NEW CONSTRUCTION ENHANCED LEAK DETECTION (NCELD)
FINAL TEST RESULTS
Client: Date.' 1211512006 38293NC
D N J Construction Stockdale Food mart
3430 A Gilmore.Ave 5321 Stockdale Hwy
Bakersfield, CA 93308 Bakersfield, CA 93309
87 15,000 Pass Pass Pass
91 8,000 Pass Pass Pass
Diesel 7,000 Pass Pass Pass
Vapor Recovery Pass
41�
Under Dispenser ; r 4 4�
Containment(UDC) 6 A Pass
I declare under penalty of perjury that the Information contained In this report Is true and correct to the best of
my knowledge
Tester: Ricardo Gonzalez State Lic.9: 04-1695
Signature: Date: 1211512006
D 0
1 of 3 38293N%Bakersfield.,Finabds III IIII IIIIIIillllll
08
IE
r
RI�1R Praxair Services, Inc.
3755 N. Business Center Drive
Tucson,AZ 85705
Praxai r Services, Inc. Tel: (800)394-9929
Fax: (520) 293-1306
NEW CONSTRUCTION ENHANCED LEAK DETECTION (NCELD)
FINAL TEST RESULTS
Secondary-Piping
�Cllent � � r „ 40i$7 12/15/2006 Sit fo iob o-. �r
- 4.•-4.Iur.�s.:ce_2. a a w,.�,...s,r; ed 38293NC
D N J Construction Stockdale Food Mart
3430 A Gilmore Ave 5321 Stockdale Hwy
Bakersfield, CA 93308 lBakersfield, CA 93309
.T3 � x ��k�'��►►�y/�+ MM "t
v1 n';o-.}
a" � `s
ti - ��1..�C� {�:� .X �' ,�' 7 ti i S `�"'f f •v 'Jy - 4� a .} �i- T�.6�,{, � 9 '
87 Pass Fail
91 Pass Fail
Diesel Pass Fail
; =..
Vapor Recove ry Pass
NOTE:Secondary test results provided for informational purposes only at request of client. DO NOT SUBMIT TO
REGULATOR.
2 of 3 38293NC QA Final DB
Praxair Services, Inc.
�A-:7PRAXAIR 3765 N. Business Center Drive
Tucson,AZ 85705
Praxair Services, Inc. Tel (800)394-9929
Fax: (520)293-1306
NEW CONSTRUCTION ENHANCED LEAK DETECTION (NCELD)
FINAL TEST RESULTS
5 X "'Z'
-U';Mr
-M
77W'.7'�-"� 5 7'�7 7N
E0
'Y
MA
Testing was performed 12/14-15/2006 using hand-held detectors and on-site lab analysis. Leak
simulation established a tracer soil migration time of 20 hours; backfill samples were collected via
horizontal sampling probes a minimum of 20 hours from system Inoculation.The multiple leaks
detected In the 87 Tank and UDCs 2,3,4,and 5 were repaired by contractor and re-tested tight before
end of testing event. No further detections were made after repairs completed.See the attached leak
log for details.
QA Summary: Test data and information has been reviewed and conforms to ELD procedure and
protocol.All systems tested pass.
Reviewed By: Drew Burk 1/10/2007
Signature:
Attached Leak Log described issues encountered and repaired during test duration
3 of 3 38293NC QA Final DB
LEAK LOG Job#I 38293NC Swo# 60003157
Site: IStockdale Food Mart Client: D N J Construction lClient Contact Jerry Hale
Site Address: 15321 Stockdale Hwy . Bakersfield,CA 93309 lContact# 661-201-3707
Log Completed By: Ricardo Gonzalez Total Detected Leaks . 6
12/14/06 1a 11:15 87TK BU 1 FVS Tracer Detected Bucket to faceshield adaptor leaking.
12/14/06 2a 11:45 87TK BU 1 FVS Note Bucket to faceshield adaptor repaired.
12/14/06 1b 13:30 87TK Final 2 FVS Tracer Detected Union on VR is leaking
12/14/06 2b 15:15 87TK Final 2 FVS Note Union on VR has been repaired.
12/14/06 1c 18:27 UDC Final 2 UDC#2 Tracer Detected Shear valve caps are leaking.
12/14/06 1d 18:28 UDC Final 2 UDC#3 Tracer Detected Shear valve caps are leaking.
12/14/06 1e 18:29 UDC Final 2 UDC#4 Tracer Detected Shear valve caps are leaking.
12/14/06 if 18:30 UDC Final 2 UDC#5 Tracer Detected Shear valve caps are leaking.
12/15/06 2c 9:00 UDC Final 2 UDC#2 Note Shear valve caps have been repaired.
12/15/06 2d 9:01 UDC Final 2 UDC#3 Note Shear valve caps have been repaired.
12/15/06 2e 9:02 UDC Final 2 UDC#4 Note Shear valve caps have been repaired.
12/15/06 2f 9:03 UDC Final 2 UDC#5 Note Shear valve caps have been repaired.