HomeMy WebLinkAbout#781 SB-989 Results 2-28-11 SWRCB Jan 2002 IIIIIIII°IIIIIIIIII 65 a of Y lE Secondary Containment Testing Report Form This form is intended for use by contractors performing periodic testing of UST secondary containment systems. Use the appropriate pages of thisform to report results for all components tested The completed form, written test procedures, and printouts from tests(f applicable),should be provided to the facility owner/operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: Fastrip#781 Date of Testing: 2/28/11 Facility Address: 4013 South H St.Bakersfield,CA Facility Contact: Jamieson Hill Phone: 1-661-393-7000 Date Local Agency Was Notified of Testing: February 23,2011 Name of Local Agency Inspector(fpresent during testing): 2. TESTING CONTRACTOR INFORMATION Company Name: Sunset Mechanical Technician Condu ' g Test: Scott Olinger Credentials: CSLB Licensed Contractor ❑SWRCB Licensed Tank Tester License Type: C-36 C-10 License Number. 589517 Manufacturer Training Manufacturer Component(s) Date Training Expires Incon TS-STS Inspection Equipment 1/18/13 Veeder Root Monitoring System 1/15/12 ICC Cal UST Service Tech 1/18%13 3. SUMMARY OF TEST RESULTS Component Pass Fail Not Repairs Component Pass Fait Not Repairs Tested Made Tested Made UDC 1-2 ❑ ❑ ❑ PIPING RUN#1 ❑ ❑ ❑ UDC 3-4 ❑ ❑ ❑ PIPING RUN#2 ❑ ❑ ❑ UDC 5-6 ❑ ❑ ❑ PIPING RUN#3 ❑ ❑ ❑ UDC 7-8 ❑ ❑ ❑ PIPING RUN#4 ❑ ❑ ❑ STP#1 ❑ ❑ TRAN#1 ❑ ❑ STP#2 ❑ ❑ ❑ TR.AN#2 9' ❑ ❑ STP#3 ❑ ❑ ❑ SPILL#1 ❑ ❑ ❑ STP#4 ❑ ❑ ❑ SPILL#2 (1 ❑ ❑ ❑ FILL#1 ❑ ❑ ❑ SPILL#3 Et ❑ ❑ ❑ FILL#2 ❑ p ❑ SPILL#4 ❑ ❑ ❑ FILL#3 ❑ ❑ ❑ V SPILL#1 ❑ ❑ ❑ FILL#4 ❑ ❑ ❑ V SPILL#2 ❑ ❑ ❑ If hydrostatic testing was performed,describe what was done with the water after completion of tests: CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING To the best of my knowledge,the fa in this document are accurate and in full compliance with legal requirements Technician's Signature: Date: 3/1/11 IIIIIII IIIII III IIII 66 IE SWRCB,January 2002 Page of Secondary Containment Testing Report Form Thu form is intendedfor use by contractors performingperia&c testing of USTsecondary containment systems. Use the appropriate pages of thisform to report results for all components tested The completed form,written test procedures, and printouts from tests(rf applicable),should be provided to the facility owner/operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: Fastrip#781 Date of Testing: 2/28/11 Facility Address: 4013 South H St Bakersfield,CA Facility Contact: Jamieson Hill Phone: 1-661-393-7000 Date Local Agency Was Notified of Testing: February 23,2011 Name of Local Agency Inspector.(ifpresent during testing): 2. TESTING CONTRACTOR INFORMATION Company Name: Sunset Mechanical Technician Conducting Test: Scott Olinger Credentials: ❑CSLB Licensed Contractor ❑SWRCB Licensed Tank Tester License Type: C-36 C-10 License Number. 589517 Manufacturer Training Manufacturer Component(s) Date Training Expires Incon TS-STS Inspection Equipment 1/18/13 Veeder Root Monitoring System 1/15/12 ICC Cal UST Service Tech 1/18/13 3. SUMMARY OF TEST RESULTS Component Pass Fail Not Repairs Component Pass Fail Not Repairs Tested Made Tested Made V SPILL#3 ❑ ❑ ❑ ❑ ❑ ❑ ❑ V SPILL#4 ❑ ❑ ❑ 0 0 0 0 ANN SPACE 1 ❑ ❑ 1 0 0 0 0 ❑ ANN SPACE 2 ❑ ❑ ❑ ❑ ❑ ❑ ❑ ANN SPACE 3 ❑ ❑ ❑ ❑ ❑ ❑ ❑ ANN SPACE 4 ❑ ❑ ❑ ❑ ❑ ❑ ❑ 0 0 ❑ 0 ❑ 0 ❑ 0 0 ❑ 0 0 0 ❑ 0 0 0 0 0 0 0 0 0 0 0 0 ❑ 0 ❑ ❑ ❑ ❑ ❑ 0 0 ❑ 0 0 0 ❑ ❑ ❑ 1 ❑ 1 ❑ ❑ 0 0 0 If hydrostatic testing was performed,describe what was done with the water after completion of tests: CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING To the best of my knowledge,the ads s ted in this document are accurate and in full compliance with legal requirements Technician's Signature Date: 3/1/11 SWRCB,January 2002 Page_of 4.4 TANK ANNULAR TESTING Test Method Developed By: M Tank Manufacturer ❑Industry Standard ❑Professional Engineer ❑Other(Specify) Test Method Used: ❑Pressure itVacuum. ❑Hydrostatic ❑Other(Specify) Test Equipment Used.4"GEL FILLED GAUGE W/CERTS Equipment Resolution:0-30 Tank#1 Tank#2 Tank#3 Tank# Is Tank Exempt From Testing?' ❑Yes ❑NO ❑Yes ONo ❑Yes ONo ❑Yes ❑No Tank Capacity- 12,000 12,000 12,000 12,000 Tank Material: GLASS ISTEEL GLASS/STEEL GLASS/STEEL GLASS/STEEL Tank Manufacturer. JOOR JOOR JOOR JOOR Product Stored: UNL UNL PREM UNL Wait time between applying pressure/vacuum/water and 10 MIN 10 A41N 10 MIN 10 MIN startin g test: Test Start Time: 9:10 9:10 10:10 10:10 Initial Reading(R�: 10 14G 10 14G 12 HG 12 HG Test End Time: 10:10 10:10 11:10 11:10 Final Reading(RF): 10 HG 10 HG 12 HG 12 HG Test Duration: I HR I HR 1 H I HR Change in Reading(RF-Ra- 0 0. 0 0 Pass/FailThreshold or Criteria: 0 0 0 0 "Test Result - :-Apiss OFafl &(Pass,-.-ahii Pass ❑Fail Pass O-Fail. Was sensor removed for testing? dYes ❑No ❑NA es ❑No ❑NA //Yes ONo [INA �(Yes ❑No 11 NA Was sensor properly replaced and dyes ❑No ❑NA 9//Yes ONo ONA Ges ❑No ❑NA ff es ❑No ❑NA Lverified functional after testin g? I Comments—(include information on repairs made prior to testing and recommended follow-up for failed tau) Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment testing. (California Code of Regulations,Title 23,Section 2637(a)(6)} SWRCB,January 2002 Page_of 5. SECONDARY PIPE TESTING Test Method Developed By Nf Piping Manufacturer ❑Industry Standard ❑Professional Engineer ❑Other(Specify) Test Method Used: ❑Pressure ❑Vacuum 9Hydrostatic ❑Other(Specify) Test Equipment Used:INCON TS-STS - Equipment Resolution: 0.0000 tr _Z Piping Run 2 Piping Run#4 Piping Run#I Piping Run#3 Piping Material: FIBERGLASS FIBERGLASS FIBERGLASS FIBERGLASS Piping Manufacturer- AO SMITH AO SMITH AO SMITH AO SMITH Piping Diameter. 312 3" 312 3" Length of Piping Run: 110, 120' 130' 140' Product Stored: LTNL UNL PREM DIESEL Method and location of TEST BOOT AT ST? TEST BOOT AT STP TEST BOOT AT iping-run isolation STP TEST BOOT AT STP p : Wait time between applying pressure/vacuum/water and 20 MIN 20 MIN 20 MIN 20 UN starting test: Test Start Time: 8:28 8:28 8:28 8:28 Initial Reading M): 3.2836 4.5585 4.6217 4.9323 Test End Time: 8:43 8:43 8:43 8:43 Final Reading(RF): 3.2834 4.5585 4.6217 4.9323 Test Duration: 15 MIN 15 NEN 15 MIN 15 NUN Change in Reading(RF-R4): .0002 0 0 0 Pass/Fail Threshold or .002 .002 .002 .002 Criteria: U(Pass, ...O:Fait ; Test Result: Fail.' Comments—(include information on repairs made prior to testing; and recommended follow-up for failed tests) SWRCB,January 2002 Page_of 6. PIPING SUMP TESTING Test Method Developed By: ❑Sump Manufacturer ❑Industry Standard ❑Professional Engineer ❑Other(Specify) Test Method Used. ❑Pressure ❑Vacuum ❑Hydrostatic 0 Other(Specify) Test Equipment Used:INCON TS-STS Equipment Resolution:0.0000 SUMP Diameter. 18"x24" 18"x24" Sump Depth: 31" 31" Sump Material: FIBERGLASS FIBERGLASS Height from Tank Top to Top of 12" Highest Piping'Penetration: Height from Tank Top to Lowest Electrical Penetration: 8" 8" Condition of sump prior to testing: DRY DRY Portion of Sump Tested' 14" 14" Does turbine shut down when sump sensor detects liquid(both ❑Yes ❑No AA ❑Yes ❑No AA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA product and water)?* Turbine,shutdown response time Is system programmed for fail-safe ❑Yes ❑No I/NA ❑Yes ❑No shutdown?* AA 0 Yes ❑No ❑NA 0 Yes ❑No ❑NA Was fail-safe verified to be 0 Yes ❑No AA 0 Yes 0 No O/NA operationall D Yes ❑No ❑NA ❑Yes ONo [INA * Wait time between applying pressure/vacuum/water and starting 10 MW Ohm test Test Start Time: 12:49 12:49 Initial Reading.(RO: 4.1601 4.0597 Test End Time- 1:04 1:04 Final Reading(RF): 4.1601 4.0594 Test Duration: 15 MIN 15 NUN Change in Reading(RF44): 0 .0003 Pass/Fail Threshold or Criteria: .002 .002 Test ResWt~ Pass ::' �O ss OFiff Was sensor removed for testing? ❑Yes ONo YNA ❑Yes ONo dNA ❑Yes ONo DNA ❑Yes ONo DNA Was sensor properly replaced and verified functional after testing? D Yes ❑No AA D Yes ❑No O/NA 0 Yes ❑No DNA 0 Yes 11 No ❑NA Comments—(mclude information on repairs made prior to testing; and recommended follow-up for failed tests) Replace all hose clamps. If the entire depth of the sump is not tested,specify how much was tested. If the answer to any of the questions indicated with an asterisk(•)is"NO"or"NA",the entire sump must be tested, (See SWRCB LG-160) SWRCB,January 2002 Page_of 6. PIPING SUMP TESTING Test Method Developed By: Sump Manufacturer ❑Industry Standard ❑Professional Engineer ❑Other(Specify) If Test Method Used: 13 Pressure ❑Vacuum Hydrostatic ❑Other(Specify) Test Equipment Used INCON TS-STS :LEquipment Resolution:0.0000 UO SUMP#1 STP SUMP#2 STP SUMP#3 STP :SUMP#4STP Sump Diameter: 48" 48" 48" 48" Sump Depth: 54" 55" 54" 56" Sump Material: FIBERGLASS FIBERGLASS FIBERGLASS FIBERGLASS Height from Tank Top to Top of 15" 16" 15" 16" Highest Piping Penetration: Height from Tank Top to Lowest 19" 19" 19" 20" Electrical Penetration: Condition of sump prior to testing- DRY DRY DRY DRY Portion of Sump Tested' 18" 18" 18" is" Does turbine shut down when sump sensor detects*liquid(both C�Yes ❑No ❑NA IYes ❑No [INA Q(Yes ❑No DNA YYes ❑No ❑NA product and water)? Turbine shutdown response time 30 SEC 30 SEC 30 SEC 30 SEC Is system programmed for fail-safe S(Yes "D No DNA YYes ❑No DNA 9�Yes ❑No 0 NA es ONo DNA shutdown?* Was fail-safe verified to be U(Yes ❑No ❑NA I/Yes ONo DNA Q/Yes 0 No 0 NA Xes ❑No DNA op erational?* Wait time between applying pressurelvacuum/water and starting 10 MIN 10 NON 10 MIN 10 NM test: Test Start Time: 12:11 10:18 10:18 10:18 Initial Reading(R j): 5.6405 5.4795 6.6855 6.7314 Test End Time: 12:26 10:33 10:33 10:33 Final Reading(RF): 5.6403 5.47% 6.6854 6.7311 Test Duration: 15 MIN 15 MIN 15 MW 15 NUN Change in Reading(RF-R4): OM .0001 .0001 .0003 Pass/Fail Threshold or Criteria: M .002 .002 M, 7 Pass jonil- .xesfR&u1t: P"s -01a 7 Was sensor removed for testing? 9 Yes D No ❑NA Q(Yes ❑No DNA Yes 0 No DNA G/Yes ❑No (INA Was sensor properly replaced and Wyes ❑No [=INAYes ONo DNA &s ❑No DNA As ❑No DNA verified functional after testing! Comments—(include information on repairs made prior to testing: and recommended follow-up for failed tests) STP#I Install 2-3"repair boots and 3-1"repair boots. If the entire depth of the sump is not tested,specify how much was tested. If the answer to any of the questions indicated with an asterisk(*)is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160) SWRCB,January 2002 Page_of 7. !MER-DISPENSER CONTAINMENT(UDC)TESTING Test Method Developed By YUDC Manufacturer ❑Industry Standard 0 Professional Engineer ❑Other(Specify) Test Method Used: 0 Pressure 0 Vacuum YHydrostatic 0 Other(Spec) Test Equipment Used: INCON TS-STS Equipment Resolution: 0.0000 ,Li _UDC#3-4 UDC#!5-6 UDC#7-8 UDC Manufacturer: AM CON AM CON AM CON AM CON UDC Material: FIBERGLASS FIBERGLASS- FIBERGLASS FIBERGLASS UDC Depth: 32" 329' 3211 32" Height from UDC Bottom to Top 12" 12" 12" 1211 of Highest Piping Penetration: Height from UDC Bottom to 8" 8" 8" 81, Lowest Electrical Penetration: Condition of UDC prior to DRY DRY DRY DRY testing: Portion of UDC Tested 14" 14" 14" 14" Does turbine shut down when UDC sensor detects liquid(both G7`Yes ❑No ❑NA Q�es ❑No DNA 5/Yes ❑No DNA [/Yes 0 No ❑NA product and water)?. Turbine shutdown response time 30 SEC 30 SEC 30 SEC 30 SEC Is system programmed for fail- 6/yes 0 No ❑NA Yes 0 No DNA Yes 0 No DNA EI/Yes DNo DNA safe shutdown?* 4 Was fail-safe verified to be �Yes D No ❑NA —dy—es ❑No DNA Yes 0 No [INA 6/yes 0 No' 0 NA operational?* Wait time between applying 20 KIN 20 MIN 20 MIN 20 MIN pressure/vacuum/water and starting test Test Start Time: 8:11 8:11 8:11 8:11 Initial Reading 3-2835 4.5579 4.6215 4.9319 Test End Time: 8:26 8:26 8:26 8:26 Final Reading(RF): 3.2836 4.5585 4.6217 4.9323 Test Duration: 15 NUN 15 MIN 15 MIN 15 MIN Change in Reading(RF-": .0001 .0006 .0002 .0004 Pass/Fail Threshold or Criteria: .002 .002 .002 Test Results d-pass 0 Fail Pass ..; 0 Fail Pass - ❑Fail- Pass ❑Fail Was sensor removed for testing? Yes 0 No ❑WA M Yes ❑No ❑NA dYes 6No DNA ffYes ❑No 0 NA Was sensor properly replaced and [/Yes DNo DNA JYes ❑No DNA WYes 0 No ❑NA Yes DNo DNA verified functional after testing? Comments—(include information on repairs made prior to testing, and recommended fol ow-up forfailed tests) If the entire depth of the UDC is not tested,specify how much was tested. If the answer to any of the questions indicated with an asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) SWRCB,January 2002 Page of 8. FILL RISER CONTAINMENT SUMP TESTING Facility is Not Equipped With Fill Riser Containment Sumps ❑ Fill Riser Containment Sumps are Prescnt,but were Not Tested 0- Test Method Developed By: I Sump Manufacturer ❑Industry Standard ❑Professional Engineer ❑Other(Specify) I Test Method Used: ❑Pressure ❑Vacuum &Aiydrostatic ❑Other(Specify) Test Equipment Used:MON TS-STS Equipment Resolution:0.0000 Fill Sump#1 Fill Sump#2 Fill Sump#3 Fill Sump#4 Sump Diameter. 42" 42" 42" 42" Sump Depth: 58" 5T' 54" 55" Height from Tank Top to Top of N/A N/A N/A N/A Highqt Piping Penetration: Height from Tank Top to Lowest N/A N/A N/A N/A Electrical Penetration: Condition of sump prior to 6"WATER DRY DRY DRY testing. Portion of Sump Tested 12" 12" IT, 12" Sump Material: FIBERGLASS FIBERGLASS FIBERGLASS FIBERGLASS Wait time between applying 10 MIN 10 MIN 10 MIN 10 MIN pressure/vacuum/water and starting test Test Start Time: 10:18 12:11 12:43 12:11 Initial Reading(R4): 4.8410 15189 4.0756 3.4420 Test End Time: 10:33 12-26 1:04 12:26 Final Reading(1kF): 4.8405 3.5185 4.0757 3.4417 Test Duration: 15 MIN 15 MIN 15 MIN 15 MIN Change in Reading(RF-P.4): .0005 .0004 .0001 .0003 Pass/Fail Threshold or Criteria: 002 .002 002 .002 ❑.Fail- Ef,-Pm , b*ail, Pass . IJ*Ail.. pisi yawl. Is there a sensor in the sump? ❑Yes No ❑Yes VNo ❑Yes No (I Yes No Does the sensor alarm when either product or water is ❑Yes ❑No dNA ❑Yes 11 No E(NA ❑Ycs ❑No U(NA OYes ONo R(NA detected? Was sensor removed for testing? 0 Yes ❑No 041A ❑Yes ❑No ENA 0 Yes ❑No ft 1 ❑Yes ❑No 9KA Was sensor properly replaced and ❑Yes ❑No C(NA ❑Yes ❑No 9/NA ❑Yes ❑No O/NA ❑Yes ❑No verified functional after testing9 I I Comments—(include information on repairs made pv,*to leabg and recommended follow-up for failed tests) SWRCB,January 2002 Page_of 9. SPHAJOVERFILL CONTAINMENT BOXES Facility is Not Equi ed With Spill/Overfill Containment Boxes ❑ Spill/Overfill Containment Boxes are Lr=t,but were Not Tested ❑ Test Method Developed By: ffSpill Bucket Manufacturer ❑Industry Standard ❑Professional Engineer ❑Other(Specify) Test Method Used. ❑Pressure ❑Vacuum 2rHydrostatic ❑Other(Specify) Test Equipment Used:- INCON TS-STS Equipment Resolution:0.0000 Split Box#V1 Spur Box#V2 SpiR Box W3 SpiR Box#V4 Bucket Diameter. 12" 12" 12" 12" Bucket Depth: 15" 15" 15" 15" Wait time between applying pressurelvacuum/water and 10 MIN 10 PAIN 10 MIN 10 MIN starting test Test Start Time: 1:27 1:27 2:28 2:28 Initial Reading(Ri): 5.9042 4.9882 2.3896 1.7887 Test End Time: 1:42 1:42 2:44 2:44 Final Reading(RF): 5.9042 4.9882 2.3892 1.7880 Test Duration: 15 NUN 15 NffN 15 MIN 15 MIN Change in Reading(RF-R): 0 0 .0004 -0007 Pass/Fail Threshold or -002 .002 .002 .002 Criteria: 4 .Test Result: ❑.Mf I Pass ` Fail Pass Fail Comments—(include information on repairs made prior to pqMn ollow-Vfarfafled tests) g, and recommendedf SWRCB,January 2002 Page_of 9. SPMUOVERFILL CONTAINMENT BOXES Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ Spill/Overfill Containment Boxes are Msent,but were Not Tested ❑ Test Method Developed By: 11 Spill Bucket Manufacturer ❑Industry Standard ❑Professional Engineer ❑Other(Specify) 4 Test Method Used- ❑Pressure ❑Vacuum WHydrostatic ❑Other(Specify) Test Equipment Used:INCON TS-STS Equipment Resolution:UNO fit.' °3. '� #1 Spin Box#2 . ....... Spill Box#3 spin Box Spin Box#4 Bucket Diameter. 12" 12" 12" 12" Bucket Depth: 15" 15" 15" 15" Wait time between applying pressure/vacuum/water and 10 MIN 10 MIN 10 N41N 10 MIN starting test: Test Start Time: 1:27 1:27 2:28 2:28 Initial Reading(Ri): 3.2708 3.3163 0.9097 2.3363 Test End Time-. 1:42 1.-42 2:44 2-44 Final Reading(RF). 32708 33158 0.9092 2.3358 Test Duration: 15 MIN 15 MIN 15 MIN 15 NEN Change in Reading(RF-Rj): 0 .0005 .0005 .0005 Pass/Fail Threshold or .002 .002 .002 .002 Criteria: Test ItQStilt Pass ;:O.Faff efpass 0. Vl6;iss:, C�1,Fail —(include information on repairs made prior to testin&and recommendedfollow-up for failed tests) FASTRIP 781 FASTRIP 781 4013 S H ST 4013 S H ST BAKERSFIELD CA BAKERSFIELD CA SUNSET CONST SUNSET CONST 1-800-984-6266 FASTRIP 781 1-800-984-6266 4013 03/01/2011 2:44 PM BAKER S H ST SFIELD CA BAKE R B 03/01/2011 11:15 AM SUNSET CONST SUMP LEAK TEST REPORT 1-800-984-6266 SUMP LEAK TEST REPORT SPILL3 03/01/2011 2:28 PM STP 2 TEST STARTED 2:28 PM SUMP LEAK TEST REPORT TEST STARTED 10:59 AM TEST STARTED 03/01/2011 TEST STARTED 03/01/2011 BEGIN LEVEL 0.9097 IN SPILL3 BEGIN LEVEL 5,4796 IN. END TIME 2:44 PM END TIME 11:14 AM END DATE 03/01/2011 TEST STARTED 2:12 PH END DATE 03/01/2011 END LEVEL 0,9092 IN TEST STARTEC► 03/01/2011 END LEVEL 5,4786 IN LEAK THRESHOLD 0,002 IN BEGIN LEVEL 0.9093 IN LEAK THRESHOLD 0.002 IN TEST RESULT PASSED END TIME 2:28 PM TEST RESULT PASSED END DATE 03/01/2011 USPILL3 END LEVEL 0.9096 IN LEAK THRESHOLD 0.002 IN STP 3 TEST RESULT PASSED TEST STARTED 2:28 PM TEST STARTED 10:59 AM TEST STARTED 03/01/2011 TEST STARTED 03/01/2011 BEGIN LEVEL 2.3896 IN VSPILL3 BEGIN LEVEL 6.6843 IN END TIME 2:44 PM END TIME. 11:14 AM END DATE 03/01/2011 TEST STARTED 2:12 PM END DATE 03/0.1/2011 END LEVEL _ 2.3$92 IN TEST STARTED 03/01/2011 END LEVEL 6,6833 IN LEAK THRESHOLD 0.002 IN LEAK THRESHOLD 0,002 IN i TEST RESULT pp BEGIN LEVEL 2,3893 IN END TIME 2:28 PM TEST RESULT PASSED END DATE 03/01/2011 SPILL4 END LEVEL 2,3895 IN LEAK THRESHOLD 0,002 IN FILL 2 TEST RESULT PASSED TEST STARTED 2:28 PM TEST STARTED 10:59 AM TEST STARTED 03/01/2011 TEST STARTED 03101/2011 BEGIN LEVEL 2,3363 IN SPILL4 BEGIN LEVEL 4.0727 IN END TIME 2:44 PM - END TIME 11:14 AM END DATE 03/01/2011 TEST STARTED 2:12 PH END.DATE 03/01/2011 END LEVEL 2,3358 IN TEST STARTED .03/01/2011 END LEVEL 4,0726 IN LEAK THRESHOLD 0.002 IN BEGIN LEVEL 2.3359-IN LEAK THRESHOLD 0.002 IN TEST RESULT PASSED END TIME 2:28 PM TEST RESULT PASSED END DATE 03/01/2011 USPILL4 END LEVEL 2.3361 IN STP 4 LEAK THRESHOLD 0.002 IN TEST RESULT PASSED TEST STARTED 2:28 PH .ST STARTED 10:59 AM TEST STARTED 03/01/2011 EST STARTED 03/01/2011 BEGIN LEVEL 1.7887 IN VSPILL4 °FGIN LEVEL 6.7300 IN END TIME 2:44 PM NO TIME 11:14 AM END DATE 03/01/2011 TEST STARTED 2:12 PM Q DATE 03/01/2011 END LEVEL 1.7880 IN TEST STARTED 03/01/2011 `1 LEVEL 6.7286 IN - LEAK THRESHOLD 0,002 IN BEGIN LEVEL 1,7885 IN THRESHOLD 0.002 IN TEST RESULT PASSED END TIME 2:28 PH RESULT PASSED END DATE 03/01/2011 END LPL 1.7887 IN LEAK THRESHOLD 0.002 IN TEST RESULT PASSED 03/01/2011 1:10 PM FASTRIP 781 4013 S H ST SUMP LEVEL REPORT BAKERSFIELD CA - SUNSET CONST 1-800-984-6266 SUMP SPILL1 3,273 IN SUMP VSPILLI 5.905 IN 03/01/2011 1:42 PM FASTRIP 781 SUMP SPILL2 3,318 IN i 4013 S H ST BAKERSFIELD CA SUMP VSPILL2 4,989 IN SUMP LEAK TEST REPORT ! SUNSET CONST FASTRIP 781 SPILLI 1-800-984-6266 4013 S H-ST - BAKERSFIELD CA TEST STARTED 1:27 PM 03/01/2011 12:47 PM SUNSET CONST TEST STARTED 03/01/2011 1-800-984-6266 BEGIN LEVEL 3.2708 IN SUMP LEAK TEST REPORT END TIME 1:42 PM 03/01/2011 1:26 PM END DATE 03/01/2011 TRANSI END LEVEL 3,2708 IN SUMP LEAK TEST REPORT LEAK THRESHOLD 0.002 IN TEST STARTED 12:32 PM TEST RESULT PASSED TEST STARTED 03/01/2011 SPILLI BEGIN LEVEL 5.3327 IN END TIME 12:47 PM TEST STARTED 1:10 PM VSPILLI END DATE 03/01/2011 TEST STARTED 03/01/2011 END LEVEL 5,3332 IN BEGIN LEVEL 3.2719 IN TEST STARTED 1:27 PM LEAK THRESHOLD 0.002 IN END TIME 1:25 PM TEST STARTED 03/01/2011 TEST RESULT PASSED END DATE 03/01/2011 BEGIN LEVEL 5.9042 IN END LEVEL 312708 IN END TIME 1,42 PM LEAK THRESHOLD 0,002 IN END DATE 03/01/2011 FILL 3 TEST RESULT PASSED END LEVEL 5.9042 IN LEAK THRESHOLD 0.002 IN TEST STARTED 12:32 PM TEST RESULT PASSED TEST STARTED 03/01/2011 VSPILLI BEGIN LEVEL 4,0877 IN END TIME 12:47 PM TEST STARTED 1:10 PM SPIN END DATE 03/01/2011 TEST STARTED 03/01/2011 END LEVEL 410880 IN BEGIN LEVEL 5.9046 IN TEST STARTED 1:27 PM LEAK THRESHOLD 0.002 IN END TIME 1:25 PM TEST STARTED 03/01/2011 TEST RESULT PASSED END DATE 03/01/2011 BEGIN LEVEL 3,3163 IN END LEVEL 5.9041 IN END TIME 1:42 PM LEAK THRESHOLD 0,002 IN END DATE 03/01/2011 TRANS2 TEST RESULT PASSED END LEVEL 3.3158 IN LEAK THRESHOLD 0.002 IN TEST STARTED 12:32 PM TEST RESULT PASSED TEST STARTED 03/01/2011 SPILL2 BEGIN LEVEL 4.3750 IN END TIME 12:47 PM TEST STARTED 1:10 PM VSPILL2 END DATE 03/01/2011 TEST STARTED 03/01/2011 END LEVEL 4.3744 IN BEGIN LEVEL 3,3172 IN TEST STARTED 1:27 PM LEAK THRESHOLD 0.002 IN END TIME 1:25 PM TEST STARTED 03/01/2011 TEST RESULT PASSED . END DATE 03/01/2011 BEGIN LEVEL 4.9882 IN END LEVEL 3.3162 IN END TIME 1:42 PM LEAK THRESHOLD 0.002 IN END DATE 03/01/2011 TEST RESULT PASSED END LEVEL 4.9882 IN - LEAK THRESHOLD 0.002 IN TEST RESULT PASSED VSPILL2 TEST STARTED 1:10 PM TEST STARTED 03/01/2011 BEGIN LEVEL 4.9887 IN - END TIME 1:25 PM END DATE 03101/2011 END LEVEL 4.9883 IN rmaimir iii 4013 S H ST SUNbL I l.UNS 1 BAKERSFIELD CA 1-800-984-6266 SUNSET CONST 03/01/2011 11:49 AM 1-800-984-6266 03/01/2011 12:27 PM SUMP LEVEL REPORT FASTRIP 781 SUMP LEAK TEST REPORT 4013 S H ST SUMP STP 1 5,537 IN BAKERSFIELD CA STP 1 SUMP.FILL 3 3,314 IN SUNSET CONST SUMP FILL 2.._ 3;517_IN- .. 1-800-984-6266 TEST STARTED 12:11 PM SUMP FILL 4 3,442 IN TEST STARTED 03/01/2011 03/01/2011 1:04 PM BEGIN LEVEL 5,6405 IN FASTRIP 781 END TIME 12:26 PM 4013 S H ST SUMP LEAK TEST REPORT END DATE 03/01/2011 BAKERSFIELD CA END LEVEL x.'403 IN SUNSET CONST TRANSI 1-800-984-6266 LEAK THRESHOLD o.002 IN TEST STARTED 12:49 PM TEST RESULT PASSED 03/01/2011 12:08 PM TEST STARTED 03/01/2011 BEGIN LEVEL 4, 1601 IN FILL 3 SUMP LEAK TEST REPORT END TIME 1:04 PM END DATE 03/01/2011 TEST STARTED 12:11 PM STP 1 END LEVEL 4.1601 IN TEST STARTED 03/'01/2011 LEAN THRESHOLD 0,002 IN BEGIN LEVEL 13119 IN TEST STARTED 11:52 AM TEST RESULT PASSED END TIME 12:26 PM TEST STARTED 03/01/2011 END DATE 03/01/2011 BEGIN LEVEL 5,6401 IN END LEVEL 3.3099 IN END TIME 12:07 PM FILL 3 LEAK THRESHOLD 0,-002 IN END DATE 03101/2011 TEST RESULT FAILED END LEVEL 5,6404 IN TEST STARTED 12:49 PM LEAK THRESHOLD 0,002 IN TEST STARTED 03/01/2011 TEST RESULT PASSED BEGIN LEVEL 4,0756 IN END TIME 1:04 PM Fill 2 END DATE . 03/01/2011 TEST STARTED 12:11 PM FILL 3 END LEVEL 4,0757 IN TEST STARTED 03/01/2011 LEAK THRESHOLD 0,002 IN BEGIN LEVEL 3.5189 IN TEST STARTED 11:52 AM TEST RESULT PASSED END TIME 12:26 PM TEST STARTED 03/01/2011 END DATE 03/01/2011 BEGIN LEVEL 3,3133 IN END LEVEL 3,5185 IN END TIME 12:07 PM TRANS2 LEAK THRESHOLD 0,002 IN END DATE 03/01/2011 TEST RESULT PASSED END LEVEL 3,3131 _IN TEST STARTED 12:49 PM LEAK.THRESHOLD 0,002 IN TEST STARTED 03/01/2011 TEST RESULT PASSED BEGIN LEVEL 4,0597 IN END TIME 1:04 PM FILL 4 END DATE 03/01/2011 TEST STARTED 12:11 PM FILL 2 END LEVEL 4,0594 IN TEST STARTED 03/0112011 LEAK THRESHOLD 0,002 IN BEGIN LEVEL 3,4420 IN TEST STARTED 11:52 AM TEST RESULT PASSED END TIME 12:25 PM TEST STARTED -03/01/2011 END DATE 03/01/2011 BEGIN LEVEL 3,5184 IN END LEVEL 3,4417 IN END TIME 12:07 PM LEAK THRESHOLD 0,002 IN END DATE 03/01/2011 TEST RESULT PASSED END LEVEL 3,5189 IN - LEAK THRESHOLD 0,002 IN TEST RESULT PASSED FILL 4 TEST STARTED . 11:52 AM TEST STARTED 03/01/2011 BEGIN LEVEL 3,4419 IN rH�iK1r ttf7 FASTRIP 781 FASTRIP 781 4013SHST 4013SHST 4013SHST BAKERSFIELD CA BAKERSFIELD CA IiAKERSFIELD CA SUNSET CONST SUNSET CONST SUNSET CONST 1-800-984-6266 1-800-984-6266 1-80D-984-6266 03/0112011 8143 AM 03/01/2011 $:2fi AM 03/01/2011 10:33 AM SUMP LEAK TEST REPORT SUMP LEAK TEST REPORT SUMP LEAK TEST REPORT UDC 1-2 UDC 1-2 STP 2 TEST STARTED 8:28 AM TEST STARTED 8:11 AM TEST STARTED 10:18 AM TEST STARTED 0310112011 TEST STARTED 03/01/2011 TEST STARTED 03/01/2011 BEGIN LEVEL 3,2836 IN BEGIN LEVEL 3,2835 IN BEGIN LEVEL 5,4795 IN END TIME 8:43 AM END TIME 8:26 AM END TIME 10:33 AM END DATE 03/01/2011 END DATE 03/01/2011 END DATE 03/01/2011 END LEVEL 3,2834 IN END LEVEL 3,2836 IN END LEVEL 5,4796 IN LEAK THRESHOLD 0,002 IN LEAH THRESHOLD 0,002 IN LEAK THRESHOLD 0,002 IN TEST RESULT PASSED TEST RESULT PASSED TEST RESULT PASSED UDC 3-4 UDC 3-4 STP 3 TEST STARTED 8:28 AM TEST STARTED 8:11 AM TEST STARTED 03/01/2011 TEST STARTED 03/01/2011 TEST STARTED 10:18 AM BEGIN LEVEL 4,5585 IN BEGIN LEVEL 4,5579 IN TEST STARTED 03/01(2011 BEGIN LEVEL 6,6855 IN END TIME 8:43 AM END TIME 8:26 AM END TIME 10:33 AM END DATE 03/01/2011 END DATE 03/01/2011 END DATE 03/01/2011 END LEVEL 4,5585 IN END LEVEL 4,5585 IN END LEVEL 6,6854 IN LEAK THRESHOLD 0.002 IN LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0,002 IN TEST RESULT PASSED TEST RESULT PASSED TEST RESULT PASSED UDC 5-6 UDC 5-6 FILL 1 TEST STARTED 8:28 AM TEST STARTED 8:11 AM TEST STARTED 03/01/2011 TEST STARTED 03/01/2011 TEST STARTED 10:18/2 011 AM TEST STARTED 03/01/2 BEGIN LEVEL 4,6217 IN BEGIN LEVEL 4,6215 IN BEGIN LEVEL 4,8410 IN END TIME 8:43 AM END TIME 8:26 AM END TIME 10:33 AM END DATE 03/01/2011 END DATE 03/01/2011 END DATE 03/01/2011 END LEVEL 4.6216 IN END LEVEL 4,6217 IN END LEVEL 4,8405 IN LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0.002 IN TEST RESULT PASSED TEST RESULT PASSED TEST RESULT PASSED UDC 7-8 UDC 7-8 STP 4 TEST STARTED 8:28 AM TEST STARTED 8:11 AM TEST STARTED 10:18 AM TEST STARTED 03/01/2011 TEST STARTED 03/01/2011 TEST STARTED 03/01/2011 BEGIN LEVEL 4,9323 IN BEGIN LEVEL 4,9319 IN BEGIN LEVEL 6,7314 IN END TIME 8:43 AM END TIME 8:26 AM END TIME 10:33 AM END DATE 03/01/2011 END DATE 03/01/2011 END DATE , 03/01/2011 END LEVEL 4,9323 IN END LEVEL 4,9323 IPJ END LEVEL 6,7311 IP1 LEAK THRESHOLD 0.002 IN - LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0,002 IN TEST RESULT PASSED TEST RESULT PASSED -.--------."-- " _ __ TEST RESULT PASSED FASTRIP 781 4013SHST BAKERSFIELD CA SUNSET CONST 1-800-984-6266 03/01/2011 9:36 AM SUMP LEAK TEST REPORT TRANSI TEST STARTED 9:20 AM TEST STARTED 03/01/2011 BEGIN LEVEL 18832 IN END TIME 1 9:36 AM END DATE 03/01/2011' END-LEVEL 3,7334 IN FASTRIP 781 LEAK:THRESHOLD 0,002 IN 4013 S H ST TEST RESULT FAILED BAKERSFIELD CA SUNSET CONST STP 1 1-800-984-6266 03/01/2011 TEST STARTED 9:20 AM 10:13 All TEST STARTED 03/01/2011 BEGIN LEVEL 4,1630 IN SUMP LEVEL REPORT END TIME 9:36 AM END DATE 03/01/2011 SUMP STP 2 040 LEVEL 4,0681 IN 5,479 IN SUMP STP 3 6,47 IN LEAK THRESHOLD 0,002 IN SW FILL i TEST RESULT FAILED 4.841. IM STP q -6, 731 IN - _ FILL 1 TEST STARTED 9:20 AM TEST STARTED 03/01/2011 BEGIN LEVEL 3,3061 IN END TIME . 9:36 AM END DATE 03/01/2011 END LEVEL 3.3057 IN LEAK THRESHOLD 0.002 IN TEST RESULT PASSED TRANS2 TEST STARTED 9:20 AM TEST STARTED 03/01/2011 BEGIN LEVEL 5,8813 IN END TIME 9:36 AM END DATE 03/01/2011 _ END LEVEL 5.8167 IN LEAK THRESHOLD 0,002 IN TEST RESULT FAILED SWRCB,January 2002 Page of Secondary Containment Testing Report Form This form is intended for use by contractors performing periodic testing of UST secondary containment systems. Use the appropriate pages of thisform to report results for all components tested The completed form,written test procedures, and printouts from tests(f applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: Fastrip#721 Date of Testing: 2/28/11 Facility Address: 4013 South H St.Bakersfield,CA Facility Contact: Jamieson Hill Phone: 1-661-393-7000 Date Local Agency Was Notified of Testing: February 23,2011 Name of Local Agency Inspector(i(present during testing): 2. TESTING CONTRACTOR INFORMATION Company Name: Sunset Mechanical Technician Condu ' g Test: Scott Olinger Credentials: 14 CSLB Licensed Contractor D SWRCB Licensed Tank Tester License Type. C-36 C-10 License Number. 589517 Manufacturer Training Manufacturer Component(s) Date Training Expires Incon TS-STS Inspection Equipment 1/18/13 Veeder Root Monitoring System 1/15/12 ICC Cal UST Service Tech 1/18/13 3. SUMMARY OF TEST RESULTS Component Pass Fail Not Repairs Component Pass Fail Not Repairs Tested Made Tested Made UDC 9& 10 ❑ El PIPING RUN#1 El ❑ ❑ UDC 11 & 12 ❑ ❑ ❑ PIPING RUN#2 ❑ ❑ ❑ UDC 13 & 14 p' ❑ ❑ ❑ PIPING RUN#3 ❑ ❑ ❑ UDC 15 & 16 [d ❑ ❑ ❑ ANN SPACE#1 ❑ ❑ ❑ UDC 17& 18 ❑ ❑ ❑ ANN SPACE#2 ❑ ❑ ❑ UDC 19&20 ❑ ❑ ❑ ANN SPACE#3 Ef ❑ ❑ ❑ STP #1 ❑ ❑ ❑ SPILL#1 ❑ ❑ ❑ STP#2 ❑ ❑ ❑ SPILL#2 ❑ ❑ ❑ STP#3 if j ❑ ❑ ❑ SPILL#3 ❑ ❑ ❑ FILL#1 ❑ ❑ V SPILL#1 ❑ ❑ ❑ FILL#2 ❑ ❑ V SPILL#2 ❑ ❑ FILL#3 p ❑ V SPILL#3 Pf ❑ ❑ ❑ If hydrostatic testing was performed,describe what was done with the water after completion of tests: CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING To the best of my knowledge,the fa tated In this document are accurate and in full compliance with legal requirements Technician's Signature: . Date: 2/28/11 SWRCB,January 2002 Page of 4. TANK ANNULAR TESTING Test Method Developed By: 11 Tank Manufacturer ❑Industry Standard ❑Professional Engineer ❑Other(Spec) Test Method Used: ❑Pressure i7vacuum, ❑Hydrostatic ❑Other(Spec) Test Equipment Used:4"GEL FILLED GAUGE W/CERTS Equipment Resolution:0-30 n0l z Tank#1 Tank#2 Tank#3 Tank# Is Tank Exempt From Testing?' ❑Yes No ❑Yes No ❑Yes o ❑Yes ❑No Tank Capacity: 12,000 12,000 12,000 Tank Material: GLASS/STEEL GLASS/STEEL GLASS/STEEL Tank Manufacturer: MODERN MODERN MODERN Product Stored: UNL PREM DIESEL Wait time between applying pressure/vacuum/water and 10 MIN 10 MIN 10 MIN starting test: Test Start Time: 10:45 10:45 12:00 Initial Reading(RO: 10 HG 10 HG 10 HG Test End Time: 11:45 11:45 1:00 Final Reading(RF): 10 HG 10 HG 10 HG Test Duration: I HR l HR 1 HR Change in Reading(RF-RO: 0 0 0 Pass/Fail Threshold or Criteria: 0 0 0 Test Result: Pass ..❑Fail - Pass 0 Fail 'Pass ,,.:d-Fail :0 Pass D Fail: Was sensor removed for testing? Yes ❑No ❑NA 4Yes ❑No ❑NA es ❑No ❑NA ❑Yes ❑No ❑NA Was sensor properly replaced and Yes ❑No ❑NA Yes ❑No ❑NA Yes ❑No ❑NA ❑Yes ❑No ❑NA verified functional after testing? Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) ` Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment testing. {California Code of Regulations,Title 23,Section 2637(a)(6)) SWRCB,January 2002 Page of 5. SECONDARY PIPE TESTING Test Method Developed By: Piping Manufacturer ❑Industry Standard ❑Professional Engineer ❑Other(Spec) Test Method Used: ssure ❑Vacuum ❑Hydrostatic ❑Other.(Specify) Test Equipment Used:4"GEL FILLED GAUGE W/CERTS Equipment Resolution: 0-15 ` Piping Run#1 Piping Run#2 Piping Run#3 Piping Run# Piping Material: 3"FIBERGLASS 3"FIBERGLASS 3"FIBERGLASS Piping Manufacturer: AO SMITH AO SMITH AO SMITH Piping Diameter. 3" 3" 3" Length of Piping Run: 150' 150' 150' Product Stored: UNL PREM DIESEL Method and location of TEST BOOT AT STP TEST BOOT AT STP TEST BOOT AT piping-run isolation: &UDC &UDC STP&UDC Wait time between applying pressure/vacuum/water and 15 MIN 15 MIN 15 MIN starting test: Test Start Time: 9:45 9:45 9:45 Initial Reading(Rq): 5.1 5.2 5.2 Test End Time: 10:45 10:45 10:45 Final Reading(RF): 5.1 5.2 5.2 Test Duration: 1 HR 1 HR i HR Change in Reading(RF-RO: 0 0 0 Pass/Fail Threshold or 0 0 0 Criteria: Test Resalt. Pass D Fail P l7 ass ; Fad Pass',_. ❑.Fail ❑ Pass Fad Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) SWRCB,January 2002 Page of 6. PIPING SUMP TESTING Test Method Developed By: Sump Manufacturer ❑Industry Standard ❑Professional Engineer ❑Other(Spec) Test Method Used: ❑Pressure ❑Vacuum ydrostatic ❑Other(Spec) Test Equipment Used:INCON TS-STS Equipment Resolution:0.0000 ., STP#1 STP#2 STP#3 Sump Diameter. 48" 48" 48" Sump Depth: 52" 49" 48" Sump Material: FIBERGLASS FIBERGLASS FIBERGLASS Height from Tank Top to Top of 16" 16" 16" Highest Piping Penetration: Height from Tank Top to Lowest 14" 14" 14" Electrical Penetration: Condition of sump prior to testing: DRY DRY DRY Portion of Sump Tested' 18" 18" 18" Does turbine shut down when sump sensor detects liquid(both i/Yes ❑No ❑NA &(Yes ❑No ❑NA &(Yes ❑No ❑NA ❑Yes ❑No ❑NA product and water)?� Turbine shutdown response time 20 SEC 20 SEC 20 SEC Is system programmed for fail-safe 9/Yes ❑No ❑NA 0&es ❑No ❑NA I(Yes ❑No ❑NA ❑Yes ❑No ❑NA shutdown?* Was fail-safe verified to be i(Yes ❑No ❑NA [(Yes ❑No ❑NA C(Yes ❑No ❑NA ❑Yes ❑No ❑NA op erational?* Wait time between applying pressure/vacuum/water and starting 15 MIN 15 MIN 15 MIN test: Test Start Time: 12:24 12:07 12:07 Initial Reading(R,): 5.6494 6.1177 5.9627 Test End Time: 12:39 12:22 12:22 Final Reading(RF): 5.6478 6.1176 5.9620 Test Duration: 15 MIN 15 MIN 15 MIN Change in Reading(RF-114): .0016 .0001 .0007 Pass/Fail Threshold or Criteria: .002 .002 .002 "Test Result Pass O Fail; C�Pass ❑Fail CPass q Fall ❑ Pass, O F$il Was sensor removed for testing? Yes ❑No ❑NA /Yes ❑No ❑NA Y ❑No 13 NA ❑Yes ❑No ❑NA Was sensor properly replaced and 5/Yes ❑No ❑NA (Y Yes ❑No ❑NA Yes ❑No ❑NA ❑Yes ❑No ❑NA verified functional after testing? Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) 'If the entire depth of the sump is not tested,specify how much was tested. If the answer to M of the questions indicated with an asterisk(*)is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160) SWRCB,January 2002 Page of 7. ER DISPENSER CONTAINMENT QTQ TESTING Test Method Developed By: 96 UDC Manufacturer ❑Industry Standard ❑Professional Engineer ❑Other(Specify) Test Method Used: ❑Pressure ❑Vacuum Hydrostatic ❑Other(Specify) Test Equipment Used: INCON TS-STS Equipment Resolution: 0.0000 UDC#17-18 UDC#19-20 UDC# UDC# UDC Manufacturer. ENVIRON ENVIRON UDC Material: PLASTIC PLASTIC UDC Depth: 30" 30" Height from UDC Bottom to Top 10" 10" of Highest Piping Penetration: Height from UDC Bottom to 5" 5" Lowest Electrical Penetration: Condition of UDC prior to DRY DRY testing: Portion of UDC Tested 12" 12" Does turbine shutdown when / UDC sensor detects liquid(both pJ Yes ❑No ❑NA l Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA product and water)?# Turbine shutdown response time 20 SEC 20 SEC Is system programmed for fail- dYes ❑No ❑NA es ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA safe shutdown?* Was fail-safe verified to be O/yes ❑No ❑NA As ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA operational?* Wait time between applying 10 MIN 10 MIN pressure/vacuum/water and starting test Test Start Time: 11:31 10:13 Initial Reading 4.3998 4.5102 Test End Time: 11:46 10:28 Final Reading 4.3988 4.5086 Test Duration: 15 MIN 15 MIN Change in Reading(Rr N: .0010 .0016 Pass/Fail Threshold or Criteria: .002 .002 TestiResidt- Pass -`.O Fail Pass .'.l7 Fail: !7 Pass, :l7 Fail ❑:Pass'':❑Fail ;:. Was sensor removed md for testing? Yes ❑No ❑NA Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA Was sensor properly replaced and yes ❑No ❑NA Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA verified functional after testis ? Comments—(include information on repairs made prior to testing; and recommended follow-rip for failed tests) `If the entire depth of the UDC is not tested,specify how much was tested. If the answer to any of the questions indicated with an asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) SWRCB,January 2002 Page of 7. UNDER-DISPENSER CONTAINMENT QT9 TESTING Test Method Developed By: 211UDC Manufacturer ❑Industry Standard ❑Professional Engineer ❑Other(Specify) Test Method Used: ❑Pressure ❑Vacuum Aydrostatic ❑Other(Specify) Test Equipment Used: INCON TS-STS Equipment Resolution: 0.0000 �_UDC#9-10 UDC#11-12 UDC#13-14 UDC#15-16 UDC Manufacturer. ENVIRON ENVIRON ENVIRON ENVIRON UDC Material: PLASTIC PLASTIC PLASTIC PLASTIC UDC the 30" 30" 30" 30" Height from UDC Bottom to Top 10" 10" 10" 10" of Highest Piping Penetration: Height from UDC Bottom to 5" 5" 5" 5" Lowest Electrical Penetration: Condition of UDC prior to DRY DRY DRY DRY testing: Portion of UDC Tested 12" 12" 12" 12" Does turbine shut down when / UDC sensor detects liquid(both 2(Yes ❑No ❑NA I Yes ❑No ❑NA Y'Yes ❑No ❑NA WI Yes ❑No ❑NA product and water)?* Turbine shutdown response time 20 SEC 20 SEC 20 SEC 20 SEC Is system programmed for fail- p'Yes ❑No ❑NA safe shutdown?* Yes ❑No DNA les 0 N DNA Yes 0 N DNA Was fail-safe verified to be dYes ❑No ❑NA C//Yes ❑No ❑NA es ❑No ❑NA es ❑No ❑NA operational?* Wait time between applying 15 MIN 15 MIN 15 MIN 15 MIN pressure/vacuum/water and starting test Test Start Time: 10:13 11:31 10:44 10:44 Initial Reading r): 5.5703 4.5602 3.3693 2.9415 Test End Time: 10:28 11:46 10:59 10:59 Final Reading(Rr): 5.5685 4.5592 3.3691 2.9412 Test Duration: 15 MIN 15 MIN 15 MIN 15 MIN Change in Reading R1): .0018 .0010 .0002 .0003 Pass/Fail Threshold or Criteria: .002 .002 .002 .002 Test.Resnit- f:Pass . ❑Fail Pass:" O`Fail- Pass . ❑'Fail Psss ;0`Fad Was sensor removed for testing? VYes ❑No ❑NA &Yes ❑No ❑NA Vfes ❑No ❑NA Yes ❑No ❑NA Was sensor properly replaced and yes ❑No ❑NA R(Yes ❑No ❑NA es ❑No ❑NA verified functional after te ? Yes ❑No ❑NA stin Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) 'If the entire depth of the UDC is not tested,specify how much was tested. If the answer to M of the questions indicated with an asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) SWRCB,January 2002 Page of 8. FILL RISER CONTAINMENT SUMP TESTING Facility is Not Equipped With Fill Riser Containment Sumps ❑ Fill Riser Containment Sumps are Pres nt,but were Not Tested ❑ Test Method Developed By: Sump Manufacturer ❑Industry Standard ❑Professional Engineer ❑Other(Specify) Test Method Used: ❑Pressure ❑Vacuum Hydrostatic ❑Other(Spec) Test Equipment Used:INCON TS-STS Equipment Resolution:0.0000 Fill Sump#1 Fill Sump#2 Fill Sump#3 Fill Sume#4 Sump Diameter. 42" 42" 42" Sump Depth: 48" 49" 48" Height from Tank Top to Top of N/A N/A N/A Highest Piping Penetration: Height from Tank Top to Lowest N/A N/A N/A Electrical Penetration: Condition of sump prior to DRY DRY DRY testing: Portion of Sump Tested 12" 12" 12" Sump Material: FIBERGLASS FIBERGLASS FIBERGLASS Wait time between applying 10 MIN 10 MIN 10 MIN pressure/vacuum/water and starting test: Test Start Time: 1:59 1:59 1:59 Initial Reading O: 1.3911 2.6514 5.8212 Test End Time: 2:14 2:14 2:14 Final Reading RF): 1.3919 2.6531 5.8197 Test Duration: 15 MIN 15 MIN 15 MIN Change in Reading(RF-R): .008 .0017 .0015 Pass/Fail Threshold or Criteria: .002 .002 .002 ''Te§t Result ,Pas s": ,0I Fail >. .;:Pass _-❑_Fail `Pass :Fail ❑:.Pass Is there a sensor in the sump? ❑Yes ItNo ❑Yes No ❑Yes No ❑Yes ❑No Does the sensor alarm when /� 1W NA either product or water is ❑Yes ❑No �7 NA ❑Yes ❑No fl NA ❑Yes ❑No P]NA ❑Yes ❑No ❑NA detected? Was sensor removed for testing? ❑Yes ❑No NA ❑Yes ❑No NA ❑Yes ❑No tAo- Yes ❑No ❑NA Was sensor properly replaced and ❑yes ❑No verified functional after testis ? NA ❑Yes ❑No ❑Yes ❑No Yes ❑No 0 N Comments—(include information on repairs made prior to testing: and recommended follow-up for failed tests) ALL FILL SUMPS WERE REGLASSED AND RETESTED ON 34-11. SWRCB,January 2002 Page of 9. SPILIJOVERFILL CONTAIIKMENT BOXES Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ Spill/Overfill Containment Boxes are Present,but were Not Tested ❑ Test Method Developed By: Spill Bucket Manufacturer ❑Industry Standard ❑Professional Engineer ❑Other(Spec) Ic Test Method Used: ❑Pressure ❑Vacuum Hydrostatic ❑Other(Spec) Test Equipment Used:INCON TS-STS Equipment Resolution:0.0000 Spill Box#1 Spill Box#2 Spill Boa#3 Spill Bog# Bucket Diameter: 12" 12" 12" Bucket Depth: 12" 12" 12" Wait time between applying pressure/vacuum/water and 10 MIN 10 MIN 10 MIN startin 9 test: Test Start Time: 2:14 2:56 2:14 Initial Reading(RT): 4.2334 3.2804 5.7255 Test End Time: 2:29 3:11 2:29 Final Reading(RF): 4.2327 32799 5.7248 Test Duration: 15 MIN 15 MIN 15 MIN Change in Reading(RF-&): .0007 .0005 .0007 Pass/Fail Threshold or .002 .002 .002 Criteria: Test Result• Pass ❑.Fail Pass, 12Pass;:' ❑Fail ❑ Fass` q`Earl Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) SWRCB,January 2002 Page of 9. SPILL/OVERFILL CONTAWWNT BOXES Facility is Not E ui d With Spill/Overfill Containment Boxes ❑ Spill/Overfill Containment Boxes are Present,but were Not Tested ❑ Test Method Developed By: Rf Spill Bucket Manufacturer ❑Industry Standard ❑Professional Engineer ❑Other(Spec) Test Method Used: ❑Pressure ❑Vacuum Hydrostatic ❑Other(Spec) Test Equipment Used:INCON TS-STS Equipment Resolution:0.0000 T:: z 'K Spill Box#Vl Spill Box#V2 Spill Boa#V3 w Spill Boa# Bucket Diameter: 12" 12" 12" Bucket Depth: 12" 12" 12" Wait time between applying pressure/vacuum/water and 10 MIN 10 MIN 10 MIN starting test: Test Start Time: 2:14 1:59 2:14 Initial Reading 4.2400 4.6575 4.9048 Test End Time: 2:29 2:14 2:29 Final Reading(RF): 4.2393 4.6576 4.9039 Test Duration: 15 MIN 15 MIN 15 MIN Change in Reading(RF-R): .0007 .0001 .0009 Pass/Fail Threshold or 002 .002 .002 Criteria: Test Result::. Pass; ❑Fail Pass ❑Fail _ Pass .` ❑Fail O';Pass,, ❑Fait Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) FASTRIP 721 FASTRIP 721 4013 SO H ST 4013 SO H ST BAKERSFIELD CA BAKERSFIELD CA . SUNSET CONST SUNSET CONST 1-800-984-6266 FASTRIP 721 1-800-984-6266 4013 SO H-ST 03/04/2011 2:14 PM BAKERSFIELD CA 03/04/2011 2:30 PM SUNSET CONST SUMP LEAK TEST REPORT SUMP LEAK TEST REPORT 1-800-984 76266 FILL 1 FILL 1 02/28/2011 3:11 PM TEST STARTED 1:59 PM TEST STARTED 2:15 PM SUMP LEAK TEST REPORT TEST STARTED 03/04/2011 TEST STARTED 03/04/2011 BEGIN LEVEL 1.3911 IN BEGIN LEVEL 1.3919 IN SPILL 2 END TIME 2:14 PM END TIME 2:30 PM END DATE 03/04/2011 ND DATE 03/04/2011 TEST STARTED 2:56 PM END LEVEL 1.3919 IN END LEVEL 1,3923 IN TEST.STARTED 02/28/2011 LEAK THRESHOLD 0.002 IN LEAK THRESHOLD 0.002 IN BEGIN LEVEL 3.2804 IN TEST RESULT PASSED TEST RESULT PASSED END TIME 3:11 PM END DATE 02/28/2011 END LEVEL 3,2799 IN FILL 2 FILL 2 LEAK THRESHOLD 0.002 IN TEST RESULT PASSED TEST STARTED 1:59 PM TEST STARTED 2:15 PH TEST STARTED 03/04/2011 TEST STARTED 03/04/2011 BEGIN LEVEL 2,6514 IN BEGIN LEVEL 2,6531 IN END TIME 2:14 PM END TIME 2:30 PM END DATE 03/04/2011 END DATE 03/04/2011 END LEVEL 2.6531 IN END LEVEL 2.6537 IN LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0.002 IN TEST RESULT PASSED, TEST RESULT PASSED FILL 3 FASTRIP 721 FILL 3 4013 SO H ST TEST STARTED 1:59 PM TEST STARTED 2:15 PM BAKERSFIELD CA TEST STARTED 03/04/2011 TEST STARTED 03/04/2011 SUNSET CONST BEGIN LEVEL 5.8212 IN 1-800-984-6266 - END TIME 2:14 PM BEGIN LEVEL 5.8160 IN END DATE 03/04/2011 ENO TIME 2:30 PM 02/28/2011 3:30 PM END DATE 03/04/2011 END LEVEL 5.8197 IN END LEVEL 5.8007 IN SUMP LEAK TEST-REPORT LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0.002 IN TEST RESULT PASSED TEST RESULT FAILED SPILL 2 TEST STARTED 3:14 PM USPILL2 VSPILL2 TEST STARTED 02/28/2011 TEST STARTED 1:59 PM BEGIN LEVEL 3,2799 IN TEST STARTED 03/04/2011 TEST STARTED 2:15 PM END TIME 3:29 PM BEGIN LEVEL 4.6575 IN TEST STARTED 03/04/2011 END DATE 02/28/2011 END TIME 2:14 PM BEGIN LEVEL 4.6577 IN END LEVEL 3.2808 IP! END TIME 2:30 PM LEAK THRESHOLD 0,002 IN END DATE 03/04/2011 END DATE 03/04/2011 TEST RESULT PASSED END LEVEL 4.6576 IN END LEVEL 4.6577 IN LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0,002 IN TEST RESULT PASSED TEST RESULT PASSED -` FASTRIP 721 FASTRIP 721 FASTRIP 721 4013 SO H ST 013 SO H ST 4013 SO H ST 4 4013S O14 CA BAKERSFIELD CA BAKERSFIELD CA ST CONST SUNSET CONST SUNSET CONST S 1UNSET 84-6266 1-800-984—m.. 1400-984-6266 02/28/2011 2:04 PM 02/28/2011 2:30 PM 02/28/2011 2:46 PM SUMP LEAK TEST REPORT SUMP LEAK TEST REPORT SUMP LEAK TEST REPORT S•P 1 SPILL 1 SPILL 1 1:49 PM TEST STARTED 2:14 PM TEST STARTED 2:30 PM TEST STARTED TEST STARTED 02/28/2011 TEST STARTED 02/28/2011 TEST STARTED 02/28/2011 BEGIN LEVEL 4.2334 IN BEGIN LEVEL BEGIN LEVEL 4,2318 IN 4 2:04 PM END TIME 2:29 PM END TIME 2:45 PM END TIME END DATE 02!28/2411 END DATE 02/28/2011 END DATE 02/28/2011 END LEVEL 4,8880 IN END LEVEL 4,2327 IN END LEVEL 4.2318 IN THRESHOLD .8890 IN LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0,002 IN LEAK TEST RESULT PASSED T TEST RESULT PASSED TES RESULT PASSED FILL 1 VSPILLI VSPILLI TEST STARTED 1:49 PM TEST STARTED 2:14 PM TEST STARTED 2:30 PM TEST STARTED 02/28/2011 TEST STARTED 02/28/2011 TEST STARTED 02/28/2011 2,7452 IN BEGIN LEVEL 4,2400 IN BEGIN LEVEL 4.2378 IN BEGIN LEVEL 2.04 PM END TIME 2:29 PM END TIME 2:45 PM DATE 2 pdD. END DATE 02/28/ 011 END DATE 02/28/2011 END DATE 02!28/2011 END LEVEL 2.6544 IN END LEVEL 4,23,93 IN END LEVEL 4.2373 IN LEAK THRESHOLD 0.002 IN LEAK THRESHOLD 0.002 IN LEAK THRESHOLD 0,002 IN E TEST RESULT PASSED TEST RESULT PASSED TEST RESULT FAILED FILL 2 SPILL3 SPILL3 TEST STARTED 1:49 PM TEST STARTED 2:14 PM TEST STARTED 2:30 PM TEST STARTED 02/28/2011 TEST STARTED 02/28/2011 TEST STARTED 02/28/2011 BEGIN LEVEL 4,2253 IN BEGIN LEVEL 5.7255 IN BEGIN LEVEL 5,7248 IN 2:04 PM END TIME 2:29 PM END TIME 2:45 PM END TIME END DATE 02/28/2011 END DATE 02/28/2011 END DATE. 02/28/2011 END LEVEL 5,7248 IN END LEVEL 5,7246 IN END LEVEL 4.1995 IN LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0.002 IN LEAK THRESHOLD 0,002" D TEST RESULT PASSED TEST RESULT TEST RESULT PASSED FILL 3 VSPILL3 VSPILL3 TEST STARTED 1:49 PM TEST STARTED 2:14 PM TEST STARTED 2:30 PM TEST STARTED 02/28/2011 TEST STARTED 02/28/2011 TEST STARTED 02/28!2011 BEGIN LEVEL 4.9048 IN BEGIN LEVEL 3,8526 IN 2.29 PH END TIME BEGIN LEVEL 4,9045 IN 2:04 PM END TIME 2:45 PM END TIME 1 END DATE 02/28/2011 END DATE 02/28/2011 END DATE 02/281201 3,7302 END LEVEL 4,9039 IN END LEVEL 4,9045 IN I1 END LEVEL LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0,0.02 IN TEST RESULT FAILED TEST RESULT PASSED TEST RESULT PASSED FASTRIP 721 4013 SO H ST BAKERSFIELD CA FASTRIP 721 SUNSET CONST 4013 SO H ST 1-800-984-6266 BAKERSFIELD CA FASTRIP 721 SUNSET CONST 4013 SO H ST 02/28/2011 12:22 PM 1-800-984-6266 BAKERSFIELD CA 9 WSET CONST SUMP LEAK TEST REPORT 02/28/2011 12:39 PM 1-800-984-6266 UDC1718 SUMP LEAK TEST REPORT 02/28/2011 11:46 AM TEST STARTED 12:07 PM UDC1718 SUMP LEAK TEST REPORT TEST STARTED 02/28/2011 BEGIN LEVEL 4,3983 IN TEST STARTED 12:24 PM UDC1718 END TIME 12:22 PM TEST STARTED 02/28/2011 END DATE 02/28/2011 BEGIN LEVEL 1.7483 IN TEST STARTED 11:31 AM END LEVEL 4,3982 IN END TIME 12:39 PM TEST STARTED 02/28/2011 LEAK THRESHOLD 0,002 IN END DATE 02/28/2011 BEGIN LEVEL 4,3998 IN TEST RESULT PASSED END LEVEL -0,2185 IN END TIME 11:46 AM LEAK THRESHOLD 0,002 IN END DATE 02/28/2011 TEST RESULT FAILED END LEVEL 4.3988 IN STP 1 LEAK THRESHOLD 0,002 IN TEST RESULT PASSED TEST STARTED 12:07 PM STP 1 TEST STARTED 02/28/2011 BEGIN LEVEL 5.6566 IN TEST STARTED 12:24 PM UDC1112 END TIME 12:22 PM TEST STARTED 02/28/2011 END DATE 02/28/2011 BEGIN LEVEL 5,6494 IN TEST STARTED 11:31 AM. END LEVEL 5.6493 IN END TIME 12:39 PM TEST STARTED 02/28/2011 LEAK THRESHOLD 0,002 IN END DATE 02/28/2011 BEGIN LEVEL . 4,5602 IN TEST RESULT FAILED END LEVEL 5.6478 IN END TIME 11:46 AM LEAK THRESHOLD 0.002 IN END DATE 02/28/2011 TEST RESULT PASSED END LEVEL 4.5592 IN STP 2 LEAK THRESHOLD 0,002 IN TEST RESULT -PASSED TEST STARTED 12:07 PM STP 2 TEST STARTED 02/28/2011 BEGIN LEVEL 6,1177 IN TEST STARTED 12:24 PM END TIME 12:22 PM TEST STARTED 02/28/2011 END DATE 02/28/2011 BEGIN LEVEL 6,1176 IN :- END LEVEL 6.1176 IN END TIME 12:39 PM LEAK THRESHOLD 0.002 IN END DATE 02/28/2011 TEST RESULT PASSED END LEVEL 6,1177 IN' LEAK THRESHOLD 0.002 IN TEST RESULT PASSED STP 3 TEST STARTED 12:07 PM STP 3 TEST STARTED 02/28/2011 BEGIN LEVEL 5.9627 IN TEST STARTED 12:24 PM = END TIME 12:22 PM TEST STARTED 02/28/2011 END DATE 02/28/2011 BEGIN LEVEL 5.9620 IN END LEVEL 5,9620 IN END TIME 12:39 PM LEAK THRESHOLD 0.002 IN END DATE 02/28/2011 TEST RESULT PASSED END LEVEL 5,9603 IN LEAK THRESHOLD 0,002 IN TEST RESULT PASSED FASTRIF 721 FASTRIP 721 4013 SO H ST 4013 SO H ST BAKERSFIELD CA FASTkIF 721 BAKERSFIELD CA SUNSET CONST SUNSET CONST 1-800-984-6256 4013 SO H ST 1-800-984-6266 BAKERSFIELD CA SUNSET CONST 02/28/2011 11:20 AM 02/28/2011 10:59 AM 1-800-984-6266 SUMP LEAK TEST REPORT SUMP-LEAK TEST REPORT 02/28/2011 10:28 AM UDC9-10 UBC1112 SUMP LEAK TEST REPORT TEST STARTED 10:44 AM TEST STARTED 11:04 AM TEST STARTED 02/28/2011 UDC9-10 TEST STARTED 02/28/2011 BEGIN LEVEL 4,4243 IN BEGIN LEVEL 5.5658 IN END TIME 11:19 AM TEST STARTED 10:13 AM END TIME 10:59 AM END DATE 02/28/2011 TEST STARTED 02/28/2011 END DATE 02/28/2011 END LEVEL 4,2233 IN BEGIN LEVEL 5,5703 IN END LEVEL 5,5650 IN LEAK LEVEL HOLD 002 IN END TIME 10:28 AM LEAK THRESHOLD 0,002 IN TEST RESULT PASSED END DATE 02/28/2011 TEST RESULT PASSED END LEVEL 5.5685 IN LEAK THRESHOLD 0,002 IN UDC1516 TEST RESULT PASSED UDC1516 TEST STARTED 10:44 AM TEST STARTED 11:04 AM TEST.STARTED 02/28/2011 UDC1718 TEST STARTED 02/28/2011 BEGIN LEVEL 2,9415 IN BEGIN LEVEL 2.9411 IN TEST STARTED 10:13 AM END TIME 10:59 AM END TIME , 11:19 AM TEST STARTED 02/28/2011 END DATE 02/28/2011 END DATE 02/28/2011 END LEVEL 2,9411 IN BEGIN LEVEL 5,6568 IN END LEVEL 2,9412 IN LEAK THRESHOLD 0,002 IN END TIME 10:28 AM LEAK THRESHOLD 0,002 IN TEST RESULT PASSED END DATE 02/28/2011 TEST RESULT PASSED END LEVEL 5.6474 IN LEAK THRESHOLD . 0.002 IN UDC1314 TEST RESULT FAILED UDC1314 TEST STARTED 10:24 AM TEST STARTED 11:04 AM TEST STARTED 02/28/2011 UBC1112 TEST STARTED 02/28/2011 BEGIN LEVEL 3,3692 IN BEGIN LEVEL 3,3693 IN ENO TIME 11:19 AM TEST STARTED 10:13 AN END TIME 10:59 AM END DATE 02/28!2011 TEST STARTED 02/2812011 END DATE 02/28/2011 END LEVEL 3.3690 IN BEGIN LEVEL 5.6867 IN END LEVEL 3,3691 IN LEAK THRESHOLD 0,002 IN END TIME 10:28 AM LEAK THRESHOLD 0,002 IN TEST RESULT PASSED END DATE 02/28/2011 TEST RESULT PASSED END LEVEL 5.6786 IN LEAK THRESHOLD 0.002 IN UDC1920 TEST RESULT FAILED UDC1920 TEST STARTED 11:04 AM TEST STARTED 10:44 AM TEST STARTED 02/28/2011 UDC1920 TEST STARTED 02/28/2017 GIN LEVEL 3,2158 IN BEGIN LEVEL 4,5032 IN END TIME 11:19 AM TEST STARTED 10:13 AM END TIME 10:59 AM END DATE 02/28/2011 TEST STARTED 02/28/2011 END DATE 02/28/2011 ENO LEVEL 3.2154 IN BEGIN LEVEL 4.5102 IN END LEVEL 4.5003 IN LEAS( THRESHOLD 0.002 IN END TIME 1C:28 AM LEAK THRESHOLD 0.002 IN END DATE 02/28/2011 TEST RESULT FAILED TEST RESULT PASSED END LEVEL 4.5086 IN LEAK THRESHOLD 0,002 IN TEST RESULT PASSED FASTRIP 721 4013 SO H ST BAKERSFIELD CA SUNSET CONST 1-800-984-6266 02/28/2011 10:03 AM SUMP LEVEL REPORT SUMP UDC9-10 5,575 IN SUMP UDC1516 4.106 IN SUMP UBC1112 5,697 IN C-1 SUMP UDC1920 4,546 IN FASTRIP 721 4013 SO H ST BAKERSFIELD CA SUNSET CONST 1-800-9134-6266 02/28/2011 10:11 AM SUMP LEVEL REPORT . SUMP UDC9-10 5.572 IN SUMP UDC1516 5.658 IN SUMP UBC1112 5.690 IN SUMP UDC1920 4,511 IN