HomeMy WebLinkAboutFMC 2010 <111011 29 MONITORING SYSTEM CERTIFICATION
IE For Use By All Jurisdictions Within the State of California PP-
Authority Cited:Chapter 6 7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations
This form must be used to document testing and servicing of monitoring equipment. A separate eertiflcation or report must be prepared for each
monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator.
The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility Name: MOBIL STATION Bldg.No.:
Site Address: 5401 STOCKDALE HWY City: BAKERSFIELD Zip:
Facility Contact Person: FONG Contact Phone No.:{ )
Make/Model of Monitoring System: TLS-350 Date of Testing/Servicing: 9/21/2010
B. Inventory of Equipment Tested/Certified
Check the aperopriate loxes to indicates cific 4niginent ins cd/serviced:
Tank ID: UNL87 Tank ID: PREM91
®In-Tank Gauging Probe. Model: MAG 0 In-Tank Gauging Probe. Model: MAG
®Annular Space or Vault Sensor. Model: 420 ®Annular Space or Vault Sensor. Model: 420
®Piping Sump/Trench Sensor(s). Model: 208 ®Piping Sump/Trench Sensor(s). Model: 208
❑Fill Sump Sensor(s). Model: ❑Fill Sump Senwr(s). Model:
®Mechanical Line Leak Detector. Model: RED JACKET ®Mechanical Line Leak Detector. Model FE PETRO
❑Electronic Line Leak Detector. Model: ❑Electronic Line Leak Detector. Model:
®Tank Overfill/High-Level Sensor. Model: FLAPPER ®Tank Overfill/High-Level Sensor. Model: FLAPPER
❑Other(specify equipment type and model in Section E on Page2). ❑Other(specify equipment type and model in Section E on Page 2).
Tank ID: DIESEL Tank ID:
®In-Tank Gauging Probe. Model: MAG ❑In-Tank Ganging.Probe. Model:
®Annular Space.or Vault Sensor. Model: 420. ❑Annular Space or Vault Sensor. Model:
®Piping Sump/Trench Sensor(s). Model: 208 ❑Piping Sump/Trench Sensor(s). Model:
❑Fill Sump Sensor(s). Model: ❑Fill Sump Sensor(s). Model:
®Mechanical Line Leak Detector. Model: FE PETRO ❑Mechanical Line Leak Detector. Model:
❑Electronic Line Leak Detector. Model: ❑Electronic Line Leak Detector_ Model:
®Tank Overfill/High-Level Sensor. Model: FLAPPER ❑Tank Overfill/High-Level Sensor. Model:
❑Other(specify equipment type and model in Section E.on Page 2). ❑Other(specify equipment type and model_in Section E on Page 2).
Dispenser ID: 112 Dispenser ED: 314
®Dispenser Containment Sensor(s). Model: 001 ®Dispenser Containment Sensw(s). Model: 001
®Shear Valve(s). ®Shear Valve(s).
❑Dispenser Containment Float(s)and Chain(s). ❑Dispenser Containment Float(s)and Chain(s).
Dispenser ID: 516 Dispenser ID: 718
I&Dispenser Containment Sensor(s). Model: 001 ®Dispenser Containment Sensor(s). Model: 001
®Shear Vafve(s). ®Shear Valve(s).
❑Dispenser Containment Float(s)and Chain(s). ❑Dispenser Containment Float(s)and Chain(s).
Dispenser ID: 9110 Dispenser ID:
®Dispenser Containment Sensor(s). Model: 001 [I Dispenser Containment Sensor(s). Model:
®Shear Valve(s). []Shear Valve(s).
❑Dispenser Containment Float(s)and Chain(s). ❑Dispenser Containment Float(s)and Chain(s).
*If the facility contains more tanks or dispensers,copy this form_ Include information for every tank and dispenser at the facility.
C. Certification-I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers'
guidelines. Attached to this Certification is information.(e.g. manufacturers' checklists) necessary verify that this information is
correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable generating such reports,I have also
attached a copy of the report;(check all that apply): System set-up Alarm ory report
Technician Name(print): RICH PHILLIPS_ Signature:
Certification No.: A2908411035169-UT License.No.: C611040 809850 .
Testing Company Name: RICH ENVIRONMENTAL Phone No.:(661) 32648402
Testing Company Address: 3305 BRITTAN RD.BAKERSFIELD,CA. 93308 Date of Testing/Servicing: 9/21/2010
Page 1 of 5
UN-036—1/4 I IIIIIII�IIII III IIII 30 www.unidocs.org Rev.01/17/08
IE
Monitoring System Certification
D. Results of Testing/Servicing
Software Version Installed: 329.01
Complete the following checklist:
• Yes ❑ No* Is the audible alarm:operational?
• Yes ❑ No* Is the visual alarm operational?
to Yes ❑ No* Were all sensors visually inspected,functionally tested,and confirmed operational?
® Yes ❑ No* Were all'sensors installed at lowest point of secondary containment and positioned so that other equipment will
not interfere with.their proper operation?
❑ Yes 0 No* If alarms are relayed to a remote .monitoring station, is all communications equipment (e.g., modem)
E N/A operational?
® Yes ❑ No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
❑ N/A monitoring system detects a leak,fails to operate,or is.electrically disconnected? If yes:which sensors initiate
positive shut-down? (Check all that apply) ®Sump/Trench Sensors; ❑Dispenser Containment Sensors.
i Did you confirm positive shut-down due to leaks and"sensor failure/disconnection? 0 Yes; ❑No.
El Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no
® N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible of the tank
fill point(s)and operating properly? If so,at what percent of tank capacity does.the alarm_trigger?
❑ Yes* ® No Was any monitoring equipment replaced? If yes,identify specific sensors,probes,or other equipment replaced
and list the manufacturer name and,model for all,replacement parts in Section E,below.
❑ Yes* ® No Was liquid found inside:any secondary containment systems designed as dry systems? (Check all that apply)
❑Product; ❑ Water. If yes,describe causes in`Section E,below.
® Yes 0 No* Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports,if,applicable
® Yes ❑ No* Is all monitoring equipment operational per manufacturer's specifications?
*In Section E below,describe how and when these deficiencies were or will be corrected..
E. Comments:
Page 2 of 5
UN-036—214 www.unid6cs.org Rev.01117M
Monitoring System Certification
F. In-Tank Gauging/SIR Equipment: ED Check this box if tank gauging is used only for inventory control.
❑ Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
❑ Yes ❑ No* Has all input wiring been.inspected for proper entry and termination,including testing for ground faults?
❑ Yes ❑ No* Were all tank.gauging probes visually inspected for damage and residue buildup?
❑ Yes ❑ NO Was accuracy of system product level readings tested?
❑ Yes ❑ No* Was accuracy of system water level readings tested?
❑ Yes ❑ No* Were all probes reinstalled,properly?
❑ Yes ❑ No* Were all items on the equipment manufacturer's maintenance checklist completed?
*In Section H,below,describe bow and when these deficiencies were or will be corrected.
G. Line Leak Detectors(LLD): ❑ Check this box if LLDs are not installed.
Complete the follo ing checklist:
® Yes ❑ No* For equipment start-up. or annual,equipment certification, was a leak simulated to verify LLD performance?
❑ N/A (Check all that apply) Simulated leak rate: ®3 g p h.; ❑0.1 g.p.h; ❑0.2 g.p.h.
® Yes ❑ No* Were all LLDs confirmed operational and accurate within regulatoryrequiiements`1
® Yes ❑ No* Was the testing apparatus properly calibrated?
® Yes ❑ No* For mechanical LLDs,does the LLD restrict product flow if it detects a leak?
❑ N/A
❑ Yes ❑ No* For electronic LLDs.;.does the,turbine automatically shut off if the LLD detects a leak?
® N/A
❑ Yes ❑ No* For electronic LEDs, does the turbine automatically shut off if any portion of the monitoring system is disabled
® N/A or disconnected?
❑ Yes ❑ No* For electronic LLDs,does the turbine automatically shut off if any portion of the monitoring system malfunctions
® N/A or fails a test?
❑ Yes ❑ No* For electronic LLDs,have all accessible wiring connections been visually inspected?
® N/A
® Yes ❑ No* Were all items on the equipment manufacturer's maintenance checklist completed?
*In Section H,below,describe bow and when these deficiencies were or will be:corrected..
A. Comments:
Page 3 of 5
UN-036-314 wwwmaidomorg Rev.01/17/08
UST . Site Plan
Site Ad&=
r r r ► r .: r. r r
• _ r -R W • r a . RWWY � r. ..
mi— w. r • i r- f. �!.;!7 r r . R _.r .. . r
r r i w w r
ON
.. .^. _ •
-
r. r a • � M' - r' • �r f
• • r -
r
i. 6 qi
w 1 w » _ � r r I a •. • r r •. ' _ 1 • l..r •I. 'r .r � x r •
a .
- r �.'.r r 4 '�. r.. � r f+ - r r � ... t r r:l. r r r r r�' Y r • . - I. r
Y rr • a »
. ..� Y r r. • a .�. -w r �. , ! r ,r. r w. r w•..'. r . w r r � I r
- T�te •wesdra�; � ,, ' .
tM
i tudu46 it,rates tiraa tIs Inge ►You
drat shows all rcggire titbtU ation,
If you al dyhave'a dtagi site s�r�ie moral rut dtauks:aad�ip U&'CSear}y'uien*
Monttoritt .System ificat� yt?ur Pte,:. .
dacatzons:of.ihe �a � i€'ip�t$}led�mazmng`sYs `oetroZ panueis mnnYtorin annular
POM,;�wn�,'di 'pall s n'U°°mRa' :Or. seeo�dax+y cwt 'to a ar erect otac line leak
d tectiars,•and in-taarfc liquid de l ptob us eii€or'kak � . P�"d' �!vte.the;dst i s Siic P3an
was prepay
RICH EN MONMENTAL
3305 BRITTAN ST.BAKERSFIELD, CA.93308
OFFICE(661)326-8402 FAX(661)326-8934
PRODUCT LINE LEAK DETECTOR TEST
WORK SHEET
W/0#:
FACILITY NAME: MOBIL STATION
FACILITY ADDRESS: 5401 STOCKDALE HWY,BAKERSFIELD
PRODUCT LINE TYPE: PRESSURE
PRODUCT LEAK DETECTOR TYPE TEST TRIP PASS
BELOW P.S.I. OR
SERIAL NUMBER 3 G.P.H. FAIL
UNL87 L/D TYPE i. RED JACKET- YES IO PASS
SERIAL# 8097
PREM91 LID TYPE: FE PETRO YES 12 PASS
SERIAL# MECHANICAL
DIESEL LID TYPE: FE PETRO YES 10 PASS
SERIAL#MECHANICAL
LID TYPE: YES PASS
SERIAL# NO FAIL
I CERTIFY THE ABOVE.TESTS WERE CONDUCTED ON THIS DATE ACCORDING TORED
JACKET PUMPS FIELD TEST APPARATUS TESTING PROCEDURE AND LIMITATIONS.
THE MECHANICAL LEAK-DETECTOR TEST PASS/FAIL IS DETERMINED BY USING A
LOW FLAW THRESHOLD TRIP RATE OF 3 GALLONS PER HOUR OR LESS AT.10 P.S.I.I
ACKNOWLEDGE THAT ALL DATA COLLECTED IS TRUE AND CORRECT TO THE BEST
OF MY KNOWLEDGE.
TECHNICIAN: RICH PHIL
SIGNATURE: DATE: 9/21110
SWRCB,January 2001
Spill Bucket Testing Report Form
This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and
printouts from tests(if applicable),should be provided to the facilityowner/operator for submittal to the local regulatory agency
1. FACILITY INFORMATION
Facility Name: MOBIL STATION Date of Testing: 9/21/10
Facility Address: 5401 STOCKDALE HWY,BAKERSFIELD
Facility Contact: Phone:
Date Local Agency Was Notified of Testing:: 7/22/10
Name of Local Agency Inspector(i(present during.testingh ERNIE MEDINA
2. TESTING CONTRACTOR INFORMATION
Company Name: RICH ENVIRONMENTAL
Technician Conducting Test: RICH'PHILLIPS
Credentials: ❑CSLB Contractor X ICC Service Tech. ❑SWRCB Tank Tester ❑Other(Specify)
License Number(s): 1035169-UT
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: X Hydrostatic ❑Vacuum ❑Other
Test Equipment Used:VISUAL Equipment Resolution:0
Identify Spill Bucket(By Tank 1 2 =9141ML 3 4
Number, Stored Product, etc) REG 87-FILL DIES EL FILL
Bucket Installation Type: X Direct Bury X Direct Bury X Direct Bury ❑Direct Bury
❑Contained in Sump ❑Contained in Sump ❑Contained in Sump ❑Contained in Sum
Bucket Diameter: 12" 12" FAILED
Bucket Depth: 14" 14"
Wait time between applying 30 MIN 30 MIN
vacuum/water and start of test:
Test Start Time(TO: 9:OOAM 9:OOAM
Initial Reading(RO: 10." 10"
Test End Time(TF): 10:00AM 10:00AM
Final Reading(RF): 10" 10"
Test Duration(TF—T): 1-HOUR I-HOUR
Change in Reading(RF-R j): 0 0
Pass/Fail Threshold or
+/-0,00 +/-0.00
Criteria:
Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests)
CRACK ON DIESEL BUCKET SIDE- FAILED
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information con in this report Is true,accurate,and lie full compliance with legal requhemen1&
Technician's Signature: Date: 9/21/10
State laws and regulations do not currebtly require testing to be performed by a qualified contractor.However,local requirements
may be more-stringent.
.7751LCI 5k.1 U1' ass—.rii w- _4..4�r
� _ _ _ _ — _ _ _ — _ _ COMMUNICATIONS. SETUP — — — — — — — —
SEP 21. 2010 8:23 AM T .1 :REGULAR 87
PRODUCT CODE 1
PORT SETTINGS: THERMAL COEFF : .000700
SYSTEM UNITS COMM BOARD 1 (EDIM ? TANK PROFILE 96.00
U.S. TANK PROFILE i PT
SYSTEM LANGUAGE RS--232 SECURITY FULL VOL 12245
ENGLISH CODE DISABLED
SYSTEM DATE/TIME FORMAT COMM BOARD 2 (RS-232) FLOAT SIZE: 4.0 IN.
MON DD YYYY HH:MM:SS xM BAUD RATE 1200
fl$1L PARITY ODD WATER WARNING 3.0
STOCKDALE M
5401 STOCKDOBI WY DATA BIT 1 STOP HIGH WATER LIMIT: 3.0
5401 SFIELD.CA DATA LENGTH: 7 DATA
661-833-2726 RS-232 SECURITY MAX OR LABEL VOL: 12245
CODE : DISABLED OVERFILL LIMIT 90%
SHIFT TIME 1 11 :00 PM 11020
SHIFT TIME 2 : 4:29 AM AUTO TRANSMIT SETTINGS: HIGH PRODUCT 95x6
SHIFT TIME 3 4:29 AM 11632
DELIVERY LIMIT 1 18336 6
SHIFT TIME 4 : 4:29 AM AUTO LEAK .ALARM LIMIT
TANK PER TST NEEDED WRN DISABLED
DISABLED AUTO..HIGH WATER LIMIT LOW PRODUCT 800
TANK ANN TST NEEDED WRN DISABLED LEAK ALARM LIMIT: 99
DISABLED AUTO OVERFILL LIMIT SUDDEN LOSS LIMIT: 50
DISABLED TANK TILT. 3.37
LINE RE—ENABLE METHOD AUTO LOW :PRODUCT PROBE ,OFFSET 0.00
PASS LINE 'PEST
DISABLED
TT
AUTO O THEFT LIMIT
DISABLED. SIPHON MANIFOLDED TANKS_
LINE PER TST NEEDED WRN AUTO DELIVERY START TO: NONE
DISABLED DISABLED LINE MANIFOLDED TANKS
LINE ANN TST NEEDED WRN AUTO DELIVERY END TO: NONE
DISABLED DISABLED
PRINT TC VOLUMES AUTO EXTERNAL INPUT ON
EfdABLED DISABLED LEAK MIN PERIODIC: 0%
AUTO EXTERNAL INPUT OFF 0
TEMP COMPENSATION DISABLED
VALUE (DEG F ) : 60,0 AUTO SENSOR FUEL ALARM LEAK MIN ANNUAL . 0%
STICK HEIGHT OFFSET DISABLED hI 0
DISABLED AUTO SENSOR WATER ALARM
ULLAGE: 9096 DISABLED
AUTO SENSOR OUT ALARM PERIODIC TEST TYPE
H—PROTOCOL DATA FORMAT DISABLED STANDARD
HEIGHT ANNUAL TEST FA'I L
DAYLIGHT SAVING TIME
DISABLED ALARM DISABLED
RE—DIRECT LOCAL PRINTOUT PERIODIC TEST FAIL
DISABLED ALARM DISABLED
EURO PROTOCOL PREFIX GROSS TEST FAIL
S RS-232 END OF MESSAGE ALARM DISABLED
DISABLED
ANN TEST AVERAGING: OFF
SYSTEM SECURITY PER TEST AVERAGING: OFF
CODE : 000000 TANK TEST NOTIFY: OFF
MAINTENANCE HISTORY TNK TST SIPHO.N BREAK:OFF
DISABLED
DELIVERY DELAY 1.5 MIN
TANK CHART SECURITY PUMP THRESHOLD 10.00%
DISABLED
CUSTOM ALARMS
DISABLED
SERVICE NOTICE
DISABLED
ISO 3166 COUNTRY
CODE:
MASS/DENSITY
DISABLED
aT 2:FR£M I UM 91 '1' J-.u t t•� L = — _ _— _
PRODUCT CODE 2 PRODUCT CORE 3 . TEST ON DATE : ALL TANK
THERMAL COEFF : .000700 TANK DI METER : ..000450 JAN 29. 2009
TANK DIAMETER 96.00 TANK DIAMETER 96.00 START TIME : DISABLED
5
TANK PROFILE 1 PT TANK PROFILE 1_ PT START
TEST RATE :0..20 GAL/HR
FULL VOL 12245 FULL VOL DURATION : 2 HOURS
FLOAT SIZE: 4.0 IN. FLOAT SIZE: 4.0 IN. TST EARL.Y. STOP:DISABLED
WATER WARNING 2.0 WATER WARNING 2.0 LEAK TEST REPORT FORMAT
HIGH .WATER LIMIT: 3.0
HIGH WATER LIMIT: 3.0. NORMAL
MAX OR LABEL VOL: 12245 MAX OR LABEL VOL: 5000
OVERFILL LIMIT
OVERFILL LIMIT 90% 4500
11020 HIGH PRODUCT 959+
HIGH PRODUCT 95% 4750
11632 DELIVERY LIMIT 16%
DELIVERY LIMIT 151% 800
1836
L LOW PRODUCT. 500
LOW PRODUCT B00
LEAK ALARM LIMIT: 99 LEAK ALARM LIMIT: 99 LIQUID SENSOR SETUP
SUDDEN. LOSS LIMIT: 50
SUDDEN LOSS LIMIT: 50 0.00 TANK — — — — — - `
TANK TILT 0.00 TANK TILT
PROBE OFFSET 0.00
PROS . OFFSET. _....._-0_.:M - L 1 :U NL 87 STP
TRI—STATE (SINGLE FLOAT)
SIPHON MANIFOLDED TANKS CATEGORY : STP SUMP
SIPHON MANIFOLDED TANKS TO: NONE
TO: NONE LINE MANIFO.LDED TANKS
LINE MANIFOLDED TANKS TO: NONE L 2:DIESEL ANNULAR
T#: NONE TRI—STATE (SI.NGL.E FLOAT)
CATEGORY : ANNULAR SPACE
LEAK MIN PERIODIC: 0% LEAK MIN PERIODIC Boo
0
LEAK MIN ANNUAL 16% L 3:DIESEL STP
LEAK MIN ANNUAL 0% B00 TRI—STATE (SINGLE FLOAT)
0 CATEGORY : STP SUMP
PERIODIC TEST TYPE PERIODIC TEST TYPE 8TSTANDARD L. 4:91 ANNULAR
.STANDARD. TRI—STATE (SINGLE FLOAT)
ANNUAL TEST FAIL CATEGORY : ANNULAR SPACE
ANNUAL TEST FAIL ALARM DISABLED
ALARM DISABLED
PERIODIC TEST FAIL PERIODIC TEST FAIL
ALARM DISABLED L 5:PREMI.UM 91 STP
ALARM DISABLED TRI—STATE (SINGLE FLOAT)
GROSS TEST FAIL CATEGORY : STP SUMP
GROSS TEST FAIL ALARM DISABLED
ALARM DISABLED
ANN TEST AVERAGING: OFF L 6:UNL 87 ANNULAR
ANN TEST AVERAGING: OFF PER TEST AVERAGING.: OFF TRI—STATE (SINGLE FLOAT)
PER TEST AVERAGING: OFF CATEGORY ANNULAR SPACE
TANK. TEST NOTIFY: OFF TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF TNK TST SIPHON BREAK:OFF
DELIVERY DELAY 15 MIN DELIVERY DELAY 15 MIN
PUMP THRESHOLD 10.00% PUMP 'THRESHOLD
UUSYUI tS1 toy 7JG1uY
- - - - _ - - - - - - SMARTSENSOR SETUP mllml1 'rata 111'ILA y
- - - - - - - - TIME 10:00 AM
R 1 :87 RELAY s 1 :CARBON CANISTOR DELAY MINUTES: 1
TYPE: CATEGORY VAPOR VALVE
STANDARD
NORMALLY CLOSED ACCEPT HIGH ORVR:
s 2:VAPOR PRESSURE DISABLED
TANK it: 1 CATEGORY VAPOR PRESSURE
I$D HOSE TABLE:
s 3:DISP 1-2 ID FP FL HL AA RR
LIQUID SENSOR ALMS CATEGORY AIR FLOW METER, ------------------------
ALL:FUEL ALARM 01 01 01 02 01 UU
ALL:SENSOR OUT ALARM s 4:DISP .3-4 02 02 02 02 01 UU
CATEGORY AIR FLOW METER 03 03 03 02 02 UU
[SD SITE ALARMS 04 04 04 02 02 UU
ISD GROG PRES FAIL s 5:DISP 5-6 05 05 05 02 03 UU
ISD DEGRD PRES FAIL CATEGORY A1R' FLOW METER 06 06 06 02 03 UU
ISD VAPOR. LEAK FAIL 07 07 07 02 04 UU
ISD VP PRES FAIL s 6:DISP 7-8 08 08 08 02 04 UU
ISD VP STATUS FAIL CATEGORY AIR FLOW METER 09 09 09 02 05 UU
10 16 10 02 05 UU
ISD HOSE ALARMS s 7:DISP 9-10
ALL:GROSS COLLECT FAIL CATEGORY AIR FLOW METER
ALL:FLOW COLLECT FAIL ISD AIRFLOW METER MAP
s 8:ATM ID SERIAL NUM LABEL
R 2:PREMIUM CATEGORY ATM. P SENSOR -------------------------
1 40036 DISP 1-2
TYPE: 2 39497 DISP 3-4
STANDARD 3 40049 DISP 5-6
NORMALLY-CLOSED
''4. 40031: DISP 7-8
5 41.522 DISP 9-10
LIQUID SENSOR ALMS ISD FUEL GRADE HOSE MAP
ALL:FUEL ALARM 1 2 3 4
ALL-SENSOR OUT ALARM FP MHH MHH MHH MHH AA
- '
ISD SITE ALARMS 01 101 201 901 U U 1-
ISD GROSS PRES FAIL 02 102 202 902 U U 1
ISD DEGRD PRES FAIL
I$D VAPOR LEAK FAIL EVR/I.8D SETUP 04 104 204 904 U U 2
ISD VP PRES FAIL 05 105 205 905 U U 3
ISD VP STATUS FAIL 06 106 206 906 U U 3
07 107 207 907 3 U 4
ISD HOSE ALARMS. EVR TYFE: BALANCE 08 08 208 908 3 U 4
ALL:GROSS COLLECT FAIL B/iLANCE NOZZLE TYPE 06 1100 200 905 3 U 5
VST
ALL:FLOW COLLECT FAIL
R 3.DIESEL VAPOR PROCESSOR TYPE LABEL TABLE
TYPE: VEEDER-ROOT POLISHER ------------------------
STANDARD 1 : UNASSIGNED
NORMALLY CLOSED 2: BLEND3
TANK 0: 3 3: REGULAR
4: MID GRADE .
5: PREMIUM
LIQUID SENSOR ALMS 6: GOLD
ALL:FUEL ALARM 7: BRONZE
ALL:SENSOV OUT ALARM 8: SILVER
9: BLEND2
10: BLEND4
PMC SETUP
PMC VERSION; 01 .02
VAPOR PROCESSOR TYPE
VEEDER-ROOT POLISHER
8 ALARM HISTORY REPORT ALARM H I STORY RL:YUK i
-- SENSOR ALARM ----- SOFTWARE REVISION LEVEL—�`—
'— SENSOR ALARM ----- L-9:91 ANNULAR VERSION 329.01
L 1 :UNL 87 STP SOFTWARE# 346329-100-3
STP SUMP ANNULAR SPACE CREATED — 09.01 .29.15.44
SENSOR OUT ALARM SENSOR OUT ALARPI
SEP 21, 2010 9:26 AM SEP 21 . 2010 9:27 AM S—MOD ULE4 330160-004—a
FUEL: ALARM SYSTEM FEATURES:
FUEL ALAN SEP 21. 2010 9:15 AM PERIODIC IN—TANK TESTS
SEP 21. 2010 9;18 AM ANNUAL IN—TANK TESTS
SETUP DATA WARNING SETUP DATA WARNING ISD
SEP 13, 2010 11 :09 AM SEP 13, 2010 11 :09 AM
STOCKDALE MOBIL
* * * END * * * 5401 STOCKDAL.E HWY
* * END HAKERSFIELO,CA
661-833-2726
SEP 21 , 2010 10:52 AM
SYSTEM STATUS REPORT
ALL FUNCTIONS NORMAL
ALARM HISTORY REPORT ALARM HISTORY REPORT INVENTORY REPORT
-- SENSOR ALARM ----- -- SENSOR ALARM ----- T 1 :REGULAR 87
L 2:DIESEL ANNUL- L 5:PREMIUM 91 STP VOLUME . 8955 GALS
ANNULAR SPACE STP SUMP ULLAGE 3290 GALS
SENSOR OUT ALARM SENSOR OUT ALARM 90% ULLAGE- 2065 GALS
SEP 21. 2010 9:26 AM SEP 21. 2010 9:27 AM TC VOLUME 8804 GALS
FUEL ALARM HEIGHT - 65.86 INCHES
FUEL ALARM SEP 21 , 2010 9:16 AM WATER VOL 24 GALS
SEP 21. 2010 9:t3 AM WATER 1 .06 INCHES
SETUP DATA WARNING SETUP DATA WARNING TEMP 84.0 AEG F
SEP 13. 2010 11 :09 AM SEP 13. 2010 11 :09 AM
T 2:PREMIUM. 91
VOLUME = 3494 GALS
ULLAGE . 875.1 GALS
90% ULLAGE- 7526 GALS
TC VOLUME = 3435 GALS
HEIGHT - 31 .48 INCHES
WATER VOL - 0 GALS
WATER - 0.00 INCHES
TEMP 84.1 AEG F
�t END * END
T 3:DIESEL
VOLUME a 1829 GALS
ULLAGE - 317d GALS
90% ULLAGE- 2671 GALS
TC VOLUME - 1800 GALS
HEIGHT . = 37.80 INCHES
WATER VOL - 0 GALS
WATER - 0.00 INCHES
TEMP - 94.9 DEG F
ALARM HISTORY REPORT ALARM HISTORY REPORT X * x END X X x x X
---- SE14SOR ALARM ----- ----- SENSOR ALARM -----
L 3:DIESEL STP L 6:UNL 87 ANNULAR
STP SUMP ANNULAR SPACE
SENSOR OUT ALARM SENSOR OUT ALARM
SEP 21, 2010 9:27 AM SEP 21, 2010 9:27 AM
FUEL ALARM FUEL ALARM
SEP 21 , 2010 9:14 AM SEP 21 , 2010 9:17 AM
SETUP DATA WARNING SETUP DATA WARNING
SEP 13. 2010 11 :09 AM SEP 13. 2010 11 :09 AM
3�ZoVo
MONITOR CERT. FAILURE REPORT
SITE NAME : MOBIL STATION DATE : 9/21/10
ADDRESS: 5401 STOCKDALE HWY TECHNICIAN : RICHPO4ws
CITY: BAKERSFIELD SIGNATURE
THE FOLLOWING COMPONENTS WERE REPLACED/REPAIRED TO COMPLETE
TESTING.
REPAIRS: DIESEL BUCKET FAILED—CRACK ON SIDE OF BUCKET
LABOR : NONE
PARTS INSTALLED • NONE
NAME : TITLE :
SIGNATURE :
THE ABOVE NAMED PERSON TAKES FULL RESPONSIBILITY OF NOTIFYING
THE APPROPRIATE PARTY TO HAVE CORRECTIVE ACTION TAKEN TO REPAIR
THE ABOVE LISTED PROBLEMS AND NOTIFYING RICH ENVIRONMENTAL FOR
ANY NEEDED RETESTING.THIS ALSO RELEASES RICH ENVIRONMENTAL OF
ANY FINES OR PENALTIES OCCURING.FROM NON-COMPLIANCE:
A COPY OF THIS.DOCUMENT HAS BEEN LEFT ON-SITE FOR YOUR
CONVIENENCE.