HomeMy WebLinkAbout2010 RESULTS 11111111111111111111 41 MONITORING SYSTEM CERTIFICATION I For Use By All Jurisdictions Within the State of California Authority Cited: Chapter 6 7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of this date. A. General Information Facility Name: #346 Fastrip#621 Bldg.No.: Site Address: 805 34th Street City: Bakersfield Zip: 93301 Facility Contact Person: Omero Garcia Contact Phone No.: 661-393-7000 Make/Model of Monitoring System: Gllbarco EMC Date of Testing/Servicing: 06/16/2010 B. Inventory of Equipment Tested/Certified Check the appropriate bola to indicate specific equipment inspected/serviced: Tank ID: 12000 gal. Regular 1 Tank ID: 12000 gal.Regular 2 [X] In-Tank Gauging Probe. Model:847390-107 [x] In-Tank Gauging Probe. Model:847390-107 [x] Annular Space or Vault Probe. Model:794390-420 [x] Annular Space or Vault Sensor. Model: 794390-420 [x] Piping Sump/Trench Sensor(s). Model:794380-208 [x] Piping Sump/Trench Sensor(s). Model: 794380-208 ❑ Fill Sump Sensor(s) Model: ❑ Fill Sump Sensor(s). Model: [J Mechanical Line Leak Detector. Model:FX1v [x] Mechanical Line Leak Detector. Model: FX1v ❑ Electronic Line Leak Detector. Model: ❑ Electronic Line Leak Detector. Model: [X] Tank Overfill/High Level Sensor. Model:847390-107 [x] Tank Overfill/High Leval Sensor. Model: 847390-107 ❑ Other(specify equip.type and model in Sec.E on Pg.2) ❑ Other(specify equip.type and model in Sec. E on Pg.2) Tank ID:_12000 gal.Super Tank ID: 12000 gal. Diesel [x] In-Tank Gauging Probe. Model:847390-107 [J In-Tank Gauging Probe. Model:847390-107 [x] Annular Space or Vault Sensor. Model-Ronan [x] Annular Space or Vault Sensor. Model: 794390-420 [X] Piping Sump/Trench Sensor(s). Model:794380-208 [x] Piping Sump/Trench Sensor(s). Model: 794380-208 ❑ Fill Sump Sensors(s). Model: ❑ Fill Sump Sensor(s). Model: [ x� Mechanical Line Leak Decector. ModehRonan U Mechanical Line Leak Detector. Model: FX1Dy ❑ Electronic Line Leak Detector. Model: ❑ Electronic Line Leak Detector. Model: [x] Tank Overfill/High Level Sensor. Model:847390-107 Tank Overfill/High Level Sensor.Model:847390-107 ❑ Other(specify equip.type and model in Sec. E on Pg.2) ❑ Other(specify equip.typs and model in Sec. E on Pg.2) Dispenser ID: 1 &2 Dispenser ID: 3&4 [x] Dispenser Containment Sensor(s). Model: 794380-208 [X] Dispenser Containment Sensor(s). Model: 794380-208 [x] Shear Valve(s). [x] Shear Valve(s). ❑ Dispenser Containment Float(s)and Chain(s). ❑ Dispenser Containment Float(s)and Chain(s) Dispenser iD: 5&6 Dispenser ID: 7&8 Fx] Dispenser Containment Sensor(s). Model: 794380-208 [x] Dispenser Containment Sensor(s). Model: 794380-208 rx] Shear Valve(s). [, Shear Valve(s). ❑ Dispenser Containment Float(s)and Chains(s). ❑ Dispenser Containment Float(s)and Chain(s). Dispenser ID: Trans.East Dispenser ID: Trans.West rX1 Dispenser Containment Sensor(s). Model: 794380-208 N Dispenser Containment Sensor(s). Model: 794380-208 U Shear Valve(s). U Shear Valve(s). ❑ Dispenser Containment Float(s)and Chain(s) ❑ Dispenser Containment Float(s)and Chain(s). *if the facility contains more tanks or dispensers,copy this form. Include information for every tank and dispenser at the facility. C. Certification -i certify that the equipment identified in this document was inspected/services in accordance with the manufacturers'guidlines.Attached to this Certification is information(e.g.manufacturers'checklist)necessary to varify that this information is correct and a plot plan showing the layout of monitoring equipment.For equipment capable of generating such reports,I have attached a copy of the report; (check all that apply) x❑System Set-up U Alarm history report Technician Name(print): Garry Maggio Signature: Certification No: 837939 License No:804904 Testing Company Name: Confldence UST Services,Inc. Phone No: 800-339-9930 Site Address: 805 34th Street,Bakersfield,CA 93301 I Illllllllllllll Ill/ —Date of Testing/Servicing: 06/16/2010 42 IE A Results of Testing/Servicing Software Version Installed: 327.04 Complete the following checklist: Lx] Yes ❑ No* Is the audible alarm operational? x Yes No* is t e Visua a arm operational? x Yes Fj No* Were all sensors visually inspected,functionally tested,and confirmed operational? x I Yes ❑ No* Were all sensors installed at the lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment(e.g.modem) Hx N/A operational? Fxj Yes ❑ No* For pressurized piping systems,does the turbine automatically shut down if the piping secondary ❑N/A containment monitoring system detects a leak,fails to operate,or is electrically disconnected?If yes: which sensors initate positive shut-down? E Sump/Trench Sensors Lx]Dispenser Containment Sensors Did you confirm positive shut-down due to leaks and sensor failure/disconnected? [X] Yes; ❑ No; [X] Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device(i.e.no ❑N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visual and audible at the tank fill point(s)and operating properly?If so,at what percent of tank capasity does the alarm trigger? 90 % Yes* ❑ No Was any monitoring equipment replaced?If Yes,identify specific sensors,probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E,below. ❑ Yes* U No Was liquid found inside any secondary containment systems designed as dry systems? ❑ Product; ❑ Water. if yes, describe causes in Section E,below. x No* Was monitoring system set-up reviewed to ensure proper settings?Attach set-up reports,if applicable. x Yes No* I Is all monitoring equipment operational per manufacturer's specifications? * In Section E below,discribe how and when these deficiencies were or will be corrected. E. Comments' Monitoring System back-up battery was replaced. All information was restored from Archive Utility. Diesel turbine would not shut off during testing. After investigation,corrected issue and positive shutdown is working correctly on all STP's. F. In-Tank Guaging/SIR Equipment: M Check this box if tank guaging is used only for inventory control. ❑ Check this box if tank guaging or SIR equipment is installed. This section must be completed if in-tank guaging equipment is used to perform leak detection monitoring. Complete the following checklist: E Yes I ❑ No* Has all input wiring been inspected for proper enter and termination,including testing for ground faults? x Yes No* Were all tank guaging probes visually inspected for damage and residue buildup? x Yes No* Was accuracy of system product level readings tested? x Yes No* Was accuracy of system water level readings tested? _[xj Yes No* Were all probes reinstalled properly? [�] Yes ❑ No* Were all items on the equipment manufacturer's maintenance checklist completed? *In the Section H,below,describe how and when these deficiencies were or will be corrected. G. Line Leak Detectors (LLD): ❑Check this box if LLD's are not installed. Complete the following checklist: Lx] Yes ❑ No* For equip. start-up or annual equipment certification,was a leak simulated to varify LLD performance? (Check all that apply) Simulated leak rate: [X]3 g.p.h.: 00.1 g.p.h.; ❑0.2 g.p.h.; x Yes No* Were all LLD's confirmed operational and accurate within regulatory requirments? x Yes No Was the testing apparatus properly calibrated? U Yes I No For machamca LLD's,does the LLD restrict product flow if it detects a leak? N/A ❑ Yes No* For electronic LLD's,does the turbine automatically shut off if the LLD detects a leak? [x] N/A ❑ Yes No* For electronic LLD's,does the turbine automatically shut off if any portion of the monitoring system is [x] N/A disabled or disconnected? ❑ Yes No* For electronic LLD's,does the turbine automatically shut off if any portion of the monitoring system Lx] N/A malfunction or fails a test? ❑ Yes No* For electronic LLD's,have all accessible wiring connections been visually inspected? U N/A Lx] Yes No Were all items on the equipment manufacturer's maintenance checklist completed? * In the section H,below,describe how and when these deficiencies were or will be corrected. H. Comments: FASTRIP 346 ALARM HISTORY REPORT 805 34TH SMARTSENSOR DIAGNOSTIC BKRSFLD.CA - ---- IN-TANK ALARM ---- 661-325-0110 - - - - - - - - JUN 16, 2010 9:35 AM JUN'.16, -201,0 '9.:35 AM T 1 :UNLEAD 1 OVERFILL ALARM s 1 :V.P'1-2 ' ?,} NOV 23, 2009 12:14 AM j SEP 25. 2009 5:51 AM SYSTEM STATUS REPORT VAPOR-PRESSURE SEP 25. 2009 5:06 AM - SERIAL NUMBER 1706 ALL FUNCTIONS NORMAL SUDDEN LOSS ALARM INVENTORY REPORT JAN 19. 2010 3:12 AM , JAN 8. 2010 3:31 AM s 2:FM 1-2 JAN 6. 2010 10:48 AM T 1 :UNLEAD 1 VAIR _FLOW- METER HIGH PRODUCT ALARM VOLUME = 9167 GALS SERIAL' NUMBER 8448 JUN 19, 2008 8:52 AM ULLAGE - 2895 GALS AUN-..13.. 2008_ 9:4,1 .AM 90% ULLAGE= 1688 GALS "JUN 19: 2007 8:50 AM TC VOLUME = 9045 GALS HEIGHT = 79.23 INCHES s 3:FM 3-4 INVALID FUEL LEVEL WATER VOL - 0 GALS JAN 21. 2010 1 :53 AM WATER = 0.00 INCHES AIR FLOW METER JAN 18, 2010 10:57 AM TEMP - 79.0 DEG F 1 SERIAL NUMBER 8409 ' JAN 9. 2010 12:36 PM ( .r:? PROBE OUT T 2:UNLEAD 2 JUN 18, 2009 10:24 AM VOLUME = 9237 GALS. s 4:FM 5-6 SEP 29, 2008 11 :31 AM ULLAGE = 2825 GALS SEP 29, 2008 11 :27 AM 90% ULLAGE= 1618 GALS AIR FLOW METER TO VOLUME = 9106 GALS SERIAL NUMBER 84C)8 HIGH WATER WARNING HEIGHT = 79.79 INCHES SEP 29, 2008 10:23 AM WATER VOL = 0 GALS WATER 0.00 INCHES . TEMP 80. 1 DEG F s 5:FM 7-,8 I DELIVERY NEEDED MAY 16, 2010 1 :16 PM AIR FLOW METER-APR 4. 2010 4:33 PM T 3:PREMIUM i SERIAL NUHBER;r :'"8455 APR 1. 2010 3:08 PM VOLUME.,. = 2471 GALS ULLAGE 9591 GALS 90,% ULLAC:E= 8384 GALS i JUN E 2 25 AM P WARNING TO VOLUME 2429 GALS HEIGHT 28.81 INCHES SEP 29, 2008 11 :32 AM WATER VOL 0.00 GALS o, SEP 29, 2008 11 :02 AM WATER TEMP 83.8 DEG F T 4:DIESL VOLUME = 2953 GALS ULLAGE 9109 GALS 90% ULLAGE= 7902 GALS + ALARM HISTORY. REPORT' TC VOLUME _ 2893 UALS HEIGHT = 32.73 INCHES ----- SYSTEM,ALARM ----- * ;� * * x WATER VOL - 14 GALS PAPER OUT END WATER a 0.90 INCHES MAY 24, 2010 1 :17 AM TEMP - 105.1 DEG F PR-INTER ERROR MAY 24. 2010 1 :17 AM MANIFOLDED TANKS INVENTORY TOTALS T I :UNLEAD l i T 2:UNLEAD 2 VOLUME = 18404 GALS TO VOLUME - 18151 GALS R END x * * )(,END �€ f' SOFTWARE REVISION LEVEL VERSION 327.04 SOFTWARE# 346327-100-E CREATED - 07.02.06.10.28 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ' ANNUAL IN-TANK TESTS ' ISD PMC ALARM HISTORY REPORT ALARM H I STORY,RERORT....�- -ALARM HISTORY REPORT ---- IN-TANK ALARM ----- IN=TANK ALARM ----- ---- IN-TANK ALARM ----- T 2:UNLEAD 2 T 3:PREMIUM - - T 4:D1ESL OVERFILL ALARM OVERFILL ALARM OVERFILL ALARM APR 11 , 2010 3:08 AM DEC 12, 2009 6:27 AM JUN 18, 2009 10:06 AM JUN 18. 2009 10:14 AM . DEC 12. 2009 6:12 AM JUN 18, 2009 10:01 AM LOW PRODUCT ALARM SUDDEN LOSS ALARM LOW PRODUCT ALARM JUN 18, 2009 9:18 AM JUN 18, 2009 9:19 AM APR 23. 2009 6:51 `AM HIGH PRODUCT ALARM HIGH PRODUCT ALARM SUDDEN LOSS ALARM JUN 19, 2008 8:53 AM JUN 19. 2008 8:52 AM JUN .18. 2009 9'19 Am JUN 13, 2008 9:45 AM JUN 13. 2008 9:42 AM APR -23. 2009 6:20 AM JUN 19, 2007 8:52 AM JUN 19, 2007 8:51 AM APR 23'. .2009 6:11 AM INVALID FUEL LEVEL PROBE OUT HIGH PRODUCT ALARM- JUN 18. 2009 10:20 AM JUN 18, 2009 10:23 AM '.JUN .19. 2008 8:53 AM. JUN 18. 2009 9:18 AM SEP 29, 2008 9:45 AM JUN 13, 2006 9:44 AM SEP 29, 2008 9:23 AM JUN 19. 2007 8:51 AM.. PROBE OUT JUN 18. 2009 10:19 AM INVALID .FUEL LEVEL DELIVERY NEEDED JUN 18, 2009 10:22 AM MAY 16, 2010 1 : 19 PM APR .23. 2009 6:50 AM DELIVERY NEEDED APR 4, 2010 5:05 PM JUN 2. 2010 6:38 PM APR 1 , 2010 3:01 PM PROBE OUT MAY 7, 2010 10:06 AM JUN 18. 2009 10:20 AM APR 28. 2010 8:43 PM LOW TEMP WARNING DELIVERY NEEDED JUN 18, 2009 10:23 AM r-JUN 12 2010 10:39 AM JUN 18. 2009 9:21 AM . SEP 29, 2008 9:45 AM i JUN, 2.- 2010 6-:20 PM MAY 29, 2010 7:36 AM END END END i ALARM HISTORY REPORT ----- SENSOR ALARM ----- L 1 :UNL 1 STP STP SUMP SENSOR OUT ALARM JUN 18. 2009 9:38 AM FUEL ALARM JUN 18, 2009 9:24 AM FUEL ALARM JUN 17. 2009 9:16 AM * * END i ALARM HISTORY REPORT FALARM HISTORY REPORT t ALARM H'1STOI/ REPORT ----- SENSOR ALARM ----- L 2:UNL 1 ANN ------ SENSOR ALARM ----- - --- SENSOR ALARM ----- ANNULAR SPACE L 4:UNL 2 ANN- L-6:PNL ANN FUEL ALARM ANNULAR SPACE ' ANNULAR SPACE JUN 18, 2009 9:51 AM FUEL ALARM SENSOR OUT ALARM SENSOR OUT ALARM JUN 18, 2009 9:38 AM JUN 18, 2009 9:38 AM JUN 18. 2009 9:38 AM FUEL ALARM JUN 18.. 2009 9:29 AM FUEL ALARM FUEL ALARM JUN 18. 2009 9:28 AM JUN 18. 2009 9:30 AM FUELI7LAR009 9:12 AM' FUEL ALARM JUN 17, 2009 9:12 AM * * END END X X-END * x x x ALARM HISTORY REPORT ALARM HISTORY REPORT ALARM HISTORY REPORT ----- SENSOR ALARM ----- L 3:UNL 2 STP ----- SENSOR ALARM ----- ----- SENSOR ALARM ----- STP SUMP L 5:PNL .STP L 7:DSL STP SENSOR OUT ALARM STP SUMP STP SUMP JUN 18, 2009 9:38 AM SENSOR OUT ALARM SENSOR OUT ALARM JUN 18. 2009 -9:38 AM JUN 1.8. 2009 9:38 AM FUEL ALARM JUN 18, 2009 9:25 AM FUEL ALARM FUEL ALARM JUN 18, 2009 9:26 AM FUEL ALARM JUN 1.8, 2009 9:27 AM JUN 17, 2009 9:16 AM { FUEL ALARM 9:t5 AM FUEL ALARM f JUN 17, 2009 9:15 AM i >4 * * X * END * xx * 9 XXxXxEND x * END X ALARM HISTORY REPORT ALARM HISTORY REPORT. ----- SENSOR ALARM ----- ALARM HISTORY REPORT L 8:DSL ANN ___-- SENSOR ALARM -- --- ----- SENSOR ALARM ----- ANNULAR SPACE L12:DISP 7-8 SENSOR OUT ALARM •L10:DISE 3-4 —DISPENSER PAN JUN 18, 2009 9:38 AM DISPENSER PAN , SENSOR OUT ALARM FUEL A'ARM JUN 18, 2009 9:38 AM FUEL ALARM I JUN 30, 2009 10:24 AM JUN 18. 2009 9:28 AM I SENSOR OUT ALARM (FUEL ALARM JUN 18, 2009 9:38 AM JUN 18. 2009 9:32 AM FUEL ALARM f'FUEL ALARM JUN 17. 2009 9:12 AM FUEL ALARM JUN 18.. 2009 . :9:31 AM JUN 17. 2009 9:20 AM END * END x * * * END. XXxx * a ALARM HISTORY REPORT ALARM HISTORY REPORT ALARM HISTORY REPORT ----- SENSOR ALARM ----- L 9:DISP 1-2 ----- SENSOR ALARM ----- ----- SENSOR ALARM ----- DISPENSER PAN i L11 :DISP 5-6 L13:E. TRANS SUMP SENSOR OUT ALARM I DISPENSER PAN ! PIPING SUMP JUN 18, 2009 9:38 AM SENSOR OUT ALARM ( SENSOR OUT ALARM FUEL ALARM JUN 18. 2009 9:38 AM IJUN 18, 2009 9:38 AM JUN 18. 2009 9:31 AM I FUEL ALARM (FUEL ALARM I JUN 18. 2009 932 AM IJUN 18. 2009 9:33 AM FUEL ALARM JUN 17, 2009 9:19 AM FUEL ALARM ' FUEL ALARM ! JUN 17. 2009 9:20 AM IJUN 17. 2009 9:20 AM i x * * END .XXxXx END x X � � � * � END ALARM HISTORY REPORT l SYSTEM SETUP -- SENSOR ALARM ----- JUN 16. 2010 9:37 AM COMMUNICATIONS SETUP L14:W. TRANS SUMP — — — — — — — — — — — — PIPING SUMP SENSOR OUT ALARM JUN 18, 2009 9:39 AM SYSTEM UNITS PORT SETTINGS: U:S...- o. _ ._ . FUEL ALARM SYSTEM LANGUAGE COMM BOARD : I (EDIM ) JUN 18, 2009 9:33 AM ENGLISH RS-232 SECURITY SYSTEM DATE./TIME. FORMAT CODE : DISABLED FUEL ALARM MON DD YYYY HH:MM:SS xM JUN 17, 2009 9:19 AM COMM BOARD 2 (RS-232) - FASTRIP 346 BAUD RATE 9600 805 34TH - PARITY NONE BKRSFLD.CA STOP BIT 1 STOP 661-325-01.10 DATA LENGTH:. 8 DATA , SHIFT TIME 1 6c00 AM CODE3 : DISABLED SHIFT TIME 2.. DISABLED SHIFT TIME 3 DISABLED COMM BOARD 3 (RS-232) ' SHIFT TIME 4 :- DISABLED BAUD RATE 9600 PA END * * * * * : TANK PER TST NEEDED WRN STOPTBIT NONE STOP iDISABLED DATA LENGTH: 8 DATA TANK ANN TST NEEDED WRN RS-232 SECURITY DISABLED CODE : DISABLED LINE RE—ENABLE METHOD PASS LINE TEST AUTO TRANSMIT SETTINGS: LINE PER TST.NEEDED WRN AUTO LEAK ALARM LIMIT DISABLED DISABLED LINE ANN TST NEEDED WRN AUTO HIGH WATER LIMIT DISABLED DISABLED ALARM HISTORY REPORT AUTO OVERFILL LIMIT PRINT TC VOLUMES DISABLED ----- SENSOR ALARM ----- ENABLED AUTO LOW PRODUCT L15: DISABLED OTHER SENSORS ; TEMP COMPENSATION AUTO THEFT LIMIT , VALUE (DEG F ) : 60.01 DISABLED STICK HEIGHT OFFSET AUTO DELIVERY START DISABLED DISABLED ULLAGE: 90Y AUTO DELIVERY END DISABLED iH—PROTOCOL DATA FORMAT AUTO EXTERNAL INPUT ON HEIGHT DISABLED DAYLIGHT SAVING TIME AUTO EXTERNAL INPUT OFF ENABLED DISABLED END * * START DATE AUTO SENSOR FUEL ALARM, . MAR WEEK 2 SUN DISABLED , START TIME AUTO SENSOR WATER ALARM 2:00 AM DISABLED END DATE AUTO SENSOR OUT ALARM NOV WEEK 1 SUN DISABLED END TIME 2:00 AM RE—DIRECT LOCAL PRINTOUT DISABLED , EURO PROTOCOL PREFIX S RS=232 END OF MESSAGE DISABLED SYSTEM SECURITY CODE : 000000 MAINTENANCE HISTORY DISABLED TANK CHART SECURITY DISABLED CUSTOM ALARMS DISABLED MASS/DENSITY DISABLED IN-TANK SETUP T 2:UNLEAD 2 i T 3:PREMIUM _ - - - - - - - PRODUCT CODE 2 PRODUCT CODE 3 THERMAL COEFF THERMAL COEFF : .000700 :.000700 T 1 :UNLEAD 1 TANK DIAMETER :' 111 .50 . TANK DIAMETER 111 .50 PRODUCT CODE 1 TANK PROFILE i PT TANK PROFILE 1 PT THERMAL COEFF : .000700 FULL VOL, k 062 FULL VOL 12062 TANK DIAMETER 111 .50 TANK PROFILE FULL VOL 12062 FLOAT SIZE. 4.0 IN. FLOAT SIZE: 4.0 IN. 4.0 IN. WATER WARNING 2.0 WATER WARNING 2.0 FLOAT SIZE: HIGH WATER LIMIT: 3.0 HIGH WATER -LIMIT' 3.11 WATER WARNING : 2.0 MAX OR LABEL VOL'-. 12062 MAX OR LABEL VOL: 1206', HIGH WATER LIMIT: 3.0 OVERFILL LIMIT 10955 OVERFILL LIMIT 10855 MAX OR LABEL VOL: 12062 HIGH PRODUCT 95% HIGH PRODUCT 95% OVERFILL LIMIT 90% 11459 11459 10855 DELIVERY LIMIT. 15% ; DELIVERY LIMIT 15% HIGH PRODUCT 95% 1809' 1809 11459 DELIVERY LIMIT 15% LOW PRODUCT 500 ' LOW PRODUCT 500 1809 LEAK ALARM LIMIT: 99 LEAK ALARM LIMIT: 99 SUDDEN LOSS LIMIT: 99 SUDDEN LOSS LIMIT: 99 LOW PRODUCT 500 TANK TILT 0.00 TANK TILT 1 .40 LEAK ALARM LIMIT: 99 PROBE OFFSET 0.00 PROBE-OFFSET 0.00 SUDDEN LOSS LIMIT: 5. 0 TANK TILT 2 2.5 PROBE OFFSET 0.00 SIPHON MANIFOLDED TANKS SIPHON MANIFOLDED TANKS T#: NONE T#: NONE LINE MANIFOLDED TANKS LINE MANIFOLDED TANKS SIPHON MANIFOLDED TANKS T#: 01 -T#:.__NONE._ T#: NONE LINE MANIFOLDED TANKS T#: 02 LEAK MIN PERIODIC: 1% LEAK MIN PERIODIC: 0% 120 0 PERIODIC TEST TYPE PERIODIC 'TEST TYPE LEAK MIN PERIODIC: 120 STANDARD STANDARD PERIODIC TEST TYPE PERIODIC TEST FAIL PERIODIC TEST FAIL STANDARD ALARM DISABLED ALARM DISABLED PERIODIC TEST FAIL GROSS TEST FAIL GROSS TEST FAIL ALARM DISABLED ALARM, DISABLED ALARM DISABLED GROSS TEST FAIL PER TEST AVERAGING: OFF PER TEST AVERAGING: OFF ALARM DISABLED TANK TEST NOTIFY: OFF PER TEST AVERAGING: OFF TANK TEST NOTIFY: OFF TNK TST SIPHON BREAK:OFF TNK TST SIPHON HREAK:OFF TANK TEST NOTIFY:` OFF DELIVERY DELAY 1 MIN DELIVERY DELAY 1 MIN TNK TST SIPHON BREAK:OFF PUMP THRESHOLD 10.00°%, PUMP THRESHOLD 10.00% i£L l;uEkY !>wLF+''�' 1 MIN,, j p0mr, THRESHOLD -T A:DIESL - PRODUCT CODE q - THERMAL COEFF : .000450 PUMP SENSOR SETUP TANK DIAMETER 111 .5i' TANK PROFILE 1 P7' LIQUID SENSOR SETUP - - - - - - - - - - - - _ _ _ _ _ _ FULL VOL 12062 - _ ;_..S_lL:.UNLEAD ,1 L I :UNL 1 STP TANK fit: 1 FLOAT SIZE: 4.0 IN. TRI-STATE (SINGLE FLOAT) DISPENSE MODE: CATEGORY STP SUMP MANIFOLDED: ALTERNATE WATER WARNING 2.0 S 2:PREMI.UM HIGH WATER LIMIT: 3.0 L 2:UNL. 1 ANN - TANK # 3 MAX OR LABEL VOL: 12062 TRI-STATE (SINGLE FLOAT) DISPENSE MODE: OVERFILL LIMIT 90% CATEGORY ANNULAR SPACE STANDARD 10855 HIGH PRODUCT 95% i 11459 L 3:UNL 2 STP DELIVERY LIMIT 15% TRI-STATE (SINGLE FLOAT) 1809 CATEGORY STP SUMP LOW PRODUCT 500 f LEAK ALARM LIMIT: 99 L 4:UNL 2 ANN SUDDEN LOSS LIMIT: 99 NORMALLY CLOSED TANK TILT 0.00 CATEGORY : ANNULAR SPACE PROBE OFFSET 0.00 OUTPUT RELAY SETUP SIPHON MANIFOLDED TANKS L 5:PNL STP R 1 :UNL 1 T#: NONE j TRI-STATE (SINGLE FLOAT) TYPE: LINE MANIFOLDED TANKS CATEGORY : STP SUMP PUMP CONTROL OUTPUT T#: NONE j TANK #: 1 LEAK h1 I N PER f OD I C: 0� L 6:PNL ANN 0 TRI-STATE (SINGLE FLOAT) LIQUID SENSOR ALMS PERIODIC TEST TYPE CATEGORY : ANNULAR SPACE L 1 :FUEL ALARM STANDARD L 3:FUEL ALARM L 9:FUEL ALARM PERIODIC TEST FAIL L10:FUEL ALARM L 7:DSL STP L1I :FUEL ALARM ALARM DISABLED TRI-STATE (SINGLE FLOAT) L12:FUEL ALARM GROSS TEST FAIL CATEGORY : STP SUMP L 1 :SENSOR OUT ALARM ALARM DISABLED L 3:SENSOR OUT ALARM L 9:SENSOR OUT ALARM PER TEST AVERAGING: OFF ; L 8:DSL ANN L10:SENSOR OUT ALARM i TRI-STATE (SINGLE FLOAT) L11 :SENSOR OUT ALARM TANK. TEST NOTIFY: OFF CATEGORY : ANNULAR SPACE L12:SENSOR OUT ALARM L 1 :SHORT ALARM TNK TST SIPHON BREAK:OFF L 3:SHORT ALARM L 9:SHORT ALARM DELIVERY DELAY 1 MIN L 9:DISP 1-2 L10:SHORT ALARM PUMP THRESHOLD 10.00% TRI-STATE (SINGLE FLOAT) L11 :SHORT ALARM CATEGORY : DISPENSER PAN L12:SHORT ALARM ! ISD SITE ALARMS ISD GROSS PRES FAIL L10:DISP 3-4 1 ISD DEGRD PRES FAIL TRI-STATE (SINGLE FLOAT) ISD VAPOR LEAK FAIL CATEGORY : DISPENSER PAN ISD VP PRES FAIL ISD SETUP FAIL ISD SENSOR OUT FAIL L11 :DISP 5-6 ISD HOSE ALARMS TRI-STATE (SINGLE FLOAT) ALL:GROSS COLLECT FAIL LEAK TEST METHOD CATEGORY : DISPENSER PAN ALL:DEGRD COLLECT FAIL _ - - - - _ _ _ - _ - ALL:FLOW COLLECT FAIL TEST ON DATE : ALL TANK FEB 6. 2007 L12:DISP 7-8 START TIME : DISABLED TRI-STATE (SINGLE FLOAT) TEST RATE :0.20 GAL/HR CATEGORY : DISPENSER PAN DURATION 2 HOURS TST EARLY STOP:DISABLED LEAK TEST REPORT FORMAT L13:E. TRANS SUMP NORMAL i �TRI-STATE' (SINGLE FLOAT) CATEGORY : PIPING SUMP i L14:W. TRANS SUMP TRI-STATE (SINGLE FLOAT) CATEGORY PIPING SUMP R 2:UNL 2 PUMP CONTROL OUTPUT ; R 4:DS1 TANK #: 2 ` , . TYPE: EVR/ISD 'SETUP STANDARD LIQUID SENSOR ALMS f NORMALLY-CLOSED L 1 :FUEL ALARM TANK #: .NONE EVR TYPE: .VACUUM ASSIST L 3:FUEL ALARM VACUUM ASSIST TYPE L 9:FUEL ALARM HEALY VAC L10:FUEL ALARM LIQUID SENSOR ALMS LII :FUEL ALARM L 7:FUEL ALARM NOZZLE A/L RANGE L12:FUEL ALARM i :, _L10:FUEL ALARM (( MAX: 1 .15 MIN: 0,95 L 1 :SENSOR OUT ALARM L1:2:FUEL ALARM i I L 3:SENSOR OUT ALARM L13:FUEL ALARM I VAPOR PROCESSOR TYPE L 9:SENSOR OUT ALARM L14:FUEL ALARM NO VAPOR PROCESSOR LIO:SENSOR OUT ALARM L 7:.SENSOR OUT ALARM L11 :SENSOR OUT ALARM L10:SENSOR 2OUT ALARM L12:SENSOR OUT ALARM z. L12:SENSOR OUT ALARM ANALYSIS TIMES L 1 :SHORT ALARM t L13:SEN2OR OUT ALARM TIME: 10:00 AM L 3:SHORT ALARM LI-4:SENSOR -OUT ALARM DELAY MINUTES: 1 L 9:SHORT ALARM L 7:SHORT ALARM LIO:SHORT ALARM 1_10:SHORT ALARM LII :SHORT ALARM L12:8HORT ALARM ACCEPT HIGH ORVR: L12:SHORT ALARM L1.3::SHORT ALARM DISABLED ISD SITE ALARMS L-1,4•:SHORT ALARM I•SD HOSE TABLE ISD GROSS PRES FAIL R• 5:OVERFILL ALARM ID FP FL HL AA RR ISD D£GRD PRES FAIL TYPE: ---- --------------------- ISD VAPOR LEAK FAIL STANDARD 01 01 01 02 01 UU ISD VP PRES FAIL NORMALLY OPEN 02 02 02 02 01 UU ISD VP STATUS FAIL { 03 03 03 02 02 UU ISD SETUP FAIL TANK #: NONE 04 04 04 02 02 UU ISD SENSOR OUT FAIL t 05 05 05 02 03 UU i 06 06 06 02 03 UU ISD HOSE ALARMS ` IN-TANK ALARMS 07 07 07 02 04 UU ALL:GROSS COLLECT FAIL ALL,OVERFILL ALARM 08 08 08 02 04 UU ALL:DEGRD COLLECT FAIL ALL:HIGH PRODUCT ALARM ALL:FLOW COLLECT FAIL ALL:MAX PRODUCT ALARM ISD AIRFLOW METER MAP R 3:PNL ID SERIAL NUM LABEL TYPE: = -----------------------•- PUMP CONTROL OUTPUT I 1 8448 FM 1-2 TANK #: 3 2 8409 FM 3-4 3 8408 FM 5-6 4 8455 FM 7-6 ! LIQUID SENSOR ALMS L 5:FUEL ALARM I L 9:FUEL ALARM - ? ISD FUEL GRADE HOSE' HAP L10:FUEL ALARM • 1 2 3 4 L11 :FUEL ALARM SMARTSENSOR SETUP FP MHH MHH MHH MHH AA _. L12:FUEL ALARM , `i _ _ ._ _ _ _ _ - ------------------------- L 5:SENSOR--OUT 'A ` � T `" - - 01 201 901 301 U U l L• 9:SENSOR.C06V"ALA s 1 :V.P 1-2 02 202 902 302 U U 1 LL048EN8OR OUT ALARM CATEGORY VAPOR PRESSURE 03 203 903 303- 5 U 2 LI I :SENSOR OUT ALARM ` 04 204 904 304 5 U 2 L12:SENSOR OUT ALARM s 2:FM 1-2 05 205 905 305 U U 3 L. 5:SHORT ALARM ,: CATEGORY AIR FLOW METER 06 206 906 306 U U 3 L 9:SHORT ALARM I 07 207 907 307 5 U' 4 L10:SHORT ALARM s 3:FM 3-4 08 208 908 308 5 U 4 L11 :SHORT ALARM f CATEGORY AIR FLOW METER L12:SHORT ALARM s 4:FM 5-6 I` LABEL TABLE ISD SITE ALARMS , CATEGORY AIR FLOW METER ------------------------ ISD GROSS PRES FAIL 1 : UNASSIGNED ISD DEGRD PRES FAIL s 5:FM 7-8 2: BLEND3 ISD VAPOR LEAK FAIL CATEGORY AIR FLOW METER 3: REGULAR ISD VP PRES FAIL 4: MID GRADE ISD VP STATUS FAIL 5: PREMIUM ISD SETUP FAIL 6: GOLD ISD SENSOR OUT FAIL 7: BRONZE ISD HOSE ALARMS 9: BL.END2 ALL:GROSS COLLECT FAIL > ; 10: BLEND4 ALL:DEGRD COLLECT .FAIL ALL:FLOW COLLECT FAIL PMC SETUP PROCESSOR CONTROL LEVEL: NONE SENSOR ALARM ----- ----= SENSOR ALARM L12:DISP 7-8 ARCHIVE UTILITY L 6:DSL ANN DISPENSER PAN ANNULAR SPACE FUEL ALARM SAVE SETUP DATA: FUEL ALARM i JUN 16. 2010 1 :48 PM START TIME: JUN 16. 2010 1 :38 PM JUN 16, 2010 1 :21 :30 PM i ----- SENSOR ALARM ----- ----- SENSOR ALARM ----- L14:W. TRANS SUMP L 6:PNL'-ANN PIPING SUMP ANNULAR SPACE FUEL ALARM ARCHIVE UTILITY FUEL ALARM JUN 16. 2010 1 :49 PM - ARCHIVE — — — — — — JUN 16, 2010• 1 :39 PM SAVE SETUP DATA: — END TIME: JUN 16, 2010 1 :24:00 PM BYTES 19200 s i r y ----- SENSOR ALARM ----- -- SENSOR ALARM ----- i L13-E. TRANS SUMP L 4:UNL 2 ANN PIPING SUMP ANNULAR SPACE FUEL ALARM FUEL 16 ARM 1 :41 PM JUN 16. 2010 1 :49 PM JUN----- SENSOR ALARM ----- L 1 :UNL 1 STP STP SUMP FUEL ALARM i JUN 16. 2010 1 :31 PM ----- SENSOR ALARM ----- -- SENSOR ALARM ----- L 5:PNL STP L 2:UNL 1 ANN ' STP SUMP ANNULAR SPACE SENSOR OUT ALARM FUNL16 A 010 1 :42 PM JUN 16. 2010 1 :51 PM ----- SENSOR ALARM ----- L 3:UNL 2 STP STP SUMP FUEL ALARM JUN. 16, 2010 1 :32 PM ----- SENSOR ALARM ----- ----- SENSOR ALARM ----- L 1 :UNL 1„STP L10:DISP 3-4 STP SUMP s DISPENSER PAN SENSOR OUT. ALARM FUNL16.ALARM 1 :44 PM JUN 16. 2010 1 :51 PM ---- SENSOR ALARM ----- L 5:PNL STP STP SUMP FUEL ALARM JUN 16, 2010 1 :33 PM ----- SENSOR ALARM —.---- ----- SENSOR ALARM ----- L 7:DSL STP L 9:DISP 1-2 i STP SUMP DISPENSER PAN i SENSOR OUT ALARM FUEL ALARM JUN 16, 2010 1 :51 PM JUN 16, 2010 1 :46 PM I ----- SENSOR ALARM ----- L 7:DSL STP STP SUMP FUEL ALARM JUN 16. 2010 1 :34 PM ----- SENSOR ALARM ----- -- SENSOR ALARM ----- L 2:UNL 1 ANN I.11 :D I SP 5-6 ANNULAR SPACE DISPENSER PAN., SENSOR OUT ALARM FUEL ALARM JUN 16, 2010 1 :51 PM JUN•. 16.. 2010 V 47° -- SENSOR ALARM L 8:DSL ANN ANNULAR SPACE -- SENSOR ALARM :-=--- J SENSOR OUT ALARM L13:E. TRANS SUMP FARTRIP 346 JUN 16. 2010 1 :51 PM PIPING SUMP 805 34TH SENSOR OUT ALARM BAKERSFIELD.CA JUN 16. 2010 1 :51 PM 661-325-0110 JUN 16. 2010 1 :55 PM SYSTEM STATUS REPORT ----- SENSOR ALARM ----- ALL FUNCTIONS NORMAL L 9:DISP 1-2 ----- SENSOR ALARM ----- DISPENSER PAN L 6:PNL ANN SENSOR OUT ALARM { ANNULAR SPACE JUN 16, 2010 1 :51 PM SENSOR OUT ALARM JUN 16. 2010 1 :51 PM --- IN-TANK ALARM ----- T 3:PREMIUM HIGH PRODUCT ALARM JUN 16, 2010 1 :55 PM ----- SENSOR ALARM ----- L10:DISP 3-4 ---- SENSOR ALARM ----= DISPENSER PAN L14,:W. TRANS SUMP SENSOR OUT ALARM PIPING SUMP JUN 16. 2010 1 :51 PM SENSOR OUT ALARM JUN 16, 2010 1 :51 PM FARTRIP 346 805 34TH BAKERSFIELD.CA 661-325-0110 ----- SENSOR ALARM ----- JUN 16. .2010 1 :56 PM L 3:UNL 2 STP ---- IN-TANK ALARM ----- STP SUMP T 1 :UNLEADED 1 SENSOR OUT ALARM HIGH PRODUCT ALARM SYSTEM STATUS REPORT JUN 16, 2010 1 :51 PM JUN 16, 2010- 1 :53 PM - - - - - - - - - - -ALL FUNCTIONS NORMAL -- SENSOR ALARM ----- FARTRIP 346 L11 :DISP 5-6 805 34TH ---- IN-TANK ALARM -- -- DISPENSER PAN BAKERSFIELD.CA T 4:DIESEL SENSOR OUT ALARM 661-325-0110 HIGH PRODUCT ALARM JUN 16. 2010 1 :51 PM JUN 16. 2010 1 :56 PM ,. JUN 16 2010 1 :54 PM SYSTEM STATUS REPORT - ALL FUNCTIONS NORMAL - -- SENSOR ALARM ----- FARTRIP 346 L 4:UNL 2 ANN 805 34TH ANNULAR SPACE BAKERSFIELD.CA FUEL ALARM 661-325-0110 JUN 16, 2010 1 :51 PM JUN 16, 2010 1 :56 PM ---- IN-TANK ALARM----- T 2:UNLEADED 2 . HIGH PRODUCT ALARM SYSTEM STATUS REPORT JUN 16, 2010 1 :54 PM - - - - - -- - - - - - ALL FUNCTIONS NORMAL. ----- SENSOR ALARM - -- L12:DISP 7-6 DISPENSER PAN SENSOR OUT ALARM JUN 16. 2010 1 :51 PM SYSTEM SETUP ARCHIVE UTILITY _JUN 16. 2010. 2:23 PM COMMUNICATIONS SETUP SAVE SETUP DATA: START TIME: MIN 16. 2010 2:07:06 PM SYSTEM UNITS - � 1 PORT SETTINGS: U.S. l COMM BOARD : I (EDIM ) SYSTEM...LANGUAGE _.__; [ _RS-232 SECURITY 'ENGL SH - CODE : DISABLED SYSTEM-'DATE/TIME 'FORMAT t-'=MOW"HD='f'�"s'4'`'H11'�MMYSB iiP4 COMM BOARD 2 (RS-232) FARTRIP 346 BAUD RATE 9600 805 34TH PARITY NONE 805 34TH STOP BIT 1 STOP 661-32IELD- DATA LENGTH: 8 DATA RS-232 SECURITY ARCHIVE UTILITY CODE : DISABLED SHIFT TIME i 6:00 AM SAVE SETUP DATA: SHIFT TIME 2. :. DISABLED COMM BOARD 3 (RS-232) END TIME: SHIFT TIME 3 :: DISABLED BAUD RATE 9600 JUN 16, 2010 2:09:37 FM SHIFT TIME 4 DISABLED PARITY NONE BYTES 19328 TANK PER TST NEEDED WRN STOP BIT 1 STOP DISABLED DATA LENGTH: B DATA TANK ANN TST NEEDED WRN ODE : SECURITY C -DISABLED CODE DISABLED LINE RE-ENABLE METHOD AUTO TRANSMIT SETTINGS: PASS LINE TEST LINE PER TST NEEDED WRN AUTO LEAK ALARM LIMIT DISABLED DISABLED LINE ANN TST NEEDED WRN AUTO HIGH WATER LIMIT DISABLED DISABLED FARTRiP 346 AUTO dVERFILL LIMIT 805 34TH PRINT TC VOLUMES DISABLED BAKERSFIELD.CA ENABLED AUTO LOW PRODUCT 661-325-0110 DISABLED JUN 16, 2010 2:23 PM TEMP COMPENSATION AUTO THEFT LIMIT VALUE (DEG F ) : 60,0 AUTO-DELIVERY 4 START STICK HEIGHT OFFSET AUTO DELIVER! DISABLED DISABLED SYSTEM STATUS REPORT ULLAGE: 90d- DISABLED DELIVERY END _ DISABLED ALL FUNCTIONS NORMAL H-PROTOCOL DATA FORMAT AUTO EXTERNAL INFUT ON HEIGHT DISABLED DAYLIGHT SAVING TIME AUTO EXTERNAL INPUT OFF ENABLED DISABLED START DATE AUTO SENSOR FUEL ALARM MAR WEEK 2 SUN DISABLED START TIME AUTO SENSOR WATER ALARM 2 DISABLED :00 AM END DATE AUTO SENSOR OUT ALARM OCT WEEK 1 SUN DISABLED END TIME 2:00 AM RE-DIRECT LOCAL PRINTOUT DISABLED EURO PROTOCOL PREFIX i S RS-232 END- OF MESSAGE DISABLED SYSTEM SECURITY CODE : 000000 MAINTENANCE HISTORY- DISABLED TANK CHART SECURITY DISABLED CUSTOM ALARMS DISABLED MASS/DENSITY DISABLED IN-TANK SETUP - - - - - - - - - - T 2:UNLEADED 2 i T 3:PREMIUM PRODUCT CODE 2 PRODUCT CODE 3 T 1 :UNLEADED 1 I THERMAL-'*COEFF µ :.000700 •= THERMAL COEFF : .000700 PRODUCT CODE TANK DIAMETER 111 .50 TANK DIAMETER 111 .50 THERMAL COEFF : .000700 TANK PROFILE 1 PT . TANK PROFILE 1 PT TANK DIAMETER 11 TANK PROFILE 1 PT FULL VOL 12062 FULL VOL 12062 I FULL VOL 12062 FLOAT SIZE: 4.0 IN. FLOAT SIZE: 4.0 IN. FLOAT SIZE: 4.0 IN. WATER WARNING 2.0 WATER WARNING 2.0 WATER WARNING 2.0 HIGH WATER LIMIT: 3.0 HIGH WATER LIMIT: 3.0 HIGH WATER LIMIT: 3.0 MAX OR LABEL VOL: 12062 MAX OR LABEL VOL: 12062 MAX OR LABEL VOL: 12062 OVERFILL LIMIT : 90% OVERFILL LIMI-T ' 90.04.1 OVERFILL LIMIT 90% HIGH -PRODUCT 10855 5 % HIGH PRODUCT 10955" 10855 HIGH PRODUCT 95% DELIVERY LIMIT 11159 DELIVERY LIMIT 1115% 11459 1809 1809 DELIVERY LIMIT 1809 LOW PRODUCT 500 LOW PRODUCT 500 LOW PRODUCT 500 LEAK ALARM LIMIT: 99 LEAK ALARM LIMIT: 99 LEAK ALARM LIMIT: 99 SUDDEN LOSS LIMIT: 99 SUDDEN LOSS LIMIT: 99 SUDDEN LOSS LIMIT: 99 TANK TILT 0.00 TANK TILT 1 .40 TANK TILT 2.50 PROBE OFFSET 0.00 PROBE OFFSET 0.00 -PROBE OFFSET 0.00 SIPHON MANIFOLDED TANKS SIPHON MANIFOLDED TANKS SIPHON MANIFOLDED TANKS T#: NONE ' TI: NONE LINE MANIFOLDED TANKS LINE MANIFOLDED TANKS TO NONE TO: 01 TO: NONE LINE MANIFOLDED TANKS TO: 02 LEAK MIN PERIODIC: 1% LEAK MIN PERIODIC: i% 120 120 LEAK MIN PERIODIC: 120 PERIODIC TEST TYPE PERIODIC TEST TYPE PERIODIC TEST TYPE STANDARD STANDARD STANDARD PERIODIC TEST FAIL PERIODIC TEST FAIL PERIODIC TEST FAIL ALARM DISABLED ALARM DISABLED ALARM DISABLED GROSS TEST FAIL GROSS TEST FAIL GROSS TEST FAIL ALARM DISABLED ALARM DISABLED ALARM DISABLED PER TEST AVERAGING: OFF PER TEST AVERAGING: OFF PER TEST AVERAGING: OFF TANK TEST NOTIFY: OFF TANK TEST NOTIFY: OFF TANK TEST NOTIFY: OFF TNK TST SIPHON BREAK:OFF TNK TST SIPHON BREAK:OFF TNK TST SIPHON BREAK:OFF DELIVERY DELAY 1 MIN DELIVERY DELAY I MIN t DELIVERY DELAY 1 MIN PUMP THRESHOLD 10.00 PUMP THRESHOLD 10.00% PUMP THRESHOLD 10.00% T 4:DIESEL -LIQUID SENSOR SETUP --- - --� -_ PRODUCT CODE 4 - - - - - - - - - - - - THERMAL COEFF : .000450 PUMP SENSOR SETUP TANK DIAMETER 111 .50 L I :UNL 1 STP - - - - - - - - - - TANK PROFILE 1 PT TRI-STATE -(SINGLE FLOAT) FULL VOL 12062 CATEGORY STP SUMP• S>-I-:UNL-EADED 1 TANK 0: 1 DISPENSE MODE: FLOAT SIZE: 4.0 IN. L 2:UNL 1 ANN MANIFOLDED: ALTERNATE TRI-STATE' (SINGLE FLOAT) WATER WARNING 2.0 CATEGORY ANNULAR-SPACE S 2:PREMIUM HIGH WATER LIMIT: 3.0 TANK #: 3 MAX OR LABEL VOL: 12062 DISPENSE MODE: OVERFILL LIMIT 90% L 3:UNL 2 STP STANDARD 10855 TRI-STATE. .(SINGLE ,FLOAT),. HIGH PRODUCT 95% CATEGORY- 'STP-SUMP `_ 11459 DELIVERY LIMIT 151% . 1809 L 4:UNL 2 ANN NORMALLY CLOSED LOW PRODUCT 500 CATEGORY :. ANNULAR- SPACE LEAK ALARM LIMIT: 99 SUDDEN LOSS LIMIT: 99 TANK TILT 0.20 PROBE OFFSET 0.00 L 5:PNL STP OUTPUT RELAY SETUP - TRI-STATE (SINGLE FLOAT) - - - - - - - - - - _ - CATEGORY :. STP SUMP SIPHON MANIFOLDED TANKS R 1 :UNL 1 TO: NONE TYPE: LINE MHNIFOLDED TANKS L 6:PNL ANN PUMP CONTROL-OUTPUT T#: NONE TRI-STATE (SINGLE FLOAT) TANK 0: 1 CATEGORY : ANNULAR SPACE LEAK MIN PERIODIC: 0% LIQUID SENSOR ALMS 0 L 1 :FUEL ALARM PERIODIC TEST TYPE L 7:DSL STP L 3:FUEL ALARM STANDARD TRI-STATE (SINGLE FLOAT) L 9:FUEL ALARM E CATEGORY : STP SUMP L10:FUEL ALARM PERIODIC TEST FAIL Lll :FUEL ALARM ALARM DISABLED L12:FUEL ALARM L B:DSL ANN L I :SENSOR OUT ALARM GROSS TEST FAIL TRI-STATE '(SINGLE FLOAT) L 3:SENSOR OUT ALARM ALARM DISABLED CATEGORY ANNULAR SPACE L 9:SENSOR OUT ALARM PER TEST AVERAGING: OFF L10:SENSOR OUT ALARM Lll :SENSOR OUT ALARM L12:SENSOR OUT ALARM TANK TEST NOTIFY: OFF L 9:DISP 1-2 L 1 :SHORT ALARM TRI-STATE .(SINGLE FLOAT) L 3:SHORT ALARM TNK TST SIPHON BREAK:OFF CATEGORY : DISPENSER PAN L 9:SHORT ALARM N DELIVERY DELAY 1 MIN LIO:SHORT ALARM PUMP THRESHOLD : 10.0 Lll :SHORT ALARM L10:D1SP 3-4 L1.2:SHORT ALARM TRI-STATE (SI•NGLE FLOAT) ISD SITE ALARMS CATEGORY : DISPENSER PAN ISD GROSS PRES FAIL ISD DEGRD PRES FAIL: ISD VAPOR LEAK FAIL ISD VP PRES- FAIL LI-1 :DISP 5-6 ISD VP STATUS FAIL i CATEGORY :(DISPENSERPAN ISD SETUP FAIL ISD SENSOR OUT FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL LEAK TEST METHOD L12:DISP 7-8 ALL:DEGRD COLLECT FAIL TEST ON DATE : ALL TANK CATEGORYE:(SINGLE DISPENSERFLOAT) ALL:FLOW COLLECT FAIL PAN FEB 6. 2007 START TIME : DISABLED TEST RATE .:0.20 GAL/HR DURATION 2 HOURS L13:E. TRANS SUMP TRI-STATE (SINGLE FLOAT) TST EARLY STOP:DISABLED CATEGORY : PIPING SUMP LEAK TEST REPORT FORMAT NORMAL L14:W. TRANS SUMP TRI-STATE (SINGLE FLOAT) CATEGORY PIP-ING SUMP i R 2:UNL 2 ^R 4:DIESEL" T TYPE: TYPE: PUMP CONTROL OUTPUT STANDARD EVR/ISD SETUP TANK #: 2 NORMALLY CLOSED TANK #: 4 LIQUID SENSOR ALMS EVR TYPE: VACUUM ASSIST L I :FUEL ALARM VACUUM ASSIST TYPE L 3:FUEL ALARM LIQUID SENSOR ALMS HEALY VAC L 9:FUEL ALARM L 7:FUEL ALARM L10:FUEL ALARM L10:FUEL ALARM NOZZLE A/L RANGE L11 :FUEL ALARM L12:FIJEL ALARM MAX: 1 .15 MIN: 0.95 1_12:FUEL ALARM L13 FUEL ALARM L I :SENSOR OUT ALARM L14:FUEL ALARM VAPOR PROCESSOR TYPE L 3:SENSOR OUT ALARM L 7:SENSOR OUT ALARM NO VAPOR PROCESSOR L 9:SENSOR OUT ALA yy� L10:SENSOR OUT ALARM L10:SENSOR OUT ALARPI 1_1.2:SENSOR OUT ALARM L 1 1 :SENSOR OUT ALARM L 1-3-:SENSOR OUT -ALARM ANALYSIS TIMES L12:SENSOR OUT 'ALARM L14:SENSOR OUT ALARM TIME:- 10:00 AM L 1 :SHORT ALARM L '7:SHORT ALARM DELAY MINUTES: 1 i L 3:SHORT ALARM LIO:SHORT ALARM L 9:SHORT ALARM r. L12:SHORT ALARM L10:SHORT ALARM L13:SHORT ALARM ACCEPT HIGH ORVR: L11 :SHORT ALARM L14:SHORT ALARM DISABLED L12:SHORT ALARM R 5:OVERFILL,ALARM ISD HOSE TABLE ISD SITE ALARMS TYPE: ID FP FL HL AA RR ISD GROSS PRES FAIL. STANDARD `- ISD DEGRD PRES FAIL NORMALLY OPEN O1- O1 -01 -02-y0I- �UU ISD VAPOR LEAK. FAIL 02 02 02 02 01 UU ISD VP PRES FAIL TANK #: "NONE 03 03 03 '02 02 :UU ISD VP STATUS FAIL 04 04 04 . 02 02 UU ISD SETUP FAIL 05 05 05 02 03 UU ISD SENSOR OUT FAIL IN-TANK ALARMS 06 06 06 02 03 'UU ALL:OVERFILL ALARM-' 07 07 07. 02 0.4 UU ISD HOSE ALARMS ALL:HIGH PRODUCT•ALARM 08 08 08 02 04 UU ALL:GROSS COLLECT FAIL ALL:MAX PRODUCT ALARM ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL - ISD AIRFLOW METER MAP ID SERIAL NUM LABEL R 3:PREr1 ----------------=---:---- TYPE: ( 1 8448 FM .1-2 PUMP CONTROL OUTPUT 2 8409 FM 3-.4 TANK #: 3 ; 3 8408 5-B FM 4 8455 FM LIQUID SENSOR ALMS L 5:FUEL ALARM ISD FUEL�GRADE H4 E:,MAP L 9:FUEL ALARM SMARTSENSOR SETUP' 1 L10:FUEL ALARM - -• - - - - - - - - FP MHH MHH MHH-MHH' AA - LII :FUEL ALARM ------------ - -7 s L 12:FUEL ALARM s. 1 :V.P 1-2 DI 201 301 901 U U `.-1 L 5:SENSOR OUT ALARM CATEGORY VAPOR PRESSURE 02 202 302 902 U :U '•1 L 9:SENSOR OUT ALARM t- 03 203 303 903 U U ; 2 L10:SENSOR OUT ALARM s 2:FM, 1-2.. 04 204 304 904 U U. .2 L11 :SENSOR OUT ALARM CATEGORY AIR FLOW METER 05 205 305 905 U U ,.!:3 L12:SENSOR OUT ALARM 06 206 306 906 U U 3 L 5:SHORT ALARM s 3:FM 3-4 07 207 307 907- U U :;;4 L 9:SHORT ALARM CATEGORY 'AIR FLOW METER 08 208 308 908 U U =.';4 L10:SHORT ALARM { L11 :SHORT ALARM s 4:5-6 FM L12:SHORT ALARM CATEGORY AIR FLOW METER LABEL TABLE ------------------- .---- ISD SITE ALARMS s 5:FM 7-8 1 UNASSIGNED i ISD GROSS PRES FAIL CATEGORY AIR FLOW METER 2: BLEND3 ISD DEGRD PRES FAIL t 3: REGULAR - ISD VAPOR LEAK FAIL 4: MID GRADE ISD VP PRES FAIL 5: PREMIUM , ISD VP STATUS FAIL 6: GOLD ISD SETUP FAIL 7 BRONZE ISD SENSOR OUT FAIL' =8: SILVER 9: BLEND2 ISD HOSE ALARMS . 10: BLEND4 ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL ' P F= FMC SETUP r' PROCESSOR_CCONTROL L,EVEL: NONE­ SWRCB,January 2006 Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printouts from tests (if applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: #346 Fastrip#621 1 Date of Testing: 06/16/2010 Facility Address: 805 34 Street, Bakersfield,CA 93301 Facility Contact: Omero Garcia I Phone: 661-393-7000 Date Local Agency Was Notified of Testing : 5/24/10 Name of Local Agency Inspector(if present during testing): Ernie Medina 2. TESTING CONTRACTOR INFORMATION Company Name: Confidence UST Services,Inc. Technician Conducting Test: Garry DiMaggio Credentials': X CSLB Contractor X ICC Service Tech. ❑SWRCB Tank Tester ❑Other(Spec) License Number(s): CSLB#804904 ICC#8019607-UT 3. SPILL BUCKET TESTING INFORMATION Test Method Used: x Hydrostatic ❑Vacuum ❑Other Test Equipment Used: Lake Test Equipment Resolution: 0.0625" Identify Spill Bucket(By Tank 1 Regular 1 2 Regular 2 3 Super(Product) 4 Diesel(Product) � Number, Stored Product, etc. Product Product Bucket Installation Type: ❑Direct Bury ❑Direct Bury ❑Direct Bury ❑Direct Bury x Contained in Sump x Contained in Sump x Contained in Sump x Contained in Sum Bucket Diameter: 12.00" 12.00" 12.00" 12.00" Bucket Depth. 14.25" 14.50" 13.75" 14.00" Wait time between applying 5 min. 5 min. 5 min. 5 min. vacuum/water and start of test: Test Start Time(Tj): 10:00 am 10:00 am 10:00 am 10:00 am Initial Reading(Rj): 9.75" 9.50" 9.50" 9.75" Test End Time(TF): 11:00 am 11:00 am 11:00 am 11:00 am Final Reading(RF): 9.75" 9.50" 9.50" 9.75" Test Duration(TF—Tj): 1 hour 1 hour 1 hour 1 hour Change in Reading(RF-Rj): 0.00" 0.00" 0.00" 0.00" Pass/Fail Threshold or 0.0625" 0.0625" 0.0625" 0.0625 Criteria: Test Result: X Pass ❑ Fail-' =IX Pass -[]Fail X Pass- ❑Fail X- Pass ❑Fail•. Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true,accurate,and in full compliance with legal requirements. Technician's Signature: Date: 06/16/2010 ' State laws and regulations do not currently require testing to be performed by a qualified contractor. However,local requirements may be more stringent. SWRCB,January 2006 Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printouts from tests (f applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: 4346 Fastrip#621 1 Date of Testing: 06/16/2010 Facility Address: 805 34` Street,Bakersfield,CA 93301 Facility Contact: Omero Garcia I Phone: 661-393-7000 Date Local Agency Was Notified of Testing : 5/24/10 Name of Local Agency Inspector(rf present during testing): Ernie Medina 2. TESTING CONTRACTOR INFORMATION Company Name: Confidence UST Services,Inc. Technician Conducting Test: Garry DiMaggio Credentials': X CSLB Contractor X ICC Service Tech. ❑SWRC13 Tank Tester ❑Other(Spec) License Number(s): CSLB#804904 ICC#8019607-UT 3. SPILL BUCKET TESTING INFORMATION Test Method Used: x Hydrostatic ❑Vacuum ❑Other Test Equipment Used: Lake Test Equipment Resolution: 0.0625" Identify Spill Bucket(By Tank 1 Regular 1 (Vapor) 2 Regular 2(Vapor) 3 Super(Vapor) 4 Number, Stored Product, etc.) Bucket Installation Type: ❑ Direct Bury ❑ Direct Bury ❑Direct Bury ❑Direct Bury x Contained in Sump x Contained in Sump x Contained in Sump ❑Contained in Sum Bucket Diameter: 12.00" 12.00" 12.00" Bucket Depth: 14.25" 14.50" 13.75" Wait time between applying 5 min. 5 min. 5 min. vacuum/water and start of test: Test Start Time(T,): 10:00 am 10:00 am 10:00 am Initial Reading(Rj): 9.50" 9.75" 9.75" Test End Time(TO: 11:00 am 11:00 am 11:00 am Final Reading(RF): 9.50" 8.25" 9.75" Test Duration(TF—T,): 1 hour 1 hour 1 hour Change in Reading(RF-R,): 0.00" 1.50" 0.00" Pass/Fail Threshold or 0,0625" 0.0625" 0.0625" Criteria: Test Result: X Pass ❑ Fail 0-Pass X Fail X Pass'. -❑Fail ❑ Pass- ❑Fail Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) Regular #2 (Vapor-OPW) Spill Bucket has been ordered and is scheduled to be Replaced 7/2/10. CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certto that all the information contained in this report is true,accurate,and in full compliance with legal requirements. Technician's Signature: Date: 06/16/2010 ' State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements may be more stringent. �# I Txly -(XWP 1AX[f WITWCGx1U " Invoice No.: 23200 9346 Fastrip #621 80534 1h Street Bakersfield, CA 93301 Repairs completed: Veeder-Root would not Re-boot after removing power for fail-safe. Investigation led to back-up battery. Replaced battery, recovered from archive and performed mapping for ISD. Finished monitoring system certification and notified Fire Department of results. Required Repairs, Still Pending: Regular#2 (Vapor— OPW) Spill Bucket needs to be replaced. Bucket has been ordered and is scheduled to be replaced 7/2/10. Technician Name: Garry DiMaggio Signature: Date: 6/28/2010