MONITORING SYSTEM CERTIFICATION 75,E
For Use By All Jurisdictions Within the State of California
Authority Cited: Chapter 6 7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be
prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided
to the tank system owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems
within 30 days of this date.
A. General Information
Facility Name: #725 Fastrip#19 Bldg.No.:
Site Address: 4901 South Union Avenue City: Bakersfield Zip: 93307
Facility Contact Person: Omero Garcia Contact Phone No.: 661-393-7000
Make/Model of Monitoring System: Veeder-Root TLS 350 Date of Testing/Servicing: 7/14/2010
B. Inventory of Equipment Tested/Certified
Check the appropriate boxes to Indicate specific equipment inspected/serviced:
Tank ID: 12000 gal.Regular Tank ID: 12000 gal.Super
[X] In-Tank Gauging Probe. Model:847390-107 [x] In-Tank Gauging Probe. Model:847390-107
[x] Annular Space or Vault Probe. Model:794390-420 [X] Annular Space or Vault Sensor. Model: 794390-420
[x] Piping Sump/Trench Sensor(s). Model:794380-208 Piping Sump/Trench Sensor(s). Model: 794380-208
❑ Fill Sump Sensor(s) Model: ❑ Fill Sump Sensor(s). Model:
N Mechanical Line Leak Detector. Model:FX1v [x] Mechanical Line Leak Detector. Model: FXIv
❑ Electronic Line Leak Detector. Model: ❑ Electronic Line Leak Detector. Model:
L] Tank Overfill/High Level Sensor. Model:847390-107 [x] Tank Overfill/High Leval Sensor. Model: 847390-107
❑ Other(specify equip.type and model in Sec. E on Pg.2) ❑ Other(specify equip.type and model in Sec. E on Pg.2)
Tank ID: 12000 gal.Diesel Tank ID:
[x] In-Tank Gauging Probe. Mode 1:847390-107 ❑ In-Tank Gauging Probe. Model:
[x] Annular Space or Vault Sensor. Model:794390-420 ❑ Annular Space or Vault Sensor. Model:
[X] Piping Sump/Trench Sensor(s). Model:794380-208 ❑ Piping Sump/Trench Sensor(s). Model:
❑ Fill Sump Sensors(s). Model: ❑ Fill Sump Sensor(s). Model:
[x� Mechanical Line Leak Decector. Model:FX1V ❑ Mechanical Line Leak Detector. Model:
❑ Electronic Line Leak Detector. Model: ❑ Electronic Line Leak Detector. Model:
[x] Tank Overfill/High Level Sensor. Model:847390-107 ❑ Tank Overfill/High Level Sensor.Model:
❑ Other(specify equip.type and model in Sec. E on Pg. 2) ❑ Other(specify equip.typs and model in Sec. E on Pg.2)
Dispenser ID: 9&10 Dispenser ID: 11 &12
R Dispenser Containment Sensor(s). Model: 794380-208 [x] Dispenser Containment Sensor(s). Model: 794380-208
[x] Shear Valve(s). U Shear Valve(s).
❑ Dispenser Containment Float(s)and Chain(s). ❑ Dispenser Containment Float(s)and Chain(s)
Dispenser ID: 13&14 Dispenser ID: 15&16
[x] Dispenser Containment Sensor(s). Model: 794380-208 [x] Dispenser Containment Sensor(s). Model: 794380-208
[x] Shear Valve(s). E Shear Valve(s).
❑ Dispenser Containment Float(s)and Chains(s). ❑ Dispenser Containment Float(s)and Chain(s).
Dispenser ID: Dispenser ID:
❑ Dispenser Containment Sensor(s). Model: ❑ Dispenser Containment Sensor(s). Model:
❑ Shear Valve(s). ❑ Shear Valve(s).
❑ Dispenser Containment Float(s)and Chain(s) ❑ Dispenser Containment Float(s)and Chain(s).
*If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification -I certify that the equipment identified in this document was inspected/services in accordance with the
manufacturers'guidlines.Attached to this Certification is information(e.g.manufacturers'checklist)necessary to varify that
this information is correct and a plot plan showing the layout of monitoring equipment.For equipment capable of generating
such reports,I have attached a copy of the report; (check all that apply) Q Syst Set-up U rm history report
Technician Name(print): Bryan A Self Signature:
Certification No: 837501 License No:804904
Testing Company Name: Confidence UST Services,Inc. Phone o: 800-339-9930
Site Address: 4901 South Union Avenue,Bakersfield,CA 93307 76 late of Testing/Servicing: 7/14/2010
- - IIIIIIIIII�IIIIIII
I
D. Results of Testing/Servicing
Software Version Installed: 327.04
Complete the following checklist:
[X] Yes ❑ No* Is the audible alarm operational?
xj Yes No* Is the Visual alarm operational?
x Yes No* Were all sensors visually inspected,functionally tested,and confirmed operational?
1.1] Yes ❑ No* Were all sensors installed at the lowest point of secondary containment and positioned so that other
equipment will not interfere with their proper operation?
Yes No* If alarms are relayed to a remote monitoring station,is all communications equipment(e.g.modem)
Rx N/A operational?
LxJ Yes ❑ No* For pressurized piping systems,does the turbine automatically shut down if the piping secondary
❑N/A containment monitoring system detects a leak,fails to operate,or is electrically disconnected'?If yes:
which sensors initate positive shut-down? Lx]Sump/Trench Sensors[x]Dispenser Containment Sensors
Did you confirm positive shut-down due to leaks and sensor failure/disconnected? [x] Yes; ❑ No;
[X] Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device(i.e.no
L]N/A mechanical overfill prevention valve is installed),is the overfill warning alarm visual and audible at
the tank fill point(s)and operating properly?If so,at what percent of tank capasity does the alarm
trigger? 90
❑ Yes* U No Was any monitoring equipment replaced?If Yes,identify specific sensors,probes,or other equipment
replaced and list the manufacturer name and model for all replacement parts in Section E,below.
❑ Yes* E No Was liquid found inside any secondary containment systems designed as dry systems?
❑Product; Lx] Water.If yes,describe causes in Section E,below.
TX No* Was monitoring system set-up reviewed to ensure proper settings?Attach set-up reports,if applicable.
x yes No* I Is all monitoring equipment operational per manufacturer's specifications?
*In Section E below,discribe how and when these deficiencies were or will be corrected.
E. Comments:
F. In-Tank Guaging/SIR Equipment: [X] Check this box if tank guaging is used only for inventory control.
❑ Check this box if tank guaging or SIR equipment is installed.
This section must be completed if in-tank guaging equipment is used to perform leak detection monitoring.
Complete the following checklist:
PxYes ❑ No* Has all input wiring been inspected for proper enter and term ination,including testing for ground faults?
No* Were all tank guaging probes visually inspected for damage and residue buildup?
No* Was accuracy of system product level readings tested?
No* Was accuracy of system water level readings tested?
No* Were all probes reinstalled properly?
❑ No*I Were all items on the equipment manufacturer's maintenance checklist completed?
* In the Section H,below,describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD): ❑Check this box if LLD's are not installed.
Complete the following checklist:
[x] Yes ❑ No* For equip. start-up or annual equipment certification,was a leak simulated to varify LLD performance?
(Check all that apply) Simulated leak rate: Lx]3 g.p.h.: 00.1 g.p.h.; ❑0.2 g.p.h.;
x Yes No* Were all LLD's confirmed operational and accurate within regulatory requirments?
x Yes No* Was the testing apparatus property calibrated?
r] Yes No* For mac amca LLD's,does the LLD restrict product flow if it detects a leak?
N/A
[__j Yes No* For electronic LLD's,does the turbine automatically shut off if the LLD detects a leak?
[x] N/A
❑ Yes 7 No* For electronic LLD's,does the turbine automatically shut off if any portion of the monitoring system is
[x] N/A disabled or disconnected?
❑ Yes No* For electronic LLD's, does the turbine automatically shut off if any portion of the monitoring system
U N/A malfunction or fails a test?
❑ Yes No* For electronic LLD's,have all accessible wiring connections been visually inspected?
[X] N/A
x Yes I ONo I Were all items on the equipment manufacturer's maintenance checklist completed?
* In the section H,below,describe how and when these deficiencies were or will be corrected.
H. Comments:
FASTR I P 725 SYSTEM SETUP -----
4901 S.UIVION _ _ _ - - COMMUNICATIONS SETUP
BAKERSFIELD.CA JUL 14, 2010 3:35 PM - - - - - - - - - - - -
661-397-9387
JUL 14, '2010 3:34 PM
PORT SETTINGS:
SYSTEM UNITS
U.S. C0I111 BOARD : I !ED I M )
SYSTEll STATUS REPORT SYSTEM LANGUAGE RS-232 SECURITY
ENGLISH CODE : DISABLED
--SYSTEM DATE/TIME FORMAT
ALL FUNCTIONS. NORMAL IMON DI? YYYY HH:MPI:SS Al COMM BOARD 2 (RS-232)
J':+"EfJT 'RY' kEF':�h'T BAUD RATE 9600
]f
FASTRIP 725 PARITY NONE
4901 SUNION STOP BIT 1 STOP
T 1 :LIIVLEAL1ELi 7'35 BAXERSFIELD,CA DATA LENGTH: 8 DATA
F,_5_ 661-397=9387 - RS-232 SECURITY
52r6
VOLUME _ GALS CODE DISflBLEU.
ULLAGE = 6724 GALS SHIFT TIME 1 12:00 Aft y-
90%, ULLAGE= 5J24 GALS: SHIFT .TIME 2 DISABLED SABLED `:. + COMM;;BOARD 3 {RS-232)
TC VOLUME = 5189 GALS SHIFT -TIME 3 DISABLED BAUD RATE- -:-9600
HEIGHT = 43.45 INCHES SHIFT TIME 4 ;�DISABLED PARITY NONE
WATEP 'v C1L = 0 i_dALS
WATER = i 1 I NC:HFS STOP H'1 T '
:' 1 ST01
TEMP = L?EG TANK PER TST NEEDED WRN j DATA LENGTH': 8 DATA
DISABLED ., RS-232-SECURITY
TAN1, ANN;�T.ST,•-NEEDED`-WkNi s.`f CODE : DISABLED
T 2'PREMIUM 725 DISABLED,,'; *
VOLUME = 4448 C;HLS LINE RE-,tNABLE METHOD
ULLAGE = 7552 GALS AUTO TkAPJSNIIT SETTINGS:
90% ULLAGE= 6352 GALS PASS LdNE,TEST
Ti=' VOLUME = 4374 GALS AUTO LEAK ALARM LIMIT
HEIGHT = 38. 18 INCHES LINE PER TST NEEDED WRN
WATER VOL = l 14 GALS DISABLED AUTO HIGH WATER LIMIT
WATER = U, 4 INCHES LINE ANN TST NEEDED WRN DISABLED
TEMP = 83.8 DECD F DISABLED AUTO OVERFILL LIMIT
DISABLED
PRINT TC VOLUMES AUTO LOW PRODUCT
3:DIESEL 725 ENABLED DISABLED
T
VOLUME = 4273 GALS AUTO THEFT LIMIT
TEMP COMPENSATION-- DISABLED
ULLAGE = 7727 GALS VALUE (DEG F ) : -0.0 AUTO DELIVERY START
90. ULLAGE= 6,527 GAL:_ STICK HEIGHT OFFSET DISABLED
TC VOLUME = 4226 IACS DISABLED i AUTO DELIVERY END
HEIGHT = 37.05 INCHES ULLAGE: 90% I DISABLED
WATER VOL = l8 GALS AUTO EXTERNAL INPUT Old
WATER = 0,91 INCHES H-PROTOCOL DATA FORMAT DISABLED
TEMP = 04.2 D'~G F HEIGHT AUTO EXTERNAL INPUT OFF
DA''LIGHT SAVING TIMME DISABLED
ri y ri END :x * E14ABLED ? AUTO SENSOR FUEL ALARM
START DATE l DISABLED
MAR WEEK 2 SUN j AUTO SENSOR WATER ALARM
START TIME DISABLED
2:00 AM AUTO SENSOR OUT ALARM
END DATE DISABLED --
NOV WEEK 1 SUN
END TIME
2:00 AM
RE-DIRECT LVC:AL. RR'll'JTOUT
DISABLED
EURO PROTOCOL PREFIX
S RS-232 END OF MESSAGE
DISABLED
SYSTEM SECURITY'
CODE : 000000
MAINTENANCE HISTORY
DISABLED
TANK CHART SECURITY
DISABLED
+
CUSTOM ALARMS
DISABLED
MASS:DENSITY.
DISABLED,
IN—TANK SETUF �-
- — — T 2:PREMIUM 725 T 3:DIESEL 725
T 1 :UNLEADED 25 PRODUCT CODE 2 PRODUCT CODE 3
THERMAL COEFF : .000700 THERMAL COEFF : .000450
PRODUCT CODE i { TANK. DIAMETER 96.00 TANK DIAMETER 96.00
THERMAL COEFF : .000700 TANK PROFILE 1 PT
TANK DIAMETER 96.00 f FULL VOL 12000 TANK PROFILE � PT
TANK PROFILE 1 PT FULL VOL : 1 000
FULL l?OL 12000
FLOAT SIZE: 4.0 IN. FLOAT SIZE: 4.0 IN.
FLOAT SIZE: 4.0 IN. WATER WARNING : 2.0 ; 2,0
' HIGH WATER LIMIT: 3.0 WATER WARNING
WATER WARNING 2.0 HIGH WATER LIMIT: 3.0
HIGH WATER LIMIT: 3.0 MAX OR LABEL VOL: 12000
OVERFILL LIMIT 90% MAX LABEL VOL: 1000
MAX OR LABEL VOL: 12000 10800 OVERFILL LIMIT 900
OVERFILL LIMIT 90°i 10800
HIGH PRODUCT 90% HIGH PRODUCT 90r
10800 10800 10800
HIGH PRODUCT 90% 1 DELIVERY LIMIT 10% DELIVERY LIMIT lOro
10800 f 1200 1200
IiEL.I VERY L I I'1 I T 1 Oro
1200 LOW PRODUCT 1200 LOW PRODUCT : 1200
LEAK ALARM LIMIT: 99 LEAK ALARM LIMIT: 99
LOW PRODUCT 1200 SUDDEN LOSS LIMIT: 99
LEAK. ALARM LIMIT: 99 TANK TILT 0.00 SUDDEN LOSS LIMIT: 99
TANK TILT 0.00
SUDDEN LOSS LIMIT: 99 PROBE OFFSET 0.00
TANK TILT 0.00 PROBE OFFSET 0.00
PROBE OFFSET 0.00
SIPHON MARIFOLDED TANKS SIPHON MANIFOLDED TANKS
SIPHON MANIFOLDED TANKS T#. NONE T#: NONE
T#: NONE LINE MANIFOLDED TANKS LINE MANIFOLDED TANKS
T#: NONE T#: NONE
LINE MANIFOLDED TANKS
T#: NONE
LEAK M 1 IV PERIODIC: 010 LEAK MIN PERIODIC-. l i
120 120
LEAK MIN PERIODIC: 1%
120 LEAK MIN ANNUAL : In LEAK MIN ANNUAL 1
120 120
LEAK MIN ANNUAL : 1a
120
PERIODIC TEST TYPE PERIODIC TEST TYPE
PERIODIC TEST TYP€ STANDARD STANDARD
STANDARD ANNUAL.;TEST. FA.IL . , _ ANNUAL TEST FAIL
ANNUAL TEST FAIL ALARM DISABLED ALARM DISABLED
ALARM DISABLED PERIODIC TEST FAIL PERIODIC TEST FAIL
PERIODIC TEST FAIL ALARM DISABLED I ALARM DISABLED
ALARM DISABLED GROSS TEST FAIL GROSS TEST FAIL
CROSS TEST FAIL ALARM DISABLED ALARM DISABLED
ALARM DISABLED ANN -TEST AVERAGING^: .OFF. ANN TEST AVERAGING: OFF
TEST AVERAGING:ANN G: OFF
PER TEST AVERA,ING: OFF PER TEST AVERAGING: OFF
PER TEST AVERAGING: OFF TANY TEST NOTIFY: OFF TANI" TEST NOTIFY: OFF
TANK TEST NOTIFY: OFF :tTNK' TST SIPHON: BREAK:OFF. TNK TST SIPHON BREAK:OFF
T14K TST SIPHON BREAK:OFF DELIVERY DELAY 1 MIN DELIVERY DELAY I MIN
DELI'JERI' DELAY 1 MIN PUMP THRESHOLD : 10,00% PUMP 10.00f
PUMP THRESHOLD 10.00%
LEAK TEST METHOD OUTPUT RELAY. SETUP
- - _ - _ ._ - - - - - R 3:DIESEL
TEST ON DATE ALL TANK TYPE:
FEB 6, 2007 R 1 :UNLEADED STANDARD
START TIME : DISABLED TYPE: NORMALLY CLOSED-
TEST RATE :0.20 GAL/HR STANDARD
DURATION : 2 HOURS NORMALLY CLOSED TANK #: 3
TST EARLY STOP:DISABLED TANK #: I
LIQUID SENSOR ALMS
LEAK TEST REPORT FORMAT L 5:FUEL ALARM
NORHAL LIQUID SENSOR ALMS L 8:FUEL ALARM
L I :FUEL ALARM LIO:FUEL ALARM
L 7:FUEL ALARM L 5:SENSOR OUT 'ALARM
L S:FUEL ALARM L 9:SENSOR OUT ALARM
L 9:FUEL ALARM L10:SENSOR OUT ALARM
L10:FUEL ALARM L 5:SHORT ALARM
L 1 :SENSOR OUT ALARM L B:SHORT ALARM
L 7:SENSOR OUT ALARM L10:SHORT ALARM
L S:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM R 4:OVERFILL ALARM
L10:SENSOR OUT ALARM TYPE:
L 1 :SHORT ALARM STANDARD
LIQUID SENSOR SETUP L 7:SHORT ALARM NORMALLY OPEN
- - - - - - L 8:SHORT ALARM
L 9:SHORT ALARM TANK 0: NONE
L I :UNL STP L10:SHORT ALARM
TRI-STATE (SINGLE FLOAT)
CATEGORY STP SUI°1F' ISD SITE ALARMS IN-TANK ALARMS
ISD GROSS PRES FAIL ALL:OVERFILL ALARM
ISD DEGRD PRES FAIL ALL:HIGH PRODUCT ALARM
L 2:UNL ANN ISD VAPOR LEAK FAIL ALL:MAX PRODUCT ALARM
TRI-STATE (SINGLE FLOAT) ISD VP' PRES FAIL
CATEGORY : ANNULAR SPACE ISD VP STATUS FAIL
ISD-SETUP FAIL
ISD SENSOR OUT FAIL
L 3:PREM STP ISD HOSE ALARMS
TRI-STATE (SINGLE FLOAT) ALL:GROSS COLLECT FAIL
CATEGORY : STP SUMP ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
L 4:PREM ANN R 2:PREMIUM
TRI-STATE (SINGLE FLOAT) TYPE: SMARTSENSOR SETUP
CATEGORY : ANNULAR SPACE STANDARD - - ` - - - - - - - - -
NORMALLY CLOSED
s 1 :VP 11-12
TANK 0: 2 CATEGORY VAPOR PRESSURE
L 5:DSL STP
TRI-STATE (SINGLE FLOAT) s 2:FM 9-10
CATEGORY : STP SUMP LIQUID SENSOR:ALMS CATEGORY AIR FLOW METER,
L 3:FUEL ALARM
L 7:FUEL ALARM s 3:FM I1-12
L 6:DSL ANN L 8:FUEL ALARM CATEGORY AIR FLOW METER
TRI-STATE (SINGLE FLOAT) L 9:FUEL ALARM
CATEGORY : ANNULAR SPACE L10:FUEL ALARM s 4:FM 13-14
L 3:SENSOR OUT ALARM CATEGORY AIR FLOW METER
L 7:SENSOR OUT ALARM
L 8:SENSOR OUT ALARM s 5:FM 15-16
L 7:DISP 9-10 L 9:SENSOR OUT ALARM ` CATEGORY AIR FLOW METER
TRI-STATE (SINGLE FLOAT) L10:SENSOR OUT ALARM
CATEGORY : DISPENSER PAN L 3:SHORT ALARM
L 7:SHORT ALARM
L 8:SHORT ALARM
L 9:SHORT ALARM
L 8:DISP 11-12 L10:SHORT ALARM
TRI-STATE (SINGLE FLOAT)
CATEGORY : DISPENSER PAN ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
-ISD VAPOR LEAK FAIL
L 9:D1SP 13-14 ISD VP PRES FAIL
TRI-STATE (SINGLE FLOAT) ISD VP STATUS FAIL
CATEGORY : DISPENSER PAN ISD SETUP FAIL
ISD SENSOR OUT FAIL
ISD HOSE ALARMS
LIO:DISP 15-16 ALL:.GROSS COLLECT FAIL
NORMALLY CLOSED ALL:DEGRD COLLECT FAIL
CATEGORY : DISPENSER PAN ALL:FLOW COLLECT FAIL
PMC SETUP ALARM HISTORY REPORT
FEVR,,ISD SETUP '�CESSOR CONTROL LEVEL:
NONE f ---- IN-TANK ALARM -----
T 1 :UNLEADED 725
EVR TYPE: VACUUM ASSIST
VACUUM ASSIST TYPE SETUP DATA WARNING
HEALY VAC JUL 11, 2008 9:37 AM
NOZZLE A/L RANGE j OVERFILL ALARM
MAX: 1 .15 MIN: 0.95 JUN 26, 2010 1 :43 PM
�.,..�► ____--_ I JUN 19, 2010 11 :00 AM
VAPOR PROCESSOR TYPE I JUN 17, 2010 5:37 AM
NO VAPOR PROCESSOR SOFTWARE REVISION LEVEL
VERSION 327.64 LOW PRODUCT ALARM
SOFTWARE# 346327-100-E JUL 9, 2016 6:53 PM
ANALYSIS TIMES CREATED - 07.02.06.10.28 JUL 7. 2010 4:59 PM
TIME: 10:00 AM S-MODULE# 330160-004-a MAY 17, 2010 1 :10 PM
DELAY MINUTES: 1 SYSTEM FEATURES:
PERIODIC IN-TANK TESTS HIGH PRODUCT ALARM
JUL 14. 2010 1 :14 PM
ANNUAL IN-TANK TESTS
ACCEPT HIGH ORVR: JUN 25, 2010 1 :43 PM
DISABLED pM JUN 19, 2010 11 :.00 AM
ISD HOSE TABLE INVALID FUEL LEVEL
ID FP FL HL AA RR MAY 17. 2010 3:32 PM
-- ___.._.-- - _- _ MAR 4, 2010 4:34 PM
01 09 09 02 01 UU FEB 28, 2010 6:10 PM
02 10 10 02 01 UU
03 11 11 02 02 UU PROBE OUT
04 12 I2 02 02 UU JUL 14, 2010 1 :14 PM
05 17 13 02 03 UU JUL 14, 2010 12:39 PM
06 18 14 02 03 UU JUL 22, 2009 11 :46 AM
07 19 15 02 04 UU ALARM HISTORY REPORT
08 20 16 02 04 UU
-- SYSTEM ALARM ----- DELIVERY NEEDED
PAPER OUT JUL 92010 6:53 PM
ISD AIRFLOW METER MAP JUN 25, 2010 6:21 PM JUL 7, 2010 4:58 PM
ID SERIAL NUM LABEL PRINTER ERROR MAY 17, 2010 1 :10 PM
1 8639 FM 9-10 JUN 25, 2010 6:21 PM
2 14880 FM 11-12 LOW TEMP WARNING
3 8666 FM 13-14 JUL 14, 2010 1 :15 PM
4 8625 FM 15-16 JUL 17, 2008 10:06 AM
ISD FUEL GRADE HOSE MAP
1 2 3 4
FP MHH MHH MHH MHH AA
09 201 301 901 U U 1 * * * END
10 202 302 902 U U 1
11 203 303 903 5 U 2
12 204 304 904 5 U 2
17 205 305 905 U U 3 * * * END
18 206 306 906 U U 3
19 207.307 907 5 U 4
20 208 308 908 5 U 4
LABEL TABLE
1 : UNASSIGNED -
2: BLEND3
3: REGULAR
4: MID GRADE
5: PREMIUM
6: GOLD
7: BRONZE
8: SILVER
9: BLEND2
10: BLEND4
ALARM HISTORY REPORT ALARM HISTORY REPORT ALARM HISTORY REPORT
_.
---- IN-TANK ALARM ----- ____ IN-TANK ALARM ----- ----- SENSOR ALARM -----
L" 1':UNL STP
T 2:PREMIUM 725 T 3:DIESEL '725 STP SUMP `
FUEL ALARM
SETUP DATA WARNING SETUP DATA WARNING JUL 14, 2010 1 :02 PM
JUL lir 2008 9:37 AM JUL 11. 2008 9:38 AM
FUEL ALARM
LOW PRODUCT ALARM OVERFILL ALARM JUL 6. 2010 12:49 PM
APR 25, 2009 12:44 PM SEE 22, 2009 3:00 PM
! SETUP DATA WARNING
HIGH PRODUCT ALARM AUG 22. 2009 3:06 AM JUN 18. 2010 1 :59 PM
JUL 14, 2010 1 :15 PM MAY 29, 2008 i1 :45 PM
JUL 22. 2009 11 :36 AM LOW PRODUCT ALARM
JUL 17. 2008 10:08 AM
JUL 14. 2010 12:41 PM
INVALID FUEL LEVEL JUL 17, 2008 10:00 AM
JUL 14, 201Q 12:.41 PM
JUL 22, 2009 11 :49 AM HIGH PRODUCT ALARM
JUL 17, 2008 10:09 AM JUL 14, 2010 1 :16 PM
SEP 22. 2009 3:00 PM
PROBE OUT AUG 22. 2009 3:06 AM
JUL 14. 2010 1 :15 PM INVALID FUEL LEVEL * * END
JUL 14, 2010 12:41 PM
JUL 22. 2009 11 :48 AM JUL 17. 2006 10:00 AM
PROBE OUT
DELIVERY NEEDED JUL 14. 2010 1 :16 PM
APR 25, 2009 12:43 PM JUL 14. 2010 12:41 PM
JUL 22. 2009 11 :50 AM
i
LOW TEMP WARNING
JUL 14, 2010 1 :16 PM DELIVERY NEEDED
JUL 22, 2009 11 :33 AM JUL 14. 2010 12:41 PM
JUL 17, 2008 10:00 AM ALARM HISTORY REPORT
LOW TEMP WARNING
-- SENSOR ALARM -----JUL 14, 2010 1 :17 PM L 2:UNL ANN ANNULAR SPACE
JUL 17, 2008 10:10 AM i FUEL ALARM
JUL 14. 2010 1 :11 PM
FUEL ALARM
JAN 18. 2010 4:31 PM
* END X x x
FUEL ALARM
DEC 30, 2009 8:52 AM
* END
* * * END * x
ALARM HISTORY REPORT
---- IN-TANK ALARM -----
T 4:
*- * X. * END X X
rALARM H I STORY REPORT AARM H I STORY REPORT SENSOR AARM ----- ----- SENSOR ALARM ALARM HISTORY REPORT
L EM STP L 5:DSL STP
SUMP
STP SUMP FUEL ALARM I ----- SENSOR ALARM -----
FUEL ALARM JUL 14, 2010 1 :03 PM L 7:DISP 9-10
JUL 14, 2010 1 :02 PM DISPENSER PAN
FUEL ALARM FUEL ALARM
FUEL ALARM JUL 5, 2010 8:03 AM JUL 14. 2010 1 :06 PM
JAN 18, 2010 1 :25 PM
FUEL ALARM FUEL ALARM FUEL ALARM
JUL 22. 2009 .11 :03 AM JUL 22, 2009 11 :06 AM
JUL 22. 2009 11 :04 AM
FUEL ALARM
JUL 17. 2008 10:15 AM
* * * * * END * * x X
* * * END
* * x END
ALARM HISTORY REPORT ALARM HISTORY REPORT
----- SENSOR ALARM -----
----- SENSOR ALARM ----- L 6:DSL ANN ALARM HISTORY REPORT
L 4:PREM ANN ANNULAR SPACE SENSOR ALARM -----
ANNULAR SPACE FUEL ALARM
FUEL ALARM JUL 14. 2010 1 :11 PM L 8:DISP 11-12
JUL 14, 2010 1 :11 PM DISPENSER PAN
FUEL ALARM FUEL ALARM JUL 14
FUEL ALARM
JAN 24. 2010 10:48 AM 1 :05 PM
JUL 22, 2009 11 :09,.AM
SENSOR OUT ALARM FUEL ALARM
FUEL ALARM JAN 14, 2010 10:15 AM JUL 22, 2009 11 :05 AM ,.
JUL 17, 2008 10:14 AM
FUEL ALARM
JUL 17, 2008 10:22 AM
* �t END * X * x
* END
x �€ * END
ALARM HISTORY REPORT
----- SENSOR ALARM -----
L 9:D1SP 13-14
DISPENSER. PAN
SENSOR OUT ALARM
JUL 14, 2010 1 :20 PM
FUEL ALARM
JUL 14, 2010 1 :07 PM
FUEL ALARM
JUL 14. 2010 1 :07 PM
END
ALARM HISTORY REPORT
----- SENSOR ALARM -----
L10:DISP 15-16
DISPENSER PAN
FUEL ALARM
JUL 14, 2010 1 :20 PM
FUEL ALARM
JUL 14, 2010 1 :08 PM
FUEL ALARM
JUL 22, 2009 11 :08 AM
* * * END
1
f
SWRCB,January 2006
Spill Bucket Testing Report Form
This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and
printouts from tests(f applicable), should be provided to the facility owner/operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: #725 Fastrip#19 1 Date of Testing: 7/14/2010
Facility Address: 4901 South Union Avenue, Bakersfield,CA 93307
Facility Contact: Omero Garcia I Phone: 661-393-7000
Date Local Agency Was Notified of Testing: 6/23/2010
Name of Local Agency Inspector(cf present during testing): Ernie Medina
2. TESTING CONTRACTOR INFORMATION
Company Name: Confidence UST Services, Inc.
Technician Conducting Test: Bryan A Self
Credentials: X CSLB Contractor X ICC Service Tech. ❑SWRCB Tank Tester ❑Other(Spec)
License Number(s): CSLB#804904 ICC#8022804-UT
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: x Hydrostatic ❑Vacuum ❑Other
Test Equipment Used: Lake Test Equipment Resolution: 0.0625"
Identify Spill Bucket(By Tank 1 Regular 2 Super 3 Diesel 4
Number, Stored Product, etc.)
Bucket Installation Type: ❑Direct Bury ❑Direct Bury ❑Direct Bury ❑ Direct Bury
x Contained in Sump x Contained in Sump x Contained in Sump ❑Contained in Sum
Bucket Diameter: 12.00" 12.00" 12.00"
Bucket Depth: 14.50" 13.75" 15.00"
Wait time between applying 5 min. 5 min. 5 min.
vacuum/water and start of test:
Test Start Time(Ti): 1:00 pm 1:00 pm 1:00 pm
Initial Reading(Rj): 11.00" 11.00" 11.50"
Test End Time(TF): 2:00 pm 2:00 pm 2:00 pm
Final Reading(RF): 11.00" 11.00" 11.50"
Test Duration (TF—Ti): 1 hour 1 hour 1 hour
Change in Reading(RF-Rj): 0.000" 0.000" 0.000"
Pass/Fail Threshold or 0.0625" 0.0625" 0.0625"
Criteria:
Test Result.. X Pass Fail X Pass, Fail X Pass Fail ❑ Pass ❑Fail
Comments— (include information on repairs made prior to testing, and recommended follow-up for.failed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true,accurate,and in full compliance with legal requirements.
Technician's Signature: Date: 7/14/2010
State laws and regulations do not current require testing to be performed by a qualified contractor.However,local requirements
may be more stringent.