSPILLI VSPILLI
TEST STARTED 1:49 PM TEST STARTED 2:14 PM TEST STARTED 2:30 PM
TEST STARTED 02/28/2011 TEST STARTED 02/28/2011 TEST STARTED 02/28/2011
2,7452 IN BEGIN LEVEL 4,2400 IN BEGIN LEVEL 4.2378 IN
BEGIN LEVEL 2.04 PM END TIME 2:29 PM END TIME 2:45 PM
DATE 2
pdD. END DATE 02/28/ 011
END DATE 02/28/2011 END DATE 02!28/2011
END LEVEL 2.6544 IN END LEVEL 4,23,93 IN END LEVEL 4.2373 IN
LEAK THRESHOLD 0.002 IN LEAK THRESHOLD 0.002 IN
LEAK THRESHOLD 0,002 IN E
TEST RESULT PASSED TEST RESULT PASSED
TEST RESULT FAILED
FILL 2 SPILL3 SPILL3
TEST STARTED 1:49 PM TEST STARTED 2:14 PM TEST STARTED 2:30 PM
TEST STARTED 02/28/2011 TEST STARTED 02/28/2011 TEST STARTED 02/28/2011
BEGIN LEVEL 4,2253 IN BEGIN LEVEL 5.7255 IN BEGIN LEVEL 5,7248 IN
2:04 PM END TIME 2:29 PM END TIME 2:45 PM
END TIME END DATE 02/28/2011 END DATE 02/28/2011
END DATE. 02/28/2011
END LEVEL 5,7248 IN END LEVEL 5,7246 IN
END LEVEL 4.1995 IN
LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0.002 IN
LEAK THRESHOLD 0,002"
D TEST RESULT PASSED
TEST RESULT TEST RESULT PASSED
FILL 3 VSPILL3 VSPILL3
TEST STARTED 1:49 PM TEST STARTED 2:14 PM TEST STARTED 2:30 PM
TEST STARTED 02/28/2011 TEST STARTED 02/28/2011
TEST STARTED 02/28!2011 BEGIN LEVEL 4.9048 IN
BEGIN LEVEL 3,8526 IN 2.29 PH END TIME BEGIN LEVEL 4,9045 IN
2:04 PM END TIME 2:45 PM
END TIME
1 END DATE 02/28/2011 END DATE 02/28/2011
END DATE 02/281201
3,7302 END LEVEL 4,9039 IN END LEVEL 4,9045 IN
I1
END LEVEL LEAK THRESHOLD 0,002 IN
LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0,0.02 IN
TEST RESULT
FAILED TEST RESULT PASSED TEST RESULT PASSED
FASTRIP 721
4013 SO H ST
BAKERSFIELD CA FASTRIP 721
SUNSET CONST 4013 SO H ST
1-800-984-6266 BAKERSFIELD CA FASTRIP 721
SUNSET CONST 4013 SO H ST
02/28/2011 12:22 PM 1-800-984-6266 BAKERSFIELD CA
9 WSET CONST
SUMP LEAK TEST REPORT 02/28/2011 12:39 PM 1-800-984-6266
UDC1718 SUMP LEAK TEST REPORT 02/28/2011 11:46 AM
TEST STARTED 12:07 PM UDC1718 SUMP LEAK TEST REPORT
TEST STARTED 02/28/2011
BEGIN LEVEL 4,3983 IN TEST STARTED 12:24 PM UDC1718
END TIME 12:22 PM TEST STARTED 02/28/2011
END DATE 02/28/2011 BEGIN LEVEL 1.7483 IN TEST STARTED 11:31 AM
END LEVEL 4,3982 IN END TIME 12:39 PM TEST STARTED 02/28/2011
LEAK THRESHOLD 0,002 IN END DATE 02/28/2011 BEGIN LEVEL 4,3998 IN
TEST RESULT PASSED END LEVEL -0,2185 IN END TIME 11:46 AM
LEAK THRESHOLD 0,002 IN END DATE 02/28/2011
TEST RESULT FAILED END LEVEL 4.3988 IN
STP 1 LEAK THRESHOLD 0,002 IN
TEST RESULT PASSED
TEST STARTED 12:07 PM STP 1
TEST STARTED 02/28/2011
BEGIN LEVEL 5.6566 IN TEST STARTED 12:24 PM UDC1112
END TIME 12:22 PM TEST STARTED 02/28/2011
END DATE 02/28/2011 BEGIN LEVEL 5,6494 IN TEST STARTED 11:31 AM.
END LEVEL 5.6493 IN END TIME 12:39 PM TEST STARTED 02/28/2011
LEAK THRESHOLD 0,002 IN END DATE 02/28/2011 BEGIN LEVEL . 4,5602 IN
TEST RESULT FAILED END LEVEL 5.6478 IN END TIME 11:46 AM
LEAK THRESHOLD 0.002 IN END DATE 02/28/2011
TEST RESULT PASSED END LEVEL 4.5592 IN
STP 2 LEAK THRESHOLD 0,002 IN
TEST RESULT -PASSED
TEST STARTED 12:07 PM STP 2
TEST STARTED 02/28/2011
BEGIN LEVEL 6,1177 IN TEST STARTED 12:24 PM
END TIME 12:22 PM TEST STARTED 02/28/2011
END DATE 02/28/2011 BEGIN LEVEL 6,1176 IN :-
END LEVEL 6.1176 IN END TIME 12:39 PM
LEAK THRESHOLD 0.002 IN END DATE 02/28/2011
TEST RESULT PASSED END LEVEL 6,1177 IN'
LEAK THRESHOLD 0.002 IN
TEST RESULT PASSED
STP 3
TEST STARTED 12:07 PM STP 3
TEST STARTED 02/28/2011
BEGIN LEVEL 5.9627 IN TEST STARTED 12:24 PM =
END TIME 12:22 PM TEST STARTED 02/28/2011
END DATE 02/28/2011 BEGIN LEVEL 5.9620 IN
END LEVEL 5,9620 IN END TIME 12:39 PM
LEAK THRESHOLD 0.002 IN END DATE 02/28/2011
TEST RESULT PASSED END LEVEL 5,9603 IN
LEAK THRESHOLD 0,002 IN
TEST RESULT PASSED
FASTRIF 721 FASTRIP 721
4013 SO H ST
4013 SO H ST BAKERSFIELD CA
FASTkIF 721 BAKERSFIELD CA SUNSET CONST
SUNSET CONST 1-800-984-6256
4013 SO H ST 1-800-984-6266
BAKERSFIELD CA
SUNSET CONST 02/28/2011 11:20 AM
02/28/2011 10:59 AM
1-800-984-6266
SUMP LEAK TEST REPORT SUMP-LEAK TEST REPORT
02/28/2011 10:28 AM
UDC9-10 UBC1112
SUMP LEAK TEST REPORT
TEST STARTED 10:44 AM TEST STARTED 11:04 AM
TEST STARTED 02/28/2011
UDC9-10 TEST STARTED 02/28/2011 BEGIN LEVEL 4,4243 IN
BEGIN LEVEL 5.5658 IN END TIME 11:19 AM
TEST STARTED 10:13 AM END TIME 10:59 AM END DATE 02/28/2011
TEST STARTED 02/28/2011 END DATE 02/28/2011 END LEVEL 4,2233 IN
BEGIN LEVEL 5,5703 IN END LEVEL 5,5650 IN LEAK LEVEL
HOLD 002 IN
END TIME 10:28 AM LEAK THRESHOLD 0,002 IN TEST RESULT PASSED
END DATE 02/28/2011 TEST RESULT PASSED
END LEVEL 5.5685 IN
LEAK THRESHOLD 0,002 IN UDC1516
TEST RESULT PASSED UDC1516
TEST STARTED 10:44 AM TEST STARTED 11:04 AM
TEST.STARTED 02/28/2011
UDC1718 TEST STARTED 02/28/2011
BEGIN LEVEL 2,9415 IN BEGIN LEVEL 2.9411 IN
TEST STARTED 10:13 AM END TIME 10:59 AM END TIME , 11:19 AM TEST STARTED 02/28/2011 END DATE 02/28/2011 END DATE 02/28/2011 END LEVEL
2,9411 IN
BEGIN LEVEL 5,6568 IN END LEVEL 2,9412 IN LEAK THRESHOLD 0,002 IN
END TIME 10:28 AM LEAK THRESHOLD 0,002 IN TEST RESULT PASSED
END DATE 02/28/2011 TEST RESULT PASSED
END LEVEL 5.6474 IN
LEAK THRESHOLD . 0.002 IN UDC1314
TEST RESULT FAILED UDC1314
TEST STARTED 10:24 AM TEST STARTED 11:04 AM TEST STARTED 02/28/2011
UBC1112 TEST STARTED 02/28/2011 BEGIN LEVEL 3,3692 IN
BEGIN LEVEL 3,3693 IN ENO TIME 11:19 AM
TEST STARTED 10:13 AN END TIME 10:59 AM END DATE 02/28!2011
TEST STARTED 02/2812011 END DATE 02/28/2011 END LEVEL 3.3690 IN
BEGIN LEVEL 5.6867 IN END LEVEL 3,3691 IN LEAK THRESHOLD 0,002 IN
END TIME 10:28 AM LEAK THRESHOLD 0,002 IN TEST RESULT PASSED
END DATE 02/28/2011 TEST RESULT PASSED
END LEVEL 5.6786 IN
LEAK THRESHOLD 0.002 IN UDC1920
TEST RESULT FAILED UDC1920
TEST STARTED 11:04 AM
TEST STARTED 10:44 AM TEST STARTED 02/28/2011
UDC1920 TEST STARTED 02/28/2017
GIN LEVEL 3,2158 IN
BEGIN LEVEL 4,5032 IN END TIME 11:19 AM
TEST STARTED 10:13 AM END TIME 10:59 AM END DATE 02/28/2011
TEST STARTED 02/28/2011 END DATE 02/28/2011 ENO LEVEL 3.2154 IN
BEGIN LEVEL 4.5102 IN END LEVEL 4.5003 IN LEAS( THRESHOLD 0.002 IN
END TIME 1C:28 AM LEAK THRESHOLD 0.002 IN
END DATE 02/28/2011 TEST RESULT FAILED TEST RESULT PASSED
END LEVEL 4.5086 IN
LEAK THRESHOLD 0,002 IN
TEST RESULT PASSED
FASTRIP 721
4013 SO H ST
BAKERSFIELD CA
SUNSET CONST
1-800-984-6266
02/28/2011 10:03 AM
SUMP LEVEL REPORT
SUMP UDC9-10 5,575 IN
SUMP UDC1516 4.106 IN
SUMP UBC1112 5,697 IN C-1
SUMP UDC1920 4,546 IN
FASTRIP 721
4013 SO H ST
BAKERSFIELD CA
SUNSET CONST
1-800-9134-6266
02/28/2011 10:11 AM
SUMP LEVEL REPORT .
SUMP UDC9-10 5.572 IN
SUMP UDC1516 5.658 IN
SUMP UBC1112 5.690 IN
SUMP UDC1920 4,511 IN