HomeMy WebLinkAbout2010 RESULTS 13 MONITORING SYSTEM CERTIFICATION
1E For Use By All Jurisdictions Within the State of California
Authority Cited: Chapter 6 7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be
prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided
to the tank system owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems
within 30 days of this date.
A. General Information
Facility Name: #360 Farrell's Fastrip Bldg.No.:
Site Address: 6401 White Lane City: Bakersfield Zip: 93309
Facility Contact Person: Omero Garcia Contact Phone No.: 661-393-7000
Make/Model of Monitoring System: Veeder-Root TLS-350 Date of Testing/Servicing: 8/16/2010
B. Inventory of Equipment Tested/Certified
Check the appropriate boxes to indicate specific equipment Inspected/serviced:
Tank ID: 12000 gal. Regular Tank ID: 12000 gal.Super
[x] In-Tank Gauging Probe. Model:847390-107 L] In-Tank Gauging Probe. Model:847390-107
[x] Annular Space or Vault Probe. Model:794380-303 [x] Annular Space or Vault Sensor. Model:794380-303
[x] Piping Sump/Trench Sensor(s). Model:794380-208 Piping Sump/Trench Sensor(s). Model: 794380-208
[x] Fill Sump Sensor(s) Model:794380-208 U Fill Sump Sensor(s). Model:794380-208
[x] Mechanical Line Leak Detector. Model:FX1V [x] Mechanical Line Leak Detector. Model: FX1V
❑ Electronic Line Leak Detector. Model: ❑ Electronic Line Leak Detector. Model:
U Tank Overfill/High Level Sensor. Model:847390-107 U Tank Overfill/High Leval Sensor. Model: 847390-107
❑ Other(specify equip.type and model in Sec. E on Pg.2) ❑ Other(specify equip.type and model in Sec. E on Pg. 2)
Tank ID: 12000 gal. Diesel Tank iD:
[x] In-Tank Gauging Probe. Mode 1:.847390-107 ❑ in-Tank Gauging Probe. Model:
[x] Annular Space or Vault Sensor. Model:794380-303 ❑ Annular Space or Vault Sensor. Model:
[x] Piping Sump/Trench Sensor(s). Model:794380-208 ❑ Piping Sump/Trench Sensor(s). Model:
[x] Fill Sump Sensors(s). Model:794380-208 ❑ Fill Sump Sensor(s). Model:
[x] Mechanical Line Leak Decector. Model:FX1DV ❑ Mechanical Line Leak Detector. Model:
❑ Electronic Line Leak Detector. Model: ❑ Electronic Line Leak Detector. Model:
[x] Tank Overfill/High Level Sensor. Model:847390-107 ❑ Tank Overfill/High Level Sensor.Model:
❑ Other(specify equip.type and model in Sec. E on Pg.2) ❑ Other(specify equip.typs and model in Sec. E on Pg.2)
Dispenser iD: 1 &2 Dispenser ID: 3&4
[x] Dispenser Containment Sensor(s). Model: 794380-208 [x] Dispenser Containment Sensor(s). Model: 794380-208
[7 Shear Valve(s). [�] Shear Valve(s).
❑ Dispenser Containment Float(s)and Chain(s). ❑ Dispenser Containment Float(s)and Chain(s)
Dispenser iD: 5&6 Dispenser ID: 7&8
[x] Dispenser Containment Sensor(s). Model: 794380-208 [x] Dispenser Containment Sensor(s).Model: 794380-208
[x] Shear Valve(s). Shear Valve(s).
❑ Dispenser Containment Float(s)and Chains(s). ❑ Dispenser Containment Float(s)and Chain(s).
i
Dispenser ID: Dispenser iD:
❑ Dispenser Containment Sensor(s). Model: ❑ Dispenser Containment Sensor(s). Model:
❑ Shear Valve(s). ❑ Shear Valve(s).
❑ Dispenser Containment Float(s)and Chain(s) ❑ Dispenser Containment Float(s)and Chain(s).
*if the facility contains more tanks or dispensers,copy this form. include information for every tank and dispenser at the facility.
C. Certification -i certify that the equipment identified in this document was inspected/services in accordance with the
manufacturers'guidlines.Attached to this Certification is information(e.g.manufacturers'checklist)necessary to varify that
this information is correct and a plot plan showing the layout of monitoring equipment.For equipment capable of generating
such reports,1 have attached a copy of the report; (check all that apply) ❑x System Set-up rxlAI#M history report
Technician Name(print): Bryan A Self Signature: '
Certification No: 837601 License No:804904
Testing Company Name: Confidence UST Services,Inc. Phone No: 800-339-9930
Site Address: 6401 White Lane,Bakersfield,CA 93309 IIIIIIIIIIIIIIIIIIII 14 _Date of Testing/Servicing: 8/16/2010
IE
D. Results of Testing/Servicing
Software Version Installed: 327.04
Complete the following checklist:
Lx] Yes ❑ No* Is the audible alarm operational?
x Yes No* Is tTe—Visual alarm operational?
x I Yes No* Were all sensors visually inspected,functionally tested,and confirmed operational?
x Yes ❑ No* Were all sensors installed at the lowest point of secondary containment and positioned so that other
equipment will not interfere with their proper operation?
Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment(e.g.modem)
Hx N/A operational?
x Yes ❑ No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary
❑N/A containment monitoring system detects a leak,fails to operate, or is electrically disconnected?If yes:
which sensors initate positive shut-down? U Sump/Trench Sensors L]Dispenser Containment Sensors
Did you confirm positive shut-down due to leaks and sensor failure/disconnected? [X] Yes; ❑ No;
U Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device(i.e.no
❑N/A mechanical overfill prevention valve is installed),is the overfill warning alarm visual and audible at
the tank fill point(s)and operating properly?If so,at what percent of tank capasity does the alarm
trigger? 90 %
❑ Yes* L] No Was any monitoring equipment replaced?If Yes, identify specific sensors,probes,or other equipment
replaced and list the manufacturer name and model for all replacement parts in Section E,below.
❑ Yes* E No Was liquid found inside any secondary containment systems designed as dry systems?
❑ Product; ❑ Water. If yes,describe causes in Section E,below.
x No* Was monitoring system set-up reviewed to ensure proper settings?Attach set-up reports, if applicable.
LxJ Yes No* I Is all monitoring equipment operational per manufacturer's specifications?
* In Section E below,discribe how and when these deficiencies were or will be corrected.
E. Comments:
F. In-Tank Guaging/SIR Equipment: U Check this box if tank guaging is used only for inventory control.
❑ Check this box if tank guaging or SIR equipment is installed.
This section must be completed if in-tank guaging equipment is used to perform leak detection monitoring.
Complete the following checklist:
[X] Yes ❑ No* Has all input wiring been inspected for proper enter and term ination,including testing for ground faults?
x Yes No* Were all tank guaging probes visually inspected for damage and residue buildup?
Tx] Yes No* Was accuracy of system product level readings tested?
x Yes 7 No* Was accuracy of system water level readings tested?
x Yes No* Were all probes reinstalled properly?
L] Yes ❑ No* Were all items on the equipment manufacturer's maintenance checklist completed?
* In the Section H,below,describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD): ❑Check this box if LLD's are not installed.
Complete the following checklist:
[x] Yes ❑ No* For equip. start-up or annual equipment certification,was a leak simulated to varify LLD performance?
(Check all that apply) Simulated leak rate: ❑3 g.p.h.: 00.1 g.p.h.; ❑0.2 g.p.h.;
x Yes No* Were all LLD's confirmed operational and accurate within regulatory requirments?
x Yes 7 No Was t e testing apparatus properly calibrated?
Yes No For mac anica LLD's,does the LLD restrict product flow if it detects a leak?
N/A
❑ Yes No* For electronic LLD's,does the turbine automatically shut off if the LLD detects a leak?
[x] N/A
❑ Yes No* For electronic LLD's,does the turbine automatically shut off if any portion of the monitoring system is
M N/A disabled or disconnected?
❑ Yes No* For electronic LLD's,does the turbine automatically shut off if any portion of the monitoring system
U N/A malfunction or fails a test?
❑ Yes No* For electronic LLD's,have all accessible wiring connections been visually inspected?
[� N/A
x Yes 10 No I Were all items on the equipment manufacturer's maintenance checklist completed?
* In the section H,below,describe how and when these deficiencies were or will be corrected.
H. Comments:
SYSTEM SETUP
- - - - - - - - - - - - COMMUNICATIONS SETUP
AUG 16. 2010 8::36 AM - - - - - - - - - - - -
PORT SETTINGS:
?ASTRIP SYSTEM UNITS
-3401 WHITE LANE U.S. COMM BOARD : I (RS-232)
SAYERSFIELD-CA 93309 SYSTEM LANGUAGE BAUD RATE : 9600
ENGLISH PARITY : NONE
SYSTEM DATE/TIVIE FORMAT STOP BIT : 1 STOP
AUG 16, 2010 8:38 AM MON DD YYYY HH:MM:SS xM DATA LENGTH: 8 DATA
RS-232 SECURITY
FASTRIP CODE : DISABLED
6401 WHITE LANE
SYSTEM STATUS REPORT BAKEP.SFIELD-4A 93309 COMM BOARD 2 tRS-232}
- - - - - - - - - - - - BAUD RATE 9600
ALL FUNCTIONS NORMAL PARITY NONE
SHIFT TIME 1 7:00 AM STOP BIT I STOP
INVENTOR`! REPORT SHIFT TIME 2 DISABLED DATA LENGTH: 8 DATA
SHIFT TIME 3 DISABLED RS-232 SECURITY
SHIFT TIME 4 DISABLED CODE : DISABLED
T 1 :UNL
VOLUME - 8641 GALS TANK PER TST NEEDED WRI4 COMM BOARD : 3 (EDIM
ULLAGE - 3159 GALS DISABLED RS-232 SECURITY
90% ULLAGE- 1959 GALS TANK ANN TST NEEDED WRN CODE : DISABLED
TC VOLUME - 8728 GALS DISABLED
HEIGHT = 66.31 INCHES
WATER VOL 0 GALS LINE RE-ENABLE METHOD AUTO,TRANSMIT SETTINGS:
WATER 0,00 INCHES PASS LINE TEST
TEMP - 78.2 DEC. F AUTO LEAK ALARM LIMIT
LINE PER TST NEEDED WRN DISABLED
DISABLED AUTO HIGH WATER LIMIT
T 2:PNL LINE ANN TST NEEDED WRN DISABLED
VOLUME _ 4035 GALS DISABLED AUTO OVERFILL LIMIT
ULLAGE - 7965 GALS DISABLED
90•% ULLAGE- 6765 GALS PRINT TO VOLUMES AUTO LOW PRODUCT
TC VOLUME 3961 GALS ENABLED DISABLED
HEIGHT =35.51 INCHES AUTO THEFT LIMIT
WATER VOL 0 GALS TEMP COMPENSATION DISABLED
WATER - 0.00 INCHES VALUE (DEG F ) : 60.0 AUTO DELIVERY START
TEMP 86.3 DEG F STICK HEIGHT OFFSET DISABLED
DISABLED AUTO DELIVERY END
ULLACE: 9w. DISABLED
T 3:DIESEL AUTO EXTERNAL INPUT ON
VOLUME = 4671 GALS H-PROTOCOL DATA FORMAT DISABLED
ULLAGE - 7329 13ALS HEIGHT AUTO EXTERNAL INPUT OFF
-90% ULLAGE- 6129 GALS DAYLIGHT SAVING TIME DISABLED
TC VOLUME - 4618 GALS ENABLED AUTO SENSOR FUEL ALARM
HEIGHT = 39.61 INCHES START DATE DISABLED
WATER VOL - 0 GALS MAR WEEK 2 SUN AUTO SENSOR WATER ALARM
WATER - 0.00 INCHES START TIME DISABLED
TEMP = 85.3 DEG F 2:00 AM AUTO SENSOR OUT ALARM
END DATE DISABLED
NOV WEEK I SUN
k w R x �k END k w „ x END TIME
2:00 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
EURO PROTOCOL PREFIX
S RS-232 E14D OF MESSAGE
DISABLED
SYSTEM SECURITY
CODE : 000000
MAINTENANCE HISTORY
DISABLED
TANK CHART SECURITY
DISABLED
CUSTOM ALARMS
DISABLED
MASS/DENSITY
DISABLED
l :7:UIt7tL
IN-TANX SETUP T 2:PNL PRODUCT CODE 3
- - - - - - - - - - - - PRODUCT CODE 2 THERMAL COEFF : .000450
THERMAL COEFF : .000700 ER 96 _
T I :UNL TANK DIAMETER 96.00 TANK DIAMTE PT
PRODUCT CODE I TANK PROFILE I PT FULL VOL : 12300
THERMAL COEFF : .Uuu7u0 FULL VOL 12000
TANK DIAMETER 96.00
TANK PROFILE i PT FLOAT SIZE: 4.0 IN.
FULL VOL 12000 FLOAT SIZE: 4.0 IN.
WATER WARNING 2.0
WATER WARNING 2.0 HIGH WATER LIMIT: 3.0
FLOAT SIZE: 4.0 114. HIGH WATER LIMIT: 3.0
MAX OR LABEL VOL: 12000
.DATER WARNING �.0 MAX OR LABEL VOL: 12000 OVERFILL LIMIT 90'/.
HIGH WATER LIMIT: 3.0 OVERFILL LIMIT 90% 10800
loaccl HIGH PRODUCT 95%
4AX OR LABEL VOL: 12000 HIGH PRODUCT 95% 11400
DVERFILL LIMIT 90% 11400 DELIVERY LIMIT 15%
10600 DELIVERY LIMIT 15%, 1800
HIGH PRODUCT 95; 1800
11400 LOW PRODUCT 500
DELIVERY LIMIT 15i LOW PRODUCT 500 LEAK ALARM LIMIT: 99
1800 LEAK ALARM LIMIT: 99 SUDDEN LOSS LIMIT: 99
SUDDEN LOSS LIMIT: 99 TANK TILT 10.00
LOW PRODUCT no TANK TILT 0.00 PROBE OFFSET 0.00
LEAK ALARM LIMIT: 99 PROBE OFFSET 0100
SUDDEN LOSS LIMIT: 99
TANK TILT 10.00 SIPHON MANIFOLDED TANKS
PROBE OFFSET 0.00 SIPHON MANIFOLDED TANKS TO: NONE
T71: NONE LINE MANIFOLDED TANKS
LINE MANIFOLDED TA14KS Tv NONE
SIPHON MANIFOLDED TANKS Tit: NONE
TV: NONE
LINE MANIFOLDED TANKS LEAK MIN PERIODIC: 1%
TO: NONE LEAK MIN PERIODIC:: 1% 120
120
LEAK MIN ANNUAL 11:
LEAK MIN PERIODIC: 1: LEAK MIN ANNUAL : 1`- 120
120 120
LEAK MIN ANNUAL : 1"" PERIODIC TEST TYPE
120 PERIODIC TEST TYPE STANDARD
STANDARD
ANNUAL TEST FAIL
PERIODIC TEST TYPE ANNUAL TEST FAIL ALARM DISABLED
STANDARD ALARM DISABLED
PERIODIC TEST FAIL
ANNUAL TEST FAIL PERIODIC TEST FAIL ALARM DISABLED
ALARM DISABLED ALARM DISABLED
GROSS TEST FAIL
PERIODIC TEST FAIL GROSS TEST FAIL ALARM DISABLED
ALARM DISABLED ALARM DISABLED
ANN TEST AVERAGING: OFF
'ROSS TEST FAIL ANN TEST AVERAGING: OFF PER TEST AVERAGI NG: OFF
ALARM DISABLED PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
ANN TEST AVERAGING: OFF TANK TEST NOTIFY: OFF
PER TEST AVERAGING: OFF TNK TST SIPHON SREAK:OFF
T14K TST SIPHON BREAK:OFF
TANK TEST NOT 1 F`r': OFF DELIVERY DELAY 1 MIN
DELIVERY DELAY 1 MIN PUMP THRESHOLD : 10.00%
TNK TST SIPHON BREAK:OFF PUMP THRESHOLD 10.OD°:
DELIVERY DELAY 1 1-11N
PUMP THRESHOLD 10.00%
LEAK TEST METHOD
TEST ON DATE : ALL TANK
JAN 16, 2006
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
LEAK TEST REPORT FORMAT
14ORMAL
R 2:PNL
LIQUID SENSOR SETUP TYPE:
- - - - - - - - - - - - PUMP SENSOR SETUP PUMP CONTROL OUTPUT
TANK 0: 2
L 1:UNL STP -
TRI-STATE (SINGLE FLOAT> S I :UNL LIQUID SENSOR. ALMS
CATEGORY : STP SUMP TANK a: 1 L 4:FUEL ALARM
DISPENSE MODE: LIO:FUEL ALARM
STANDARD L11 :FUEL ALARM
L 2:UNL ANN L12:FUEL ALARM
DUAL POINT HYDROSTATIC'O, S 2:PNL L13:FUEL ALARM
CATEGORY : ANNULAR SPACE TANK 0: 2 L 4:SENSOR OUT ALARM
DISPENSE MODE: 1_10:SENSOR OUT ALARM
STANDARD Lll :SENSOR OUT ALARM
L 3:UNL FILL L12:SENSOR OUT ALARM
TRI-STATE (SINGLE FLOAT) L13:SENSOR OUT ALARM
CATEGORY : OTHER SENSORS L 4:SHORT ALARM
LIO:SHORT ALARM
LII :SHORT ALARM
L12:SHORT ALARM
L 4:PNL STP L13:SHORT ALARM
TRI-STATE (SINGLE FLOAT) ISD SITE ALARMS
CATEGOR`! : STP SUMP ISD GROSS PRES FAIL
OUTPUT RELAY SETUP ISD DEGRD PRES FAIL
L 5:PNL FILL - - - - - _ _ _ _ _ _ ISD VAPOR LEAK FAIL
TRI-STATE (SINGLE FLOAT) ISD VP PRES S FA
ISD VP STATUS IL
FA
CATEGORY : OTHER SENSORS R I :UNL
TYPE: ISD HOSE ALARMS
PUMP CONTROL OUTPUT ALL:GROSS COLLECT FAIL
L 6:PNL ANN
TANK 0: 1 ALL:DEGRD COLLECT FAIL DUAL POINT HYDROSTATIC ALL:FLOW COLLECT FAIL
CATEGORY : ANNULAR SPACE LIQUID SENSOR ALMS R 3:DIESEL
L ( :FUEL ALARM TYPE:
L10:FUEL ALARM STANDARD
LiI :FUEL ALARM NORMALLY CLOSED
L 7:DIE STP L12:FUEL ALARM
TRI-STATE (SINGLE FLOAT) L13:FUEL ALARM TANK 4: 3
CATEGORY : STP SUMP L I :SENSOR OUT ALARM
L10:SENSOR OUT ALARM
Lll :SENSOR OUT ALARM LIQUID SENSOR. ALMS
L 8:DIE FILL L12:SENSOR OUT ALARM L 7:FUEL ALARM
TRI-STATE (SINGLE FLOAT) L13:SENSOR OUT ALARM LIO:FUEL ALARM
CATEGORY : OTHER SENSORS L ( :SHORT ALARM L12:FUEL ALARM
LIO:SHORT ALARM L 7:SENSOR OUT ALARM
L11 :SHORT ALARM LIO:SENSOR OUT ALARM
L12:SHORT ALARM L12:SENSOR OUT ALARM
L 9:DIE ANN L13:SHORT ALARM L 7:SHORT ALARM
DUAL POINT HYDROSTATIC; LIO:SHORT ALARM
CATEGORY : ANNULAR SPACE ISD SITE ALARMS L12:SHORT ALARM
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL R 4:OVERFILL ALARM
ISD VAPOR LEAK-FAIL TYPE:
LIO:DISP 1-2 ISD VP PRES FAIL STANDARD
TRI-STATE (SINGLE FLOAT'S ISD VP STATUS FAIL NORMALLY OPEN
CATEGORY : DISPENSER PAN
ISD HOSE ALARMS TANK a: NONE
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
L11 :DISP 3-4 ALL=FLOW COLLECT FAIL IN-TANK ALARMS
TRI-STATE (31NGLE FLOAT) ALL:OVERFILL ALARM
CATEGORY : DISPENSER PAN ALL:HIGH PRODUCT ALARM
ALL:MAX PRODUCT ALARM
L12:DISP 5-6
TRI-STATE (SINGLE FLOAT)
CATEGORY : DISPENSER PAN
L13:D1SP 7-8
TRI-STATE (SIWLE FLOAT)
CATEGORY : DISPENSER PAN
S9ARTS£NSOR SETUP
s I :V.P SEI9S0R DISP 3-4 EVR TYPE: VACUUM ASSIST
CATEGORY VAPOR PRESSURE VACUUM ASSISI' TYPE
HEALY VAC
a 2:F.M.DISP 1-2 SOFTWARE REVISION LEVEL
CATEGORY AIR FLOW METER NOZZLE AIL RANGE VERSION 327.04
MAX: 1 .15 MIN: 0.95 SOFTWAREO 346327-100-E
s 3:F.M.DISP 3-4 CREATED - 07.02.06.10.28
CATEGORY AIR FLOW METER VAPOR PROCESSOR TYPE
NO VAPOR PROCESSOR S-MODULEO 330160-004-a
s 4:F.M.DISP 5-6 SYSTEM FEATURES:
CATEGORY AIR FLOW METER PERIODIC IN-TANK TESTS
ANALYSIS TIMES ANNUAL IN-TANK TESTS
s 5:F.M.DiSP 7-8 TIME: 10:00 AM ISD
CATEGORY AIR FLOW METER DELAY MINUTES: I PMC
ACCEPT HIGH ORVR:
DISABLED
ISD HOSE TABLE
ID FP FL HL AA RR
------------------------
01 01 Ol 02 01 UU
02 02 02 02 Ol UU
03 03 03 02 02 UU ALARM HISTORY REPORT
04 04 04 02 02 UU
05 05 05 02 03 UU ---- IN-TANK ALARM -----
06 '06 06 02 03 UU
07 07 07 02 04 UU T 1 :UNL
08 08 08 02 '04 UU
' OVERFILL ALARM
JUL 14, 2010 2:08 PM
ISD AIRFLOW METER MAP JUL 4, 2010 11 :04 PM
ID SERIAL NUM LABEL OCT 16, 2009 10:18 PM
1 8255 F.M.DISP-1 SUDDEN LOSS ALARM
28272 F.M.DISP 3 AUG 7, 2009 9:34 AM
3 8614 F.M.DISP 5
4 8258 F.M.DISP 7 HIGH PRODUCT ALARM
AUG 7. 2009 10:12 AM
ISD FUEL GRADE HOSE MAP INVALID FUEL LEVEL
1 2 3 4 AUG 9, 2010 7:58 AM
FP MHH MHH MHH MHH AA JUL 22., 2010 6:12 PM
--------------- ---------- JUL 7, 2010 4:59 PM
01 201 3o1 901 5 u 1
02 202 302 902 5 U 1 PROBE OUT
03 203 303 903 U U 2 NOV 12. 2009 6:48 PM
04 204 304 904 U U 2 NOV 12, 2009 12:56 PM
05 205 305 905 5 U 3 NOV 12, 2009 7:42 AM
06 206 306' 906 5 U 3
07 207 307 907 U U 4
OB 206 308 908 U U 4 DELIVERY NEEDED
AUG 91 2010 6:49 AM
JUL 22. 2010 737 F'M
LABEL TABLE JUL 7. 2010 4: 17 PM
----------------------
1 : UNASSIGNED
2: BLEND3
3: REGULAR
4: MID GRADE
5: PREMIUM
6: GOLD
7: BRONZE
8: SILVER
9: BLEND2
10; BLEND4
K x x END x
PMC SETUP
PROCESSOR CONTROL LEVEL:
NONE
ALARM HISTORY REPORT ALARM HISTORY REPORT
ALARM HISTORY REPORT SENSOR ALARM -----
IN-TANK ALARM ----- SENSOR ALARM ----- L 6:PNL ANN
T 2:PNL L I :UNL STP ANNULAR SPACE
STP SUMP LOW LIQUID ALARM
OVERFILL ALARM FUEL ALARM MAR 1, 2010 2:48 PM
AUG 7, 2009 10: 15 All AUG 7. 2009 10:06 All LOW LIQUID ALARM
SUDDEI4 LOSS ALARM MAR 1 . 2010 2:46 PM
AUG 7. 2009 9:33 AM LOW LIQUID ALARM
PROBE OUT AUG 7. 2009 10:27 Ali
AUG 7, 2009 10:16 All
AUG 7, 2009 9:33 Hm
HIGH WATER WARNING
AUG 7, 2009 10:13 AM
k x x x x END x x x x
DELIVERY NEEDED
FEB 17, 2010 11 :22 Pl•1
JAN 31 , 2010 2:39 PM x ;: x # END n x x x
AUG 7, 2009 10: 16 All
LOW TEMP WARNING
AUG 7, 2009 10:16 AM
ALARM HISTORY REPORT
----- SEI4BOR ALARM -----
L 4:PNL STP
STP SUMP
FUEL ALARM ALARM HISTORY REPORT
AUG 7, 2009 10:07 All ----- SENSOR ALARM -----
'� x x x END : x x x r: L 7:DIE STP
STP SUMP
FUEL ALARM
JUL 26. 2010 6:42 AM
FUEL ALARM
AUG 7, 2009 10:06 All
FUEL ALARM
END x R JUL 16, 2009 10:45 AM
ALARM HISTORY REPORT
---- IN-TANK ALARM -----
T 3:DIESEL
HIGH PRODUCT ALARM
AUG 7, 2009 10:17 Hht ii x x END
INVALID FUEL LEVEL ALARM HISTORY REPORT
MAR 26, 2010 6:42 Pl,1
----- SENSOR ALARM -----
PROBE OUT L 5:PNL FILL
AUG 7, 2009 10:18 AM OTHER SENSORS
AUG 7, 2009 9:31 AM FUEL ALARM
FEB 27. 2010 12:59 AM
DELIVERY NEEDED FUEL ALARM
HAR 26, 2010 12:06 P11 DEC 10, 2009 10:Ot PM
LOW TEMP WARNING AUGL 72009 5:51 AM
AUG 7, 2009 10:19 AM
END K x r
A.X w x. x END
ALARM HISTORY REPORT
ALARM HISTORY REPORT
----- SENSOR ALARM -----
SENSOR ALARM ----- L10:DISP 1-2 ALARM HISTORY REPORT
L 8:151E FILL DISPENSER PAN
OTHER SENSORS SENSOR OUT ALARM ----- SENSOR ALARM -----
FUEL ALARM AUG 7. 2009 10:35 AM L12:DISP 5-6
FEB 21. 2010 5:17 PM DISPENSER PAN
FUEL ALARM' SENSOR OUT ALARM
FUEL ALARM AUG 7. 2009 9:42 AM AUG 7. 2009 10:35 AM
AUG 7, 2009 10:00 All
" FUEL ALARM
FUEL ALARM AUG 7. 2009 9:43 AM
AUG 7. 2009 9:56 AM
x x x X x END x x x x x
END
END x x x x r
ALARM HISTORY REPORT
----- SENSOR ALARM ----
Ll1 :DISP 3-4 ALARM HISTORY REPORT
ALARM HISTORY REPOP.T DISPENSER PAN
FUEL ALARM ----- SENSOR ALARM -----
----- SENSOR ALARM -- -- AUG 13. 2009 12:42 Phi L13:DISP 7-8
L 9:DIE ANN DISPENSER PAN
ANNULAR SPACE SENSOR OUT ALARM SENSOR OUT ALARM
.SENSOR OUT ALARM AUG 7. 2009 10:35 AM AUG 7. 2009 10:35 AM
AUG 7. 2009 10:35 AM FUEL ALARM FUEL ALARM
LOW LIQUID ALARM AUG 7. 200'9 9:39 AM AUG 7, 12009 9:44 AM
AUG 7, 2009 to:2B AM
i
END k x . s x ;( ,s x.I k END K x k k
v x x x x END x x x
FASTRIP FASTRIP
IN-TANK ALARM ----- 6401 WHITE LANE 6401 WHITE LANE
T 1 :UNL BA}.ERSFiELD,�A 93369 SAKERSFIELD-CA 93309
HIGH PRODUCT ALARM
AUG 16, 2010 9:34 AM AUG 16. 2010 9:36 AM AUG 16, 2010 9:37 AM
SYSTEM STATUS REPORT
- - - SYSTEM STATLO REPORT
T 1 :LOW TEMP WARNING ALL FUNCTIONS NORMAL
T 2:OUERFILL ALARM
---- IN-TANK ALARM -----
T 1 :UNL
PROBE OUT
AUG 16, 2010 9:34 AM
---- IN-TANK ALARM -----
T 3:DIESEL
HIGH PRODUCT ALARM
---- IN-TANK ALARM ----- AUG 16, 2010 9:36 AM
T 2:PNL
PROBE OUT
---- IN-TANK ALARM ----- AUG 16. 2010 9:36 Alh
T I :UNL
LOW TEMP WARNING
AUG 16. 2010 9:35 AM
FA.STR I P
6401 WHITE LANE
BAKERSFIELD.CA 93309
FASTRIP
6401 WHITE LANE AUG 16. 2010 9:36 AM
BAKERSFIELD,CA 93309
---- 114-TANK ALARM -----
T 2:P14L
OVERFILL ALARM AUG 16, 2010 9:36 Aft SYSTEM STATUS REPORT
AUG 16. 2010 9:36 AM _ _
T 3:HIGH PRODUCT ALARM
SYSTEM STATUS REPORT
T I :LOW TEMP WARNING
T 2:PROSE OUT
FASTRIP
6401 WHITE LANE
BAKEP.SFIELD.GA 93309
FASTRIP
AUG 16. 2010 9:36 AM 6401 WHITE LANE
BAKERSFIELD,CA 93309
SYSTEM STATUS REPORT ---- 114-TANK ALARM --- AUG 16, 2010 9:313 AM
- - - - - - - - - - T 2:PNL
T 1 :LOW TEKP WARNING LOW TEMP WARNING
T OVERFILL ALARM
AUG 16, 2010 9:37 Am SYSTEM STATUS REPORT
- _
T 3:HIGHPRODUCT ALARM
FASTRIP T 2:PNL
6401 WHITE LANE INVENTORY INCREASE
HAY.ERSFIELD.CA 93309
INCREASE START
AUG 16. 2010 9:35 AM
AUG 16, 2010 9:38 AM
VOLUME - 7925 GALS
HEIGHT - 60.23 INCHES ----- SENSOR ALARM -----
WATER - 0.83 INCHES L 9:DIE ANN
SYSTEM STATUS REPORT TEMP = 92.2 DEC F ANNULAR SPACE
- - - - - - - - - - - - SENSOR OUT ALARM
T 3:H1GH PRODLK T ALARM AUG 16. 2010 9:40 AM
INCREASE END
AUG 16. 2010 9:38 AM
VOLUME = 11160 GALS
HEIGHT - 84.25 INCHES
WATER - 0.84 INCHES
TEMP = 92.0 DEG F
:,ROSS INCREASE- 3235 ----- SENSOR ALARM -----
TC NET INCREASE- 3164 LIO:DISP 1-2
IN-TANK ALARM ---- DISPENSER PAN
T 3:DIESEL SENSOR OUT ALARM
PROBE OUT AUG 16, 2010 9:40 AM
AUG 16. 2010 9:36 RM
---- IN-TAN); ALARM ----- ----- SENSOR ALARM -----
T I :UNL T 3:DIESEL L11 :DISP 3-4
INVENTORY INCREASE LOW TEMP WARNING DISPENSER PAN
AUG 16. 2010 9:39 AM SENSOR OUT ALARM
INCREASE START AUG 16, 2010 9:41 AM
AUG 16. 2010 9:35 AM
VOLUME 6639 GALS
HEIGHT - 52.02 II.•HES
WATER - 0.00 INCHES
TEMP -99.0 DEG F
INCREASE END T 3:DIESEL
AUG 16. 2010 9:38 AM INVENTORY INCREASE ----- SENSOR ALARM -----
L12:DISP 5-6
VOLUME a 8811 GALS INCREASE START DISPENSER PAN
HEIGHT - 66.10 INCHES AUG 16, 2010 9:37 All SENSOR OUT ALARM
WATER v 0.00 INCHES AUG 16. 2010 9:41 AM
TEMP - -99.0 DEG F VOLUTE - 7367 GALS
HEIGHT - 56.63 INCHES
WATER - 0.88 1NCWES
GROSS INCREASE- 2172 TEMP - 92.5 DEG F
TO NET INCREASE- 2414
INCREASE END
AUG 16. 2010 9:40 AM
VOLUME - 9476 GALS ----- SENSOR ALARM -----
HEIGHT - 70.72 INCHES L13:DISP 7-8
WATER = 1 .17 INCHES DISPENSER PAN
TEMP - 92.2 DEG F SENSOR OUT ALARM
AUG 16. 2010 9:41 AM
GROSS INCREASE- 2109
TC NET INCREASE- 2080
ARCHIVE UTILITY
FEE 6, 2007 5:00 AM RESTORE SETUP DATA:
FASTk1P END TIME:
6401 WHITE LANE FEB 6, 2007 8:05:26 AM
BAKERSFIELD,CA 93309
SYSTEM STATUS REPORT SYSTEM SETUP
-
AUG 16, 2.010 9:41 AM ALL FUN(::TIONS NORI94tL FEB 6, 2007 8:05 AM-
- SYSTEP1 STATUS REPORT SYSTEM UNITS
U.S.
L S:SEN-OR OUT ALARM SYSTEM LANGUFiGE
ENGLISH
L10:SEIVSOR OUT ALARM SYSTEM DATE/TIME FORT
L12:8ENSOR OUT HLARh] ---- ISD SITE ALARM ----
MON DD YYYY HH:MM:SS :,1°)
MISSING TANK SETUP FASTRIP
FEB 6, 2007 8:01 AM 6401 WHITE LANE
BAKERSFIELD.CA 93309
SHIFT TIME 1 7:00 AM
SHIFT TIME 2 DISABLED
SHIFT TIME 3 DISABLED
SHIFT TIME 4 DISABLED
TANK PER TST NEEDED WRN
SY5TEP1 RESET ---- ISD SITE ALARM ---- DISABLED
FEB 6. 2007 8:00 Arl MISSING HOSE SETUP TANK ANN TST NEEDED WRN
FEB 6, 2007 @:O! AM DISABLED
LINE RE-ENABLE METHOD
PASS LINE TEST
LINE PER TST NEEDED WRN
DISABLED
LINE ANN TST NEEDED WRN
DISABLED
ISD SITE ALARM ---- PRINT TC VOLUMES
ARI-HIVE UTILITY MISS VAPOR FLOW MTR ENABLED
FEB E. 2007 8:01 All
RESTORE SETUP DATA: TEMP COMPENSATION
START TIME: VALUE (DEG, F ) : 60.0
FEB 6, 2007 8:00:1=1 41 STICK HEIGHT OFFSET
DISABLED
ULLAGE: 90%
H-PROTOCOL DATA FORMAT
HEIGHT
---- ISD SITE ALARM ---- DAYLIGHT SAVING TIME
ENABLED
MISS VAPOR PRES BEN
START DATE
FEB 6, 2007 8:01 AM
MAR WEEK _ SUN
START TIME
2:00 AM
END DATE
NOV WEEK 1 SUN
END TIME
2:00 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
EURO PROTOCOL PREFIX
S
SYSTEM SECURITY
CODE : 000000
MAINTENANCE HISTORY
DISABLED
TANK CHART SECURIT:'
DISABLED
CUSTOM ALARMS
DISABLED
MASS/DENSIT`!
DISABLED
T 2:P1L
COMMUNICATIONS SETUP PRODUCT CODE 2
1N-TAN14 SETUP THERMAL COEFF :.000700
- - - - - - - - - - - - - - TANK DIAMETER 96.00
TANK PROFILE I PT
PORT SETTINGS: T 1 :UNL FULL VOL 12000
PRODUCT CODE I
COMM BOARD 1 (RS-2321 THERMAL COEFF : .000?00
BAUD RATE 9600 TANK DIAMETER 96.00 FLOAT SIZE: d.0 IN_
PARITY NONE TANK PROFILE 1 PT
STOP BIT 1 STOP FULL VOL 12000 WATER WARNING : 2.0
DATA LENGTH: 8 DATA HIGH WATER LIMIT: 3.0
RS-•232 SECURITY FLOAT SIZE: 4.0 IN. MATS OR LABEL VOL: 12000
CODE : DISABLED
OVERFILL LIMIT 90/
COMM BOARD 2 IRS-232> WATER WARNING 2.0 10800
BAUD RATE 9600 HIGH WATER LIMIT: 3.0 HIGH PRODUCT 95v.
PARITY NONE 11400
STOP BIT I STOP MAX OR LABEL VOL: 12000 DELIVERY LIMIT 15%
DATA LENGTH: 8 DATA OVERFILL LIMIT 901% 1800
RS-232 SECURITY 10800
CODE : DISABLED HIGH PRODUCT 95% LOW PRODUCT 500
11400 LEAK ALARM LIMIT: 99
COMM BOARD 3 (EDlrt t DELIVERY LIMIT 15% SUDDEN LOSS LIMIT: 99
RS-232 SECURITY PROBE TANK TILT 0.00
PROBE OFFSET 0.00
CODE : DISABLED LOW PRODUCT 500
LEAK ALARM LIMIT: 99
AUTO TRANSMIT SETTINGS: SUDDEN LOSS LIMIT: 99 SIPHON MANIFOLDED TANKS
TANK TILT 10.00 TO: NONE
AUTO LEAK ALARM LIMIT PROBE OFFSET 0.00 LINE MANIFOLDED TANKS
DISABLED
TO: NONE
AUTO HIGH WATER LIMIT SIPHON MANIFOLDED TANKS
DISABLED TO: NONE LEAK MIN PERIODIC: 1%
AUTO OVERFILL LIMIT
DISABLED LINE MANIFOLDED TANKS 120 AUTO LOW PRODUCT Tp: NONE LEAK MIN ANNUAL : 1%
DISABLED 120
AUTO THEFT LIMIT LEAK MIN PERIODIC: IV
DISABLED 120
AUTO DELIVERY START PERIODIC TEST TYPE
DISABLED LEAK MIN AN14UAL 11% STANDARD
AUTO DELIVERY END
DISABLED ANNUAL TEST FAIL
AUTO EXTER14AL INPUT ON ALARM DISABLED
DISABLED AUTO EXTERNAL INPUT OFF PERIODIC TEST TYPE
DISABLED STANDARD PERIODIC TEST FAIL
AUTO SENSOR FUEL ALARM ALARM DISABLED
DISABLED ANNUAL TEST FAIL
AUTO SENSOR WATER ALARM
DISABLED GROSS TEST FAIL
DISABLED ALARM DISABLED
AUTO SENSOR OUT ALARM PERIODIC TEST
DISABLED ALARM M DISABLED ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
GROSS TEST FAIL
ALARM DISABLED TANK TEST NOTIFY: OFF
ANN TEST AVERAGING: OFF TNK TST SIPHON BREAK:OFF
PER TEST AVERAGING: OFF
DELIVERY DELAY 1 MIN
TANK TEST NOTIFY: OFF PUMP THRESHOLD 10.00'.
RS-232 END OF MESSAGE TNK TST SIPHON 9REAr:OFF
DISABLED
DELIVERY DELAY 1 MIN
PUMP THRESHOLD 10.00Y
T 3:DIESEL
PRODUCT CODE 3 LIQUID SENSOR SETUP PIU�IP SENSOR SETUP _
THERMAL COEFF : .000450 - - - - - - - - - - - -
TANK DIAMETER 96.00 _
TANK PROFILE 1 PT L 1 :UNL STP S I .UNL
FULL VOL 12000 TRI-STATE (SINGLE FLOATS I
CATEGORY : STP SUMP
TA PENBF i'IODE
FLOAT SIZE: 4.0 IN. STANDARD
L 2:UNL ANN S 2;PNL
WATER WARNING 2.0 DUAL POINT HYDROSTATIC TANK 0; 2
HIGH WATER LIMIT: 3.0 CATEGORY ANNULAR SPACE DISPENSE MODE'
MAX OR LABEL VOL: 12000 STANDARD
OVERFILL LIMIT 90%
10800 L 3:UNL FILL
HIGH PRODUCT 95% TRI-STATE (SINGLE FLOAT)
11400 CATEGORY : OTHER SENSORS
DELIVERY LIMIT 15%
1800
LOW PRODUCT 500 L 4:PNL STP
LEAK ALARM LIMIT: 99 TRI-STATE (SINGLE FLOAT)
SUDDEN LOSS LIMIT: 99 CATEGORY : STP SUMP
TANK TILT 10.00 OUIF M RELAY SETUP
PROBE OFFSET 0.00
L 5:PNL FILL
TRI-STATE (SINGLE FLOAT) R 1 ;UNL
SIPHON MaNIFOLDEL TANKS CATEGORY : OTHER SENSORS
TO: N014E T',PE CONTROL OUTPUT
LINE MANIFOLDED TANKS TA pwp
K >s: I
TO: NONE
L 6:PNL ANN
LEAK MIN PERIODIC: 19G DUAL POINT HYDROSTHTIC SENSOR A
CATEGORY : ANNULAR. SPACE L�j{FUEL ALARM
120 L10:FUEL ALARM
LEAK MIN ANNUAL 14 L11-FUEL ALARM L12:FUEL ALARM
120 L 7:DIE STP L13"FUEL A OUT ALARM
TRI-STATE (SINGLE FLOAT)
CATEGORY : STP SUMP L.10'
1 p:SENSOR OUT ALARM
PERIODIC TEST TYPE LII;SENSOR OUT ALARM
STANDARD L12;SENSOR OUT ALA
ANNUAL TEST FAIL TRe-STATE I(SIIVGLE FLOAT) L13•SENSOR S
ALARM
L I :SµORT
ALARM DISABLED CATEGORY OTHER aEWSORS L10.SHORT ALARM
P)rR l OD 1 G TEST 'FA i L Lit '. RT ALARM
ALARM D I SABI ED L13;SHORT ALA
GROSS TEST FAIL L DUAL ANN
ALARM D[SHBLEG DUAL POINT HYDROSTATIC tSD SITE ALARt'S FAIL
CATEGORY : ANNULAR SPACE GROSS PRES
1 Sl) DEGRD PRE K FAIL
ANN TEST AVERAGING: OFF ISO VAPOR LEAK,
PER TEST AVERAGING: OFF VP PRES
1SD STATUS FAIL
LlO:D1SP 1-2 VP ST
TANK, TEST NOTIFY: OFF TRI-STATE (SlWLE FLOAT)
SSD
F1+}::4FF CATEGORY : DISPENSER PAN 1SD HOSE AL Q�EVT FAIL
TNK TST SIPHON BR
ALL;GROSS COLLECT FAIL
DELIVERY DELAY 1 MlN
ALL FLOW COLLECT FAIL
PUMP THRESHOLD 10.00% L11 :DISP 3-4 HLL
TRI-STATE (SINGLE FLOAT)
CATEGORY : DISPENSER PAN
L12:DISP 5-6
TRI-STATE (SINGLE FLOAT)
CATEGORY : DISPENSER PAN
L13:D1SP 7-8
LEAK TEST METHOD TRI-STATE (SINGLE FLOAT)
- - - - - - - - - - - CATEGORY DISPENSER PAN
TEST ON DATE : ALL TANK
JAN 16. 2006
START TIME : DISABLED
TEST RATE :0.20 GAL.,HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLEG
.LEAK TEST REPORT FORMAT
NORMAL
R 2:PNL ISD AIRFLOW METER hWP
TYPE: SMARTSENSOR SETUP ID SERIAL NUM LABEL
PUMP,CONTROL OUTPUT - - - - - — - - - - - ------------------------ _
TANK p: 2 l 0 F.M.DISP 1
S I :V.P SENSOR DISP 3-4 2 0 F.M.DISP 3
CATEGORY VAPOR PRESSURE 4 0 F .M .DISP 7
LIQUID SENSOR ALMS
L 4:FUEL LARII s 2:F.M.DISP 1-2
1_10:FUEL ALARM CATEGORY AIR FLOW'METER
L1l :FUEL ALARM ISD FUEL GRADE HOSE MAP
L12:FUEL ALARM s 3:F.M.DISP 3-4 1 2 3 4
L13:FUEL ALARM CATEGORY AIR FLOW METER FP MHH MHH MHH MHH AA
L 4:SENSOR OUT ALARM ------------------------
LIO:SENSOR OUT ALARM s 4:F.M.DISP 5-6 O1 201 301 901 5 U I
LII:SENSOR OUT ALARM CATEGORY AIR FLOW METER 02 202 302 902 5 U I
L12:SENSOR OUT ALARM 03 203 303 903 U U 2
L13:SENSOR OUT ALARM s 5:F.M.DISP 7-8 04 204 304 904 U U 2
L 4:SHORT ALARM CATEGORY AIR FLOW METER . 05 205 305 905 5 U 3
LIO:SHORT ALARM 06 206 306 906 5 U 3
LII :SHORT ALARM 07 207 307 907 U U 4
L12:SHORT ALARM 08 208 308 908 U U 4
L13:SHORT ALARM
ISD SITE ALARMS LABEL TABLE
ISD GROSS PRES FAIL --------------'----
ISD DEGRD PRES FAIL 1: UNASSIGNED
ISD VAPOR LEAK FAIL 2: BLEND3
ISD VP PRES FAIL 47 3: REGULAR
ISD VP STATUS FAIL 4: MID GRADE
5: PREMIUM
ISD HOSE ALARMS M 6: GOLD
ALL:GROSS COLLECT FAIL 7: BRONZE
ALL:DEGRD COLLECT FAIL £VR/ISD SETUP '-.' B: SILVER
ALL:FLOW COLLECT FAIL 9: BLEND2
V0: BLEND4
R 3:DIESEL
TYPE: EVR TYPE: VACUUM /FIST
STANDARD VACUUM ASSIST TYPE
NORMALLY CLOSED HEALY VAC
TANK 9: 3 NOZZLE A/L RANGE
MAX: 1 .15 MIN: 0.95
LIQUID SENSOR H1JiS VAPOR PROCESSOR TYPE
L ?:FUEL ALARM NO VAPOR PROCESSOR
LIO:FUEL ALARM P14C SETUP
LI2:FUEL ALARM
L 7:SENSOR OUT ALARM ANALYSIS TIMES PROCESSOR CONTROL LEVEL:
LIO:SENSOR OUT ALARM TIME: 10:00 Aft NONE
L12:SENSOR OUT ALARM DELAY MINUTES: I
L 7:SHORT ALARM
L10:SHORT ALARM
L12:SHORT ALAR11 ACCEPT HIGH ORVR:
DISABLED
R 4:OVERFILL ALARM
TYPE: ISD HOSE TABLE
STANDARD ID FP FL HL AA RR
NORMALLY OPEN --------------------------
01 01 01 02 01 UU
TANK 9: NONE 02 02 02 02 01 UU
03 03 03 02 02' UU
04 04 04 02 02 UU
IN-TANK ALARMS 05 05 05 02 03 UU
ALL:OVERFILL ALARM 06 06 06 02 03 UU
ALL:HIGH PRODUCT ALARM 07 07 07 02 04 UU
ALL:MAX PRODUCT ALARM 08 08 08 02 04 UU
J
SWRCB, January 2006
Spill Bucket Testing Report Form
This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and
printouts from tests(f applicable), should be provided to the facility owner/operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: #360 Farrell's Fastrip I Date of Testing: 8/16/2010
Facility Address: 6401 White Lane,Bakersfield,CA 93309
Facility Contact: Omero Garcia I Phone: 661-393-7000
Date Local Agency Was Notified of Testing: 7/23/2010
Name of Local Agency Inspector(fpresent during testing): Ernie Medina
2. TESTING CONTRACTOR INFORMATION
Company Name: Confidence UST Services, Inc.
Technician Conducting Test: Bryan A Self
Credentials: X CSLB Contractor X ICC Service Tech. ❑SWRCB Tank Tester ❑Other(Spec)
License Number(s): CSLB#804904 ICC#8022804-UT
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: x Hydrostatic ❑Vacuum ❑Other
Test Equipment Used: Lake Test Equipment Resolution: 0.0625"
Identify Spill Bucket(By Tank 1 Regular 2 Super 3 Diesel 4
Number, Stored Product, etc.)
Bucket Installation Type: ❑Direct Bury ❑Direct Bury ❑Direct Bury ❑Direct Bury
x Contained in Sump x Contained in Sump x Contained in Sump ❑Contained in Sum
Bucket Diameter: 14.00" 14.00" 14.00"
Bucket Depth: 12.25" 12.25" 12.25"
Wait time between applying 5 min. 5 min. 5 min.
vacuum/water and start of test:
Test Start Time(Tj): 9:00am 9:00am 9:00am
Initial Reading(R,): 10.25" 10.75" 10.25"
Test End Time(TF): 10:00am 10:00am 10:00am
Final Reading(RF): 10.25" 10.75" 8.25"
Test Duration(TF—Tj): 1 hour 1 hour 1 hour
Change in Reading(RF-R�): 0.00" 0.00" 2.00"
Pass/Fail Threshold or 0.0625" 0.0625" 0.0625"
Criteria:
�P
Test.Result. XPass; ,p`.Fail�rt �XRPassr �wFailj a�sP,ass= X Fail; ; y ❑,JPasst 0 Fail
Comments—(include information on repairs made prior to testing and recommended follow-up or failed tests)
Diesel Spill Bucket failed and needs to be replaced.
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true,accurate, and in full compliance with legal requirements.
Technician's Signature: Date: 8/16/2010
State laws and regulations do not currently require testing to be performed by a qualified contractor. However,local requirements
may be more stringent.