HomeMy WebLinkAboutFMC 2011 MONITORING SYSTEM CERTIFICATION For Use By All Jurisdictions Within the State of California Authority Cited:Chapter 6.7, Health and Safety Code;Chapter 16, Division 3 Title 23, California Code of Regulations This form must be used to document testing and servicing of monitoring equipment. If more than one monitoring system control panel is Installed at the facility,a separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date. A.General Information Facility Name: CIRCLE K 2701270 City: BAKERSFIELD CA Zip:93313 Site Address: 5634 STINE RD Contact Phone No: 834-8625 Date of Testing/Service: 01/20/2011 Facility Contact Person: JOHN-MANAGER Make/Model of Monitoring System:TLS350 Work Order Number: 3180345 IIIlillllllll III IIII 31 B.Inventory of Equipment Tested/Certified Check the appropriate boxes to indicate specific equipment inspected/serviced IE Tank ID: 87 Tank ID: 91 X In-Tank Gauging Probe. Model: MAG PROBE E In-Tank Gauging Probe. Model: MAG PROBE X Annular Space or Vault Sensor. Model: 409 Annular Space or Vault Sensor. Model: 409 X Piping Sump/Trench Sensogs). Model: 208 Piping Sump/Trench Sensor(s). Model: 208 Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model: X Mechanical Line Leak Detector. Model: LD2000 X Mechanical Line Leak Detector. Model: LD2000 Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model: X Tank Overfill/High-Level Sensor. Model: FLAPPER Tank Overfill/High-Level Sensor. Model: FLAPPER Other(specify equipment type and model in Section E on page 2). D Other(specify equipment type and model in Section E on page 2). TanklD: TanklD: In-Tank Gauging Probe. Model: In-Tank Gauging Probe. Model: Annular Space or Vault Sensor. Model: Annular Space or Vault Sensor. Model: Piping Sump/Trench Sensor(s). Model: Piping Sump/Trench Sensor(s). Model: Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model: Mechanical Line Leak Detector. Model: Mechanical Line Leak Detector. Model: Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model: Tank Overfill/High-Level Sensor. Model: Tank OverfilUHigh-Level Sensor. Model: Other(specify equipment type and model in Section E on page 2). Other(specify equipment type and model in Section E on page 2). Dispenser : 112 Dispenser ID: 3/4 7 Dispenser Containment Sensor(s) Model: 7 Dispenser Containment Sensor(s) Model: X]Shear Valve(s). X Shear Valve(s) �X Dispenser Containment Float(s)and Chain(s). X Dispenser Containment Float(s)and Chain(s). Dispenser ID: 5/6 Dispenser ID: 7/8 Dispenser Containment Sensors) Model: 7 Dispenser Containment Sensogs). Model: X❑'Shear Valve(s). Shear Valve(s). X 'Dispenser Containment Float(s)and Chain(s). 71 Dispenser Containment Float(s)and Chain(s). Dispenser lD: Dispenser ID: Dispenser Containment Sensor(s) Model: Dispenser Containment Sensors). Model: Shear Valve(s). Shear Valve(s). Dispenser Containment Float(s)and Chain(s). Dispenser Containment Float(s)and Chain(s). "If the facility contains more tanks or dispensers,copy this form.Include information for every tank and dispenser at the facility. C. Certification I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers'guidelines. Attached to this certification is information(e.g manufacturers'checklists)necessary to verify that this information is correct. and a'Site Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports,I have also attached a copy of the(Check all that apply): ❑X System set-up X❑Alarm history report Technician Name(print): ROBERT ALLEN Signature: Certification No.: A20125 License.No.: 743160(Class'A'General Enginering Contractor License) Testing Company Name:Tanknology Phone No.: (8 0)800-4633 Site Address: 11000 N. MoPac Expressway,suite 500,Austin,TX 78759 Date of Testing/Servicing: 01/20/2011 Monitoring System Certification Page 1 of 3 I IIIIIII II�IIII IIII 32 Based on CA form dated 03/08 IE Monitoring System Certification Site Address 5634 STINE RD Date of Testing/Service: 01/20/2011 D. Results of Testing/Servicing Software Version Installed: 328.03 Complete the following checklist: X Yes No• Is the audible alarm operational? Q Yes No Is the visual alarm operational? 0 Yes No• Were all sensors visually inspected,functionally tested,and confirmed operational? Yes No Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not ❑ ' interfere with their proper operation? X Yes D.No' N/A If alarms are relayed to a remote monitoring station,is all communications equipment(e.g. modem)operational? For pressurized piping systems,does the turbine automatically shut down if the piping secondary containment ❑x Yes ❑No• ❑N/A monitoring system detects a leak,fails to operate,or is electrically disconnected?If yes:which sensors initiate positive shut-down?(check all that apply) ❑X Sump/Trench Sensors; ❑ Dispenser Containment Sensors. Did you confirm positive shut-down due to leaks and sensor failure/disconnection? ❑x Yes No ❑ Yes ❑No• ❑X N/A For tank systems that utilize the monitoring system as the primary tank overfill warning device(i.e.:no mechanical overfill prevention valve is installed),is the overfill warning alarm visible and audible at the tank fill points(s)and operating properly? If so,at what percent of tank capacity does the alarm trigger? ❑ Yes* ❑x No Was any monitoring equipment replaced?If yes,identify specific sensors, probes,or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E,below. ❑ Yes- ❑x No Was liquid found inside any secondary containment systems designed as dry systems?(check all that apply) ❑Product; ❑ Water. If yes,describe causes in Section E.below. ❑X Yes ❑No• Was monitoring system set-up reviewed to ensure proper settings?Attach set-up reports,if applicable. Q Yes ❑No• Is all monitoring equipment operational per manufacturers'specifications? •In Section E below,describe how and when these deficlences were or will be corrected. E. Comments: Page 2 of 3 Based on CA form dated 03/08 Monitoring System Certification Site Address: 5634 STINE RD Date of Testing/Service: 01/20/2011 F. In-Tank Gauging / SIR Equipment ❑ Check this box if tank gauging is used only for inventory control. ❑ Check this box if no tank gauging or SIR equipment is installed. Check this box if no tank gauging or SIR equipment is installed. This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring. Complete the following checklist: 0 Yes ❑No• Has all input wiring been inspected for proper entry and termination,including testing for ground faults? Yes ❑No Were all tank gauging probes visually inspected for damage and residue buildup? Yes ❑No• Was accuracy of system product level readings tested? OYes ❑No' Was accuracy of system water level readings tested? X Yes ❑No Were all probes reinstalled properly? ❑X Yes 0 N•FWere all items on the equipment manufacturers'maintenance checklist completed? `In the Section H,below,describe how and when these deficiencies were or will be corrected. G. Line Leak Detectors (LLD) : ❑ Check this box if LLDs are not installed. Complete the following checklist: For equipment start-up or annual equipment certification,was a leak simulated to verify LLD performance? Q_Yes ❑No' ❑N/A (Check all that apply)Simulated leak rate: X❑ 3 g.p.h❑0.1 g.p.h ❑0.2 g.p.h FRI Yes ❑No Were all LLDs confirmed operational and accurate within regulatory requirements? x Yes ❑No' Was the testing apparatus properly calibrated? X❑Yes ❑No• ❑N/A For mechanical LLDs,does the LLD restrict product flow if it detects a leak? ❑Yes ❑No' ®N/A For electronic LLDs,does the turbine automatically shut off if the LLD detects a leak? ❑Yes, ❑No' ❑X N/A For electronic LLDs,does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? ❑Yes ❑No.• 0 N/A For electronic LLDs,does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a test? ❑Yes No 0 N/A For electronic LLDs,have all accessible wiring connections been visually inspected? L'J Yes ❑No• Were all items on the equipment manufacturers'maintenance checklist completed? `In the Section H,below,describe how and when these deficiencies were or will be corrected. H. Comments: Page 3 of 3 Based on CA form dated 03/08 SWRCB,January 2002 Page 1 . Secondary Containment Testing Report Form This form is intended for use by contractors performing periodic testing of UST secondary containment systems. Use the appropriate pages of this form to report'results for all components tested. The completed form, written test procedures, and printouts from tests(if applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: CIRCLE K 2701270 Date of Testing: 01/20/2011 Facility Address: 5634 STINE RD , BAKERSFIELD, CA, 93313 Facility Contact: JOHN - MANAGER Phone: (6 61) 834-8625 Date Local Agency Was Notified of Testing : 01/04/2011 Name of Local Agency Inspector(if present during testing): Ernie Madena 2. TESTING CONTRACTOR INFORMATION Company Name: TANKNOLOGY, INC. Technician Conducting Test: ROBERT ALLEN 'Credentials: CSLB Licensed Contractor SWRCB Licensed Tank Tester License Type: A License Number: 743160 Manufacturer Trainine Manufacturer Component(s) Date Training Expires Incon STS 05/14/2011 3. SUMMARY OF TEST RESULTS Not Repairs Not Repair Component Pass Fail Tested Made Component Pass Fail Tested Made Spill Box 1 UNL FILL F ❑ ❑ ❑ 0 0 0 0 Spill Box 1 UNL FILL x Ell 0 0 F-11 ❑ 0 0 Spill Box 2 PRE FILL X ❑ ❑ 0 ❑ 0 ❑ Spill .Box 2 PRE FILL ❑ ❑ ❑ 0 ❑ 0 ❑ Spill Box 1 UNL VAPOR a ❑ ❑ ❑ El ❑ ❑ Spill Box 1 UNL VAPOR ❑ ❑ ❑ ❑ 0 ❑ Spill Box 2 PRE VAPOR X ❑ ❑ ❑ ❑ ❑ ❑ ❑ Spill Box 2 PRE VAPOR X 0 ❑ 0 0 0 I 0 0 0 0 O ❑ 0 ❑ ❑ 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 17110 ❑ I Eli Ell 0 If hydrostatic testing was performed,describe what was done with the water after completion of tests: Test water left on site in drum provided CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING To the best of my knowledge, the facts stated in this document are accurate and in full compliance with legal requirements Technician's Signature: Date: 01/20/2011 SWRCB, January 2006 9. Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printouts from tests(if applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: CIRCLE K 2701270 Date of Testing: 01/20/2011 Facility Address: 5634 STINE RD , BAKERSFIELD, CA, 93313 Facility Contact: JOHN - MANAGER Phone: (6 61) 834-8625 Date Local Agency Was Notified of Testing : 01/04/2011 Name of Local Agency Inspector(if present during testing): Ernie Madena 2. TESTING CONTRACTOR INFORMATION Company Name: TANKNOLOGY, INC. Technician Conducting Test: ROBERT ALLEN Credentials: CSLB Contractor X❑ICC Service Tech, ❑SWRCB Tank Tester ❑Other(Specify)A License Number: 743160 3. SPILL BUCKET TESTING INFORMATION Test Method Used: El Hydrostatic ❑ Vacuum ❑ Other 'Test Equipment Used: Incon Equipment Resolution: .0020 Identify Spill Bucket By Tank 1 1 UNL FILL 2 1 UNL FILL 3 2 PRE FILL 4 2 PRE FILL Number, Stored Product, etc.) X❑Direct Bury ]Direct Bury ❑Direct Bury ❑X Direct Bury Bucket Installation Type: ❑ Contained in Sump ❑ Contained in Sump ❑Contained in Sump ❑ Contained in Sump Bucket Diameter: 11" 1111 11" ill, Bucket Depth: 13" 13" 13" 13" Wait time between applying 15min 15min 15min 15min vacuum/water and starting test: Test Start Time(TI ): , 11: 06am 11:24am 11:06am 11:24am Initial Reading(RI ): 5.4100 5. 4102 5. 6805 5. 6800 Test End Time(TF ): 11:21am 11:39am 11:2lam 11:39am Final Reading(R F ): 5.4091 5. 4096 5. 6801 5. 6800 Test Duration: 15min 15min 15min 15min Change in Reading(R F -R1 ): .0009 .0 0 0 6 .0004 0 Pass/Fail Threshold or 0020 .0020 .0020 .0020 Criteria: E€ate rti s }�}, Eglrc .E, 7tiSSd ;y t9} ;*,E} k,:ua,i, 3„GE i z"E21 g :,,tiEid! , ri�Rv_{w �l. �,t[b �' }i,.. r Test esult. ! �:Pass,, ,}EFa►1f:��X 3;Pass ,, ,3 ,a�4,-. �; Pass �, ,} ail (it ,iPass Faila; XI P 1�'' k 1 a „ il�r1, a r ( n ��s t ! �1 s ._ "!�. - a '� EEO - ...._ .._ �„ i,w __.<.3a�t,.' Comments 7 (include information on repairs made prior to testing, and recommended follow-up for failed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true,accurate,and in full compliance with legal requirements. Technician's Signature: �I�� Date: 01/20/2011 1 C♦�to 1.,.,,o .,...7«o..,.l.,r:..,.o .1..,,..t..,.««e.,�l.,«o.....«o♦o,.r:.,..f..ho..o«f'......,ea 1..,., ...,.,1:F.o.l ....,.�«.,..t.,« LT....,n.,o« 1.....,1«o.....«o...or♦� SWRCB,January 2006 9. Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and Printouts from tests(if applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: CIRCLE K 2701270 DateofTesting: 01/20/2011 Facility Address: 5634 STINE RD , BAKERSFIELD, CA, 93313 Facility Contact: JOHN - MANAGER Phone: (6 61) 834-8625 Date Local Agency Was Notified of Testing : 01/0 4/2 011 Name of Local Agency Inspector(if present during testing): Ernie Madena 2. TESTING CONTRACTOR INFORMATION Company Name: TANKNOLOGY, INC. Technician Conducting Test: ROBERT ALLEN Credentials CSLB Contractor a ICC Service Tech. 0 SWRCB Tank Tester E Other(Specify)A License Number: 743160 3. SPILL BUCKET TESTING INFORMATION Test Method Used: a Hydrostatic El Vacuum Other Test Equipment Used: I n co n Equipment Resolution:.0 0 2 0 MURNMRIMME Identify Spill Bucket(By Tank 1 1 UNL VAPOR Z 1 UNL VAPOR 3 2 PRE VAPOR 4 2 PRE VAPOR Number, Stored Product, etc.) QX Bucket Installation Type: Direct Bury XQ Direct Bury ]Direct Bury QX Direct Bury ❑Contained in Sump ❑ Contained in Sump ❑Contained in Sump ❑ Contained in Sump Bucket Diameter: 11" lift lilt 11 ' Bucket Depth; is" 15" is" 151, Wait time between applying 15min 15min 15min 15min vacuum/water and starting test: Test Start Time(TI ): 11:06am 11:24am 11:06am 11:24am Initial Re ading(RI ): 5.0534 5.0528 4 . 9243 4 . 9233 Test End Time(TF ): 11:21am 11:39am 11:2lam 11:39am Final Reading(RF ): 5.0527 5.0523 4 . 9233 4 . 9232 Test Duration: 15min 15min 15min 15min Change in Reading(R F -R1 ): .0007 .0005 .0010 .0001 Pass/Fail Threshold or .0020 .0 0 2 0 . 0020 . 0 0 2 0 Criteria: �; .:a�}�_„ � >VV i a �i dE� r4 ( k A{ r ... VAS Wiestsuls � �Pass: 4 '�1atl _ M„�, Passr 11CaiI �,pih Pass � a�I , ���Pass�,� �a�ls, '.'.. �.. ,E r,. .� Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true,accurate,and in full compliance with legal requirements. Technician's Signature: Date: 01/20/2011 CM+o 1..,,... .,.,,1 .1......+..,.r.e.,N.. ........... 1.....,1 .o....:. o..r� Work Order: 3180345 �e�1�{Nom►-M�tdar t-6►�07 Emergency Shut Off(ESO) & I*ienser Emergency Shutoff VaWe (ESV) ANNUAL TEST RECORD LOCATIONS AND TEST DATA tee 2 > -c G Slmofic Shft ID ft Addrew cur. Emmmff Shut Off&Q&Taft On - in accordance with`ESA Vendor {3-21-05).(W,fim Vakm's Rail e Dapartngarnt,es a pact of ammsi cmoqimw testier this eve teabtd the Emmoncy 3hrmR O$CM switches iadua ted on this Ante�. lisped below Emmp-y Shut offow) 1M.Provide OpwmkmW IV A *hftMoe IGg# Die CeMd: On j_�y�ink with NFPA MIA this r�tesoed the a ftmat odosing feature of tl a ispensu Emergency Sbutvff VALVE(S)MM located m the supply lftm at the base of each individual island type dispenser indiicamd on the diagram below.Each device(#) in all, would close.F' listed below: _ Disp•EmaNwey Mw Of IfNo,Provide �� Val-(EM Opmudwan ON I Mehmwaoe a Dow Called Sak& p OrLOCNIM�d iho®mK Tmte� i LAC 0 C'6 r Tanknology Inc. 11000 N. MoPac Expwy#500,Austin,Texas 78759 •Tankwicogy 8501 N MOPAC EXPRESSWAY,SUITE 400 AUSTIN,TEXAS 78759 (512)451-6334 FAX(512)459-1459 TEST DATE:01/20/11 WORK ORDER NUMBER3180345 CLIENT:CIRCLE K STORES SITE:CIRCLE K 2701270 COMMENTS Monitor Cert, Leak Detector, Spill Bucket, Impact Valve & e-stop. All tests passed. PARTS REPLACED ££+,jE_}E €€ES€fit{3€E •,E,:E.¢ -l' € E:tss¥rsj, ,.,q.t.( g ,E?€,'di.t{t3t7 €€ €'':i[(qts it tigltE:r3 ., r it jrosEt, ;E; ;t E �Ey� URS���E a£,;,,**ANT 1TTY �; a"a€I E HELIUM PINPOINT TEST RESULTS (IF APPLICABLE) tj�jll's �tE3itt33 I .. (€j F 7, r 'x €v it_ i t {.). r{ i �ct} €liii(If t r £ is {t 4 ,FSiEi4E{ i i 'i I '...3! + t„ x'�'z�.(.j-.:lj£)#i ,3 t.,.x,<_:Pl iE(�i PO S. ;.<t � ,, r� n d a;& t tg l {1�„ # c,� ' €:,a£ « «4: ttlE .IT.EMS TESTED s p ( 'tip -1 t!tjrt 111 1 .�� ,, . �1- i�11 .�,.�1 t t�u;€i,[t il�pp 19 l...,,,I). jl I ,,,� $t .�Pt I �@�yylll..,:'�. a. t�, �.:� ..��.� €. .9,, S, c "f'f i It 3. p.t- �; :£I .€,_ll t' ,t. b..: .:s-E. x € j!j -r,'r;E it' gt,'� -3. tIT a���Eti�h�SM�E la,.'Ir �+ ,£i�iiN'1, t n��I,r1���,ji�<Lc=o� ,�a,�E. ,E htltl������a o I��M.<I}2�11 � t,3 'TE!�IIi +l�:� .. r. E � E t € t _ � {>fi _ � , E of §} tt j7 { J ((tt}}� II L I '€ (a M t1E €l�i i1ltl€i.. { „I s tE_,_< t HELtWM;PINPOA#C£{TESTIRE5�ilsTS�� r€�5€i. l ';4_ ✓r'. a9E •�Et a£ ;EEE ,., ,. .,3.,� ;l r ”,"':q V 't'i`'j E E'g¢?..t E1 E:'1. £,€( E, -.v,}3'%P M � 7E. i y] 3...,.E Il t g yE(,,ll((g7� (� ,I:;(t 7 Ippy E.,.A t� (yy p ''.i , .7{�,f tE#� E. ., j 5]I.E (.q 7 jp ,}!�a "y�yy, E I'l �k 59rka{, �, �... >n € _ -,IE, }Il,�,n E. {j�l{$3d9i�f,»..n E�4i PP 13E"d,:,�I 1, i$>�„ N1%1i3t l..��i- o-t.f£,- ,�#{�tI.�.E>, x.j�p e�E 41,1;EEt9tdri} {p£''ikF{l'>�. EE,EadE{EF�t&fi€1€.-,� Printed 02/14/2011 08:14 ACRAMER SITE DIAGRAM i Tanknology 8501 N MOPAC EXPRESSWAY,SUITE 400 AUSTIN,TEXAS 78759 (512)451-6334 FAX(512)459-1459 TEST DATE:01/20/11 WORK ORDER NUMBER3180345 CLIENT:CIRCLE K STORES SITE: CIRCLE K 2701270 DUMP- STER v Z7 O_ 0 N m 4m CANOPY ESO • /EN cas I F STP 0 pv I zero A AIR1 V N H2O E F wt mugggm Printed 02/14/2011 08:14 ACRAMER Work Order: 3180345 ALARM HISTORY REPORT ALARM HISTORY REPORT ---- IN-TANK ALARM ----- ---- IN-TANK ALARM ----- T 2:UNL-PREM T 1:UNL-REG HIGH WATER ALARM CIRCLE K 2701270 HIGH WATER ALARM JAN 20. 2011 11:29 AM 5634 STINE RD. JAN 20. 2011 11:24 API BAKERSFIELD, CA OVERFILL ALARM OVERFILL ALARM JAN 20, 2011 11:42 AM JAN 20, 2011 11 :41 AM JAN 20, 2011 1 :31 PM DEC 21, 2010 4:36 AM LOW.PRODUCT ALARM DEC 21, 2010 4:29 AM JAN 20. 2011 11 :24 AM JAN 1. 2011 1 :15 AM LOW PRODUCT ALARM SYSTEM STATUS REPORT JAN 20, 2011 11 :21 AM HIGH PRODUCT ALARM - - - - - - - - - - - - JAN 20. 2011 11 :42 AM ALL FUNCTIONS NORMAL HIGH PRODUCT ALARM JAN 20. 2011 11 :42 AM INVALID FUEL LEVEL DEC 20. 2010 11 :37 Phl JAN 20, 2011 11 :26 AM INVALID FUEL LEVEL PROBE OUT JAN 20. 2011 11:21 AM JAN 20. 2011 11 :53 AM JAN 20, 2011 11:25 AM PROBE OUT JAN 20, 2011 11:22 AM JAN 20. 2011 11 :56 AM JAN 20. 2011 11 :20 AM HIGH WATER WARNING ALARM HISTORY REPORT HIGH WATER WARNING JAN 20. 2011 11 :29 AM ----- SYSTEM ALARM ----- JAN 20, 2011 11:24 AM PAPER OUT DELIVERY NEEDED JAN 3, 2011 6:31 AM JAN 20. 2011 11:24 AM PRINTER ERROR DELIVERY NEEDED DEC: 31. 2010 5:23 PM JAN 3, 2011 6:31 AM JAN 20, 2011 11:22 AM SERVICE NOTICE JAN 19. 2011 12:01 PM LOW TEMP WARNING JAN 20. 2011 11:23 AM Tanknology Inc. 11000 N.MoPac Expwy#500,Austin,Texas 78759 Work Order: 3180345 ALARM HISTORY REPORT ----- SENSOR ALARM ----- L 1 :87 ANNULAR ANNULAR SPACE SENSOR OUT ALARM JAN 20. 2011 9:41 AM FUEL ALARM JAN 20. 2011 9:37 A9 ALARM HISTORY REPORT ----- SENSOR ALARM ----- L 3:91 ANNULAR ANNULAR SPACE END * K M SENSOR OUT ALARM JAN 20. 2011 9:41 AM FUEL ALARM JAN 20, 2011 9:31 AM ALARM HISTORY REPORT --- - SENSOR ALARM ----- L 1 :07 ANNULAR x x * * w END O 'vi m ri o ANNULAR SPACE SENSOR OUT ALARM JAN 20, 2011 9:41 AM FUEL ALARM JAN 20. 2011 9:37 AM ALARM HISTORY REPORT ----- SENSOR ALARM ----- L 4:91 TURBINE STP SUMP x x k' x END * k * X SENSOR OUT ALARM JAN 20, 2011 9:41 AM FUEL ALARM JAN 20, 2011 9:29 AM ALARM HISTORY REPORT ----- SENSOR ALARM ----- L 2:87 TURBINE STP SUMP SENSOR OUT ALARM JAN 20. 2011 9:41 AM FUEL ALARM JAN 20, 2011 9:35 AM Tanknology Inc. 11000 N.MoPac Expwy#500,Austin,Texas 78759 Work Order: 3180345 SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIr1E FORMAT MON DD YYYY HH:MM:SS ,S1 CIRCLE K 2701270 5634 S71NE RD. BAKERSFIELD, CA SHIFT TIME 1 5:00 AM SHIFT TIME 2 DISABLED SHIFT TIME 3 DISABLED CIRCLE K 2701270 SHIFT TIME 4 DISABLED 5634 STINE RD. COMMUNICATIONS SETUP BAKERSFIELD. CA TANK PER TST NEEDED WRN - - - - - - - - - - - - DISABLED TANK ANN TST NEEDED WRN JAN 20. 2011 6:26 AM DISABLED PORT SETTINGS: LINE RE-ENABLE METHOD COMM BOARD : 1 (EDIM ) PASS LINE TEST RS-232 SECURITY SYSTEM STATUS REPORT CODE : DISABLED - - - - - - - - - - - LINE PER TST NEEDED WRN ALL FUNC:T 1 ONS NORMAL DISABLED COMM BOARD 2 (RS-232) LINE ANN TST NEEDED WRN BAUD RATE 9600 DISABLED PARITY ODD STOP BIT l STOP PRINT TG VOLUMES STOP LENGTH: 7 DATA ENABLED RS-232 SECURITY TEMP COMPENSATION CODE : DISABLED VALUE (DEG F ): 60.0 COMM BOARD 3 (RS-232) STICK HEIGHT OFFSET BAUD RATE 9600 CIRCLE K 2701270 DISABLED PARITY ODD 5634 STINE RD. ULLAGE: 90% STOP BIT : 1 STOP BAYERSFIELD. CA DATA LENGTH: 7 DATA H-PROTOCOL DATA FORMAT RS-232 SECURITY HEIGHT CODE : DISABLED JAN 20, 2011 8:2C AM DAYLIGHT SAVING TIME ENABLED START DATE AUTO TRANSMIT SETTINGS: MAR WEEK 2 SUN SYSTEM STATUS REPORT START TIME AUTO LEAK ALARM LIMIT - - - - - - - - - - - - 2:00 AM DISABLED ALL FUNCTIONS NORMAL END DATE AUTO HIGH WATER LIMIT 140V WEEK 1 SUN DISABLED END TIME AUTO OVERFILL LIMIT 2:00 AM DISABLED AUTO LOW PRODUCT RE-DIRECT LOCAL PRINTOUT DISABLED DISABLED AUTO THEFT LIMIT DISABLED EURO PROTOCOL PREFIX AUTO DELIVERY START S DISABLED SOFTWARE REVISION LEVEL AUTO DELIVERY END VERSION 328.03 DISABLED SOFTWARE# 346328-100-1) AUTO EXTERNAL INPUT ON CREATED - 08.06.06.17.21 SYSTEM SECURITY DISABLED CODE : 000000 AUTO EXTERNAL INPUT OFF S=MOIIULEG 330160-004-a DISABLED SYSTEM FEATURES: MAINTENANCE HISTORY AUTO SE14SOR FUEL ALARM PERIODIC IN-TANK TESTS DISABLED DISABLED ANNUAL IN-TANK TESTS AUTO SENSOR WATER ALARM ISD DISABLED TANK CHART SECURITY AUTO SENSOR OUT ALARM DISABLED DISABLED CUSTOM ALARMS DISABLED SERVICE NOTICE ENABLED DELIVERY OVERRIDE ENABLED MASS.,,DENSITY DISABLED Tanknology Inc. 11000 N.MoPac Expwy#500,Austin,Texas 78759 Work Order: 3180345 IN-TANK SETUP T 1:UNL-REC; T 2:UNL-PREM PRODUCT CODE A PRODUCT CODE B THERMAL COEFF :.000700 THERMAL COEFF : .000700 TANK. DIAMETER 120.00 TANK DIAMETER 117.75 TANK PROFILE 4 PTS TANK PROFILE 4 PTS FULL VOL : 14976 FULL VOL 11649 90.0 INCH VOL : 12232 88.3 INCH VOL 9710 60.0 INCH VOL : 7761 58.9 INCH VOL : 5995 30.0 INCH VOL : 2078 29.4 INCH VOL 2245 FLOAT SIZE: 4.0 IN. FLOAT SIZE: 4.0 IN, WATER WARNING : 2.0 WATER WARNING 1 .5 HIGH WATER LIMIT: 2.5 HIGH WATER LIMIT: 2.5 RECEIVER SETUP: MAX OR LABEL VOL: 14976 MAX OR LABEL VOL: 11849 NONE OVERFILL LIMIT 13478 » OVERFILL LIMIT 90 10664 HIGH PRODUCT 1495% HIGH PRODUCT 95,% 11256 DELIVERY LIMIT `y DELIVERY LIMIT 8% 748 947 LOW PRODUCT 1084 LOW PRODUCT 900 LEAK ALARM LIMIT: 99 LEAK ALARM LIMIT: 99 SUDDEN LOSS LIMIT: 99 SUDDEN LOSS LIMIT: 99 TANK TILT 0.00 TANK TILT 0.00 PROBE OFFSET 0100 PROBE OFFSET 0.00 AUTO DIAL TIME SETUP: SIPHON MANIFOLDED TANKS SIPHON MANIFOLDED TANKS NONE TO: NONE Td: NONE LINE MANIFOLDED TANKS LINE MANIFOLDED TANKS TO: NONE TO: NONE LEAK MIN PERIODIC.: 0% LEAK MIN PERIODIC: 0% 0 LEAK MIN ANNUAL 0% LEAK MIN ANNUAL 0'6 PERIODIC TEST TYPE PERIODIC TEST TYPE STANDARD STANDARD RS-232 END OF MESSAGE ANNUAL TEST FAIL ANNUAL TEST FAIL DISABLED ALARM DISABLED ALARM DISABLED AUTO DIAL ALARM SETUP PERIODIC TEST FAIL PERIODIC: TEST FAIL - - - - - - - - - - ALARM DISABLED ALARM DISABLED GROSS TEST FAIL GROSS TEST FAIL ALARM DISABLED ALARM DISABLED ANN TEST AVERAGING: OFF ANN TEST AVERAGING: OFF PER TEST AVERAGING: OFF PER TEST AVERAGING: OFF TANK TEST NOTIFY: OFF TANK TEST NOTIFY: OFF TNK TST SIPHON BREAK:OFF TNK TST SIPHON BREAK:OFF DELIVERY DELAY 2 MIN DELIVERY DELAY 2 MIN PUMP THRESHOLD : 10.00% PUMP THRESHOLD : 10.00%s Tanknology Inc. 11000 N. MoPac Expwy#500,Austin,Texas 78759 Work Order: 3180345 OUTPUT RELAY SETUP R 1:87 SHUTDOWN TYPE: STANDARD NORMALLY CLOSED TANK 0: 1 LEAK TEST METHOD IN-TANK. ALARMS - - - - - - - - - - - - T 1 :HIGH WATER ALARM TEST ON DATE : ALL TANK T ]:LOW PRODUCT ALARM JUN 6. 2008 LIQUID SENSOR ALMS START TIME 12:00 AM TEST RATE :0.20 GAL,HR L i:FUEL ALARM DURATION 2 HOURS L 2:FUEL ALARM L ]:SENSOR OUT ALARM TST EARLY STOP:UISHBLED L 2:SENSOR OUT ALARM L I:SHORT ALARM LEAK TEST REPORT FORMAT L 2:SHORT ALARM NORMAL ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOLJ COLLECT FAIL R 2:91 SHUTDOWN LIQUID SENSOR SETUP TYPE: - - - - - - STANDARD NORMALLY CLOSED L 1:87 ANNULAR TRI-STATE (SINGLE FLOAT) TANK M: 2 CATEGORY : ANNULAR SPACE IN-TANK ALARM T 2:HIGH WATER ALARM L 2:87 TURBINE T 2:LOW PRODUCT ALARM TRI-STATE (SINGLE FLOAT) T 2:PROBE OUT CATEGORY SUMP LIQUID SENSOR ALMS L 3:FUEL ALARM L 3:91 ANNULAR L 4:FUEL ALARM TRI-STATE (SINGLE FLOAT) L 3:SENSOR OUT ALARM CATEGORY : ANNULAR SPACE L 4:SENSOR OUT ALARM L 3:SHORT ALARM L 4:SHORT ALARM L 4:91 TURBINE ISD SITE ALARMS TRI-S ATE (SINGLE FLOAT) . ISD GROSS PRES FAIL CATEGORY STP SUMP ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 4:FUEL ALARMS TYPE: STANDARD NORMALLY OPEN TANK it: NONE LIQUID SENSOR ALMS ALL:FUEL ALARM Tanknology Inc. 11000 N.MoPac Expwy#500,Austin,Texas 78759 Work Order: 3180345 SMARTSENSOR SETUP s i:DISP 1-2 AFM ISD AIRFLOW METER MAP CATEGORY AIR FLOW METER ID SERIAL NUM LABEL_ _ s 2:DISP 3-4 AFM 1-21590 -DISP 1-2 A CATEGORY AIR FLOW METER 2 21561 DISP 3-4 A s 3:DISP 5-6 AFM 3 21597 DISP 5-6 A CATEGORY AIR FLOW METER 4 21572 DISP 7-8 A s 4:D1SP 7-8 AFM ISD FUEL GRADE HOSE MAP CATEGORY AIR FLOW METER 1 2 3 4 s 5:DISP 1-2 VPS FP MHH MHH MHH MHH AA CATEGORY VAPOR PRESSURE ------------------------ 01 401 5D1 901 U U 1 02 402 502 902 U U 1 03 403 903 503 U U 2 04 404 504 904 U U 2 05 405 905 505 U U 3 06 406 506 906 U U 3 07 407 507 907 U U 4 08 40B 508 908 U U 4 LABEL TABLE ------------------------ 1 : UNASSIGNED 2: BLENDS EVR/ISD SETUP 3: REGULAR 4: MID GRADE 5: PREMIUM 6: GOLD EVR TYPE: VACUUM ASSIST 7: BRONZE VACUUM ASSIST TYPE 8: SILVER HEALY VAC 9: BLEND2 10: BLEND4 NOZZLE A,-L RANGE MAX: 1 .15 MIN: 0.95 VAPOR PROCESSOR TYPE NONE ANALYSIS TIMES TIME: 9:00 AM DELAY MINUTES: 1 PRO SETUP PMG VERSION: 01 :01 ACCEPT HIGH ORVR: DISABLED VAPOR PROCESSOR TYPE ISD HOSE TABLE NONE ID FP FL HL AA RR ------------------------- PROCESSOR CONTROL LEVEL: 01 01 01 02 01 UU NONE 02 02 02 02 01 UU 03 03 03 02 02 UU 04 04 04 02 02 UU 05 05 05 02 03 UU 06 06 06 02 03 UU 07 07 07 02 04 UU 08 08 08 02 04 UL Tanknology Inc. 11000 N.MoPac Expwy#500,Austin,Texas 78759 Work Order: 3180345 CIRCLE K 2701270 5634 STINE RD CIRCLE K 2701270 BAKERSFIELD 5634 STINE RD CALIFORNIA BAKERSFIELD 3180345 CALIFORNIA 3180345 01/20/2011 11:22 AM 01/20/2011 11:39 AM SLK LEAK TEST REPORT 87SP1LL SUMP LEAK TEST REPORT 87SPILL TEST STARTED 11:06 AM TEST STARTED 01/20/2011 TEST STARTED 11:24 AM BEGIN LEVEL 5,4100 IN TEST STARTED 01/20/2011 END TIME 11:21 AM BEGIN LEVEL 5,4102 IN END DATE 01/20/2011 END TIME 11:39 AM END LEVEL 5,4091 IN END DATE 01/20/2011 LEAK THRESHOLD 0,002 IN END LEVEL 5,4096 IN TEST RESULT PASSED LEAK THRESMLD 0,002 IN TEST RESULT PASSED 91SPILL 91SPILL TEST STARTED 11:08 AM TEST STARTED 01/20/2011 TEST STARTED 11:24 AM BEGIN LEVEL 5.6805 IN TEST STARTED 01/20/2011 END TIME 11:21 AM BEGIN! LEVEL 5,6800 IN END DATE 01/20/2011 END TIME 11:39 AM END LEVEL 5.6801 IN Ertl DATE 01/20/2011 LEAK THRESHOLD 0,002 IN END LEVEL 5,6800 IN TEST RESULT PAM LEAK THRESHOLD 0,002 IN TEST RESULT PASSED 87VAPOR 87VAPOR TEST STARTED 11:05 AM TEST STARTED 01/20/2011 TEST STARTED 11:24 AM BEGIN LEVEL 5.0534 IN TEST STARTED 01/20/2011 END TIME 11:21 AM BEGIN LEVEL 5,0528 IN END DATE 01/20/2011 END TIME 11:39 AM END LEVEL 5,0527 IN END DATE 01/20/2011 LEAK THRESHOLD 0.002 IN END LEVEL 5,0523 IN TEST RESULT PASSED LEAK THRESHOLD 0,002 IN TEST RESULT PASSED 91VAPOR 91VAPOR TEST STARTED 11:06 AM TEST STARTED 01/20/2011 TEST STARTED 11:24 AM BEGIN LEVEL 4,9243 IN TEST STARTED 01/20/2011 END TIME 11:21 AM BEGIN LEVEL 4,9233 IN END DATE 01/20/2011 END TIME 11:39 AM END LEVEL 4,9233 IN END DATE 01/20/2011 LEAK THRESHOLD 0,002 IN ENO LEVEL d.9232 IN TEST RESULT PASSED LEAK THRESHOLD 0,002 IN TEST RESULT PASSED Tanknology Inc. 11000 N.MoPac Expwy#500,Austin,Texas 78759 Pp, manknoiogy 11000 N. MoPac Expressway,Suite 500 Austin,Texas 78759 Phone: (512)451-6334 Fax: (512)459-1459 Date Printed and Mailed: 02/14/2011 BAKERSFIELD FIRE DEPARTMENT OFFICE OF ENVIRONMENTAL SERVICES INSPECTOR CRAIG PERKINS 1501 TRUXTUN AVE. BAKERSFIELD, CA. 93301 Test Date: 01/20/2011 Order Number: 3180345 Dear Regulator, Enclosed are the results of recent testing performed at the following facility: CIRCLE K 2701270 5634 STINE RD BAKERSFIELD, CA. 93313 Testing performed: Leak detector tests Monitor Certification Secondary Containment-Spill Container Sincerely, Dawn Kohlmeyer Manager, Field Reporting � ^ TANKNOLOGY CERTIFICATE OF TESTING 8501 N MOPAC EXPRESSWAY,SUITE 400 AUSTIN,TEXAS 78759 TELEPHONE(512)451-6334 FAX(512)459-1459 PURPOSE: COMPLIANCE TEST RESULT SUMMARY REPORT TEST DATE: 01/20/11 WORK ORDER NUMBER: 3180345 CUSTOMER PO: Rex Abacan CLIENT: CIRCLE K STORES SITE:CIRCLE K 2701270 495 E.RINCON,STE.150 5634 STINE RD CORONA,CA 92879 BAKERSFIELD,CA 93313 REX ABACAN JOHN-MANAGER (951)270-5193 (661)834-8625 TEST TYPE: TLD-1 Product Pipe Tightness Test Results INN 3�u3ryE[t f 3y:: ,E.i2� .9r:". €; 3€ d! s 1 r .-€� 3 n :'t E s ,,,A,;l' it t^ t.ti j!i E)r ,t a , ![l is ((, d ' 3 ,,ddb(. 1 3.^.=,i€I tl(fit l I 1 l(I'm t SIMPACT, INE ' ,t .`>€ ���3�T� 3.:1,,, �t �..,E;i, € aE )4{ ,:. l•,,E€E.EESis;3 ,! t ,:,33n€E S€5,r.',R.3ECl, I!l TE T'R U €T' i11I1„C FINALKL'EAK=RATE.. , ;-,h S , S L t! El lgp 1 31 VALVE [,. •i`�,€.[ � ,pl5snil'e' 33�E.,E. € ,II, 3 PIS„ I 7 3 ?�.:. 1,i ➢� �£', y E. i E( RbDU gyp, ATERIAL(iEi'' 'i ITYPSi t€'Sit 1d lti ,;+ E • ,I`, I.,r,i; 111{ 3 , tt,,e t�GtD3; A _.[ r. B ,_. ..,„C, D i W�•.=,�C.� 3 ,..,.,,.E�u ,.,. �d.�w 1E �a �.. ti,z,vwfY ,:..„'l��ti� �f� {ate Fl1NCTIQ. T1-87 1 UNLEADED DW FIBERG PRESSURE Y T2-91 2 PREMIUM DW FIBERG PRESSURE Y Existing Line Leak Detector Test i tl '+�Rio'E' !(', 1 € 'to-;; i 'i`E c 113 1El„ P 3ir3 EE ...TI G,L`EEAKi1D,E ;E ORj#2,r V+ d x'- F e: .?.3 ,E;� :x, 1k 5„'.1'” F'1 e.'.'.' ..,e z�,LSi,,.. 'nti < 'A,. .... :i,r,. k` �. c. „•. 11 5vx T,,,a,,r Et€i §'°;•,,t .«t;1!` 2msi,t€iEK f1lt€Psa „t,[EEI, �1P�df€IE3„ ;,€E MEEt{ I"s s E 5 it1?11 €4.5,Et tlltikE 1. 94 II LINE .: r I , yii. II, � l Ii � UFACIIItER =MODEL!! ' RESULT MANUACtTURER IIAAODEL,# SE, AL# _ ,,RESUL I , re, € a ,1,a •,3 1uG (l�da' '1' 1 ��£luty' ,1[��i tl ku„� t,U�d�l$#}a3,3 „ ,�; ,,,,`�d;,1��M,�., 3,«u,(3» T1-87 1 VAPORLESS MLD 08041484 P T2-91 2 VAPORLESS MLD 09111129 P ) New Replacement Line Leak Detector Test a E$ "N[N f W,”S k+r tll i items t41`s+h 1i €tr€3r t fit €I€ , . li ,i,., rs;:;: ,d ,,,..,. �,;�€�s ➢�5,.,.,a..:. EE i`5 1 yx..�,.�',,t,n i _ _;; , , F1{ 'LINE ., A; u; €€3# , , S,F,. ,, t 3E Mi4NUPACTURER,':,.,,EM DEL# IJt M.NUEAC .URER . , IMO EL,y.,,it EPt AL I. RESULT ra3, 4,;. O . 1 Qa„3 �l k a i«°1.19 tld d 3 1k k 333Eu :� k� ba .,.d:I 'T For owner detailed report information,visit www.tanknology.com and select On-Line Reports-WRAP,or contact your local Tanknology office. Tester Name:ROBERT ALLEN Technician Certification Number:3637843760 L Printed 02/14/2011 08:14 ACRAMER INDIVIDUAL TANK INFORMATION AND TEST RESULTS elp TenknokVy TEST DATE: 01/20/11 8501 N MOPAC EXPRESSWAY,SUITE 400 WORK ORDER NUMBER: 3180345 AUSTIN,TEXAS 78759(512)451-6334 CLIENT: CIRCLE K STORES SITE: CIRCLE K 2701270 Tank ID: Ti-87 1 Tank manifolded: NO Bottom to top fill in inches: Product: UNLEADED Vent manifolded: YES Bottom to grade in inches: Capacity in gallons: 14,976 Vapor recovery manifolded: YES Fill pipe length in inches: Diameter in inches: 92.00 Overfill protection: YES Fill pipe diameter in inches: 4.0 Length in inches: 527 Overspill protection: YES Stage I vapor recovery: DUAL Material: Dw FIBERG Installed: ATG Stage II vapor recovery: ASSIST CP installed on: COMMENTS .�, 6 {.>�..,1.>. E...,...{8£i b .p•.[si;xl v,...rx{ t j£. TANKTEST RESULTS I)(I YfTest 7jMethtld _NONE N f LEAK DETECTOR TEST:RESULTS°` p}t p)# !I`ii#i TBSt%irtle nv�.?»>�i (ieF:Yi�1Jf;'ai3Y�.., ..£.s s y....��SFi4#.�n,ii#iitiil��.f.,.',o #I#iU�s is<LytF�'• PSI at tank bottom: New/passed Failed/replaced New/passed Failed/replaced Fluid level in inches: L.D.#1 L.D.#1 L.D.#2 L.D.#2 LIFT/OFT: Make: VAPORLESS Fluid volume in gallons: Model: rQD Tank water level in inches: S/N: 08041484 Test time: NOT Open time in sec: 4.00 Number of thermisters: TESTED Holding psi: 29 NOT Specific gravity: Resiliency cc: 150 TESTED Water table depth in inches: Test leak rate ml/m: 189.0 Determined by(method): Metering psi: 18 Leak rate in gph: Calib. leak in gph: 3.00 Result: Results: PASS COMMENTS COMMENTS tYt's=&�?t tjS{S;lN, e3'tnC¢E?sE;E dPJ':p, ei};a f9 m-,:,:)r? 4f#?e;aEt 4.hih:'eE_;, rgy",F:qE.,,#, #;. .•t,k11: CE# 1 'R.!'.�7 t',a` . ...... w^«°+w,ei'";titttl t a 'F..>R::1. FJLLA '' E5 F RS1ltS: e t t '. y.: 0 ',{£ t�INEiITES7 RES�J LTS rt 11t E l :Test type xz,�E #a •sk�l.'! { t'� S M FiUta 41 t 3 #I 7� 5 w,s£N f_ 3. gs ti 3�`F d #;':. F a i g s V d F! £',' £s kll�ilul'':{ - rlax a'{(fi'h _�---alh. s.t;~ .9h�za1>.`=.g ..; [iNh 3},,,�>r :�a-.Ct�.xi i,.�a-;S;d Test time: Ullage volume: Material: Dw FIBERG Ullage pressure: Diameter(in): 2.0 Results: Length(ft): 160.0 Test psi: DATA FOR UTS-4T ONLY: Bleedback cc: Time of test 1: Test time(min): Temperature: NOT Start time: NOT NOT NOT NOT Flow rate(cfh): TESTED End time: TESTED TESTED TESTED TESTED Time of test 2: Final gph: Temperature: Result: Flow rate(cfh): Pump type: PRESSURE Time of test 3: Pump make: FE PETRO Temperature: Flow rate(cfh): Impact Valves Operational: YES COMMENTS COMMENTS Printed 02/14/2011 08:14 ACRAMER INDIVIDUAL TANK INFORMATION AND TEST RESULTS Mr 713n TEST DATE: 01/20/11 8501 N MOPAC EXPRESSWAY,SUITE 400 WORK ORDER NUMBER: 3180345 AUSTIN,TEXAS 78759(512)451-6334 CLIENT: CIRCLE K STORES SITE: CIRCLE K 2701270 E ' "tN : i -. R*NFORMA7 . I-" h l :7W7,0 r TAN Tank ID: T2-91 2 Tank manifolded: No Bottom to top fill in inches: Product: PREMIUM Vent manifolded: YES Bottom to grade in inches: Capacity in gallons: 11,849 Vapor recovery manifolded: YES Fill pipe length in inches: Diameter in inches: 92.00 Overfill protection: YES Fill pipe diameter in inches: 4.0 Length in inches: 417 Overspill protection: YES Stage I vapor recovery: DUAL Material: Dw FIBERG Installed: ATG Stage II vapor recovery: ASSIST CP installed on: COMMENTS '.t�ksv - "—u,..._. TANK tTEST)RE$ LTS, - ,TBtst ethod NONEli ,ii F i pp E,4K°DETECTOR TES S RESULTS 'l1Elli' T.est.:method: i 113 c��3i.. ,,� fi��,. .i_r sr,- PSI at tank bottom: New/passed Failed/replaced New/passed Failed/replaced Fluid level in inches: L.D.#1 L.D.#1 L.D.#2 L.D.#2 UFT/OFT: Make: VAPORLESS Fluid volume in gallons: Model: MLD Tank water level in inches: SIN: 09111129 Test time: NOT Open time in sec: 5.00 Number of thermisters: TESTED Holding psi: 25 NOT Specific gravity: Resiliency cc: 125 TESTED Water table depth in inches: Test leak rate ml/m: 189.0 Determined by(method): Metering psi: 19 Leak rate in gph: Calib. leak in gph: 3.00 Result: Results: PASS COMMENTS COMMENTS ���ycjt3Mrr.r- %su[rotlirttxi:�ya:=.s rs. ;�,'.r$ r--' I{ F.. F i.z e�Ei 4R" 6.. ,- i.,.;..;n. `€..... >Ri r LINE TESTAESULTS"Ili,:l � ,t<��Test t "e TLD.dill€ I � }.,I,Eri i a .-. U LLAQE,TEST RESULTS F:sE Mithad;:NONE I it YP. �.. � �a i ri'�_.�r ,: -�.'�f liiii.?1lui;.n.� �dii�ll l�llm,aii Test time: Ullage volume: Material: Dw FIBERG Ullage pressure: Diameter(in): 2.0 Results: Length(ft): 160.0 Test psi: DATA FOR UTS-4T ONLY: Bleedback cc: Time of test 1: Test time(min): Temperature: NOT Start time: NOT NOT NOT NOT Flow rate(cfh): TESTED End time: TESTED TESTED TESTED TESTED Time of test 2: Final gph: Temperature: Result: Flow rate(cfh): Pump type: PRESSURE Time of test 3: Pump make: FE PETRO Temperature: Flow rate(cfh): Impact Valves Operational: YES COMMENTS COMMENTS Printed 02/14/2011 08:14 ACRAMER