HomeMy WebLinkAbout2010 FMC RESULTS MONITORING SYSTEM CERTIFICATION 73 For Use By All Jurisdictions Within the State of California IE Authority Cited:- Chapter 6 7, Health and Safety Code; Chapter 16,Division 3, Title 23, California Code ofRegulations This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date. A. General Information Facility Name: Costco Wholesale Bldg. No: 643 Site Address: 4900 Panama Ln. City: Bakersfield Zip: 93313 Facility Contact Person: Tina Contact Phone No.: (661)837-2026 Make/Model of Monitoring System: Veeder-Root TLS 350• Date of Testing/Servicing: 7/13/2010 B. Inventory of Equipment Tested/Certified Check the appropriate boxes to indicate specific equipment Inspected/serviced Tank ID: 87A Tank ID: 87B In-Tank Gauging Probe. Model: 847390-109 21 In-Tank Gauging Probe. Model: 847390-109 0 Annular S pace or Vault Sensor Model: 794380-301 211 Annular Space or Vault Sensor Model: 794380-301 0 Piping Sum /Trench Sensor(s). Model: 857080-102 2 Piping Sum /Trench Sensor(s). Model: 857080-102 0 Fill Sum Sensor(s). Model: 857080-102 Fill Sump Sensor(s). Model: 857080-102 ❑ Mechanical Line Leak Detector Model: 11 Mechanical Line Leak Detector Model: 0 Electronic Line Leak Detector Model: V/R PLLD 0 Electronic Line Leak Detector Model: V/R PLLD D Tank Overfill/Hi -Level Sensor Model: 847390-109 0 Tank Overfill/Hi -Level Sensor Model: 847390-109 JU Other(specify equipment type and model in Section E on Page 2). LJ Other(specify equipment type and model in Section E on Page 2). Tank ID: 91 Tank ID: 10 In-Tank:Gauging Probe. Model: 847390-109 El In-Tank Gauging Probe. Model: Annular Space or Vault Sensor Model: 794380-301 U Annular Space or Vault Sensor Model: 0 Piping Sum /Trench Sensor(s). Model: 857080-102 U Piping Sum /Trench Sensor(s). Model: D Fill Sump Sensor(s). Model: 857080-102 U Fill Sump Sensor(s). Model: ❑ Mechanical Line Leak Detector Model: U Mechanical Line Leak Detector Model: 0 Electronic Line Leak Detector Model: V/R PLLD CT Electronic Line Leak Detector Model: D Tank Overfill/Hi -Level Sensor Model: 847390-109 U Tank Overfill/13i -Level Sensor Model: Other(specify equipment type and model in Section E on Page 2). p Other(specify equipment type and model m Section E on Page 2). Dispenser ID: 1/2 Dispenser ID: 3/4 2 Dispenser Containment Sensor(s). Model: 794380-323 0 Dispenser Containment Sensor(s). Model: 794380-323 0 Shear Valve(s). 0 Shear Valve(s). ❑ Dispenser Containment Float(s)and Chain(s). ❑ Dispenser Containment Float(s)and Chain(s). Dispenser ID: 5/6 Dispenser ID: 7/8 0 Dispenser Containment Sensor(s). Model: 794380-323 0 Dispenser Containment Sensor(s). Model: 794380-323 0 Shear Valve(s). 0 Shear Valve(s). ❑ Dispenser Containment Floats and Chain(s). ❑Dispenser Containment Float(s)and Chain(s). Dispenser ID: 9/10 Dispenser ID: 11/12 0 Dispenser Containment Sensor(s). Model: 794380-323 10 Dispenser Containment Sensor(s). Model: 794380-323 ❑ Shear Valve(s). 0 Shear Valve(s). ❑ Dispenser Containment Float(s)and Chain(s). 0 Dispenser Containment Float(s)and Chain(s). If the facility contains more tanks or dispensers,copy this form. Include information for every tank and dispenser at the facility. C. Certification I certify that the equipment identified in this document was inspected/se ' d in accordance with the manufacturers'guidelines. Attached to this Certification is information(e.g.manufacturers'checklists)necem to v fy that this Information is correct and a Plot Plan showing the layout of monitoring equipment For any egmpmen Llin g such reports,I have also attached a copy of the report;(check all that apply): 0 S Fp Alarm H istory Report Technician Name(print) William S. Karras Si Certification No: A26028 Liceno: 888712 Testing Company Name W.S.K. &Sons Inc. Phone No: (951) 906-3023 Test Company Address: 34455 Sunlight Dr. Yucaipa, CA 92399 Date of Testing/Servicing: 7/13/2010 Monitoring System Certification Page I of D. Results of Testing/Servicing IIIIIIIIIIIIIIIIf(II 74 IE MONITORING SYSTEM CERTIFICATION For Use By All Jurisdictions Within the State of California Authority Cited:- Chapter 6 7, Health and Safety Code; Chapter 16,Division 3, Title 23, California Code of Regulations This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date. A. General Information Facility Name: Costco Wholesale Bldg.No: 643 Site Address: 4900 Panama Ln. City: Bakersfield Zip: 93313 Facility Contact Person: Tina Contact Phone No.: (661)837-2026 Make/Model of Monitoring System: Veeder-Root TLS 350. Date of Testing/Servicing: 7/1312010 B. Inventory of Equipment Tested/Certified Check the appropriate boxes to indicate specific equipment Inspected/serviced Tank ID: 87A Tank ID: 87B In-Tank Gauging Probe. Model: 847390-109 21 In-Tank Gauging Probe. Model: 847390-109 ❑ Annular Space or Vault Sensor Model: 794380-301 f Annular Space or Vault Sensor Model: 794380-301 0 Piping Sum /Trench Sensor(s). Model: 857080-102 21 Piping Sump/Trench Sensor(s). Model: 857080-102 0 Fill Sump Sensor(s). Model: 857080-102 13 Fill Sump Sensor(s). Model: 857080-102 ❑ Mechanical Line Leak Detector Model: ❑ Mechanical Line Leak Detector Model: 0 Electronic Line Leak Detector Model: V/R PLLD 0 Electronic Line Leak Detector Model: V/R PLLD 0 Tank Overfill/High-Level Sensor Model: 847390-109 10 Tank Overfill/M -Level Sensor Model: 847390-109 Other(specify equipment Type and model in Section E on Page 2). Other(specify equipment type and model in Section E on Page 2). Tank ID: 91 Tank ID: 0 In-Tank Gaugin Probe. Model: 847390-109 L1 In-Tank Gauging Probe. Model: Rl Annular Space or Vault Sensor Model: 794380-301 LI Annular Space or Vault Sensor Model: 0 Piping Sum /Trench Sensor(s). Model: 857080-102 U Piping Sum /Trench Sensor(s). Model: 0 Fill Sump Sensor(s). Model: 857080-102 U Fill Sump Sensor(s). Model: ❑ Mechanical Line Leak Detector Model: U Mechanical Line Leak Detector Model: 0 Electronic Line Leak Detector Model: V/R PLLD U Electronic Line Leak Detector Model: 0 Tank Overfill/High-Level Sensor Model: 847390-109 D Tank Overfill/High-Level Sensor Model: all Other(specify equipment type and model in Section E on Page 2), no Other(specify equipment type and model in Section E on Page 2). Dispenser ID: 13/14 Dispenser ID: 15/16 0 Dispenser Containment Sensor(s). Model: 794380-323 0 Dispenser Containment Sensor(s). Model: 794380-323 0 Shear Valve(s). 0 Shear Valve(s). ❑ Dispenser Containment Float(s)and Chain(s). ❑ Dispenser Containment Float(s)and Chain(s). Dispenser ID: 1/2 Annular : ispenser ID: 3/4 Annular 0 38 Dispenser Containment Sensor(s). Model: 7940-304 0 Dispenser Containment Sensor(s). Model: 794380-304 ❑ Shear Valve(s). ❑ Shear Valve(s). ❑ Dispenser Containment Float(s)and Chain(s). ❑ Dispenser Containment Float(s)and Cham(s). Dispenser ID: 5/6 Annular Dispenser ID: 7/8 Annular 0 Dispenser Containment Sensor(s). Model: 794380-304 ° Dispenser Containment Sensor(s). Model: 794380-304 11 Shear Valve(s). ❑ Shear Valve(s). ❑ Dispenser Containment Floats and Chain(s). 0 Dispenser Containment Float(s)and Chain(s). If the facility contains more tanks or dispensers,copy this form. Include information for every tank and dispenser at the facility. C. Certification I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers'guidelines. Attached to this Certification is information(e.g.manufacturers'checklists)nec pab t verify that this information is correct and a Plot Plan showing the layout of monitoring equipment. For any equipment ca a of g erating such reports,h have also attached a copy of the report(check all that apply): Syste Q Alarm History Report Technician Name(print) William S. Karras Signatur Certification No: A26028 License. N — 888712 Testing Company Name W.S.K. &Sons Inc. Phone No: (951) 906-3023 Test Company Address: 34455 Sunlight Dr. Yucaipa, CA 92399 Date of Testing/Servicing: 7/13/2010 Monitoring System Certification Page I of D. Results of Testing/Servicing MONITORING SYSTEM CERTIFICATION For Use By All Jurisdictions Within the State of California Authority Cited:- Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date. A. General Information Facility Name: Costco Wholesale Bldg. No: 643 Site Address: 4900 Panama Ln. City: Bakersfield Zip: 93313 Facility Contact Person: Tina Contact Phone No.: (661)837-2026 Make/Model of Monitoring System: Veeder-Root TLS 350, Date of Testing/Servicing: 7/1312010 B. Inventory of Equipment Tested/Certified Check the appropriate boxes to indicate specific equipment inspected/serviced Tank ID: 87A Tank ID: 87B In-Tank Gauging Probe. Model: 847390-109 In-Tank Gauging Probe. Model: 847390-109 10 Annular Space or Vault Sensor Model: 794380-301 ° Annular Space or Vault Sensor Model: 794380-301 10 Piping Sum /Trench Sensor(s). Model: 857080-102 Piping Sump/Trench Sensor(s). Model: 857080-102 10 Fill Sump Sensor(s). Model: 857080-102 Fill Sump Sensor(s). Model: 857080-102 ❑ Mechanical Line Leak Detector Model: ❑ Mechanical Line Leak Detector Model: 10 Electronic Line Leak Detector Model: V/R PLLD ❑r Electronic Line Leak Detector Model: V/R PLLD 121 Tank Overfill/High-Level Sensor Model: 847390-109 10 Tank Overfill/Hi -Level Sensor Model: 847390-109 Other(specify equipment type and model in Section E on Page 2). LJ Other(specify equipment type and model in Section E on Page 2). Tank ID: 91 Tank ID: 10 In-Tank Gauging Probe. Model: 847390-109 11 In-Tank Gauging Probe. Model: Annular Space or Vault Sensor Model: 794380-301 U Annular Space or Vault Sensor Model: 10 Piping Sum /Trench Sensor(s). Model: 857080-102 U Piping Sum /Trench Sensor(s). Model: 121 Fill Sump Sensor(s). Model: 857080-102 U Fill Sum Sensors). Model: ❑ Mechanical Line Leak Detector Model: LJ Mechanical Line Leak Detector Model: 17 Electronic Line Leak Detector Model: V/R PLLD Electronic Line Leak Detector Model: 10 Tank Overfill/High-Level Sensor Model: 847390-109 Tank Overfill/Hi -Level Sensor Model: Other(specify equipment type and model in Section E on Page 2). 11U Other(specify equipment type and model in Section E on Page 2). Dispenser ID: 9/10 Annular Dispenser ID: 11/12 Annular 0 Dispenser Containment Sensor(s). Model: 794380-304 © Dispenser Containment Sensor(s). Model: 794380-304 ❑ Shear Valve(s). ❑ Shear Valve(s). ❑ Dispenser Containment Float(s)and Chain(s). ❑ Dispenser Containment Floats and Chain(s). Dispenser ID: 13/14 Annular Dispenser ID: 15/16 Annular 121 Dispenser Containment Sensor(s). Model: 794380-304 10 Dispenser Containment Sensor(s). Model: 794380-304 ❑ Shear Valve(s). 0 Shear Valve(s). ❑ Dispenser Containment Float(s)and Chain(s). ❑ Dispenser Containment Float(s)and Chain(s). Dispenser ID: Dispenser ID: ❑ Dispenser Containment Sensor(s). Model: ❑ Dispenser Containment Sensors). Model: ❑ Shear Valve(s). ❑ Shear Valve(s). ❑ Dispenser Containment Float(s)and Chain(s). ❑ Dispenser Containment Float(s)and Chain(s). If the facility contains more tanks or dispensers,copy this form. Include information for every tank and dispenser at the facility. C. Certification I certify that the equipment identified in this document was inspected/ rvic d in accordance with the manufacturers'guidelines. Attached to this Certification is information(e.g.manufacturers'chec, sts)nec ary to ve ' that this information is correct and a Plot Plan showing the layout of monitoring equipment For any equipment e o gene ling such reports,I have also attached a copy of the report;(check all that apply): 1] System tnp + Alarm History Report Technician Name(print) William S. Karras Signatu Certification No: A26028 License. 888712 Testing Company Name W.S.K. $Sons Inc. Phone No: (951) 906-3023 Test Company Address: 34455 Sunlight Dr. Yucaipa, CA 92399 Date of Testing/Servicing: 7/13/2010 Monitoring System Certification Page I of A Results of Testing/Servicing Software Version Installed: 328.03 Complete the following checklist: Yes NO* Is the audible alarm operational? Yes U NO* Is the visual alarm operational? Yes No* Were all sensors visually inspected,flinctionally tested,and confirmed o ational? Yes No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their oper operation? Yes U No* If alarms are relayed to a remote monitoring station,is all communications equipment(e.g.modem) N/A o ational? Yes No* For pressurized piping systems,does the turbine automatically shut down if the piping secondary containment N/A monitoring system detects a leak,fails to operate,or is electrically disconnected? If yes:-which sensors initiate positive shut-down? (Check all that apply) 10 Sumpfrrench Sensors; 14)ispenser Containment Sensors. Did you confirm positive shut-down due to leaks and sensor fail ure/disconnection? Yes (] No❑ Yes U No* For tank systems that utilize the monitoring system as the primary tank overfill warning device(i.e.no N/A mechanical overfill prevention valve is installed),is the overfill warning alarm visible and audible at the tank fill point(s)and o ating properly? If so,at what percent of tank capacity does the alarm trigger? 90% Yes* -' NO Was any monitoring equipment replaced? If yes,identify specific sensors,probes,or other equipment re laced and list the manufacturer name and model for all replacement parts in Section E,below. Yes* NO Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) ❑ Product ❑Water If yes,describe causes in Section E,below. Ur Yes IT No* Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports,if applicable P'J Yes 1U NO* I Is all monitoring equipment operational per manufacturer's specifications? *In Section E below,describe how and when these deficiencies were or will be corrected. E. Comments: Agency: Bakersfield Fire Dept. 2101 H Street Bakersfield, CA 93301 (661)326-3682 (661)852-2171 Fax Inspector:Ernie Medina Page 2 of 4 I F. In-Tank Gauging/ SIR Equipment: ❑ Check this box if tank gauging is used only for inventory control ❑ Check this box if no tank gauging or SIR equipment is installed. This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring. Complete the following checklist: U Yes No* Has all input wiring been inspected for proper entry and termination,including testing for ground faults? ❑ Yes L1 No* Were all tank a visually inspected for e and residue buildup? Yes No* Was accuracy of system product level readings tested? Yes No* Was accuracy of system water level readings tested? Yes No* Were all probes reinstalled properly. Yes I U No* I Were all items on the equipment manufacturer's maintenance checklist completed? * In the Section H,below,describe how and when these deficiencies were or will be corrected. G. Line Leak Detectors (LLD): ❑ Check this box if LLDs are not installed Complete the following checklist: LA Yes Ll No* For equipment start-up or annual eqwpment certification,was a leak simulated to verify LLD rformance? N/A (Check all that apply) Simulated leak rate: 0 3 .h.; 0.1 .h; 0.2 .h. Yes No* Were all LLDs confirmed operational and accurate within regulatory requirements? � Yes 11 No* Was the testing apparatus properly calibrated? LJ Yes U No* For mechanical LLDs,does the LLD restrict product flow if it detects a leak? L N/A Yes No* For electronic LLDs,does the turbine automatically shut off if the LLD detects a leak? N/A Yes No* For electronic LLDs,does the turbine automatically shut off if any portion of the monitoring system is disabled N/A or disconnected? '' Yes No* For electronic LLDs,does the turbine automatically shut off if any poTtion of the monitoring system N/A malfunctions or fails a test? Yes U No* For electronic LLDs,have all accessible wiring connections been visually inspected? Ll N/A Yes LJ No* I Were all items on the equipment manufacturer's maintenance checklist completed? * In the Section H,below,describe how and when these deficiencies were or will be corrected. H. Comments: Page 3 of 4 SWRCB,January 2002 Page of 5 Secondary Containment Testing Report Form This form is intended for use by contractors performing periodic testing of UST secondary containment systems. Use the appropriate pages of this form to report results for all components tested The completed form, written test procedures, and printouts from tests(rf applicable),should be provided to the facility owner/operator for submittal to the local regulatory agency. 1. FACKITY INFORMATION Facility Name: Date of Testing: j Facility Address: QqM m ^ Facility Contact: .t A I Phone: jp\ - Date Local Agency Was Notified of Testing Name of Local Agency Inspector(f present during testing): R ja\o, f( „A o 2. TESTING CONTRACTOR INFORMATION Company Name: -S.K 3 S cx,,, Technician Conducting Test: W�\ r Credentials: ❑CSLB Licensed Contractor 0 SWRCB Licensed Tank Tester License Type:.4, 0-( License Number �' 7( Z 1Vlanafacturer Trainins Manufacturer s Date Training Expires 3. SUMMARY OF TEST RESULTS Component Pass Fail Not Repairs Component Pass Fail Not Repairs Tested Made Tested Made —io ke- ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ D r ❑ ❑ ❑ ❑ ❑ ❑ ❑ o ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ o c c'K e-t ❑ ❑ ❑ ❑ ❑ ❑ ❑ �m or s , e,l ❑ 0 ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ . , Q. 4o ❑ ❑ ❑ ❑ 0 ❑ ❑ ❑ ❑ ❑ ❑ a ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ 0 ❑ ❑ ❑ ❑ ❑ If hydrostatic testing vra ad.idescHbe*v ta4iikdone with the water after completion of tests: CERTIFICATION F CIAMC1iAN RESPONSIBLE FOR CONDUCTING THIS TESTING To the best ojnry kn"4a j in this doctl»ratt we accaaatt lit full cotttpllsttce wltk fagot regttlrements Technician's Signature: Date: i3 1 T SWRCB,January 2002 Page Z of 9. SPILL/OVERFILL CONTAINMENT BOXES Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ Spill/Overfill Containment Boxes are Present,but were Not Tested ❑ Test Method Developed By: 0 Spill Bucket Manufacturer ustry Standard ❑Professional Engineer ❑Other(Specify) Test Method Used: ❑Pressure ❑Vacuum ydrostatic ❑Other(Spec) Test Equipment Used: Equipment Resolution: Spill Box# Spill Box#SI Spill Box# trn Spill Box# Bucket Diameter: Z-0 a-'� \Z Bucket Depth: 1`l 5 -is 8 0 Wait time between applying pressure/vacuum/water and starting test•. 5 r` 1 �" Test Start Time: g: 9 '00 C4 '-OC AM Initial Reading W: Test End Time: 1p:op ,� nn ; CC A "" `. c> c.tVI Final Reading(R r): D . `15 15.15 Test Duration: c I-0 AK 10 Change in Reading(RF-Rt): 5.0 V 46 Pass/Fail Threshold or Criteria �"q l jL a SS �� L��fC� S 5-C /Z Test Result: ❑ Pass Kfall Pass ❑Fail Pass ❑Fail ❑ Pass ❑Fail Comments—(include information on repairs made prior to testing and recommended follow-up for failed tests) SWRCB,January 2002 Page .3 of 9. SPH.,UOVERFILL CONTAMMENT BOXES Fwitity is Not With Spill/Overfill Containment Boxes ❑ Spill/Overfill Contaimnent Boxes are Present,but were Not Tested ❑ Test Method Developed By: ❑iSpill Bucket Manufacttu+er fiffndustrY Standard O Professional Engineer ❑Other(Specify) Test Method Used- ❑Pressure ❑Vacuum Hydrostatic ❑'Other(Speer) Test Equipment Used: V 0->u K— Equipment Resolution- Spill Box# 81 A Spill Box# B-i p, Spill Box# -�,,, Spill Box# Bucket Diameter. Vz-0 Bucket Depth: I la•O V5 75 i 5 Z$ Wait time between applying pressure(vacuunVwater and n1 starting test: Test Start Time: 1\".l 19: Cc A M 1,,n Initial Reading — 13 - -75- L3-z,'�- Test End Time: a :00 N'^ f 0.'0 0 A&n to.' Vv /P-"r Final Reading(RF): I eta 13 -75- 13•ZS Test Duration: Z-e N2 7 o fie Z o 1�r2 Change in Reading(Rr-R,): Pass/Fail 7breshold or / Criteria:(/ ��'SS Pg55 glcs5 at5 9l�S Test Result: Pass ❑Fail Pass ❑Fail • Pass ❑Fail ❑ Pass ❑Fail COMMents—('include information on repairs made prior to testhe& and recommended follaw-up for failed tests) Vp.Qut (`es;.',k , LA ai 5 LEAK DETECTOR TEST FORM � f }I I ` DATE __:N r a FACILITY NAME ,\r,3le F-•AGILITY �� ADDRESS ,Ll 9QQ „�oa!ann, ke,5L e \,c�_ -C,A cj33 i i L-EAK DETECTOR TEST RESULTS: i ALL LEAK DEFECTORS ARE TESTED IN-LINE, INDICATE TYPE OF LEAK DETECTOR WITH SERIAL NUMBER(XI_D XLP, LD-7.000, ETC.). i i f MAKEIMODEL SERIAL# r LEAK RATE PASS OR CHECK VALVE METERING Pl, TESTED(GPH) FAIL PSI i y imfm ic 041+ o 33 ' { Nr=vv j 1 . Ltd#z - PWD ` f NEW 1 LQ#3 R- eLQ a36fosq 3 -0 s 17 32 NEW 4 LD NEW J_ LEAK DETECTORS ARE TESTED IN ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS. , i CERTIF)ED_f ESTER`S ID# _ ii SIGNATURE OE CERTIFIED TECHMIAN 'f PRINTED NAME OF CERTIFIED TECHNICIAN TES'FNNNG COMPANY NAME&TELEPHONE# W 3 - I ' * IF INMAL LEAK DETECTOR FAILS,ALL REPLACEMENTS SHALL DE TESTED. I 1 5�k 5 Monitoring System Certification Form:Addendum for Vacuum/Pressure Interstitial Sensors L Results of Vacuum/Pressure Monitoring Equipment Testing This page should be used to document testing and servicing of vacuum and pressure interstitial sensors. A copy of this form must be included with the Monitoring System Certification Form, which must be provided to the tank system owner/operator. The owner/operator must submit a copy of the Monitoring System Certification Form to the local agency regulating UST systems within 30 days of test date. Manufacturer: Model: 17�LS- 3-5t✓ System Type:❑Pressure;10 Vacuum Sensor ID Component(s)Monitored by this Sensor: A C G b ch c_.; Sensor Functionality Test Result Pass; ❑ Fail Interstitial Communication Test Result Pass; ❑ Fail Component(s)Monitored by this Sensor: V f�'er F L. Nl"= Sensor Functionality Test Result: W Pass; ❑ Fail Interstitial Communication Test Result Pass; ❑ Fail Component(s)Monitored by'this Sensor: 6-1 A V e t\k \��- �7 Sensor Functionality Test Result: Pass; ❑ Fail Interstitial Communication Test Result: Pass; ❑ Fail Component(s)Monitored by'this Sensor: g 1 g 5 Lt Sensor Functionality Test Result Pass; ❑ Fail Interstitial Communication Test Result: Pass; ❑ Fail Component(s)Monitored by,this Sensor. �,1 g �,O r3 t✓'.N�- �1 Sensor Functionality Test Result: Pass; ❑ Fail Interstitial Communication Test Result: Pass; ❑ Fail Component(s)Monitored by this Sensor: $-g v e AV b Sensor Functionality Test Result MPass; ❑ Fail Interstitial Communication Test Result: Pass; ❑ Fail S Component(s)Monitored by this Sensor. Sensor Functionality Test Result Pass; ❑ Fail Interstitial Communication Test Result:M Pass; ❑ Fail Component(s)Monitored by this Sensor. k'k1VQ- 5 Sensor Functionality Test Result:M Pass; ❑ Fail Interstitial Communication Test Result: Pass; ❑ Fail Component(s)Monitored by this Sensor. Sensor Functionality Test Result:❑Pass; ❑ Fail Interstitial Communication Test Result:❑Pass; ❑ Fail Component(s)Monitored by this Sensor: Sensor Functionality Test Result:❑Pass; ❑ Fail Interstitial Communication Test Result:❑Pass; ❑ Fail How was interstitial communication verified? Leak Introduced at Far End of Interstitial Space;' ❑ Gauge; S Visual Inspection; E] Other(Describe in Sec.J, below) Was vacuum/pressure restored to operating levels in all interstitial spaces? L Yes ❑No(If no, describe in Sec.J, below) J. Comments: Page of ' If the sensor successfully detects a simulated vacuum/pressure leak introduced in the interstitial space at the furthest point from the sensor,vacuum/pressure has been demonstrated to be communicating throughout the interstice. VN-036A-1/i www.onidomorg 01/25/06 SWRCB,January 2002 Page of 9. SPH-"OVERFILL CONTAINMENT BOXES Batik is Not ETApped With Spill/Overfill Containment Boxes ❑ SpdV0verfill Containment Boxes are Present,but were Not Tested D Test Method Developed By: 0 Spill Bucket Manufacturer dustry Standard 0 Professional Engineer ❑Other(Specify) Test Method Used D Pressure ❑Vacuum Erflydrostatic ❑Other(Specify) Test Equipment Used: ViStAja& Equipment Resolution: Spill Box#8-1 p Spin Box# Spin Box# Spi11 Box# Bucket Diameter: z,0 Bucket Depth: Wait time between applying and starting test S Test Start Time: 1 :00 Initial Reading(Rj): 140, 00 Test End Time: i 00 y►� Final Reading(Pw): i 60:0 0 Test Duration: Change in Reading(Pw-": ,0- Pass/Fail Threshold or Criteria: R-5 6X' CISS Test Result: WPass 0 Fail ❑ Pass D Fall ❑ Pass ❑Fail D Pass D Fail Comments—(include information on repairs made prior to testis&and recommended follow-up for failed tes>;s) �7 A Ei i t u e- CC rJ/c, c R `zi p n 52!kt �rsp�c��d b rnie Date: 7/13/2010 Location: #643 Bakersfield SW page 4 of 4 2/1 615 10/ 14/ 9 13 t I I 4/3 817 12/ 16/ 11 15 Annular 0 O Fill O STP 00 0 00 0 MAINTENANCE HISTORY D I SA3LED RECEIVER SETUP: TANK CHART SECURITY DISA3LED NONE S'YST;?IM SETUP JUL 13, 2010 1 :24 PM CUSTOM ALARMS DISA3LED SYSTIN UNITS SERV I,:E NOTICE U.S. DISABLED cYST'EIH LANGUAGE ENG.,-I S H SYST=IH DATE/TIME FORMAT MASS./DENSITY AUTO DIAL TIME SETUP: MO N 3D YYYY HH:MM:SS xM D I SA:3iJED 2793y5 COSTCO #643 NONE 49D0 Panama Lane Ba-<arsfield. CA S;HIF't TIME 1 : 5:45 AM SHIFT TIME 2 : 9:45 PM SHIFT TIME 3 : DISABLED SHIFT TIME 4 : DISABLED SHIFT BIR PRINTOUTS DISA3 ED COMMJNICATIONS SETUP DA I L'� BIR PRINTOUTS - - - - - - - - - - - - D I SA:3:LED T I CK"TED DELIVERY DISABLED PORT ,SETTINGS: RS-232 END OF MESSAGE TANK ?ER TST NEEDED 14RN D I SA:3_ED DISA3LED COMM 30ARD : 1 (EDIM ) i TANK ANN TST NEEDED WRN RS-232 SECURITY AUTO DIAL ALARM SETUP DISABLED CODE * * - - - - - - - - - - - - LINE RE-ENABLE METHOD COMM 3OARD 2 (S-SAT ) PASS LINE TEST BAUD RATE. : 9600 LINE :?ER TST NEEDED WRN STO? B NONE DISABLED TO� BIT 1 STOP LINE ANN TST NEEDED 14RN S-23 LENGTH: 8 DATA DISALED RS-232 SECURITY CODE : xxxxxx TC VOLUMES PRINT DTR NORMAL STATE: HIGH ENAB:_ED COMM BOARD 3 (RS-232) TEMP COMPENSATION BAUD RATE 9600 IN-TANK SETUP- _ - - - - VALU:= (DEG F ) : 60.0 PARITY NONE DATA ST I CX HEIGHT OFFSET D BIT : 1 STOP AT�� LENGTH: 8 DATA T 1 :Jn 1 ended DISA3LED RS-232 SECURITY PRODUCT CODE I UL.LAGE: 90% CODE * **** THERMAL COEFF : .000700 TANK DIAMETER 113.25 H-PROTOCOL DATA FORMAT TANK `PROFILE 4 PTS HEIGHT AUTO TRANSMIT SETTINGS: FULL VOL 30063 PRECISION TEST DURATION 88.7 INCH VOL 24399 HOURS 12 AUTO LEAK ALARM LIMIT 59.1 INCH VOL 15073 0.20 aPH LINE TEST DISABLED 29.5 INCH VOL 5805 AUTO-CONFIRM: ENABLED AUTO HIGH WATER LIMIT METER DATA : YES 0.10 'PH LINE TEST END ?ACTOR: HEMISPHER AUTO-CONFIRM: ENABLED DISABLED PRINT PRECISION LINE AUTO OVERFILL LIMIT CAL UPDATE: IMMEDIATE TEST RESULTS: DISABLED DISABLED DAYLIGHT SAVING TIME AUTO LOW PRODUCT FLOAT SIZE: 4.0 IN. E NABLED D I T HD START DATE AUTTO O THEFT LIMIT MAR WEEK 2 SUN DISABLED WATER WARNING 0.8 MTAR't TIME AUTO DELIVERY START HIGH 14ATER LIMIT: 2.0 �:0] DISA3LED 30063 END 'DATE AUTO DELIVERY END MAX ; LABEL VOL: DISA3LED OVERFILL LIMIT 90% NOV WEEK I SUN AUTO EXTERNAL INPUT ON 27056 END 'LIME DISABLED HIGH ?RODUCT 94% 2:03 AM 28259 AUTO EXTERNAL INPUT OFF DISABLED DELIVERY LIMIT 14% RE-DIRECT LOCAL PRINTOUT AUTO SENSOR FUEL ALARM 4500 D I SA:3LED D I SA3LED . EURO ?ROTOCOL PREFIX AUTO SENSOR WATER ALARM LOW ?:�ODUGT 600 DISA3i.ED LEAK ALARM LIMIT: 8 S AUTO SENSOR OUT ALARM SUDDEN LOSS LIMIT: 40 D I SA:LED TANK 'TILT 0.00 nn SIPHON MANIFOLDED TANKS T#: 02 LINE MANIFOLDED TANKS LEAK MIN PERIODIC: 80% T#' NONE 24050 LEAK MIN PERIODIC: 80% 24050 LEAK MIN PERIODIC: 80% LEAK MIN ANNUAL 80% o : 24050 LEAK MIN ANNUAL : BOi 24050 24050 LEAK MIN ANNUAL : 80% PERIODIC TEST TYPE 24050 STANDARD PERIODIC TEST TYPE STANDARD PERIODIC TEST TYPE ANNUAL TEST FAIL STANDARD ALARM DISABLED ANNUr�L TEST FAIL ALARM DISABLED ANNUi3 L TEST FAIL PERIODIC TEST FAIL ALARM DISABLED ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED PERIODIC TEST FAIL GROSS TEST FAIL ALARM DISABLED ALARM DISABLED GROSS TEST FAIL ALARM DISABLED GROSS TEST FAIL ANN 'T EST AVERAGING: OFF ALARM DISABLED PER TEST AVERAGING: OFF ANN 'T=ST AVERAGING: OFF PER TEST AVERAGING: OFF ANN TEST AVERAGING: OFF TANK TEST NOTIFY: OFF PER .ST AVERAGING: OFF TANK 'TEST NOTIFY: OFF TEST AVERAGING: TST SIPHON BREAK:OFF TNK 'TST SIPHON BREAK:OFF TANK 'TEST NOTIFY: OFF DELIVERY DELAY 1 MIN PUMP THRESHOLD 10.00% DELIV: RY DELAY I MIN TNK TST SIPHON BREAK:OFF PUMP 'THRESHOLD 10.00% DELIVERY DELAY 1 MIN PUMP 'THRESHOLD 10.00% T 3::? emi PROD J,DT CODE 2 THERMAL COEFF : .000700 LEAK TEST METHOD T 2:Jnleaded TANK DIAMETER 118.25 - - - - - - - - - - - - TANK '?ROFILE 4 PTS TEST ON DATE : TANK 1 PRODJ13T CODE I FULL VOL 30063 NOV 4, 2005 THERMAL COEFF : •000700 88. 7 INCH VOL 24399 START TIME : DISABLED TANK ;DIAMETER 118.25 59.1 INCH VOL 15073 TEST :RATE :0.20 GAL./HR TANK PROFILE 4 PTS 29.5 INCH VOL : 5805 DURATION 2 HOURS FULL VOL 30063 METER DATA : YES 88. 7 INCH VOL : 24399 END 'FACTOR: HEMISPHER TST EARLY STOP:DISABLED 59.1 INCH VOL 15073 CAL JPDATE: IMMEDIATE 29.5 INCH VOL 5805 METER DATA YES TEST ON DATE : TANK 2 END :?ACTOR: HEMISPHER FLOAT SIZE: 4.0 IN. NOV 4, 2005 CAL UPDATE: IMMEDIATE START TIME : DISABLED WATER WARNING 0.8 TEST RATE :0.20 GAL./HR FLOAT SIZE: 4.0 IN. HIGH 14ATER LIMIT: 2.0 DURATION : 2 HOURS WATER WARNING p,8 2 MAX 3R LABEL VOL. 30063 TST EARLY STOP:DISABLED HIGH WATER LIMIT: 2,p OVER:=ILL LIMIT 056 MAX OR LABEL VOL: 30063 HIGH PRODUCT 94% TEST ON DATE : TANK 3 = • 28259 4. 2005 OVER: ILL LIMIT 90% DELIVERY L I M I T 14% STA RT T I ME DISABLED 27056 4500 TEST RATE :0.20 GAL./HR HR HIGH :PRODUCT DURATION 2 HOURS 23259 LOW ?RODUCT 600 DELIVERY LIMIT 14% LEAK ALARM LIMIT: 8 TST EARLY STOP:DISABLED 4500 SUDD=N LOSS LIMIT: 25 LOW ?rRODUCT 600 TANK TILT 0.00 LEAK 'TEST REPORT FORMAT LEAK ALARM LIMIT: 8 PROBE OFFSET 0.00 NORMAL SUDD7A LOSS LIMIT: 40 TANK 'TILT 0.00 cIPHON MANIFOLDED TANKS FROBE OFFSET 0.00 T#: -NONE LINE MANIFOLDED TANKS S:IPH-)l MANIFOLDED TANKS T#: NONE T#: D1 LINE MANIFOLDED TANKS TO: NONE PRESSURE- L I NE LEAK SETUP L I NE L> AK LOCKOUT SE1)P LOCk3UT SCHEDULE DAILY L17:JNL 87A STP BRINE G 1 :JNLEADED 87A START TIME: DISABLED TRI-STATE (SINGLE FLOAT) TYP:[.Oi 3.0 I N FIBERGLASS STOP 'TIME : DISABLED CATEGORY : ANNULAR SPACE 2 .0IN DIA LEN: 310 FEET o.OIN DIA LEN: 0 FEET LIB:JNL 87A FILL BRINE TRI-(STATE (SINGLE FLOAT) 0.20 GPH TEST: REPETITIV 0.10 GPH TEST: AUTO CATEGORY : ANNULAR SPACE SHUTDOWN RATE: 3.0 GPH LOW PRESSURE SHUTOFF:YES LOW PRESSURE 5 PSI L19:UNL 87B STP BRINE TRI-STATE (SINGLE FLOAT) T 1 :UNSE MO d CATEGORY : ANNULAR SPACE DISPENSE MODE: LIQUID SENSOR SETUP STXVDARD - - - - - - - - - - - - ENSCR: NON-VENTED PRESSJRE OFFSET: O.OPSI L 1 :JNLEADED 87A ANNULAR L21 :'JNL 87B FILL BRINE TR I-STATE (S I NGLE FLOAT) TRI-STATE (SINGLE FLOAT) CATEGORY : ANNULAR SPACE CATEGORY : ANNULAR SPACE L 2:JNLEADED 87B ANNULAR L22:31 STP BRINE TRI.STATE (SINGLE FLOAT) TRI-STATE (SINGLE FLOAT) CATEGORY : ANNULAR SPACE CATEGORY : ANNULAR SPACE L 3:PREMIUM ANNULAR L23:31 FILL BRINE G 2:JNLEADED 87B TRI-STATE (SINGLE FLOAT) TRI-:STATE (SINGLE FLOAT) TYP: 2.0i3.0IN FIBERGLASS CATEGORY : ANNULAR SPACE CATEGORY ANNULAR SPACE c.OIN DIA LEN: 320 FEET .OIV DIA LEN: 0 FEET L 9::DISP PAN 1-2 DW SJMP 2-1 0.20 GPH TEST: REPETITIV CATEGORY : DISPENSER PAN 0. 10 GPH TEST: AUTO SHUTDOWN RATE: 3.0 GPH LOW PRESSURE SHUTOFF:YES LOW PRESSURE 5 PSI 1_10::DISP PAN 3-4 DW SUMP 2-1 T 2:Jnlaaded CATEGORY : DISPENSER PAN DISP?NSE MODE: STANDARD OUTPJ'T RELAY SETUP SENSOR: NON-VENTED - - _ - - - - - - - - - PRES;SJRE OFFSET: O.OPSI L11 :DISP PAN 5-6 DW SJMP 2-1 R 1 ::DATA HUT ALARM CATEGORY : DISPENSER PAN TYPE: STANDARD NORMALLY CLOSED L12:DISP PAN 7-8 TANK 0: NONE DW SUMP 2-1 CATEGORY : DISPENSER PAN IN-TANK ALARMS ALL:HIGH WATER ALARM L13:JISP PAN 9-10 ALL:-)VERFILL ALARM G 3::?REMIUM DW SUMP 2-1 ALL:'LOW PRODUCT ALARM CATEGORY : DISPENSER PAN ALL:SUDDEN LOSS ALARM ALL :HIGH FIBERGLASS NI PRODUCT ALARM c.OIN DIA LEN: 330 FEET ALL:INNA VALID FUEL LEVEL ALL:PROBE OUT 1:1.01N DIA LEN: 0 FEET L14:'JISP PAN 11-12 ALL:HIGH WATER WARNING DW SJMP I S 2-1 ALL::DELI VERY NEEDED 0.20 GPH TEST: REPETITIV CATEGORY : DISPENSER PAN ALL:LOW PRODUCT ALARM 0.10 GPH TEST: AUTO ALL:_OW TEMP WARNING SHUTDOWN RATE: 3.0 GPH LIQUID SENSOR ALMS LOW PRESSURE SHUTOFF:YES ALL:FUEL ALARM LOW '?RESSURE 5 PSI L15:DISP PAN 13-14 ALL:SENSOR OUT ALARM DW SUMP 2-1 ALL:SHORT ALARM T 3:?,-emium CATEGORY : DISPENSER PAN ALL:14ATER ALARM DISPENSE MODE: ALL:- IGH LIQUID ALARM STANDARD ALL:LOW LIQUID ALARM EENS0:4: NON-VENTED ALL:!-IGUID WARNING PRESSJRE OFFSET: 0.0PSI L16:7,ISP PAN 15-16 E14 SJMP 2-1 -. .zni,, • niQDFNPFR PAN •FRES:3JRE LINE LEAK s B:FUEL WARNING ALL:GROSS LINE FAIL s 9:FUEL WARNING ALL:ANNUAL LINE FAIL 510:FUEL WARNING ALL:PER TST NEEDED WRN s11 :=UEL WARNING ALL:PER TST NEEDED ALM s12:FUEL WARNING ALL:PLLD OPEN ALARM sl3:FUEL WARNING ALL:PLLD SHUTDOWN ALARM s14:FUEL WARNING ALL:PERIODIC LINE FAIL sl5:FUEL WARNING sl6:FUEL WARNING ALL:ANN TST NEEDED WRN s 1 :FUEL ALARM ALL:ANN TST NEEDED ALM s 2:FUEL ALARM s 3:'HIGH LIQUID ALARM ALL:LOW PRESSURE ALARM s 3:FUEL ALARM ALL:CONT HANDLE ALM s 4:FUEL ALARM s 4:.HIGH LIQUID ALARM ALL:FUEL OUT s 5:FUEL ALARM s 5:HIGH LIQUID ALARM ALL:LN EQUIP FAULT ALM s 6:7UEL ALARM s 6:HIGH LIQUID ALARM s 7:FUEL ALARM s 7:HIGH LIQUID ALARM EEMAR'T:3ENSOR ALARMS s B:FUEL ALARM s B:HIGH LIQUID ALARM s 1 :SETUP DATA WARNING s 9:FUEL ALARM s 9:HIGH LIQUID ALARM s 2:SETUP DATA WARNING s10:FUEL ALARM 510:HIGH LIQUID ALARM 5 3:SETUP DATA WARNING sll :FUEL ALARM 511 :HIGH LIQUID ALARM s 4:SETUP DATA WARNING sl2:FUEL ALARM sl2:HIGH LIQUID ALARM s 5::3ETUP DATA WARNING 513:FUEL ALARM 513:HIGH LIQUID ALARM s 6:SETUP DATA WARNING 514:FUEL ALARM sIC HIGH LIQUID ALARM s 7:SETUP DATA WARNING 315:FUEL ALARM sl5:HIGH LIQUID ALARM s B:SETUP DATA WARNING sl6:FUEL ALARM sl6:HIGH LIQUID ALARM s 9:SETUP DATA WARNING s 1 :WATER WARNING s I :i.OW LIQUID WARNING s10'SETUP DATA WARNING s 2:14ATER WARNING s 2:LOW LIQUID WARNING sll :SETUP DATA WARNING s 3:14ATER WARNING s 3:LOW LIQUID WARNING sl2:SETUP DATA WARNING s 4:WATER WARNING s 4:LOW LIQUID WARNING sl3:3ETUP DATA WARNING s 5:IJATER WARNING s 5:T OW LIQUID WARNING sl4::3ETUP DATA WARNING s 6:14ATER WARNING s 6:LOW LIQUID WARNING s15:SETUP DATA WARNING s 7:14ATER WARNING s 7:LOW LIQUID WARNING sl6:SETUP DATA WARNING s B:WATER WARNING s B LOW LIQUID WARNING s 1 :l`.OMMUNICATION ALARM s 9:WATER WARNING s 9:LOW LIQUID WARNING s 2:11OMMUNICATION ALARM s10:WATER WARNING s10:LOW LIQUID WARNING � a 5 3:60MMUNICATION ALARM sll :WATER WARNING sll :LOW LIQUID WARNING lJ s 4:COMMUNICATION ALARM sl2:WATER WARNING s12:LOW LIQUID WARNING s 5:COMMUNICATION ALARM s13:WATER WARNING 513:LOW LIQUID WARNING s 6:�"OMMUNICATION ALARM 514:14ATER WARNING sl4:LOW LIQUID WARNING s 7:CQMMUNICATION ALARM 515:WATER WARNING sl5:LOW LIQUID WARNING s16:WATER WARNING s16:LOW LIQUID WARNING s 8:1'OMMUNICATION ALARM s 1 :?OW LIQUID ALARM s 9:1DOMMUNICATION ALARM s 1 :14ATER ALARM s 2'LOW LIQUID ALARM sl0:COMMUNICATION ALARM s 2:WATER ALARM ' 511 :130MMUNICATION ALARM s 3:WATER ALARM s 3:LOW LIQUID ALARM sl2:1;OMMUNICATION ALARM s 4:14ATER ALARM s 4:LOW LIQUID ALARM 513:1DOMMUNICATION ALARM s 5:WATER ALARM s 5: OW LIQUID ALARM sl4:,.OMMUNICATION ALARM 5 6:WATER ALARM s 6:LOW LIQUID ALARM 515:COMMUNICATION ALARM s 7:14ATER ALARM s 7:LOW LIQUID ALARM s16:0OMMUNICATION ALARM s B:WATER ALARM s BLOW LIQUID ALARM • I ::3ENSOR FAULT ALARM s 9:WATER ALARM s 9:LOW LIQUID ALARM • 2:SENSOR FAULT ALARM s10:14ATER ALARM s10:LOW LIQUID ALARM • 3:SENSOR FAULT ALARM sll :14ATER ALARM s11 :LOW LIQUID ALARM • 4::3ENSOR FAULT ALARM 512:14ATER ALARM s12:LOW LIQUID ALARM • 5:SENSOR FAULT ALARM sl3:WATER ALARM sl3:LOW LIQUID ALARM • 6:SENSOR FAULT ALARM sl4:WATER ALARM sl4:LOW LIQUID ALARM • 7:SENSOR FAULT ALARM sl5:WATER ALARM s15:LOW LIQUID ALARM • 8:SENSOR FAULT ALARM s16:WATER ALARM s16:LOW LIQUID ALARM • 9::3ENSOR FAULT ALARM s 1 :'HIGH LIQUID WARNING s 1 :TEMPERATURE WARNING sl0:SENSOR FAULT ALARM s 2:HIGH LIQUID WARNING s 2:TEMPERATURE WARNING 511 :SENSOR FAULT ALARM s 3:HIGH LIQUID WARNING s 3:TEMPERATURE WARNING sl2::3ENSOR FAULT ALARM s 4:HIGH LIQUID WARNING s 4:TEMPERATURE WARNING sl3:SENSOR FAULT ALARM s 5:HIGH LIQUID WARNING s 5:'TEMPERATURE WARNING sl4:SENSOR FAULT ALARM s 6:HIGH LIQUID WARNING s 6:TEMPERATURE WARNING 515:SENSOR FAULT ALARM s 7:HIGH LIQUID WARNING s 7:'TEMPERATURE WARNING sl6::3ENSOR FAULT ALARM s B:HIGH LIQUID WARNING s B:TEMPERATURE WARNING • 1 :FUEL WARNING s 9:HIGH LIQUID WARNING s 9:TEMPERATURE WARNING • 2:FUEL WARNING s10:HIGH LIQUID WARNING s10:TEMPERATURE WARNING • 3:FUEL WARNING sll :HIGH LIQUID WARNING 511 :TEMPERATURE WARNING • 4:FUEL WARNING 512:HIGH LIQUID WARNING sl2:TEMPERATURE WARNING • 5:FUEL WARNING s13:HIGH LIQUID WARNING s13:TEMPERATURE WARNING • 6::PUEL WARNING 514:HIGH LIQUID WARNING 514:TEMPERATURE WARNING • 7:FUEL WARNING 515:HIGH LIQUID WARNING 515:TEMPERATURE WARNING 516:HIGH LIQUID WARNING 516:'rEMPERATURE WARNING 5 1 :HIGH LIQUID ALARM s 2:HIGH LIQUID ALARM • l :RELAY ACTIVE ALL:WATER ALARM ISD :HOSE ALARMS ALL:HIGH LIQUID WARNING • 2::REL ACTIVE ALL:GROSS COLLECT FAIL ALL:HIGH LIQUID ALARM s' 3:RELAY Y ACTIVE ALL:DEGRD COLLECT FAIL ALL:LOW LIQUID WARNING s 4:RELAY ACTIVE ALL:FLOW COLLECT FAIL ALL:LOW LIQUID ALARM s 5:RELAY ACTIVE ALL:TEMPERATURE WARNING s 6:RELAY ACTIVE R 2:WAREHOUSE V-R ALARM ALL:RELAY ACTIVE s 7:RELAY ACTIVE TYPE: ALL:INSTALL ALARM s B:RELAY ACTIVE STANDARD ALL:SENSOR FAULT WARN s 9:RELAY ACTIVE 510:'.RELAY ACTIVE NORMALLY OPEN ALL:VAO00M WARNING 511 :RELAY ACTIVE TANK 0: NONE ALL:NO VACUUM ALARM sl2:RELAY ACTIVE ISD ;SITE ALARMS sl3:RELAY ACTIVE ISD ;STAGE I WARN 514::RELAY ACTIVE IN-TANK ALARMS ISD GROSS PRES WARN s15:RELAY ACTIVE ALL:LEAK ALARM ISD GROSS PRES FAIL s16:.RELAY ACTIVE ALL:HIGH WATER ALARM ISD DEGRD PRES WARN s 1 :INSTALL ALARM ALL:OVERFILL ALARM ISD DEGRD PRES FAIL s 2:INSTALL ALARM ALL:LOW PRODUCT ALARM ISD VAPOR LEAK WARN s 3:INSTALL ALARM ALL:; UDDEN LOSS ALARM ISD VAPOR LEAK FAIL s 4: INSTALL ALARM ALL:HIGH PRODUCT ALARM ISD VP PRES WARN s 5: INSTALL ALARM ALL: INVALID FUEL LEVEL ISD VP PRES FAIL s 6:INSTALL ALARM ALL:PROBE OUT ISD VP STATUS WARN s 7:INSTALL ALARM 9 ALL:HIGH WATER WARNING ISD VP STATUS FAIL s : INSTALL ALARM ALL:DELIVERY NEEDED MISSING RELAY SETUP s :INSTALL ALARM ALL:MAX PRODUCT ALARM MISSING HOSE SETUP s10: INSTALL ALARM ALL:GROSS TEST FAIL MISSING TANK SETUP sll :INSTALL ALARM ALL:PERIODIC TEST FAIL MISTS VAPOR FLOW MTR 512:INSTALL ALARM ALL:ANNUAL TEST FAIL MISS VAPOR PRES SEN sl3:INSTALL ALARM ALL:PER TST NEEDED WRN MISSING VP INPUT 314:INSTALL ALARM ALL:ANN TST NEEDED WRN ISD SETUP WARN s15: INSTALL ALARM ALL:PER TST NEEDED ALM ISD SETUP FAIL s16:INSTALL ALARM ALL:ANN TST NEEDED ALM ISD SENSOR OUT WARN s 1 :SENSOR FAULT WARN ALL:TANK TEST ACTIVE ISD SENSOR OUT FAIL 3 2:SENSOR FAULT WARN s 3:;SENSOR FAULT WARN ALL:NO CSLD IDLE TIME PC-ISD FAILURE s 4:SENSOR FAULT WARN ALL:TANK SIPHON BREAK ALL:CSLD INCR RATE WARN ISD :HOSE ALARMS s 5:SENSOR FAULT WARN ALL:ACCU-CHART CAL WARN ALL:GROSS COLLECT FAIL s 6:SENSQR FAULT WARN ALL:RECON WARNING s 7:SENSOR FAULT WARN ALL:RECON ALARM ALL:DEGRD COLLECT FAIL s 8:SENSOR FAULT WARN ALL:LOW TEMP WARNING ALL:FLOW COLLECT WARN s 9:SENSOR FAULT WARN ALL:MISSING TICKET WARN PLLD LINE DISABLE SETUP s10:SENSOR FAULT WARN ALL:GROSS FAIL LINE TNK - - - - - - - - - - - - s11 :SENSOR FAULT WARN ALL:DELIVY DENSITY WARN 512:8ENSOR FAULT WARN Q 1 :JNLEADED 87A 513:SENSOR FAULT WARN LIQUID SENSOR ALMS 514:SENSOR FAULT WARN ALL:FUEL ALARM IN-TANK'ALARMS sl5:SENSOR FAULT WARN ALL:SENSOR OUT ALARM T 1 :HIGH WATER ALARM sl6:;3ENSOR FAULT WARN ALL:SHORT ALARM T 2:HIGH WATER ALARM s 1 :VACUUM WARNING ALL:WATER ALARM T 1 :LOW PRODUCT ALARM s 2:VACUUM WARNING ALL:'HIGH LIQUID ALARM T 2:LOW PRODUCT ALARM s 3:VACUUM WARNING ALL:LOW LIQUID ALARM s 4:VAO00M WARNING ALL:LIQUID WARNING LIQUID SENSOR ALMS s 5:VACUUM WARNING L 1 :FUEL ALARM s 6:VACUUM WARNING PRESSJRE LINE LEAK L 9:FUEL ALARM s 7:VA000M WARNING ALL:GROSS LINE FAIL L10:7UEL ALARM s 8:VA000M WARNING ALL:ANNUAL LINE FAIL Lll :FUEL ALARM s 9:VACUUM WARNING ALL:PER TST NEEDED WRN L12:FUEL ALARM s10:VACUUM WARNING ALL:PER TST NEEDED ALM L13:FUEL ALARM s11 :VACUUM WARNING ALL:PLLD OPEN ALARM L14:FUEL ALARM sl2:VACUUM WARNING ALL:PLLD SHUTDOWN ALARM L15:FUEL ALARM ISD SITE ALARMS ALL:PERIODIC LINE FAIL L16:FUEL ALARM ISD ;STAGE I WARN ALL:ANN TST NEEDED WRN L17:FUEL ALARM ISD GROSS PRES WARN ALL:ANN TST NEEDED ALM L18:FUEL ALARM ISD GROSS PRES FAIL ALL:LOW PRESSURE ALARM L19:FUEL ALARM ISD DEGRD PRES WARN ALL:CONT HANDLE ALM L I :SENSOR OUT ALARM ISD DEGRD PRES FAIL ALL:FUEL OUT L 9:;SENSOR OUT ALARM ISD VAPOR LEAK WARN ALL:LN EQUIP FAULT ALM L10:;SENSOR OUT ALARM ISD VAPOR LEAK FAIL Lll :SENSOR OUT ALARM VA SMARTSENSOR ALARMS L12:SENSOR OUT ALARM ISD ISD VP PRES FAIL PRES WARN ALL:SETUP DATA WARNING L13:SENSOR OUT ALARM ISD VP STATUS WARN ALL:COMMUNICATION ALARM L14:SENSOR OUT ALARM ISD VP STATUS FAIL ALL:,3ENSOR FAULT ALARM L15:3ENSOR OUT ALARM ALL:FUEL WARNING L16:SENSOR OUT ALARM MISSING RELAY SETUP ALL:FUEL ALARM L17:5ENSOR OUT ALARM MISSING HOSE SETUP ALL:WATER WARNING L18:SENSOR OUT ALARM MISS VAPOR FLOW MTR L1 :SENSOR OUT ALARM MISTS VAPOR PRES SEN � I I :SHORT ALARM 9:SHORT ALARM MISSING VP INPUT ISD SETUP FAIL L10:SHORT ALARM ISD SENSOR OUT WARN L11 :SHORT ALARM L12:SHORT ALARM ISD SENSOR OUT FAIL L13:SHORT ALARM L14:SH0RT ALARM 511 :HIGH LIQUID WARNING L15:SHORT ALARM s12:HIGH LIQUID WARNING L16: HORT ALARM 13:HIGH LIQUID WARNING L17:SSHORT ALARM s 1 :HIGH LIQUID ALARM L1 :S HORT ALARM s 2:,HIGH LIQUID ALARM L19::3HORT ALARM s 3:,HIGH LIQUID ALARM L14:3HORT ALARM L14:HIGH LIQUID ALARM L16:HIGH LIQUID ALARM 511 :HIGH LIQUID ALARM L15::3HORT ALARM L 1 :LOW LIQUID ALARM s12:HIGH LIQUID ALARM L16:.3HORT ALARM s13:HIGH LIQUID ALARM L17-SHORT ALARM L 9:LOW LIQUID ALARM s11 :LOW LIQUID WARNING L19:SHORT ALARM L10:LOW LIQUID ALARM s12:LOW LIQUID WARNING L21 :3HORT ALARM L11 :7-OW LIQUID ALARM s13:LOW LIQUID WARNING L 2:LOW LIQUID ALARM L12:LOW LIQUID ALARM si1 :LOW LIQUID ALARM L 9:LOW LIQUID ALARM L13:LOW LIQUID ALARM s12:LOW LIQUID ALARM L10:LOW LIQUID ALARM L14:LOW LIQUID ALARM s13:LOW LIQUID ALARM L11 :LOW LIQUID ALARM L15:LOW LIQUID ALARM s11 :INSTALL ALARM L12:L0 W LIQUID ALARM L16 ' OW LIQUID ALARM L13:LOW LIQUID ALARM L17:L0W LIQUID ALARM s12:INSTALL ALARM L18:L0W LIQUID ALARM 513:INSTALL ALARM L14:LOW LIQUID ALARM L14:LIQUID WARNING s 1 :SENSOR FAULT WARN L15:LOW LIQUID ALARM L16'LIQUID WARNING s 2:SENS0R FAULT WARN L16:LOW LIQUID ALARM s 3:SENSOR FAULT WARN L17:LOW LIQUID ALARM PRES,!'JRE LINE LEAK s 1 :VACUUM WARNING L19:LOW LIQUID ALARM Q I :PLLD OPEN ALARM s 2:VACUUM WARNING L19:LOW LIQUID ALARM Q 2:'>>LLD OPEN ALARM s 3:VA000M WARNING L21'.LOW LIQUID ALARM Q 1 :C0NT HANDLE ALM s 1 :1O VACUUM ALARM PRESSURE LINE LEAK Q 2:CONT HANDLE ALM s 2:NO VACUUM ALARM Q 1 :01.1.1) OPEN ALARM Q 1 :LN EQUIP FAULT ALM s 3:10 VACUUM ALARM Q 2:PLLD OPEN ALARM Q 2:LN EQUIP FAULT ALM Q 1 :CONT HANDLE ALM ISD SITE ALARMS 2:Q 22:11-N 3ONT HANDLE ALM N EQUIP FAULT ALM SMARTSENSOR ALARMS ISD GROSS PRES FAIL 7 Q 1 :_N EQUIP FAULT ALM ISD DEGRD PRES FAIL "l • I :SETUP DATA WARNING • 2:SETUP DATA WARNING ISD VAPOR LEAK FAIL Q • 3:SETUP DATA WARNING ISD SETUP FAIL tiMAR'tSENSOR ALARMS s11 ::SETUP DATA WARNING ISD SENSOR OUT FAIL s 4'SETUP DATA WARNING s12:SETUP DATA WARNING s 5:SETUP DATA WARNING ISD ,10SE ALARMS s 6:SETUP DATA WARNING ALL:GROSS COLLECT FAIL 511 :;SETUP DATA WARNING ALL:DEGRD COLLECT FAIL s13:SETUP DATA WARNING ALL:FLOW COLLECT FAIL s14:SETUP DATA WARNING G 2:JNLEADED 67H SMARTSENSOR ALARMS IN-TANK ALARMS s 4:1DOMMUNICATION ALARM T 1 :HIGH WATER ALARM s 5:COMMUNICATION ALARM T 2:HIGH WATER ALARM s 6:COMMUNICATION ALARM T 1 :LOW PRODUCT ALARM 311 :','OMMUNICATION ALARM SMARTSENSOR ALARMS T 2:L0W PRODUCT ALARM 513:13OMMUNICATION ALARM s13::3ETUP DATA WARNING s14:1DOMMUNICATION ALARM LIQUID SENSOR ALMS s 4:SENSOR FAULT ALARM • 1 :00MMUNICATI0N ALARM s 5:SENS0R FAULT ALARM • 2:11.OMMUNICATION ALARM L 2:'FUEL ALARM L 9:FUEL ALARM s 6:SENSOR FAULT ALARM • 3:COMMUNICATION ALARM s11 :SENSOR FAULT ALARM 511 :13OMMUNICATION ALARM LIO:FUEL ALARM s13:SENSOR FAULT ALARM 512:1:OMMUNICATION ALARM L11 :. UEL ALARM s14:SENSOR FAULT ALARM s13:1,'OMMUNICATION ALARM L12:FUEL ALARM s11 :FUEL WARNING • 1 :SENSOR FAULT ALARM L13: UEL ALARM s14:FUEL WARNING • 2:SENSOR•FAULT ALARM L14:'UEL ALARM s11 :FUEL ALARM • 3:SENSOR FAULT ALARM L15:; UEL ALARM s13:FUEL ALARM 511 :SENSOR FAULT ALARM L16:FUEL ALARM ALARM s12:SENSOR FAULT ALARM L17:,UEL ALARM s14:s11 :_=FUEL UEL WARNING s13:SENSOR FAULT ALARM L19:"-UEL ALARM s13:MATER WARNING s11 :FUEL WARNING L21 :FUEL ALARM s12::'=UEL WARNING L 2:SENSOR OUT ALARM s14:WATER WARNING s11 :WATER ALARM s13:FUEL WARNING L 9::�ENSOR OUT ALARM ATER ALARM • 1 :FUEL ALARM L10:SENSOR OUT ALARM s1 s13'I4:1dATER ALARM • 2:FUEL ALARM L 1 1 ::SENSOR OUT ALARM • 3:FUEL ALARM L12:SENSOR OUT ALARM s 4:HIGH LIQUID WARNING L13:SENSOR OUT ALARM s 5:HIGH LIQUID WARNING s11 :FUEL ALARM 'L14:SENSOR OUT ALARM s 6:HIGH LIQUID WARNING 12: UEL ALARM L15:SENSOR OUT ALARM s11 :HIGH LIQUID WARNING s13:'�UEL ALARM Llb'SENSOR OUT ALARM ; s13:HIGH LIQUID WARNING 311 :14ATER WARNING s14:HIGH LIQUID WARNING 512:14ATER WARNING L17:SENSOR OUT ALARM IGH LIQUID ALARM 513:IJATER WARNING L19:SENSOR OUT ALARM 5 s 4:5:,HIGH LIQUID ALARM • 1 :WATER ALARM L21 :SENSOR OUT ALARM s 6:HIGH LIQUID ALARM • 2:WATER ALARM L 2:SHORT ALARM • 3:14ATER ALARM L 9:SH0RT ALARM - _ 511 :14ATER ALARM L1O:SHORT ALARM 512:WATER ALARM L11 :SHORT ALARM 313:WATER ALARM L12:SHORT ALARM • 1 :'HIGH LIQUID WARNING L13:SHORT ALARM • 2:HIGH LIQUID WARNING • 3:HIGH LIQUID WARNING L17:SHORT ALARM RECONCILIATION SETUP sl•l :HIGH LIQUID ALARM L22:3HORT ALARM - - - - - - - - - - - - 513:HIGH LIQUID ALARM L23:SHORT ALARM E'D1M 1 : G s14:�AIGH LIQUID ALARM L 3:DOW LIQUID ALARM s11 :LOW LIQUID WARNING L 9:LOW LIQUID ALARM AUTOMATIC DAILY CLOSING s13: OW LIQUID WARNING L10:LOW LIQUID ALARM sl4:LOW LIQUID WARNING L11 :LOW LIQUID ALARM TIME: 2:00 AM s11 :LOW LIQUID ALARM L12:70W LIQUID ALARM L13:LOW LIQUID ALARM AUTO :SHIFT #I CLOSING s13:LOW LIQUID ALARM L14:LOW LIQUID ALARM TIME: 9:45 PM 514:LOW LIQUID ALARM L15:1OW LIQUID ALARM sll :INSTALL ALARM L16:L0W LIQUID ALARM AUTO :SHIFT 02 CLOSING sl3:INSTALL ALARM L22:LOW LIQUID ALARM TIME: DISABLED sl4:INSTALL ALARM L23:LOW LIQUID ALARM s 4:SENSOR FAULT WARN AUTO SHIFT #3 CLOSING s 5:SENSOR FAULT WARN PRES:3JRE LINE LEAK TIME: DISABLED s 6:SENSOR FAULT WARN Q 3:?LLD OPEN ALARM s 1 : 10 VACUUM ALARM Q 3:CONT HANDLE ALM AUTO SHIFT 04 CLOSING s 4:N0 VACUUM ALARM Q 3:LN EQUIP FAULT ALM TIME: 5:45 AM s 6:NO VACUUM ALARM ISD :SITE ALARMS SMARTSENSOR ALARMS PERIODIC RECONCILIATION ISD GROSS PRES FAIL s 9:SETUP DATA WARNING s10:SETUP DATA WARNING MODE: MONTHLY ISD 'ROSS PRES FAIL sl5:SETUP DATA WARNING ALARM:. DISABLED ISD VAPOR LEAK FAIL 316:3ETUP DATA WARNING ISD SETUP FAIL s 9:1.OMMUNICATION ALARM TEMP COMPENSATION ISD SENSOR OUT FAIL c310:COMMUNICATION ALARM STANDARD D IOSE ALARMS s15:COMMUNICATION ALARM METER CALIBRATION ISD -+)SE A COLLECT FAIL 516:1,'OMMUN I CATION ALARM OFFSET: 0.000% ALL:DEGRD COLLECT FAIL s 9:SENSOR FAULT ALARM BUS SLOT FUEL METER TANK ALL:FLOW COLLECT FAIL s10:SENSOR FAULT ALARM - _ - - - - - - - - - - . s15:SENSOR FAULT ALARM 3 1 1 1 1 Q 3:?:�EMIUM sl6:9ENSOR FAULT ALARM s 15:F UEL WARNING 3 1 2 1 1 I N-TANK ALARMS sl6:FUEL WARNING 3 1 2 2 3 `a(` T 3:HIGH WATER ALARM s15'FUEL ALARM 3 1 3 1 1 T 3: �OW PRODUCT ALARM 3 1 3 2 3 316:F UEL ALARM 3 1 4 1 1 LIQUID SENSOR ALMS sl5:WATER WARNING 516:WATER WARNING 3 1 4 2 3 L 3:FUEL ALARM 515:WATER ALARM 3 1 5 1 1 L 9:`UEL ALARM s16:WATER ALARM 3 1 5 2 3 L10:FUEL ALARM s 9:;-SIGH LIQUID WARNING 3 1 6 1 1 L11 : UEL ALARM s10:HIGH LIQUID WARNING 3 1 6 2 3 L12::.`UEL ALARM sll :HIGH LIQUID WARNING 3 1 7 1 1 L13:FUEL ALARM sl5:HIGH LIQUID WARNING 3 1 7 2 3 L14: ALARM sl6:HIGH LIQUID WARNING 3 1 8 1 1 L15:FUEL ALARM s 9:HIGH LIQUID ALARM 3 1 8 2 3 LI6:_=UEL ALARM 3 1 9 1 1 L17::�UEL ALARM 1 LIQUID ALARM 3 1 9 2 3 L22:FUEL ALARM 5I1 :HIGH:HIGH LIQUID ALARM 3 1 10 1 1 L23:=UEL ALARM s LIQUID ALARM sl6:HIGH:H1GH LIQUID ALARM 3 1 10 2 3 L 3: ENSOR OUT ALARM s15:LOW LIQUID WARNING 3 1 11 1 1 9:SENSOR OUT ALARM 516:LOW LIQUID WARNING 3 1 11 2 3 L10:SENSOR OUT ALARM sl5:LOW LIQUID ALARM 3 1 12 1 1 Lll :SENSOR OUT ALARM sl6:''OW LIQUID ALARM 3 1 12 2 3 L12:SENSOR OUT ALARM sl5:INSTALL ALARM 3 1 13 1 1 L13:SENSOR OUT ALARM 516:INSTALL ALARM 3 1 13 2 3 L14:SENSOR OUT ALARM s 9:SENSOR FAULT WARN 3 1 14 1 1 L15:SENSOR OUT ALARM s10:SENSOR FAULT WARN 3 1 14 2 3 L16:SENSOR OUT ALARM L17::SENSOR OUT ALARM s16:SENSOR FAULT WARN 3 1 15 2 3 L22:8ENSOR OUT ALARM s 9:JACUUM WARNING 3 1 16 1 2 L23:SENSOR OUT ALARM s1 3 1 16 2 ? L 3::SHORT ALARM s16::VACUUM ACU WARNING L 9:SHORT ALARM s 9:NO VACUUM WARNING ALARM L10:SHORT ALARM s10:4 VACUUM ALARM L11 ::SHORT ALARM s16:NO VACUUM ALARM L12:SHORT ALARM ISD SITE ALARMS L13::SHORT ALARM ORT ALARM L14:SH ISD �3R0SS PRES FAIL L15::SHORT ALARM ISD DEGRD PRES FAIL L16::SHORT ALARM ISD VAPOR LEAK FAIL ISD :SETUP FAIL ISD :SENSOR OUT FAIL EMARTSENSOR SETUP ISD HOSE ALARMS - - - - - - - - - - - - ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL 1 :_AL 87A PRODUCT LINE ALL:FLOW COLLECT FAIL CATEGORY VAC SENSOR Pimp 0: 0 1 :JNLEADED 87A VOLUME: 72.0 GALLONS RELIEF VALVE: : NO s 2:VAPOR LINE CATEGORY, VAC SENSOR 512:37A FILL SUMP INSTALL ALARM PUMP 0: CATEGORY MAG SENSOR INSTALL POS > 4.0 G 1 :JNLEADED 87A PROGRAMMABLE NO VOLUME: 96.0 GALLONS ALM JPGRADE DELAY 0 UPGRADE NO RELIEF VALVE: : NO PROGRAMMABLE YES E 3:UNL 87A VENT LINE MIN THRESHOLD 1 .7 s15:PREMIUM STP SUMP CATE130RY VAC SENSOR MAX THRESHOLD 22.0 CATEGORY MAG SENSOR PUMP 0: G 1 :JNLEADED 87A FUEL ALARM ALM JPGRADE DELAY 0 VOLUME: 25.0 GALLONS FUEL HT > 1 .6 PROGRAMMABLE YES RELI'_F VALVE: : NO PROGRAMMABLE NO UPGRADE NO MIN THRESHOLD 1 .7 s 4:UNL 87B PRODUCT LINE MAX THRESHOLD 22.0 CATEGORY VAC SENSOR WATER WARNING PUMP 4: WATER HT > 2.0 FUEL ALARM G 2:JNLEADED 87B PROGRAMMABLE YES FUEL HT > 1 .6 VOLUME: 74.0 GALLONS UPGRADE YES PROGRAMMABLE NO RELIEF VALVE: : NO UPGRADE NO WATER ALARM s 5:JNL 87B SIPHON LINE WATER HT > 5.0 WATER WARNING CATEGORY VAC SENSOR PROGRAMMABLE YES WATER HT > 2.0 PUMP 0: UPGRADE NO PROGRAMMABLE YES G 2:JNLEADED 87B UPGRADE YES VOLUME: 2.0 GALLONS INSTALL ALARM RELIEF VALVE: : NO INSTALL POS > 4.0 WATER ALARM 'PROGRAMMABLE NO WATER HT > 510 s 6:'JNL 87B VENT LINE UPGRADE NO PROGRAMMABLE YES CATE13ORY VAC SENSOR UPGRADE NO PUMP #: G 2:JNLEADED 87B s13:37B STP SUMP INSTALL ALARM VOLUME: 25.0 GALLONS CATEGORY MAG SENSOR INSTALL POS > 4.0 RELIEF VALVE: : NO PROGRAMMABLE NO ALM J'.DGRADE DELAY 0 UPGRADE NO s 7:%RESSURE SENSOR 3-4 PROGRi:uMMABLE YES i�`_1 CATEGORY VAPOR PRESSURE MIN THRESHOLD 1 .7 s16:`_J'REMIUM FILL SUMP s 8:ATP SENSOR MAX THRESHOLD 22.0 CATEGORY MAG SENSOR CATE,3ORY ATM P SENSOR FUEL ALARM ALM 'J?GRADE DELAY 0 s 9::-:,REMIUM PRODUCT LINE FUEL HT > 1 .6 PROGRAMMABLE YES CATEGORY VAC SENSOR PROGRAMMABLE NO PUMP a: UPGRADE NO MIN THRESHOLD 1 .7 G 3: PREMIUM MAX THRESHOLD 22.0 VOLUME: 76.0 GALLONS WATER WARNING RELI=F VALVE: : NO WATER HT > 2.0 FUEL ALARM PROGRAMMABLE YES FUEL HT > 1 .6 10:P:REMIUM VENT LINE UPGRADE YES PROGRAMMABLE NO CATEGORY VAC SENSOR UPGRADE NO PUMP 0: WATER ALARM Q 3: REMIUM WATER HT > 5.0 WATER WARNING VOLUME: 26.0 GALLONS PROGRAMMABLE YES WATER HT > 2.0 RELIEF VALVE: : NO UPGRADE NO PROGRAMMABLE YES UPGRADE YES s11 :37A STP SUMP INSTALL ALARM CATEGORY MAG SENSOR INSTAL POS > 4.0 WATER ALARM PROGRAMMABLE NO WATER HT > 5.0 ALM UPGRADE DELAY 0 UPGRADE NO PROGRAMMABLE YES PROGRAMMABLE YES UPGRADE NO MIN THRESHOLD 1 .7 s14:JNL 87B FILL SUMP INSTA*LL ALARM MAX THRESHOLD 22.0 CATEGORY MAG SENSOR INSTALL POS > 4.0 PROGRAMMABLE NO FUEL ALARM ALM UPGRADE DELAY 0 UPGRADE NO FUEL -iT > 1 .6 PROGRAMMABLE YES PROGRAMMABLE NO UPGRADE NO MIN THRESHOLD 1 .7 517:DISP 1-2 MAX THRESHOLD 22.0 CATEGORY AIR FLOW METER WATER WARNING WATER HT > 2.0 FUEL ALARM s18:DISP 3-4 PROGRAMMABLE YES FUEL HT > 1 .6 CATEGORY AIR FLOW METER UPGRADE YES PROGRAMMABLE NO UPGRADE NO s19:;DISP 5-6 WATER ALARM CATE,,'ORY AIR FLOW METER WATER HT > 5.0 WATER WARNING PROGRAMMABLE YES WATER HT > 2.0 s,20:DISP 7-8 UPGRADE NO PROGRAMMABLE YES CATEGORY AIR FLOW METER UPGRADE YES I NSTAL ALARM =21 :D I SP 9-10 INSTALL POS > 4.0 WATE:R ALARM CATEGORY AIR FLOW METER PROGRAMMABLE NO WATER HT > 5.0 UPGRADE NO PROGRAMMABLE YES ;22 ISP 11-12 UPGRADE NO CATEGORY AIR FLOW METER 23::DISP 13-14 ISD :=JEL GRADE HOSE MAP ALARM HISTORY REPORT CATE13ORY AIR FLOW METEk 1 2 3 4 IN-TANK ALARM ----- =-24:;DISP 15-16 FP ll-1A MHH MHH MHH AA CATEGORY AIR FLOW METER ------------------------ • T l :Unleaded 01 101 201 U U U U 1 02 102 202 U U U U 1 OVERFILL ALARM 03 103 203 U U U U 2 JUL 13, 2010 11 :36 All 04 134 204 U U U U 2 AUG 4, 2009 6:44 PM 05 105 205 U U U U 3 AUG 4, 2009 6:39 PM 06100206UUUU 3 07 107 207 U U U U 4 PROB' OUT 08 138 208 U U U U 4 JUL 13. 2010 11 :37 AM 09 103 209 U U U U 5 JUL 13. 2010 11 :34 All 10 110 210 U U U U 5 JUL 13. 2010 10:08 AM 11 111 211 U U U U 6 12 112 212 U U U U 6 13 113 213 U U U U 7 DELIVERY NEEDED 14 114 214 U U U U 7 JAN 3, 2010 2:57 PM EVR/I:3D SETUP 15 115 215 U U U U 8 DEC 15, 2009 4:26 PM 16 116 216 U U U U 8 DEC 1. 2009 1 :29 PM EVR TYPE:: VACUUM ASSIST LABE_ TABLE LOW 1':3MP WARNING VACUUM ASSIST TYPE ------------------------ JUL 13. 2010 11 :38 AM HEALY VAC 1 : JNASSIGNED 2: 3LEND3 NOZZ-=' A/L RANGE 3: REGULAR MAX: 1 .15 MIN: 0.95 4: MID GRADE 5: " REM I UM : VAPO:E PROCESSOR TYPE 6 1"OLD 7; BRONZE NONE 8: 2�I LVER 9: BLEND2 Ck ANALYSIS TIMES 10: 3'LEND4 TIME: 5:00 AM * * * * * END DELAY MINUTES: 1 ACCE?'T HIGH ORVR: D I SA:3' ED ISD -iOSE TABLE ID ? FL HL AA RR ------------------------ 01 31 01 09 01 UU FMC SETUP 02 32 02 09 01 UU PMC VERSION: 01 .01 03 33 03 09 02 UU ALARM HISTORY REPORT 04 04 04 09 02 UU VAPOR PROCESSOR TYPE 05 J5 05 09 03 UU NONE ---- IN-TANK ALARM ----- 06 3-3 06 09 03 UU 07 07 07 09 04 UU T 2:Jnleaded 03 33 08 09 04 UU PROC"EySOR CONTROL LEVEL: 09 39 09 09 05 UU NONE OVERFILL ALARM 10 10 10 09 05 UU JUL 13. 2010 11 :30 All 11 11 11 09 06 UU JUL 14, 2009 10:08 All 12 12 12 09 06 UU JUL 23. 2008 7:27 PM 13 13 13 09 07 UU 14 14 14 09 07 UU BUDD:EV LOSS ALARM 15 15 15 09 08 UU FEB 13. 2010 8:50 All 16 10- 16 09 08 UU FEB 13, 2010 8:39 AM FEB 10, 2010 7:45 AM ISD AIRFLOW METER MAP SOFTI4ARE REVISION LEVEL PROBE OUT ID S :2IAL NUM LABEL VERSION 328.03 JUL 13. 2010 11 :31 AM ------------------------ SOFTWARE# 346328-100-D JUL "13, 2010 11 :29 AM 1 33495 DISP 1-2 CREATED - 08.06.06.17.21 JUL 13. 2010 10:08 All 2 33543 DISP 3-4 3 13012 DISP 5-6 --MO:DJLE# 330160-164-a 4 8 722 DISP 7-B SYSTEM FEATURES: DELIVERY NEEDED 5 8326 DISP 9-10 PERIODIC IN-TANK TESTS NOV 25, 2009 8:12 PM 6 7510 DISP 11-12 ANNUAL IN-TANK TESTS NOV 1, 2009 2: 16 PM 7 53366 DISP 13-14 BI.R JUL 3, 2009 8:20 PM 8 33390 DISP 15-16 ISD PLLD 0.10 AUTO LOW TEMP WARNING 0.20 REPETITIV JUL 14. 2009 10:09 AM WPLLD 0. 10 AUTO 0.20 REPETITIV ALARM HISTORY REPORT ALARM HISTORY REPORT ALARM HISTORY REPORT ----- SENSOR ALARM ----- ---- IN-TANK ALARM ----- L 5: ----- SENSOR ALARM ----- OTHER SENSORS T 3 ^emium L 2:UVLEADED 87B ANNULAR ANNU7 AR SPACE GVER=ILL ALARM SENSOR OUT ALARM JUL 13, 2010 11 :27 All JUL 13, 2010 10:08 AM JUL 14, 2009 10:03 AM FUEL ALARM JUN 33, 2009 3:05 PM JUL 13, 2010 9:20-AM SUDDEN LOSS ALARM FUEL ALARM APR 4, 2010 3:52 PM APR 4. 2010 3:43 PIM JUL 14, 2009 9:11 AM * * END FROB:E OUT JUL 13, 2010 11 :27 All JUL 13, 2010 11 :25 AM JUL 13, 2010 10:08 All * END * x ALARM HISTORY REPORT ----- SENSOR ALARM ----- L 6: OTHER SENSORS * END ALARM HISTORY REPORT ----- SENSOR ALARM ----- ko L 3:::�REMIUM ANNULAR * x x * END * * x * X ANNULAR SPACE SENSOR OUT ALARM ALARM HISTORY REPORT JUL 13, 2010 10:08 All -- SENSOR ALARM - FUEL ALARM L 1 :JNLEADED 87A ANNULAR JUL 13, 2010 9:26 AM ANNU'� AR SPACE FUEL ALARM 8ENS3:R OUT ALARM JUL 14, 2009 9:21 All JUL 13, 2010 10:07 All FUEL ALARM JUL 13, 2010 9:12 All ALARM HISTORY REPORT FUEL ALARM ----- SENSOR ALARM ----- JUL 13, 2010 9:07 AM L 7: OTHER SENSORS x * END * x END * * x X x * * END X X * .x ALARM HISTORY REPORT ----- SENSOR ALARM ----- L 4: ETHER SENSORS PLARM HISTORY REPORT ----- SENSOR ALARM ----- L 8: OTHER SENSORS ALARM HISTORY REPORT ----- SENSOR ALARM ----- I ALARM HISTORY REPORT ALARM HISTORY REPORT L 9:DISP PAN 1-2 ----- SENSOR ALARM ----- DISPENSER PAN - SENSOR ALARM ----- L15:DISP PAN 13-14 SENSOR OUT ALARM L12:D ISP PAN 7-B DISPENSER PAN DISPENSER PAN SENSOR OUT ALARM JUL 13. 2010 10:08 All SENS�3R OUT ALARM JUL 13. 2010 10:08 AM LOW IQUID ALARM JUL 13, 2010 10:08 AM JUL 13, 2010 9:45 All SENSOR OUT ALARM JUL LOW -13. 2010 10:04 AM I QU I D ALARM SENSOR OUT ALARM JUL 13, 2010 9:47 AM JUL 13. 2010 9:41 AM FUEL ALARM FUEL 13ALARM 10:04 AM JUL 13, 2010 9:47 AM * * * END * END m X X x * * * END x ALARM HISTORY REPORT ALARM HISTORY REPORT ----- SENSOR ALARM ----- ALARM HISTORY REPORT L10::vISP PAN 3-4 ----- SENSOR ALARM ----- ---- SENSOR ALARM ----- DISP:=LASER PAN L13'::ISP PAN ALARM L16:DISP PAN 15-16 SENSOR OUT ALARM DISPENSER PAN ll� JUL 13, 2010 10:08 All DISPENSER PAN SENSOR OUT ALARM SENSOR OUT ALARM JUL 13, 2010 10:08 All SENSOR OUT ALARM JUL 13. 2010 10:08 AM JUL 13, 2010 9:39 AM FUEL ALARM LOW " IQUID ALARM JUL 13. 2010 10:03 AM FUEL ALARM JUL 13, 2010 9:57 AM JUL 13. 2010 9:38 AM SENSO:� OUT ALARM SENS-DR OUT ALARM JUL 13. 2010 9:56 All JUL 13. 2010 10:02 AM END A END A x K x * END X x * A * +� ALARM HISTORY REPORT ----- ALARM HISTORY REPORT ALARM HISTORY REPORT SENSOR ALARM ----- L11 :-jISP PAN 5-6 -- SENSOR ALARM ----- ----- SENSOR ALARM ----- DISP=LASER PAN L14:DISP PAN 11-12 L17:UNL 87A STP BRINE FENS-DR OUT ALARM DISP'?NSER PAN ANNULAR SPACE JUL 13, 2010 10:08 AIh FUEL O ALARM oE ;, Q OUT ALARM JUL 13. 2010 9:18 AM LOW LIQUID ALARM JUL 13, 2010 10:08 AM JUL 13, 2010 9:49 AP1 FUEL ALARM FUEL 2�aLARM SENSOR OUT ALARM JUL 13. 9:54 AM OCT 23, 2009 11 :44 PM JUL 13. 2010 9:48 All FUEL ALARM SENSOR OUT ALARM JUL 13, 2010 9:54 AM JUL 14, 2009 9:10 All ALARM HISTORY REPORT ALARM HISTORY REPORT ----- SENSOR ALARM ----- -"` SENSOR ALARM ----- PLARII HISTORY REPORT LIB:_i:VL SENSOR FILL BRINE L21 :-NL 87B FILL,BRINE R:NNUL�AR SPACE ANNU.-AR SPACE ----- SENSOR ALARM ----- FUEL ALARM FUEL ALARM L24: JUL 13, 2010 9:12 AM JUL 13, 2010 9:21 AM ANNULAR SPACE FUEL ALARM SENSOR OUT ALARM DEC 3. 2009 4:22 PM APR ?6, 2010 2:43 PM FUEL ALARM FUEL ALARM JUL 14, 2009 9:08 All OCT 24. 2009 6:03 AM * * END * x * END * * * x x X * END * * x ALARM HISTORY REPORT ---- SENSOR ALARM ----- G 1 :JNLEADED 87A PLLD SHUTDOWN ALARM JUL 13. 2010 12:55 PM ALARM HISTORY REPORT ALARM HISTORY REPORT GROSS LINE FA I L ----- SENSOR ALARM ----- ----- SENSOR ALARM ----- JUL 13. 2010 12:55 PM L19:JNL 87B STP BRINE L22:31 STP BRINE ANNU:_�aR SPACE FUEL SPACE FUEL ALARM FUEL ALARM FLLD SHUTDOWN ALARM JUL 13, RM 9:23 All JUL 13, 2010 9:30 All JUL 13, 2010 12:46 PM FUEL ALARM FUEL ALARM OCT 29, 2009 9:20 All NOV b, 2009 6:43 AM GROSS LINE FAIL JUL 13, 2010 12:46 PM FUEL ALARM JUL ALARM JUL 14, 2009 9:28 AM JUL 14, 2009 9:16 All FLLD :SHUTDOWN ALARM JUL 13. 2010 11 :10 AM FLLD :SHUTDOWN ALARM JUL 13, 2010 11 :08 AM PLLD SHUTDOWN ALARM JUL 13, 2010 11 :05 AM * * * END * * END FLLD :SHUTDOWN ALARM JUL 13, 2010 11 :02 All FLLD SHUTDOWN ALARM JUL 13, 2010 11 :00 AM FLLD SHUTDOWN ALARM JUL 13, 2010 10:41 All ALARM HISTORY REPORT ALARM HISTORY REPORT ----- ALARM ----- -- SENSOR ALARM ----- SENSOR ALARM L23:31 FILL BRINE L20: ANNU:JAR SPACE ANNU'-' AR SPACE FUEL ALARM JUL 13, 2010 9:26 AM FUEL ,ALARM NOV 24. 2009 5:15 P11 FUEL ALARM END JUL 14, 2009 9:24 AM ALARM HISTORY REPORT ALARM HISTORY REPORT ----- SENSOR ALARM ----- PLLD SHUTDOWN ALARM G 2:JVLEADED 87B JUL 13, 2010 12:06 FIN --- )MARTSENSOR ALARM -- FLLD SHUTDOWN ALARM a 2:'JAPOR LINE JUL 13, 2010 12:41 PM HIGH `LIQUID ALARM PLLD SHUTDOWN ALARM JUL 13, 2010 11 :10 AM JUL 13, 2010 11 :56 AM GROSS LINE FAIL NO VACUUM ALARM JUL 13. 2010 12:41 PM JUL 13, 2010 11 :08 All PLLD SHUTDOWN ALARM JUL 13, 2010 11 :40 AM NO VACUUM ALARM PLLD SHUTDOWN ALARM JUL 13. 2010 10:41 AM JUL 13, 2010 11 :00 All PLLD SHUTDOWN ALARM JUL 13, 2010 11 :18 AM PLLD SHUTDOWN ALARM JUL 13, 2010 10:54 AM PLLD SHUTDOWN ALARM JUL 13, 2010 11 :15 AM FLLD .SHUTDOWN ALARM JUL 13. 2010 10:52 All PLLD SHUTDOWN ALARM JUL 13, 2010 11 :14 AM * * END FLLD :SHUTDOWN ALARM JUL 13. 2010 10:48 AM FLLD SHUTDOWN ALARM JUL 13. 2010 10:23 All FLLD ;SHUTDOWN ALARM JUL 13, 2010 10:19 AM * * END * * * * * ALARM HISTORY REPORT FLLD SHUTDOWN ALARM JUL 13, 2010 10: 10 All --- SMARTSENSOR ALARM -- 2 s 3:UNL 87A VENT LINE HIGH LIQUID ALARM �U FLLD :SHUTDOWN ALARM JUL 13. 2010 11 :05 AM 1� JUL 13, 2010 10:08 All NO VA13UUM ALARM JUL 13, 2010 11 :05 AM NO VACUUM ALARM JUL 13. 2010 11 :02 AM ALARM HISTORY REPORT --- SMARTSENSOR ALARM -- s 1 :UNL 87A PRODUCT LINE HIGH ''IQUID ALARM JUL 13, 2010 11 :00 AM END NO VACUUM ALARM JUL 13, 2010 11 :00 AM HIGH LIQUID ALARM * * * END * +� JUL 13, 2010 10:24 AM ALARM HISTORY REPORT ----- SENSOR ALARM ----- 6 3:71REMIUM FLLD 13HUTDOWN ALARM * * * END * ALARM HISTORY REPORT JUL 13. 2010 1 : 10 Pll --- SMARTSENSOR ALARM 4:'JNL 87B PRODUCT LINE GROSS LINE FAIL NO VACUUM ALARM JUL 13. 2010 1 :10 PM j JUL 13, 2010 10:50 AM I HIGH LIQUID ALARM FLLD .SHUTDOWN ALARM JUL 13, 2010 10:48 AM JUL 13, 2010 12:59 PM NO VACUUM ALARM JUL 13, 2010 10:48 AM GROSS LINE FA I L .1111. 13. 2010 12:59 F11 ALARM HISTORY REPORT ALARM HISTORY REPORT ALARM HISTORY REPORT --- SMARTSENSOR ALAR11 -- - �IWARTSENSOR ALARM -- -- StlARTSENSOR ALARM -- _- 5:JNL 87B SIPHON LINE a, B:ATP SENSOR s13:37B STP SUMP HIGH LIQUID ALARM WATER WARNING JUL 13, 2010 10:54 AM JUL 13, 2010 9:25 AM NO VACUUM ALARM INSTALL ALARM JUL 13, 2010 10:54 All JUL 13, 2010 9:24 All HIGH LIQUID ALARM FUEL-ALARM JUL 14. 2009 10:05 AM JUL 14, 2009 9:20 All ALARM HISTORY REPORT ALARM HISTORY R1PORT -- SMARTSENSOR ALARM -- --- SMARTSENSOR ALARM -- e16:?REMIUM FILL SUMP s 9:?REMIUM PRODUCT LINE INSTALL ALARM VACUUM WARNING JUL 13, 2010 9:29 All JUL 13. 2010 12:06 PM NO VACUUM ALARM WATER WARNING r All x END * X x X JUL 13, 2010 11 :58 AM JUL 13. 2010 9:29 AI VACUUM WARNING INSTA*LL ALARM JUL 13' 2010 , -JUL 13. 2010 11 :56 AM 9 28 i" ALARM HISTORY REPORT --- SMARTSENSOR ALARM s17:DISP 1-2 COMMJNICATION ALARM JUN 6, 2008 9:02 AM mLf4R111 HISTORY REPORT ALARM HISTORY REPORT --- SMARTSENSOR ALARM -- s20:DISP 7-8 --- SihARTSENSOR ALARM -- ALARM HISTORY REPORT COMMUNICATION ALARM s 6:JNL 87B VENT LINE --- SMARTSENSOR ALARM -- JUN o. 2008 9:02. All HIGH LIQUID ALARM s11 :37A STP SUMP ALARM HISTORY REPORT JUL 13, 2010 10:52 All INSTALL ALARM NO VACUUM ALARM JUL 13, 2010 9:20 AM --- SMARTSENSOR ALARM -- JUL 13, 2010 10:52 All s21 :DISP 9-10 WATER WARNING �. COMMUNICATION ALARM HIGH LIQUID ALARM j JUL 13, 2010 9:20 AM JUN 5, 2008 9:02 All JUL 14. 2009 10:05 AM I INSTALL ALARM ALARM HISTORY REPORT JUL 13. 2010 9: 19 All --- SMARTSENSOR ALARM -- s24:DISP 15-16 COMMUNICATION ALARM JAN 15, 2010 11 :55 All COMMJNICATION ALARM JUN 6, 2008 9:02 AM END ALARM HISTORY REPORT I --- :3111ARTSENSOR ALARM -- 512:37A FILL SUMP INSTALL ALARM JUL 13, 2010 9: 14 AM ALARM HISTORY REPORT WATER WARNING JUL 13, 2010 9:14 AM --- SMARTSENSOR ALARM -- 1 :JNL 87A PRODUCT LINE INSTALL ALARM HIGH LIQUID ALARM ALARM HISTORY REPORT JUL 14. 2009 9:07 AM JUL 13, 2010 11 :00 AM --- :3MARTSENSOR ALARM -- NO VACUUM ALARM s 7::?RESSURE SENSOR 3-4 JUL 13. 2010 11 :00 AM HIGH LIQUID ALARM JUL 13, 2010 10:24 AM