HomeMy WebLinkAboutSB989 2011 SWRCB,January 2002 I IIIIIII VIII III IIII 43 IE Page of Secondary Containment Testing Report Form This form is intended for use by contractors performing periodic testing of UST secondary containment systems. Use the appropriate pages of thisform to report results for all components tested The completed form,written test procedures, and printouts from tests(if applicable),should be provided to the facility owner/operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: Fastrip#366 Date of Testing: 2/24111 Facility Address: 8001 White Lane Bakersfield CA Facility Contact: Jaco Hill Phone: 1-661-393-7000 Date Local Agency Was Notified of Testing: 2/16/11 Name of Local Agency Inspector(rf present during testing): 2. TESTING CONTRACTOR INFORMATION Company Name: Sunset Mechanical Technician Conduc ' g Test- Scott Olinger Credentials: CSLB Licensed Contractor ❑SWRCB Licensed Tank Tester License Type. C-36 C-10 License Number. 589517 Manufacturer Trainine Manufacturer Component(s) Date Training Expires Incon TS-STS INSPECTION EQUIPMENT 1/18/13 VEEDER ROOT MONITORING SYSTEM 1/15/12 ICC CAL UST SERVICE TECH 1/18/13 3. SUMMARY OF TEST RESULTS Not Repairs Not Repairs Component Pass Fail Tested Made Component Pass Fail Tested Made UDC# 1-2 X FILL#1 X UDC#3-4 X FILL#2 X UDC#5-6 X FILL#3 X UDC#7-8 X FILL#4 X UDC#9-10 X PIPING RUN#1 X UDC# 11-12 X PIPING RUN#2 X STP#1 X PIPING RUN#3 X STP#2 X PIPING RUN#4 X STP#3 X PIPING RUN#5 X STP#4 X PIPING RUN#6 X ANN SPACE#1 X PIPING RUN#7 X ANN SPACE#2 X PIPING RUN#8 XLI If hydrostatic testing was performed,describe what was done with the water after completion of tests: CERTIFICATION;LTECRdCIAN RESPONSIBLE FOR CONDUCTING THIS TESTING To the best of my knowledge,the din this document are accurate and in full compliance with legal requirements Technician's Signature' Date: 2-24-11 IIIIIIIIIIIIIIIiilll 44 IE SWRCB,January 2002 Page of Secondary Containment Testing Report Form This form is intended for use by contractors performing periodic testing of UST secondary containment systems. Use the appropriate pages of this form to report results for all components tested The completed form,written test procedures, and printouts from tests(rf applicable),should be provided to the facility ownerloperator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: Fastrip#366 Date of Testing: 2/24/11 Facility Address: 8001 White Lane Bakersfield CA Facility Contact: Jaco Hill Phone: 1-661-393-7000 Date Local Agency Was Notified of Testing: 2/16/11 Name of Local Agency Inspector(if present during testing): 2. TESTING CONTRACTOR INFORMATION Company Name: Sunset Mechanical Technician Conducti Test: Scott Olinger Credentials: CSLB Licensed Contractor ❑SWRCB Licensed Tank Tester License Type: C-36 C-10 License Number: 589517 Manufacturer Trainine Manufacturer Component(s) Date Training Expires Incon TS-STS INSPECTION EQUIPMENT 1/18/13 VEEDER ROOT MONITORING SYSTEM 1/15/12 ICC CAL UST SERVICE TECH 1/18/13 3. SUMMARY OF TEST RESULTS Not Repairs Not Repairs Component Pass Fail Tested Made Component Pass Fail Tested Made ANN SPACE#3 X ANN SPACE#4 X SPILL#1 X SPILL#2 X SPILL#3 X SPILL#4 X • SPILL#1 X • SPILL#2 X • SPILL#3 X • SPILL#4 X If hydrostatic testing was performed,describe what was done with the water after completion of tests: CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING To the best of my knowledge,the facts stated in this document are accurate and in full compliance with legal requirements Technician's Signature: Date: 2-24-11 SWRCB,January 2002 Page of 4. TANK ANNULAR TESTING Test Method Developed By: Tank Manufacturer ❑Industry Standard ❑Professional Engineer ❑Other(Spec) Test Method Used: ❑Pressure Vacuum ❑Hydrostatic ❑Other(Specify) Test Equipment Used:4"Gauge with Certs Equipment Resolution: 0-30 Tank#1 Tank#2 Tank#3 Is Tank Exempt From Testing?' ❑Yes No ❑Yes No ❑Yes AO ❑Yes Ao Tank Capacity: 12,000 12,000 12,000 12,000 Tank Material: GLASS/STEEL GLASS/STEEL GLASS/STEEL GLASS/STEEL Tank Manufacturer. JOOR JOOR JOOR JOOR Product Stored: UNLEADED UNLEADED PREMIUM DIESEL Wait time between applying pressure/vacuum/water and 10 MIN 10 MIN 10 MIN 10 MIN starting test: Test Start Time: 9:15 9:15 9:15 10:45 Initial Reading(R4): 12 HG 12HG 12HG 12 HG Test End Time: 10:15 10:15 10:15 11:45 Final Reading(Rr): 12 HG 12HG 12HG 12 HG Test Duration: 1 HR 1 HR 1 HR 1 HR Change in Reading(RF-R): 0 0 0 0 Pass/Fail Threshold or Criteria: 0 0 0 0 Ot Test Result Pass ;::❑Fail Pass ❑Fail Pass'.. ❑.Fail Pass ❑'Fail, Was sensor removed for testing? V Yes ❑N- o ❑NA 16 Yes ❑No ❑NA dYes ❑No ❑NA Yes ❑No ❑NA Was sensor properly replaced and �j Yes ❑No ❑NA Yes ❑No ❑NA verified functional after testis ? t/Yes ❑N=ONA Yes ❑No ❑NA Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment testing. (California Code of Regulations,Title 23,Section 2637(a)(6)} S WRCB,January 2002 Page of 5. SECONDARY PIPE TESTING Test Method Developed By: Piping Manufacturer ❑Industry Standard ❑Professional Engineer ❑Mer(Spec) Test Method Used: Pressure ❑Vacuum ❑Hydrostatic ❑Other(Spec) Test Equipment Used:4"Gel Filled Gauge W/Certs Equipment Resolution: 0-15 .� _ Piping Run#5 Piping Ran#6 Piping Run#7 Piping Run#8 Piping Material: Fiberglass Fiberglass Fiberglass Fiberglass Piping Manufacturer. AO Smith AO Smith AO Smith AO Smith Piping Diameter: 3" 3" 3" 3" Length of Piping Run: 60' 60' 60' 60' Product Stored: UNL UNL PREM DIESEL Method and location of Test Boot at STP& Test Boot at STP& Test Boot at STP& Test Boot at STP& piping-run isolation: Line Line Line Line Wait time between applying pressure/vacuum/water and 10 Min 10 Min 10 Min 10 Min starting test: Test Start Time: 11:00 am 11:00 am 11:00 am 11:00 am Initial Reading(R): 5.0 52 52 5.1 Test End Time: 12:00 am 12:00 am 12:00 am 12:00 am Final Reading(RF): 5.0 52 5.2 5.1 Test Duration: 1 Hour I Hour 1 Hour 1 Hour Change in Reading(RF-R): 0 0 0 0 Pass/Fail Threshold or 0 0 0 0 Criteria: Test Result Pass .❑Fail Pass :Fad Pass ";.❑Fad Pass.. ❑Fail Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) SWRCB,January 2002 Page of 5. SECONDARY PIPE TESTING Test Method Developed By: KPiping Manufacturer ❑Industry Standard ❑Professional Engineer ❑Other(Spec) Test Method Used: Vpressure ❑Vacuum ❑Hydrostatic ❑Other(Specify) Test Equipment Used:4"Gel Filled Gauge W/Certs Equipment Resolution: 0-15 Piping Run#1 Piping Run#2 Piping Run#3 Piping Run#4 Piping Material: Fiberglass Fiberglass Fiberglass Fiberglass Piping Manufacturer: AO Smith AO Smith AO Smith AO Smith Piping Diameter: 3" 3" 3" 3" Length of Piping Run: 160' 160' 160' 160' Product Stored: UNL PREM DIESEL VAPOR Method and location of Test Boot at STP& Test Boot at STP& Test Boot at STP& Test Boot at STP& piping-run isolation: Line Line Line Line Wait time between applying pressurelvacuum/water and 10 Min 10 Min 10 Min 10 Min starting test: Test Start Time: 9:10 am 9:10 am 9:10 am 9:10 am Initial Reading(RI): 52 5.0 52 5.4 Test End Time: 10:10 am 10:10 am 10:10 am 10:10 am Final Reading(RF): 5.2 5.0 5.2 5.4 Test Duration: I Hour 1 Hour 1 Hour 1 Hour Change in Reading(RF-N: 0 0 0 0 Pass/Fail Threshold or 0 0 0 0 Criteria: Test Result Pass :aj Fail Pass;` Fail :Pass: O Fair !Pass ❑Fail Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) S WRCB,January 2002 Page of 6. PIPING SUMP TESTING Test Method Developed By: 9Sump Manufacturer ❑Industry Standard ❑Professional Engineer ❑Other(Specify) Test Method Used: ❑Pressure ❑Vacuum Hydrostatic ❑Other(Specify) Test Equipment Used: Incon TS-STS Equipment Resolution: 0.0000 „�. ,� , Sump#1 STP Samp#2 STP Sump#3 STP Sump#4 STP Sump Diameter: 48" 48" 48" 48" Sump Depth: 74" 74" 70" 66" Sump Material: Fiberglass Fiberglass Fiberglass Fiberglass Height from Tank Top to Top of 14" 15" 14" 14" Highest Piping Penetration: Height from Tank Top to Lowest 22" 24" 12" 24" Electrical Penetration: Condition of sump prior to testing: DRY DRY DRY DRY Portion of Sump Tested' 16" 16" 16" 16" Does turbine shut down when / / / sump sensor detects liquid(both ®Yes ❑No ❑NA 1dYes ❑No ❑NA 1Yes ❑No ❑NA �B'Yes ❑No ❑NA prod uct and water)?* Turbine shutdown response time 20 Sec 20 Sec 20 Sec 20 See Is system programmed for fail-safe Yes ❑No ❑NA 9 Yes ❑No ❑NA &(Yes ❑No ❑NA V(Yes ❑No ❑NA shutdown?* Was fail-safe verified to be operational?* ❑No ❑NA Yes ❑No ❑NA es ❑No ❑NA N Yes ❑No ❑NA Wait time between applying pressure/vacuum/water and starting 10 Min 10 Min 10 Min 10 Min test: Test Start Time: 10:17 11:03 11:03 12:17 Initial Reading(114): 2.4247 2.9531 5.4940 3.5519 Test End Time: 10:32 11:18 11:18 12:32 Final Reading(RF): 2.4246 2.9525 5.4938 5.5518 Test Duration: 15 MW 15 Min 15 Min 15 Min Change in Reading(RF-Rj: .0001 .0006 .0002 .0001 Pass/Fail Threshold or Criteria: .002 .002 .002 .002 Test Result . °< Pass ❑Failc Pass` ❑Fail Pass. ❑Fail Pass' ❑Fail `.., Was sensor removed for testing? es ❑No ❑NA dYes ❑No ❑NA --LLY--es ❑No ❑NA es ❑No ❑NA Was sensor properly replaced and Yes ❑No ❑NA Yes ❑No ❑NA lk Yes ❑No ❑NA es ❑No ❑NA verified functional after testin ? Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) 'if the entire depth of the sump is not tested,specify how much was tested. If the answer to any of the questions indicated with an asterisk(•)is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160) SWRCB,January 2002 Page of 7. UNDER ISPENSER CONTAINMENT TESTING Test Method Developed By: UDC Manufacturer ❑Industry Standard ❑Professional Engineer ❑Other(Specify) Test Method Used: ❑Pressure ❑Vacuum WHydrostatic ❑Other(Spec) Test Equipment Used: INCON TS-STS Equipment Resolution:0.0000 +�"�� '.f•v �.1:i.�tvsY. :d"'iC=rA.^;:+"P'&,.°s - '.F '33iiw tea'.'A.�l z.. . UDC#1-2 UDC#3-4 UDC#5-6 UDC#7-8 UDC Manufacturer. Western Western Western Western UDC Material: Fiber ass Fiber lass Fiberglass Fiberglass UDC Depth: 30" 30" 30" 30" Height from UDC Bottom to Top 8" 8" 8" 8" of Highest Piping Penetration: Height from UDC Bottom to 6" 6" 6" 6" Lowest Electrical Penetration: Condition of UDC prior to DRY DRY DRY DRY testing: Portion of UDC Tested 12" 12" 12" 12" Does turbine shut down when _.,/ // / UDC sensor detects liquid(both BH Yes ❑No ❑NA VYes ❑No ❑NA 'Yes ❑No ❑NA CYYes ❑No ❑NA _product and water?• Turbine shutdown response time 20 SEC 20 SEC 20 SEC 20 SEC Is system programmed for fail- safe shutdown?* Yes ❑No ❑NA As ❑No ❑NA Yes ❑No ❑NA Yes ❑No ❑NA Was fail-safe verified to be _operational?* Yes ❑No ❑NA Yes ❑No ❑NA 5/Yes ❑No ❑NA es ❑No ❑NA Wait time between applying 10 Min 10 Min 10 Min 10 Min pressure/vacuum/water and starting test Test Start Time: 10:17 8:53 8:53 8:53 Initial Reading( 5.0791 5.8525 4.7969 3.1071 Test End Time: 10:32 9:08 9:08 9:08 Final Reading Rr): 5.0787 5.8522 4.7960 3.1070 Test Duration. 15 Min 15 Min 15 Min 15 Min Change in Reading &): .0004 .0003 .0009 .0001 Pass/Fail Threshold or Criteria: .002 .002 .002 .002 Test Result Pass .,`:❑ 0_Fail: Pass ❑Fail Was sensor removed for testing? Yes ❑No ❑NA es ❑No ❑NA VYes ❑No ❑NA es ❑No ❑NA Was sensor properly replaced and verified functional after to ? Yes ❑No ❑NA Yes ❑No ❑NA es ❑No ❑NA Yes ❑No ❑NA Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) 'If the entire depth of the UDC is not tested,specify how much was tested. If the answer to W of the questions indicated with an asterisk(")is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) SWRCB,January 2002 Page of 7. 12TE&RISPENSER CONTAINMENT QLDg TESTING Test Method Developed By UDC Manufacturer ❑Industry Standard 0 Professional Engineer ❑Other(Specify) Test Method Used: ❑Pressure ❑Vacuum StHydrostatic ❑Other(Sped) Test Equipment Used: INCON TS-STS Equipment Resolution:0.0000 UDC#9-10 UDC#11-12 UDC# UDC# UDC Manufacturer Western Western UDC Material: Fiberglass Fiberglass UDC 30" 30" Height from UDC Bottom to Top 8" 8" of Highest Piping Penetration: Height from UDC Bottom to 6" 6" Lowest Electrical Penetration: Condition of UDC prior to DRY DRY testing: Portion of UDC Tested 12" 12" Does turbine shut down when ` 5��" UDC sensor detects liquid(both Yes ❑No 0 NA 5i Yes ❑No ❑NA 0 Yes El No ❑NA 0 Yes ❑No ❑NA roduct and water)?` f� Turbine shutdown response time 20 SEC 20 SEC Is system programmed for fail- safe shutdown?` Yes ❑No ❑NA es ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA Was fail-safe verified to be yes ❑No ❑NA R//Yes ❑No ❑NA ❑Yes 0 No 0 NA ❑Yes ❑No ❑NA o tional?` Wait time between applying 10 Min 10 Min pressure/vacuum/water and startin test Test Start Time: 8:53 10:34 Initial Reading(114): 6.5541 3.9940 Test End Time: 9:08 10:49 Final Reading(Rr): 6.5549 3.9940 Test Duration: 15 Min 15 Min Change in Reading R): .0008 .0 Pass/Fail Threshold or Criteria: .002 .002 Test idt " ;.; Pass . .p Fail - ;' :Pass ❑Fs�t<. 0,Pass ;: lj Fail; ❑ Pass. Ead Was sensor removed for testing? es ❑No ❑NA es ❑No ONAI ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA Was sensor properly replaced and Yes ❑No ❑NA IV//Yes ❑No ❑NA I ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA verified functional after testin ? Comments—(include information on repairs made prior to testing: and recommended follow-up for failed tests) 'If the entire depth of the UDC is not tested,specify how much was tested. If the answer to any of the questions indicated with an asterisk(*)is"NOI or"NA",the entire UDC must be tested. (See SWRCB LG-160) i SWRCB,January 2002 Page of 8. FILL RISER CONTAINMENT SUMP TESTING Facility is Not Equipped With Fill Riser Containment Sums ❑ Fill Riser Containment Sumps are Emnt but were Not Tested ❑ Test Method Developed By: Sump Manufacturer ❑Industry Standard ❑Professional Engineer ❑Other(Specify) Test Method Used: ❑Pressure ❑Vacuum Hydrostatic ❑Other(Specify) Test Equipment Used: INCON TS-STS Equipment Resolution: 0.0000 .. Fill Sump#1 Fill Sump#2 Fill Sump#3 Fill Sump#4 Sump Diameter. 42" 42" 42" 42" Sump Depth: 79" 78" 72" 72" Height from Tank Top to Top of 12" 12" 14" 12" Highest Piping Penetration: Height from Tank Top to Lowest 12" 12" 14" 12" Electrical Penetration: Condition of sump prior to DRY DRY DRY DRY testing: Portion of Sump Tested 14" 14" 14" 14" Sump Material: Fib ass Fiberglass Fiberfjass Fibe ass Wait time between applying 10 Min 10 Min 10 Min 10 Min pressure/vacuum/water and starting test: Test Start Time: 10:17 12:17 1128 12:17 Initial Reading : 1.0962 2.3371 2.1847 5.0244 Test End Tune: 10:32 12:32 11:43 12:32 Final Reading 1.0959 2.3371 2.1846 5.0244 Test Duration.. 15 Min 15 Min 15 Min 15 Min Change in Readin Ril: .0003 0 .0001 0 Pass/Fail Threshold or Criteria: .002 .002 .002 .002 Test-Result: Pass p Fail Pass - 0 Fair P s 0 Fail ass .❑:Fail , Is there a sensor in the sump? Yes ❑No 2 Yes ❑No QfYes ❑No es ❑No Does the sensor alarm when L- either product or water is E�'Yes ❑No ❑NA R Yes ❑No ❑NA Wares ❑No ❑NA 1 es ❑No ❑NA detected? Was sensor removed for testing? WYes ❑No ❑NA es ❑No ❑NA Fw(Yes ❑No ❑NA Yes ❑No ❑NA Was sensor properly replaced and yes ❑No ❑NA Yes ❑No ❑NA R'Yes ❑No ❑NA Yes ❑No ❑NA verified functional after testin ? Comments—(include information on repairs made prior to testing and recommended follow-up for failed tests) SWRCB,January 2002 Page of 9.SPILIJOVERFILL CONTAINMENT BOXES Facili is Not Equipped With Spill/Overfill Containment Boxes ❑ Spill/Overfill Containment Boxes are sent,but were Not Tested ❑ Test Method Developed By: Spill Bucket Manufacturer ❑Industry Standard ❑Professional Engineer ❑Other(Specify) Test Method Used: ❑Pressure ❑Vacuum gHydrostatic ❑Other(Spec) Test Equipment Used:1NCON TS-STS Equipment Resolution:0.0000 Spill Box#V1 Spill Bog#V2 Spill Bog#V3 Spill Bog#V4 Bucket Diameter: 12" 12" 12" 12" Bucket Depth: 12" 12" 12" 12" Wait time between applying pressure/vacuum/water and 10 MIN 10 MIN 10 MIN 10 MIN starting test: Test Start Time: 2:50 2:50 2:09 12:17 Initial Reading(R1): 3.0926 4.4142 3.0837 3.4593 Test End Time: 3:05 3:05 2:24 12:32 Final Reading(RF): 3.0935 4.4144 3.0819 3.4587 Test Duration: 15 MIN 15 MIN 15 MIN 15 MIN Change in Reading(RF-R.): .0011 .0002 .0018 .0006 Pass/Fail Threshold or .002 .002 .002 .002 Criteria: Test-Residt Pass..°❑Fail 'Pass ,'D Fail Pass -Fall` Pass ❑Fail'> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) SWRCB,January 2002 Page of _ 9.SPILL/OVERFH L CONTAINMENT BOXES Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ Spill/Overfill Containment Boxes are sent,but were Not Tested ❑ Test Method Developed By. Spill Bucket Manufacturer 0 Industry Standard ❑Professional Engineer ❑Other(Spec) Test Method Used: ❑Pressure ❑Vacuum YHydrostatic ❑Other(Specify) Test Equipment Used:INCON TS-STS Equipment Resolution:0.0000 x Spill Box#1 Spill Box#2 Spill Boa#3 Spill Box#4 Bucket Diameter: 12" 12" 12" 12" Bucket Depth: 12" 12" 12" 12" Wait time between applying pressure/vacuum/water and 10 MIN 10 M1N 10 MIN 10 MIN starting test: Test Start Time: 2:50 2:50 2:09 2:09 Initial Reading(R): 5.3632 4.5215 4.0680 3.8219 Test End Time: 3:05 3:05 2:24 2:24 Final Reading(RF): 5.3630 4.5215 4.0666 3.8219 Test Duration: 15 MIN 15 MIN 15 MIN 15 MIN Change in Reading(RF-1?4): .0002 0 .0014 0 Pass/Fail Tbresbold or 002 .002 .002 .002 Criteria: Test:Result: Pass ❑Fail, Pass`: p Fail Pass ; ❑FaiF Pass �'Feil Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) FASTRIP 366 FASTRIP 366 FASTRIP 366 8001 WHITE LANE 8001 WHITE LANE 8001 WHITE LANE BAKERSFIELD BAKERSFIELD BAKERSFIELD SUNSET CONST SUNSET.CONST SUNSET CONST 1-800-984-6266 1-800-984-6266 1-800-984-6266 02/24/2011 2:40 PM 02/24/2011 3:05 PM 02/24/2011 2:24 PM SUMP LEAK TEST REPORT SUMP LEAK TEST REPORT SUMP LEAK TEST REPORT SPILL4 VSPIL2 SPILL4 TEST STARTED 2:25 PM TEST STARTED 2:50 PM TEST STARTED 2:09 PM TEST STARTED 02/24/2011 TEST STARTED 02/24/2011 TEST STARTED 02/24/2011 BEGIN LEVEL 3.8219 IN BEGIN LEVEL 4,4142 IN BEGIN LEVEL 3.8219 IN END TIME 2:40 PM END TIME 3:05 PM END TIME 2:24 PM END DATE 02/24/2011 END DATE 02/24/2011 END DATE 02/24/2011 END LEVEL 3.8219 IN END LEVEL 4,4144 IN END LEVEL 3,8219 IN LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0.002 IN LEAK THRESHOLD 0,002 IN TEST RESULT PASSED TEST RESULT PASSED TEST RESULT PASSED STILL3 VSPILI STILL3 TEST STARTED 2:25 PM TEST STARTED 2:50 PM TEST STARTED 2:09 PM TEST STARTED 02/24/2011 TEST STARTED 02/24/2011 TEST STARTED 02/24/2011 BEGIN LEVEL 4.0664 IN BEGIN LEVEL 3,0926 IN BEGIN LEVEL 4,0680 IN END TIME 2:40 PM END TIME 3:05 PM END TIME 2:24 PM END DATE 02/24/2011 END DATE 02/24/2011 END DATE 02/24/2011 END LEVEL 4,0666 IN END LEVEL 3,0935 IN END LEVEL 4,0666 IN LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0,002 IN TEST RESULT PASSED TEST RESULT PASSED TEST RESULT PASSED VSPIL&: SPILL/ VSPIL3 TEST STARTED 2:25 PM TEST STARTED 2:50 PM TEST STARTED 2:09 PM TEST STARTED 02/24/2011 TEST STARTED 02/24/2011 TEST STARTED 02/24/2011 BEGIN LEVEL 3.0820 IN BEGIN LEVEL 5,3632 IN BEGIN LEVEL 3,0837 IN END TIME 2:40 PM END TIME 3:05 PM END TIME 2:24 PM END DATE 02/24/2011 END DATE 02/24/2011 END-DATE 02/24/2011 END LEVEL 3,0824 IN END LEVEL 5.3630-IN END LEVEL 3,0819 IN LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0.002 IN LEAK THRESHOLD 0,002 IN TEST RESULT PASSED TEST RESULT PASSED TEST RESULT PASSED SPILL2 SPILL2 SPILL2 TEST STARTED 2:25 PM TEST STARTED 2:50 PM TEST STARTED 2:09 PM TEST STARTED 02/24/2011 TEST STARTED 02/24/2011 = TEST STARTED 02/24/2011 BEGIN LEVEL 4,5194 IN BEGIN LEVEL 4.5215 IN BEGIN LEVEL 4,5223 IN END TIME 2:40 PM END TIME 3:05 PM END TIME 2:24 PM END DATE 02/24/2011 END DATE 02/24/2011 END DATE 02/24/2011 END LEVEL 4.5177 IN END LEVEL 4,5215 IN END LEVEL 4,5202 IN LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0.002 IN LEAK THRESHOLD 0,002 IN TEST RESULT PASSED TEST RESULT PASSED TEST RESULT FAILED FASTRIP 366 8001 WHITE LANE FASTRIP 366 FASTRIP 366 BAKERSFIELD 8001 WHITE LANE 8001 WHITE LANE SUNSET CONST BAKERSFIELD BAKERSFIELD 1-800-984-6266 SUNSET CONST SUNSET CONST 1-800-984-6266 1-800-984-6266 02/24/2011 11:44 AM 02/24/2011 12:33 PM 02/24/2011 12:55 PM SUMP LEAK TEST REPORT SUMP LEAK TEST REPORT SUMP LEAK TEST REPORT STP 2 STP 4 STP 4 TEST STARTED 11:28 AM TEST STARTED 02/24/2011 TEST STARTED 12:17 PM TEST STARTED 12:39 PM BEGIN LEVEL 2,9528 IN TEST STARTED 02/24/2011 TEST STARTED 02/24/2011 END TIME 11:43 AM BEGIN LEVEL 5,5519 IN BEGIN LEVEL 5,5517 IN END DATE 02/24/2011 END TIME 12:32 PM END TIME 12:55 PM END LEVEL 2,9525 IN END DATE 02/24/2011 END DATE 02/24/2011 LEAK THRESHOLD 0,002 IN END LEVEL 5,5518 IN END LEVEL 5.5514..IN TEST RESULT PASSED LEAK THRESHOLD 0.002 IN LEAK THRESHOLD 0,002 IN TEST RESULT PASSED TEST RESULT PASSED STP 3 FILL 4 FILL 4 TEST STARTED 11:28 AM TEST STARTED 02/24/2011 TEST STARTED 12:17 PM TEST STARTED 12:39 PM BEGIN LEVEL 5.4937 IN TEST STARTED 02/24/2011 TEST STARTED 02/24/2011 END TIME 11:43 AM BEGIN LEVEL 5.0244 IN BEGIN LEVEL 5.0243 IN END DATE 02/24/2011 END TIME 12:32 PM END TIME 12:55 PM END LEVEL 5.4935 IN END DATE 02/24/2011 END DATE 02/24/2011 LEAK THRESHOLD 0,002 IN END LEVEL 5.0244 IN END LEVEL 5,0238 IN TEST RESULT PASSED LEAK THRESHOLD 0.002 IN LEAK THRESHOLD 0,002 IN TEST RESULT PASSED TEST RESULT PASSED FILL 2 VSPIL4 VSPIL4 TEST STARTED 11:28 AM TEST STARTED 12:17 PM TEST STARTED 02/24/2011 ST STARTED 02/24/2011 TEST STARTED 12:39 PM TEST BEGIN LEVEL 2,6657 IN TEST STARTED 02/24/2011 END TIME 11:43 AM BEGIN LEVEL 3,4593 IN BEGIN LEVEL 3,4579 IN END DATE 02/24/2011 END TIME 12:32 PM END TIME 12:55 PM END LEVEL 2,6706 IN END DATE 02/24/2011 END DATE 02/24/2011 LEAK THRESHOLD 0,002 IN END LEVEL 3,4587.IN END LEVEL 3.4571 'IN TEST RESULT INCREASED LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0,002 IN TEST RESULT PASSED TEST RESULT PASSED FILL 3 FILL 2 FILL 2 TEST STARTED 11:28 AM TEST STARTED 12:17 PM TEST STARTED 02/24/2011 TEST STARTED 12:39 PM BEGIN LEVEL 2. 1847 IN TEST STARTED 02/24/2011 TEST STARTED 02/24/2011 END TIME 11:43 AM BEGIN LEVEL 2.3371 IN BEGIN LEVEL 2,3371 IN END DATE 02/24/2011 END TIME 12:32 PM END TIME 12:55 PM END LEVEL 2.1846 IN END DATE 02/24/2011 END DATE 02/24/2011 LEAK THRESHOLD 0,002 IN END LEVEL 2,3371 IN END LEVEL 2,3371 IN TEST RESULT PASSED LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0,002 IN TEST RESULT PASSED TEST RESULT PASSED FASTRIP 366 8001 WHITE LANE FASTRIP 366 BAKERSFIELD O3SSHd 11{1S3d 1S31 8001 WHITE,LANE NT 200'0 O1DHS3L�H1 X131 ' SUNSET CONST BAKERSFIELD 1-800-984-6266 %I V960't 13,31 ON3 SUNSET IONST u OZ VW0 3iVO ON3: 1-800-934-6266 WH bt:01 3WI1 ON3`:' 02/24/2011 11:28 AM NI - 960't 13,31 N1939 02/24/2011 10:49 AM SUMP LEAK TEST REPORT llOUVUZO 131�VIS 1531 wv 69:6 O318H1S 1S31 SUMP LEAK TEST REPORT STP 2 l 11I3 UDC 1-2 TEST STARTED 11:03 AM TEST STARTED 02/24/2011 .TEST STARTED 10:34 AM BEGIN LEVEL 2,9531 IN 03SSUd iinS38 1S31. TEST STARTED 02/24/2011 END TIME 11:18 AM P:I Z00'C iIiOHS3b1+1 Xti31 BEGIN LEVEL 0,OU00 IN END DATE 02/24/2011 MI 8bZb'Z 13A31 ON3 END TIME 10:49 AM END LEVEL 2,9525 IN IIOZ/WO 31VO OIN3 END DATE C,2/2&/2611 LEAK THRESHOLD 0,002 IN WV bl:0l 3WIl ON3 END LEVEL 0,0000 IN TEST RESULT PASSED NI 05Zb'Z 13A31 1,111539 LEAK THRESHOLD 0.002 IN ItOZ/bZ/Z0 OhdV1S iS3i TEST RESULT PASSED. WV 6S:6 031dViS 1S31 ;- STP 3 L d1S UDC1112 TEST STARTED 11:03 AM TEST STARTED 02/24/2011 .TEST STARTED 10:34 AM BEGIN LEVEL 5,4940 IN 03SSVd 11f1S3a 1S31 TEST.STARTED .02/24112011 END TIME 11:18 AM NI Z03'0 0lOHS3MHi XV31• BEGIN LEVEL 3,9940 IN END DATE 02/24/2011 NI Zl66'£ 13A31 ON3 ` END TIME 10:49 AM END LEVEL 5,4938 IN llOZ/bZ/ZO 31NO ONE END DATE' 02/24/2011', : LEAK THRESHOLD 0,002 IN WH bl:Ol 3WI1 ON3:,. -`END LEVEL:. 3.9,940 IN TEST RESULT PASSED NI Z166'S 13A31 NI939 LEAK THRCE ROLD 0.002 IN ltOc/bZ%Z0 O31'ddiS IS31 TEST RESULT PASSED 0318VIS 1S31 FILL 2 ZtllDOf1 STP 1 _. TEST STARTED 11:03 AM TEST STARTED 02/24/2011 TEST STARTED 10:34 A-M BEGIN LEVEL 2,6438 IN 03SSbd 10.S38 IS31 TESTS U2/L'4i2O11 NI 200'0 O10HS38Hi XV31 END TIME 11:18 AM BEGIN LEVEL 0:1205 iN END DATE 02/24/2011 NI 062-O'S 131131 ON3 END TIME . 10:4G AM END LEVEL 2,6624 IN u OZ/bZ!ZO 31VfJ ON3 ,END DATE 02/24/2011 LEAK THRESHOLD 0,002 IN WV bl:Ot . 3WIi.ON3' END LEVEL 0;0151 IN TEST RESULT IPICREASED NI l6}0'S 13A31 Ni938 LEAK THRESHOLD 0,002 IN 1LOZ/WZ0 031dViS-IS31 TEST RESULT FAILED WV 6S:6 , 031dVlS 1S31 FILL 3 Z-1 ion FILL. 1 TEST STARTED 11:03 AM IdN]8 1S31 Xtl3l dons TEST STARTED 02/24/2011 = TEST STARTED 10:34 AM BEGIN LEVEL 2,1852 IN TEST STARTED 02/24/2011 END TIME= 11:18 AM Wt+ Sl:OI II02/Z0 BEGIN LEVEL 3:8751 IN,- END DATE 02/24/2011 ENO TIME 10:49 AM END LEVEL . 2,1848 IN 9929-G86-00$-1 END DATE 02/24/2011 P•iD1 13SN(1S LEVEL - LEAK THRESHOLD 0.002 IN 1S END LEVEL . 3,875., IN TEST RESULT PASSED 013IdS83NVO LEAK THRESHOLD 0,002 IN 31,41 311HA 100S TEST RESULT PASSED 99S dlal_SVd FASTRIP 356 FASTRIP 366 FASTRIP 366 8001 `dHITE LANE 8001 VHITE LANE 8001 UNITE LANE BAKERSFIELD BAKERSFIELD BAKERSFIELD SUNSET CONST SUNSET CONST. SUNSET CONST 17400-984-6266 1-800-984-6266 1-800-984-6265 02/24/2011 9:08 AM 02/24/2011 .9:26 Ail 02/24/2011 10:32 AM SUMP LEAK TEST REPORT SUMP LEAK TEST REPORT SUMP LEAK TEST REPORT UDC 3-4 UDC 3-4 UDC 1-2 TEST STARTED 8'53 AM TEST STARTED ::10 AM TEST STARTED 10:17 AM TEST STARTED 02±24/2011 TEST STAkTEU 02/14;'2011 TEST STARTED 02/24/2011 BEGIN LEVEL 5,8525 IN BEGIN LEVEL 5,8523 IN BEGIN LEVEL 5.0791 IN END TIME 9:08 AM END TIME 9:26 AM END TIME 10:32 AM END DATE 02/24/2011 END DATE 02/24/2011 END DATE 02/24/2011 END LEVEL 5,8522 IN END LEVEi_ 5,852 2 IN END LEVEL 5,0787 IN LEAK THRESHOLD 0.002 IN LEAK THRESHOLD 0.002 IN LEAK THRESHOLD 0,002 IN TES*f RESULT PASSED TEST RESULT PASSED TEST RESULT PASSED UDC 5-6 UDC 5-6 UDC1112 TEST STARTED -,s:53 AM LEST STARTED 9:10 AM TEST STARTED 10:17 AM TEST STARTED 02/2412011 TEST STARTED 62/24/2011 TEST STARTED 02/24%2011 BEGIN LEVEL 4,79b9 IN BEGIN LEVEL 4.7949:IN BEGIN LEVEL 3,9808 IN END TIME 9:O8 AM END TIME 9:26 AM END TIME 10:32 AM �n END DATE 02i24/2011 ENG DATE 02/24/2011 END DATE 02/24112011 END LEVEL 4,7960 IN END LEVEL 4,7946 IN END LEVEL 3,9944 IN LEAK THRESHOLD O, J2 IN 'LEAK THRESHGLO 0,GO2 IN LEAK THRESHOLD 0 002 IN TEST RESULT PASSED TEST RESULT. PASSED TEST RESULT INCREASED UDC 7-8 UDC 7-$ STP 1 TEST STARTED 8:53 AM TEST STARTED 02/24/2011 TEST STARTED 9:10 AM. TEST STARTED 10:17 AM TEST STARTED 02/24/2011 TEST STARTED 02/2L/2011i .BEGIN LEVEL 3. 1071 IN BEGIN LEVEL 3, 1066 IN BEGIN LEVEL 2.L07 IN END TIME 9:08 AM END TIME 9:26 AM END TIME 10:32 AM END DATE 02/242011 END DATE 02/24/2011 END. DATE 0212412011 END LEVEL 3,1070 IN END LEVEL 3, 1054 IN END LEVEL 2.4246 IN LEAK THRESHOLD 0.002 I'rJ LEAK THRESHOLD' Cl.OD% 1N ?ASSEU LEAK THRESH 0,002 IN. TEST RESULT TEST RESULT PASSED TEST RESULT PASSED UDC9-10 UDC9-10 FILL 1 TEST STARTED 8:53 AM TEST STARTED 9:10 AM TEST STARTED 10:17 AM TEST STARTED 02/24/'2011 TEST STARTED G2/2t'/2011 TEST STARTED 02/24/2011 BEGIN LEVEL 6,5541 It! BEGIN LEVEL 6,5554 IN BEGIN LEVEL 1.6962 IN END TIME 9:08 AM END TIME 9:26 AM END TIME 10:32 AM END DATE 02/24/2011 6.5549 IN END DATE 02j24/2011 END. OATE 02/24/2011 END LEVEL END LEVEL 6;5562 IN END LEVEL 1,0959 IN LEAK THRESHOLD 0:002 TN END THRESHOLD 0,002 IN LEAK THRESHOLD 0,002 IN TEST RESULT PASSED TEST RESULT PASSED TEST RESULT PASSED