HomeMy WebLinkAbout2010 RESULTS 11111111111111111111 41 MONITORING SYSTEM CERTIFICATION
I For Use By All Jurisdictions Within the State of California
Authority Cited: Chapter 6 7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be
prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided
to the tank system owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems
within 30 days of this date.
A. General Information
Facility Name: #346 Fastrip#621 Bldg.No.:
Site Address: 805 34th Street City: Bakersfield Zip: 93301
Facility Contact Person: Omero Garcia Contact Phone No.: 661-393-7000
Make/Model of Monitoring System: Gllbarco EMC Date of Testing/Servicing: 06/16/2010
B. Inventory of Equipment Tested/Certified
Check the appropriate bola to indicate specific equipment inspected/serviced:
Tank ID: 12000 gal. Regular 1 Tank ID: 12000 gal.Regular 2
[X] In-Tank Gauging Probe. Model:847390-107 [x] In-Tank Gauging Probe. Model:847390-107
[x] Annular Space or Vault Probe. Model:794390-420 [x] Annular Space or Vault Sensor. Model: 794390-420
[x] Piping Sump/Trench Sensor(s). Model:794380-208 [x] Piping Sump/Trench Sensor(s). Model: 794380-208
❑ Fill Sump Sensor(s) Model: ❑ Fill Sump Sensor(s). Model:
[J Mechanical Line Leak Detector. Model:FX1v [x] Mechanical Line Leak Detector. Model: FX1v
❑ Electronic Line Leak Detector. Model: ❑ Electronic Line Leak Detector. Model:
[X] Tank Overfill/High Level Sensor. Model:847390-107 [x] Tank Overfill/High Leval Sensor. Model: 847390-107
❑ Other(specify equip.type and model in Sec.E on Pg.2) ❑ Other(specify equip.type and model in Sec. E on Pg.2)
Tank ID:_12000 gal.Super Tank ID: 12000 gal. Diesel
[x] In-Tank Gauging Probe. Model:847390-107 [J In-Tank Gauging Probe. Model:847390-107
[x] Annular Space or Vault Sensor. Model-Ronan [x] Annular Space or Vault Sensor. Model: 794390-420
[X] Piping Sump/Trench Sensor(s). Model:794380-208 [x] Piping Sump/Trench Sensor(s). Model: 794380-208
❑ Fill Sump Sensors(s). Model: ❑ Fill Sump Sensor(s). Model:
[
x� Mechanical Line Leak Decector. ModehRonan U Mechanical Line Leak Detector. Model: FX1Dy
❑ Electronic Line Leak Detector. Model: ❑ Electronic Line Leak Detector. Model:
[x] Tank Overfill/High Level Sensor. Model:847390-107 Tank Overfill/High Level Sensor.Model:847390-107
❑ Other(specify equip.type and model in Sec. E on Pg.2) ❑ Other(specify equip.typs and model in Sec. E on Pg.2)
Dispenser ID: 1 &2 Dispenser ID: 3&4
[x] Dispenser Containment Sensor(s). Model: 794380-208 [X] Dispenser Containment Sensor(s). Model: 794380-208
[x] Shear Valve(s). [x] Shear Valve(s).
❑ Dispenser Containment Float(s)and Chain(s). ❑ Dispenser Containment Float(s)and Chain(s)
Dispenser iD: 5&6 Dispenser ID: 7&8
Fx] Dispenser Containment Sensor(s). Model: 794380-208 [x] Dispenser Containment Sensor(s). Model: 794380-208
rx] Shear Valve(s). [, Shear Valve(s).
❑ Dispenser Containment Float(s)and Chains(s). ❑ Dispenser Containment Float(s)and Chain(s).
Dispenser ID: Trans.East Dispenser ID: Trans.West
rX1 Dispenser Containment Sensor(s). Model: 794380-208 N Dispenser Containment Sensor(s). Model: 794380-208
U Shear Valve(s). U Shear Valve(s).
❑ Dispenser Containment Float(s)and Chain(s) ❑ Dispenser Containment Float(s)and Chain(s).
*if the facility contains more tanks or dispensers,copy this form. Include information for every tank and dispenser at the facility.
C. Certification -i certify that the equipment identified in this document was inspected/services in accordance with the
manufacturers'guidlines.Attached to this Certification is information(e.g.manufacturers'checklist)necessary to varify that
this information is correct and a plot plan showing the layout of monitoring equipment.For equipment capable of generating
such reports,I have attached a copy of the report; (check all that apply) x❑System Set-up U Alarm history report
Technician Name(print): Garry Maggio Signature:
Certification No: 837939 License No:804904
Testing Company Name: Confldence UST Services,Inc. Phone No: 800-339-9930
Site Address: 805 34th Street,Bakersfield,CA 93301 I Illllllllllllll Ill/ —Date of Testing/Servicing: 06/16/2010
42
IE
A Results of Testing/Servicing
Software Version Installed: 327.04
Complete the following checklist:
Lx] Yes ❑ No* Is the audible alarm operational?
x Yes No* is t e Visua a arm operational?
x Yes Fj No* Were all sensors visually inspected,functionally tested,and confirmed operational?
x I Yes ❑ No* Were all sensors installed at the lowest point of secondary containment and positioned so that other
equipment will not interfere with their proper operation?
Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment(e.g.modem)
Hx N/A operational?
Fxj Yes ❑ No* For pressurized piping systems,does the turbine automatically shut down if the piping secondary
❑N/A containment monitoring system detects a leak,fails to operate,or is electrically disconnected?If yes:
which sensors initate positive shut-down? E Sump/Trench Sensors Lx]Dispenser Containment Sensors
Did you confirm positive shut-down due to leaks and sensor failure/disconnected? [X] Yes; ❑ No;
[X] Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device(i.e.no
❑N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visual and audible at
the tank fill point(s)and operating properly?If so,at what percent of tank capasity does the alarm
trigger? 90 %
Yes* ❑ No Was any monitoring equipment replaced?If Yes,identify specific sensors,probes, or other equipment
replaced and list the manufacturer name and model for all replacement parts in Section E,below.
❑ Yes* U No Was liquid found inside any secondary containment systems designed as dry systems?
❑ Product; ❑ Water. if yes, describe causes in Section E,below.
x No* Was monitoring system set-up reviewed to ensure proper settings?Attach set-up reports,if applicable.
x Yes No* I Is all monitoring equipment operational per manufacturer's specifications?
* In Section E below,discribe how and when these deficiencies were or will be corrected.
E. Comments' Monitoring System back-up battery was replaced. All information was restored from Archive Utility.
Diesel turbine would not shut off during testing. After investigation,corrected issue and positive shutdown is working
correctly on all STP's.
F. In-Tank Guaging/SIR Equipment: M Check this box if tank guaging is used only for inventory control.
❑ Check this box if tank guaging or SIR equipment is installed.
This section must be completed if in-tank guaging equipment is used to perform leak detection monitoring.
Complete the following checklist:
E Yes I ❑ No* Has all input wiring been inspected for proper enter and termination,including testing for ground faults?
x Yes No* Were all tank guaging probes visually inspected for damage and residue buildup?
x Yes No* Was accuracy of system product level readings tested?
x Yes No* Was accuracy of system water level readings tested?
_[xj Yes No* Were all probes reinstalled properly?
[�] Yes ❑ No* Were all items on the equipment manufacturer's maintenance checklist completed?
*In the Section H,below,describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD): ❑Check this box if LLD's are not installed.
Complete the following checklist:
Lx] Yes ❑ No* For equip. start-up or annual equipment certification,was a leak simulated to varify LLD performance?
(Check all that apply) Simulated leak rate: [X]3 g.p.h.: 00.1 g.p.h.; ❑0.2 g.p.h.;
x Yes No* Were all LLD's confirmed operational and accurate within regulatory requirments?
x Yes No Was the testing apparatus properly calibrated?
U Yes I No For machamca LLD's,does the LLD restrict product flow if it detects a leak?
N/A
❑ Yes No* For electronic LLD's,does the turbine automatically shut off if the LLD detects a leak?
[x] N/A
❑ Yes No* For electronic LLD's,does the turbine automatically shut off if any portion of the monitoring system is
[x] N/A disabled or disconnected?
❑ Yes No* For electronic LLD's,does the turbine automatically shut off if any portion of the monitoring system
Lx] N/A malfunction or fails a test?
❑ Yes No* For electronic LLD's,have all accessible wiring connections been visually inspected?
U N/A
Lx] Yes No Were all items on the equipment manufacturer's maintenance checklist completed?
* In the section H,below,describe how and when these deficiencies were or will be corrected.
H. Comments:
FASTRIP 346 ALARM HISTORY REPORT
805 34TH SMARTSENSOR DIAGNOSTIC
BKRSFLD.CA - ---- IN-TANK ALARM ----
661-325-0110 - - - - - - - -
JUN 16, 2010 9:35 AM
JUN'.16, -201,0 '9.:35 AM T 1 :UNLEAD 1
OVERFILL ALARM
s 1 :V.P'1-2 ' ?,} NOV 23, 2009 12:14 AM
j SEP 25. 2009 5:51 AM
SYSTEM STATUS REPORT VAPOR-PRESSURE SEP 25. 2009 5:06 AM
-
SERIAL NUMBER 1706
ALL FUNCTIONS NORMAL SUDDEN LOSS ALARM
INVENTORY REPORT JAN 19. 2010 3:12 AM
, JAN 8. 2010 3:31 AM
s 2:FM 1-2 JAN 6. 2010 10:48 AM
T 1 :UNLEAD 1 VAIR _FLOW- METER HIGH PRODUCT ALARM
VOLUME = 9167 GALS SERIAL' NUMBER 8448 JUN 19, 2008 8:52 AM
ULLAGE - 2895 GALS AUN-..13.. 2008_ 9:4,1 .AM
90% ULLAGE= 1688 GALS "JUN 19: 2007 8:50 AM
TC VOLUME = 9045 GALS
HEIGHT = 79.23 INCHES s 3:FM 3-4 INVALID FUEL LEVEL
WATER VOL - 0 GALS JAN 21. 2010 1 :53 AM
WATER = 0.00 INCHES AIR FLOW METER JAN 18, 2010 10:57 AM
TEMP - 79.0 DEG F 1 SERIAL NUMBER 8409 ' JAN 9. 2010 12:36 PM
( .r:? PROBE OUT
T 2:UNLEAD 2 JUN 18, 2009 10:24 AM
VOLUME = 9237 GALS. s 4:FM 5-6 SEP 29, 2008 11 :31 AM
ULLAGE = 2825 GALS SEP 29, 2008 11 :27 AM
90% ULLAGE= 1618 GALS AIR FLOW METER
TO VOLUME = 9106 GALS SERIAL NUMBER 84C)8 HIGH WATER WARNING
HEIGHT = 79.79 INCHES SEP 29, 2008 10:23 AM
WATER VOL = 0 GALS
WATER 0.00 INCHES .
TEMP 80. 1 DEG F s 5:FM 7-,8 I DELIVERY NEEDED
MAY 16, 2010 1 :16 PM
AIR FLOW
METER-APR 4. 2010 4:33 PM
T 3:PREMIUM i SERIAL NUHBER;r :'"8455 APR 1. 2010 3:08 PM
VOLUME.,. = 2471 GALS
ULLAGE 9591 GALS
90,% ULLAC:E= 8384 GALS i JUN E 2 25 AM P WARNING
TO VOLUME 2429 GALS
HEIGHT 28.81 INCHES SEP 29, 2008 11 :32 AM
WATER VOL 0.00 GALS o, SEP 29, 2008 11 :02 AM
WATER
TEMP 83.8 DEG F
T 4:DIESL
VOLUME = 2953 GALS
ULLAGE 9109 GALS
90% ULLAGE= 7902 GALS + ALARM HISTORY. REPORT'
TC VOLUME _ 2893 UALS
HEIGHT = 32.73 INCHES ----- SYSTEM,ALARM ----- * ;� * * x
WATER VOL - 14 GALS PAPER OUT END
WATER a 0.90 INCHES MAY 24, 2010 1 :17 AM
TEMP - 105.1 DEG F PR-INTER ERROR
MAY 24. 2010 1 :17 AM
MANIFOLDED TANKS
INVENTORY TOTALS
T I :UNLEAD l i
T 2:UNLEAD 2
VOLUME = 18404 GALS
TO VOLUME - 18151 GALS
R END x
* * )(,END �€
f'
SOFTWARE REVISION LEVEL
VERSION 327.04
SOFTWARE# 346327-100-E
CREATED - 07.02.06.10.28
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS '
ANNUAL IN-TANK TESTS '
ISD
PMC
ALARM HISTORY REPORT
ALARM H I STORY,RERORT....�- -ALARM HISTORY REPORT
---- IN-TANK ALARM ----- IN=TANK ALARM ----- ---- IN-TANK ALARM -----
T 2:UNLEAD 2
T 3:PREMIUM - - T 4:D1ESL
OVERFILL ALARM OVERFILL ALARM OVERFILL ALARM
APR 11 , 2010 3:08 AM
DEC 12, 2009 6:27 AM JUN 18, 2009 10:06 AM JUN 18. 2009 10:14 AM
.
DEC 12. 2009 6:12 AM JUN 18, 2009 10:01 AM
LOW PRODUCT ALARM
SUDDEN LOSS ALARM LOW PRODUCT ALARM JUN 18, 2009 9:18 AM
JUN 18, 2009 9:19 AM APR 23. 2009 6:51 `AM
HIGH PRODUCT ALARM
HIGH PRODUCT ALARM SUDDEN LOSS ALARM JUN 19, 2008 8:53 AM
JUN 19. 2008 8:52 AM JUN .18. 2009 9'19 Am JUN 13, 2008 9:45 AM
JUN 13. 2008 9:42 AM APR -23. 2009 6:20 AM JUN 19, 2007 8:52 AM
JUN 19, 2007 8:51 AM APR 23'. .2009 6:11 AM
INVALID FUEL LEVEL
PROBE OUT HIGH PRODUCT ALARM- JUN 18. 2009 10:20 AM
JUN 18, 2009 10:23 AM '.JUN .19. 2008 8:53 AM. JUN 18. 2009 9:18 AM
SEP 29, 2008 9:45 AM JUN 13, 2006 9:44 AM
SEP 29, 2008 9:23 AM JUN 19. 2007 8:51 AM.. PROBE OUT
JUN 18. 2009 10:19 AM
INVALID .FUEL LEVEL
DELIVERY NEEDED JUN 18, 2009 10:22 AM
MAY 16, 2010 1 : 19 PM APR .23. 2009 6:50 AM DELIVERY NEEDED
APR 4, 2010 5:05 PM JUN 2. 2010 6:38 PM
APR 1 , 2010 3:01 PM PROBE OUT MAY 7, 2010 10:06 AM
JUN 18. 2009 10:20 AM APR 28. 2010 8:43 PM
LOW TEMP WARNING DELIVERY NEEDED
JUN 18, 2009 10:23 AM r-JUN 12 2010 10:39 AM
JUN 18. 2009 9:21 AM .
SEP 29, 2008 9:45 AM i JUN, 2.- 2010 6-:20 PM
MAY 29, 2010 7:36 AM
END
END
END
i
ALARM HISTORY REPORT
----- SENSOR ALARM -----
L 1 :UNL 1 STP
STP SUMP
SENSOR OUT ALARM
JUN 18. 2009 9:38 AM
FUEL ALARM
JUN 18, 2009 9:24 AM
FUEL ALARM
JUN 17. 2009 9:16 AM
* * END
i ALARM HISTORY REPORT
FALARM HISTORY REPORT t ALARM H'1STOI/ REPORT
----- SENSOR ALARM -----
L 2:UNL 1 ANN ------ SENSOR ALARM ----- - --- SENSOR ALARM -----
ANNULAR SPACE L 4:UNL 2 ANN- L-6:PNL ANN
FUEL ALARM ANNULAR SPACE ' ANNULAR SPACE
JUN 18, 2009 9:51 AM FUEL ALARM SENSOR OUT ALARM
SENSOR OUT ALARM JUN 18, 2009 9:38 AM JUN 18, 2009 9:38 AM
JUN 18. 2009 9:38 AM FUEL ALARM
JUN 18.. 2009 9:29 AM FUEL ALARM
FUEL ALARM
JUN 18. 2009 9:28 AM
JUN 18. 2009 9:30 AM FUELI7LAR009 9:12 AM' FUEL ALARM
JUN 17, 2009 9:12 AM
* * END
END X X-END * x x x
ALARM HISTORY REPORT
ALARM HISTORY REPORT ALARM HISTORY REPORT
----- SENSOR ALARM -----
L 3:UNL 2 STP ----- SENSOR ALARM ----- ----- SENSOR ALARM -----
STP SUMP L 5:PNL .STP L 7:DSL STP
SENSOR OUT ALARM STP SUMP STP SUMP
JUN 18, 2009 9:38 AM SENSOR OUT ALARM SENSOR OUT ALARM
JUN 18. 2009 -9:38 AM JUN 1.8. 2009 9:38 AM
FUEL ALARM
JUN 18, 2009 9:25 AM FUEL ALARM FUEL ALARM
JUN 18, 2009 9:26 AM
FUEL ALARM JUN 1.8, 2009 9:27 AM
JUN 17, 2009 9:16 AM { FUEL ALARM 9:t5 AM FUEL ALARM
f JUN 17, 2009 9:15 AM
i
>4 * * X * END * xx * 9
XXxXxEND x * END X
ALARM HISTORY REPORT ALARM HISTORY REPORT.
----- SENSOR ALARM ----- ALARM HISTORY REPORT
L 8:DSL ANN ___-- SENSOR ALARM --
--- ----- SENSOR ALARM -----
ANNULAR SPACE L12:DISP 7-8
SENSOR OUT ALARM •L10:DISE 3-4 —DISPENSER PAN
JUN 18, 2009 9:38 AM DISPENSER PAN , SENSOR OUT ALARM
FUEL A'ARM JUN 18, 2009 9:38 AM
FUEL ALARM I JUN 30, 2009 10:24 AM
JUN 18. 2009 9:28 AM I SENSOR OUT ALARM (FUEL ALARM
JUN 18, 2009 9:38 AM JUN 18. 2009 9:32 AM
FUEL ALARM f'FUEL ALARM
JUN 17. 2009 9:12 AM FUEL ALARM
JUN 18.. 2009 . :9:31 AM JUN 17. 2009 9:20 AM
END
* END x * * * END. XXxx *
a
ALARM HISTORY REPORT
ALARM HISTORY REPORT ALARM HISTORY REPORT
----- SENSOR ALARM -----
L 9:DISP 1-2 ----- SENSOR ALARM ----- ----- SENSOR ALARM -----
DISPENSER PAN i L11 :DISP 5-6 L13:E. TRANS SUMP
SENSOR OUT ALARM I DISPENSER PAN ! PIPING SUMP
JUN 18, 2009 9:38 AM SENSOR OUT ALARM ( SENSOR OUT ALARM
FUEL ALARM JUN 18. 2009 9:38 AM IJUN 18, 2009 9:38 AM
JUN 18. 2009 9:31 AM I FUEL ALARM (FUEL ALARM
I JUN 18. 2009 932 AM IJUN 18. 2009 9:33 AM
FUEL ALARM
JUN 17, 2009 9:19 AM FUEL ALARM ' FUEL ALARM
! JUN 17. 2009 9:20 AM IJUN 17. 2009 9:20 AM
i x * * END .XXxXx
END x X � � � * � END
ALARM HISTORY REPORT l SYSTEM SETUP
-- SENSOR ALARM ----- JUN 16. 2010 9:37 AM COMMUNICATIONS SETUP
L14:W. TRANS SUMP — — — — — — — — — — — —
PIPING SUMP
SENSOR OUT ALARM
JUN 18, 2009 9:39 AM SYSTEM UNITS PORT SETTINGS:
U:S...- o. _ ._ .
FUEL ALARM SYSTEM LANGUAGE COMM BOARD : I (EDIM )
JUN 18, 2009 9:33 AM ENGLISH RS-232 SECURITY
SYSTEM DATE./TIME. FORMAT CODE : DISABLED
FUEL ALARM MON DD YYYY HH:MM:SS xM
JUN 17, 2009 9:19 AM COMM BOARD 2 (RS-232) -
FASTRIP 346 BAUD RATE 9600
805 34TH - PARITY NONE
BKRSFLD.CA STOP BIT 1 STOP
661-325-01.10 DATA LENGTH:. 8 DATA
, SHIFT TIME 1 6c00 AM CODE3 : DISABLED
SHIFT TIME 2.. DISABLED
SHIFT TIME 3 DISABLED COMM BOARD 3 (RS-232)
' SHIFT TIME 4 :- DISABLED BAUD RATE 9600
PA
END * * * * * : TANK PER TST NEEDED WRN STOPTBIT NONE STOP
iDISABLED DATA LENGTH: 8 DATA
TANK ANN TST NEEDED WRN RS-232 SECURITY
DISABLED CODE : DISABLED
LINE RE—ENABLE METHOD
PASS LINE TEST AUTO TRANSMIT SETTINGS:
LINE PER TST.NEEDED WRN AUTO LEAK ALARM LIMIT
DISABLED DISABLED
LINE ANN TST NEEDED WRN AUTO HIGH WATER LIMIT
DISABLED DISABLED
ALARM HISTORY REPORT AUTO OVERFILL LIMIT
PRINT TC VOLUMES DISABLED
----- SENSOR ALARM ----- ENABLED AUTO LOW PRODUCT
L15: DISABLED
OTHER SENSORS ; TEMP COMPENSATION AUTO THEFT LIMIT
, VALUE (DEG F ) : 60.01 DISABLED
STICK HEIGHT OFFSET AUTO DELIVERY START
DISABLED DISABLED
ULLAGE: 90Y AUTO DELIVERY END
DISABLED
iH—PROTOCOL DATA FORMAT AUTO EXTERNAL INPUT ON
HEIGHT DISABLED
DAYLIGHT SAVING TIME AUTO EXTERNAL INPUT OFF
ENABLED DISABLED
END * * START DATE AUTO SENSOR FUEL ALARM,
. MAR WEEK 2 SUN DISABLED
, START TIME AUTO SENSOR WATER ALARM
2:00 AM DISABLED
END DATE AUTO SENSOR OUT ALARM
NOV WEEK 1 SUN DISABLED
END TIME
2:00 AM
RE—DIRECT LOCAL PRINTOUT
DISABLED
, EURO PROTOCOL PREFIX
S
RS=232 END OF MESSAGE
DISABLED
SYSTEM SECURITY
CODE : 000000
MAINTENANCE HISTORY
DISABLED
TANK CHART SECURITY
DISABLED
CUSTOM ALARMS
DISABLED
MASS/DENSITY
DISABLED
IN-TANK SETUP T 2:UNLEAD 2 i T 3:PREMIUM
_ - - - - - - - PRODUCT CODE 2 PRODUCT CODE 3 THERMAL COEFF THERMAL COEFF : .000700
:.000700
T 1 :UNLEAD 1 TANK DIAMETER :' 111 .50 . TANK DIAMETER 111 .50
PRODUCT CODE 1 TANK PROFILE i PT TANK PROFILE 1 PT
THERMAL COEFF : .000700 FULL VOL, k 062 FULL VOL 12062
TANK DIAMETER 111 .50
TANK PROFILE
FULL VOL 12062 FLOAT SIZE. 4.0 IN. FLOAT SIZE: 4.0 IN.
4.0 IN. WATER WARNING 2.0 WATER WARNING 2.0
FLOAT SIZE: HIGH WATER LIMIT: 3.0 HIGH WATER -LIMIT' 3.11
WATER WARNING : 2.0 MAX OR LABEL VOL'-. 12062 MAX OR LABEL VOL: 1206',
HIGH WATER LIMIT: 3.0 OVERFILL LIMIT 10955 OVERFILL LIMIT 10855
MAX OR LABEL VOL: 12062 HIGH PRODUCT 95% HIGH PRODUCT 95%
OVERFILL LIMIT 90% 11459 11459
10855 DELIVERY LIMIT. 15% ; DELIVERY LIMIT 15%
HIGH PRODUCT 95% 1809' 1809
11459
DELIVERY LIMIT 15% LOW PRODUCT 500 ' LOW PRODUCT 500
1809 LEAK ALARM LIMIT: 99 LEAK ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 99 SUDDEN LOSS LIMIT: 99
LOW PRODUCT 500 TANK TILT 0.00 TANK TILT 1 .40
LEAK ALARM LIMIT: 99 PROBE OFFSET 0.00 PROBE-OFFSET 0.00
SUDDEN LOSS LIMIT: 5. 0
TANK TILT 2 2.5
PROBE OFFSET 0.00 SIPHON MANIFOLDED TANKS SIPHON MANIFOLDED TANKS
T#: NONE T#: NONE
LINE MANIFOLDED TANKS LINE MANIFOLDED TANKS
SIPHON MANIFOLDED TANKS T#: 01 -T#:.__NONE._
T#: NONE
LINE MANIFOLDED TANKS
T#: 02 LEAK MIN PERIODIC: 1% LEAK MIN PERIODIC: 0%
120 0
PERIODIC TEST TYPE PERIODIC 'TEST TYPE
LEAK MIN PERIODIC: 120 STANDARD STANDARD
PERIODIC TEST TYPE PERIODIC TEST FAIL PERIODIC TEST FAIL
STANDARD ALARM DISABLED ALARM DISABLED
PERIODIC TEST FAIL GROSS TEST FAIL GROSS TEST FAIL
ALARM DISABLED ALARM, DISABLED ALARM DISABLED
GROSS TEST FAIL PER TEST AVERAGING: OFF PER TEST AVERAGING: OFF
ALARM DISABLED
TANK TEST NOTIFY: OFF
PER TEST AVERAGING: OFF TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF TNK TST SIPHON HREAK:OFF
TANK TEST NOTIFY:` OFF DELIVERY DELAY 1 MIN DELIVERY DELAY 1 MIN
TNK TST SIPHON BREAK:OFF PUMP THRESHOLD 10.00°%, PUMP THRESHOLD 10.00%
i£L l;uEkY !>wLF+''�' 1
MIN,, j
p0mr, THRESHOLD
-T A:DIESL -
PRODUCT CODE q -
THERMAL COEFF : .000450 PUMP SENSOR SETUP
TANK DIAMETER 111 .5i'
TANK PROFILE 1 P7' LIQUID SENSOR SETUP
- - - - - - - - - - - -
_ _ _ _ _ _
FULL VOL 12062 - _ ;_..S_lL:.UNLEAD ,1
L I :UNL 1 STP TANK fit: 1
FLOAT SIZE: 4.0 IN. TRI-STATE (SINGLE FLOAT) DISPENSE MODE:
CATEGORY STP SUMP MANIFOLDED: ALTERNATE
WATER WARNING 2.0 S 2:PREMI.UM
HIGH WATER LIMIT: 3.0 L 2:UNL. 1 ANN - TANK # 3
MAX OR LABEL VOL: 12062 TRI-STATE (SINGLE FLOAT) DISPENSE MODE:
OVERFILL LIMIT 90% CATEGORY ANNULAR SPACE STANDARD
10855
HIGH PRODUCT 95% i
11459 L 3:UNL 2 STP
DELIVERY LIMIT 15% TRI-STATE (SINGLE FLOAT)
1809 CATEGORY STP SUMP
LOW PRODUCT 500 f
LEAK ALARM LIMIT: 99 L 4:UNL 2 ANN
SUDDEN LOSS LIMIT: 99 NORMALLY CLOSED
TANK TILT 0.00 CATEGORY : ANNULAR SPACE
PROBE OFFSET 0.00 OUTPUT RELAY SETUP
SIPHON MANIFOLDED TANKS L 5:PNL STP R 1 :UNL 1
T#: NONE j TRI-STATE (SINGLE FLOAT) TYPE:
LINE MANIFOLDED TANKS CATEGORY : STP SUMP PUMP CONTROL OUTPUT
T#: NONE j TANK #: 1
LEAK h1 I N PER f OD I C: 0� L 6:PNL ANN
0 TRI-STATE (SINGLE FLOAT) LIQUID SENSOR ALMS
PERIODIC TEST TYPE CATEGORY : ANNULAR SPACE L 1 :FUEL ALARM
STANDARD L 3:FUEL ALARM
L 9:FUEL ALARM
PERIODIC TEST FAIL L10:FUEL ALARM
L 7:DSL STP L1I :FUEL ALARM
ALARM DISABLED TRI-STATE (SINGLE FLOAT) L12:FUEL ALARM
GROSS TEST FAIL CATEGORY : STP SUMP L 1 :SENSOR OUT ALARM
ALARM DISABLED L 3:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
PER TEST AVERAGING: OFF ; L 8:DSL ANN L10:SENSOR OUT ALARM
i TRI-STATE (SINGLE FLOAT) L11 :SENSOR OUT ALARM
TANK. TEST NOTIFY: OFF CATEGORY : ANNULAR SPACE L12:SENSOR OUT ALARM
L 1 :SHORT ALARM
TNK TST SIPHON BREAK:OFF L 3:SHORT ALARM
L 9:SHORT ALARM
DELIVERY DELAY 1 MIN L 9:DISP 1-2 L10:SHORT ALARM
PUMP THRESHOLD 10.00% TRI-STATE (SINGLE FLOAT) L11 :SHORT ALARM
CATEGORY : DISPENSER PAN L12:SHORT ALARM
! ISD SITE ALARMS
ISD GROSS PRES FAIL
L10:DISP 3-4 1 ISD DEGRD PRES FAIL
TRI-STATE (SINGLE FLOAT) ISD VAPOR LEAK FAIL
CATEGORY : DISPENSER PAN ISD VP PRES FAIL
ISD SETUP FAIL
ISD SENSOR OUT FAIL
L11 :DISP 5-6 ISD HOSE ALARMS
TRI-STATE (SINGLE FLOAT) ALL:GROSS COLLECT FAIL
LEAK TEST METHOD CATEGORY : DISPENSER PAN ALL:DEGRD COLLECT FAIL
_ - - - - _ _ _ - _ - ALL:FLOW COLLECT FAIL
TEST ON DATE : ALL TANK
FEB 6. 2007 L12:DISP 7-8
START TIME : DISABLED TRI-STATE (SINGLE FLOAT)
TEST RATE :0.20 GAL/HR CATEGORY : DISPENSER PAN
DURATION 2 HOURS
TST EARLY STOP:DISABLED
LEAK TEST REPORT FORMAT L13:E. TRANS SUMP
NORMAL i �TRI-STATE' (SINGLE FLOAT)
CATEGORY : PIPING SUMP
i
L14:W. TRANS SUMP
TRI-STATE (SINGLE FLOAT)
CATEGORY PIPING SUMP
R 2:UNL 2
PUMP CONTROL OUTPUT ; R 4:DS1
TANK #: 2 `
, . TYPE: EVR/ISD 'SETUP
STANDARD
LIQUID SENSOR ALMS f
NORMALLY-CLOSED
L 1 :FUEL ALARM TANK #: .NONE EVR TYPE: .VACUUM ASSIST
L 3:FUEL ALARM VACUUM ASSIST TYPE
L 9:FUEL ALARM HEALY VAC
L10:FUEL ALARM LIQUID SENSOR ALMS
LII :FUEL ALARM L 7:FUEL ALARM NOZZLE A/L RANGE
L12:FUEL ALARM i :, _L10:FUEL ALARM (( MAX: 1 .15 MIN: 0,95
L 1 :SENSOR OUT ALARM L1:2:FUEL ALARM i I
L 3:SENSOR OUT ALARM L13:FUEL ALARM I VAPOR PROCESSOR TYPE
L 9:SENSOR OUT ALARM L14:FUEL ALARM NO VAPOR PROCESSOR
LIO:SENSOR OUT ALARM L 7:.SENSOR OUT ALARM
L11 :SENSOR OUT ALARM L10:SENSOR 2OUT ALARM
L12:SENSOR OUT ALARM z. L12:SENSOR OUT ALARM ANALYSIS TIMES
L 1 :SHORT ALARM t L13:SEN2OR OUT ALARM TIME: 10:00 AM
L 3:SHORT ALARM LI-4:SENSOR -OUT ALARM DELAY MINUTES: 1
L 9:SHORT ALARM L 7:SHORT ALARM
LIO:SHORT ALARM 1_10:SHORT ALARM
LII :SHORT ALARM L12:8HORT ALARM ACCEPT HIGH ORVR:
L12:SHORT ALARM L1.3::SHORT ALARM DISABLED
ISD SITE ALARMS L-1,4•:SHORT ALARM
I•SD HOSE TABLE
ISD GROSS PRES FAIL R• 5:OVERFILL ALARM ID FP FL HL AA RR
ISD D£GRD PRES FAIL TYPE: ---- ---------------------
ISD VAPOR LEAK FAIL STANDARD 01 01 01 02 01 UU
ISD VP PRES FAIL NORMALLY OPEN 02 02 02 02 01 UU
ISD VP STATUS FAIL { 03 03 03 02 02 UU
ISD SETUP FAIL TANK #: NONE 04 04 04 02 02 UU
ISD SENSOR OUT FAIL t 05 05 05 02 03 UU
i 06 06 06 02 03 UU
ISD HOSE ALARMS ` IN-TANK ALARMS 07 07 07 02 04 UU
ALL:GROSS COLLECT FAIL ALL,OVERFILL ALARM 08 08 08 02 04 UU
ALL:DEGRD COLLECT FAIL ALL:HIGH PRODUCT ALARM
ALL:FLOW COLLECT FAIL ALL:MAX PRODUCT ALARM
ISD AIRFLOW METER MAP
R 3:PNL ID SERIAL NUM LABEL
TYPE: = -----------------------•-
PUMP CONTROL OUTPUT I 1 8448 FM 1-2
TANK #: 3 2 8409 FM 3-4
3 8408 FM 5-6
4 8455 FM 7-6 !
LIQUID SENSOR ALMS
L 5:FUEL ALARM I
L 9:FUEL ALARM - ? ISD FUEL GRADE HOSE' HAP
L10:FUEL ALARM • 1 2 3 4
L11 :FUEL ALARM SMARTSENSOR SETUP FP MHH MHH MHH MHH AA
_. L12:FUEL ALARM , `i _ _ ._ _ _ _ _ - -------------------------
L 5:SENSOR--OUT
'A ` � T `" - - 01 201 901 301 U U l
L• 9:SENSOR.C06V"ALA s 1 :V.P 1-2 02 202 902 302 U U 1
LL048EN8OR OUT ALARM CATEGORY VAPOR PRESSURE 03 203 903 303- 5 U 2
LI I :SENSOR OUT ALARM ` 04 204 904 304 5 U 2
L12:SENSOR OUT ALARM s 2:FM 1-2 05 205 905 305 U U 3
L. 5:SHORT ALARM ,: CATEGORY AIR FLOW METER 06 206 906 306 U U 3
L 9:SHORT ALARM I 07 207 907 307 5 U' 4
L10:SHORT ALARM s 3:FM 3-4 08 208 908 308 5 U 4
L11 :SHORT ALARM f CATEGORY AIR FLOW METER
L12:SHORT ALARM
s 4:FM 5-6 I` LABEL TABLE
ISD SITE ALARMS , CATEGORY AIR FLOW METER ------------------------
ISD GROSS PRES FAIL 1 : UNASSIGNED
ISD DEGRD PRES FAIL s 5:FM 7-8 2: BLEND3
ISD VAPOR LEAK FAIL CATEGORY AIR FLOW METER 3: REGULAR
ISD VP PRES FAIL 4: MID GRADE
ISD VP STATUS FAIL 5: PREMIUM
ISD SETUP FAIL 6: GOLD
ISD SENSOR OUT FAIL 7: BRONZE
ISD HOSE ALARMS 9: BL.END2
ALL:GROSS COLLECT FAIL > ; 10: BLEND4
ALL:DEGRD COLLECT .FAIL
ALL:FLOW COLLECT FAIL
PMC SETUP
PROCESSOR CONTROL LEVEL:
NONE
SENSOR ALARM -----
----= SENSOR ALARM L12:DISP 7-8
ARCHIVE UTILITY L 6:DSL ANN DISPENSER PAN
ANNULAR SPACE FUEL ALARM
SAVE SETUP DATA: FUEL ALARM i JUN 16. 2010 1 :48 PM
START TIME: JUN 16. 2010 1 :38 PM
JUN 16, 2010 1 :21 :30 PM
i
----- SENSOR ALARM -----
----- SENSOR ALARM ----- L14:W. TRANS SUMP
L 6:PNL'-ANN PIPING SUMP
ANNULAR SPACE FUEL ALARM
ARCHIVE UTILITY FUEL ALARM JUN 16. 2010 1 :49 PM -
ARCHIVE — — — — — — JUN 16, 2010• 1 :39 PM
SAVE SETUP DATA: —
END TIME:
JUN 16, 2010 1 :24:00 PM
BYTES 19200 s
i
r
y
----- SENSOR ALARM -----
-- SENSOR ALARM ----- i L13-E. TRANS SUMP
L 4:UNL 2 ANN PIPING SUMP
ANNULAR SPACE FUEL ALARM
FUEL 16 ARM 1 :41 PM JUN 16. 2010 1 :49 PM
JUN----- SENSOR ALARM -----
L 1 :UNL 1 STP
STP SUMP
FUEL ALARM i
JUN 16. 2010 1 :31 PM
----- SENSOR ALARM -----
-- SENSOR ALARM ----- L 5:PNL STP
L 2:UNL 1 ANN ' STP SUMP
ANNULAR SPACE SENSOR OUT ALARM
FUNL16 A 010 1 :42 PM JUN 16. 2010 1 :51 PM
----- SENSOR ALARM -----
L 3:UNL 2 STP
STP SUMP
FUEL ALARM
JUN. 16, 2010 1 :32 PM
----- SENSOR ALARM -----
----- SENSOR ALARM ----- L 1 :UNL 1„STP
L10:DISP 3-4 STP SUMP
s DISPENSER PAN SENSOR OUT. ALARM
FUNL16.ALARM 1 :44 PM JUN 16. 2010 1 :51 PM
---- SENSOR ALARM -----
L 5:PNL STP
STP SUMP
FUEL ALARM
JUN 16, 2010 1 :33 PM
----- SENSOR ALARM —.----
----- SENSOR ALARM ----- L 7:DSL STP
L 9:DISP 1-2 i STP SUMP
DISPENSER PAN i SENSOR OUT ALARM
FUEL ALARM JUN 16, 2010 1 :51 PM
JUN 16, 2010 1 :46 PM
I
----- SENSOR ALARM -----
L 7:DSL STP
STP SUMP
FUEL ALARM
JUN 16. 2010 1 :34 PM
----- SENSOR ALARM -----
-- SENSOR ALARM ----- L 2:UNL 1 ANN
I.11 :D I SP 5-6 ANNULAR SPACE
DISPENSER PAN., SENSOR OUT ALARM
FUEL ALARM JUN 16, 2010 1 :51 PM
JUN•. 16.. 2010 V 47°
-- SENSOR ALARM
L 8:DSL ANN
ANNULAR SPACE -- SENSOR ALARM :-=--- J SENSOR OUT ALARM L13:E. TRANS SUMP FARTRIP 346 JUN 16. 2010 1 :51 PM PIPING SUMP 805 34TH SENSOR OUT ALARM BAKERSFIELD.CA
JUN 16. 2010 1 :51 PM 661-325-0110
JUN 16. 2010 1 :55 PM
SYSTEM STATUS REPORT
----- SENSOR ALARM ----- ALL FUNCTIONS NORMAL
L 9:DISP 1-2 ----- SENSOR ALARM -----
DISPENSER PAN L 6:PNL ANN
SENSOR OUT ALARM { ANNULAR SPACE
JUN 16, 2010 1 :51 PM SENSOR OUT ALARM
JUN 16. 2010 1 :51 PM
--- IN-TANK ALARM -----
T 3:PREMIUM
HIGH PRODUCT ALARM
JUN 16, 2010 1 :55 PM
----- SENSOR ALARM -----
L10:DISP 3-4 ---- SENSOR ALARM ----=
DISPENSER PAN L14,:W. TRANS SUMP
SENSOR OUT ALARM PIPING SUMP
JUN 16. 2010 1 :51 PM SENSOR OUT ALARM
JUN 16, 2010 1 :51 PM
FARTRIP 346
805 34TH
BAKERSFIELD.CA
661-325-0110
----- SENSOR ALARM ----- JUN 16. .2010 1 :56 PM
L 3:UNL 2 STP ---- IN-TANK ALARM -----
STP SUMP T 1 :UNLEADED 1
SENSOR OUT ALARM HIGH PRODUCT ALARM SYSTEM STATUS REPORT
JUN 16, 2010 1 :51 PM JUN 16, 2010- 1 :53 PM - - - - - - - - - - -ALL FUNCTIONS NORMAL
-- SENSOR ALARM ----- FARTRIP 346
L11 :DISP 5-6 805 34TH ---- IN-TANK ALARM -- --
DISPENSER PAN BAKERSFIELD.CA T 4:DIESEL
SENSOR OUT ALARM 661-325-0110 HIGH PRODUCT ALARM
JUN 16. 2010 1 :51 PM JUN 16. 2010 1 :56 PM
,. JUN 16 2010 1 :54 PM
SYSTEM STATUS REPORT
- ALL FUNCTIONS NORMAL -
-- SENSOR ALARM ----- FARTRIP 346
L 4:UNL 2 ANN 805 34TH
ANNULAR SPACE BAKERSFIELD.CA
FUEL ALARM 661-325-0110
JUN 16, 2010 1 :51 PM
JUN 16, 2010 1 :56 PM
---- IN-TANK ALARM-----
T 2:UNLEADED 2 .
HIGH PRODUCT ALARM SYSTEM STATUS REPORT
JUN 16, 2010 1 :54 PM - - - - - -- - - - - -
ALL FUNCTIONS NORMAL.
----- SENSOR ALARM - --
L12:DISP 7-6
DISPENSER PAN
SENSOR OUT ALARM
JUN 16. 2010 1 :51 PM
SYSTEM SETUP
ARCHIVE UTILITY _JUN 16. 2010. 2:23 PM COMMUNICATIONS SETUP
SAVE SETUP DATA:
START TIME:
MIN 16. 2010 2:07:06 PM SYSTEM UNITS - � 1 PORT SETTINGS:
U.S. l COMM BOARD : I (EDIM )
SYSTEM...LANGUAGE _.__; [ _RS-232 SECURITY
'ENGL SH - CODE : DISABLED
SYSTEM-'DATE/TIME 'FORMAT
t-'=MOW"HD='f'�"s'4'`'H11'�MMYSB iiP4 COMM BOARD 2 (RS-232)
FARTRIP 346 BAUD RATE 9600
805 34TH PARITY NONE
805 34TH STOP BIT 1 STOP
661-32IELD- DATA LENGTH: 8 DATA
RS-232 SECURITY
ARCHIVE UTILITY CODE : DISABLED
SHIFT TIME i 6:00 AM
SAVE SETUP DATA: SHIFT TIME 2. :. DISABLED COMM BOARD 3 (RS-232)
END TIME: SHIFT TIME 3 :: DISABLED BAUD RATE 9600
JUN 16, 2010 2:09:37 FM SHIFT TIME 4 DISABLED PARITY NONE
BYTES 19328 TANK PER TST NEEDED WRN STOP BIT 1 STOP
DISABLED DATA LENGTH: B DATA
TANK ANN TST NEEDED WRN ODE : SECURITY
C
-DISABLED CODE DISABLED
LINE RE-ENABLE METHOD AUTO TRANSMIT SETTINGS:
PASS LINE TEST
LINE PER TST NEEDED WRN AUTO LEAK ALARM LIMIT
DISABLED DISABLED
LINE ANN TST NEEDED WRN AUTO HIGH WATER LIMIT
DISABLED DISABLED
FARTRiP 346 AUTO dVERFILL LIMIT
805 34TH PRINT TC VOLUMES DISABLED
BAKERSFIELD.CA ENABLED AUTO LOW PRODUCT
661-325-0110 DISABLED
JUN 16, 2010 2:23 PM TEMP COMPENSATION AUTO THEFT LIMIT
VALUE (DEG F ) : 60,0 AUTO-DELIVERY 4
START
STICK HEIGHT OFFSET AUTO DELIVER!
DISABLED DISABLED
SYSTEM STATUS REPORT ULLAGE: 90d- DISABLED
DELIVERY END
_ DISABLED
ALL FUNCTIONS NORMAL H-PROTOCOL DATA FORMAT AUTO EXTERNAL INFUT ON
HEIGHT DISABLED
DAYLIGHT SAVING TIME AUTO EXTERNAL INPUT OFF
ENABLED
DISABLED
START DATE AUTO SENSOR FUEL ALARM
MAR WEEK 2 SUN DISABLED
START TIME AUTO SENSOR WATER ALARM
2 DISABLED
:00 AM
END DATE AUTO SENSOR OUT ALARM
OCT WEEK 1 SUN DISABLED
END TIME
2:00 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
EURO PROTOCOL PREFIX i
S RS-232 END- OF MESSAGE
DISABLED
SYSTEM SECURITY
CODE : 000000
MAINTENANCE HISTORY-
DISABLED
TANK CHART SECURITY
DISABLED
CUSTOM ALARMS
DISABLED
MASS/DENSITY
DISABLED
IN-TANK SETUP
- - - - - - - - - - T 2:UNLEADED 2 i T 3:PREMIUM
PRODUCT CODE 2 PRODUCT CODE 3
T 1 :UNLEADED 1 I THERMAL-'*COEFF µ :.000700 •= THERMAL COEFF : .000700
PRODUCT CODE TANK DIAMETER 111 .50 TANK DIAMETER 111 .50
THERMAL COEFF : .000700 TANK PROFILE 1 PT . TANK PROFILE 1 PT
TANK DIAMETER 11
TANK PROFILE 1 PT FULL VOL 12062 FULL VOL 12062
I
FULL VOL 12062
FLOAT SIZE: 4.0 IN. FLOAT SIZE: 4.0 IN.
FLOAT SIZE: 4.0 IN. WATER WARNING 2.0 WATER WARNING 2.0
WATER WARNING 2.0 HIGH WATER LIMIT: 3.0 HIGH WATER LIMIT: 3.0
HIGH WATER LIMIT: 3.0 MAX OR LABEL VOL: 12062 MAX OR LABEL VOL: 12062
MAX OR LABEL VOL: 12062 OVERFILL LIMIT : 90% OVERFILL LIMI-T ' 90.04.1
OVERFILL LIMIT 90% HIGH -PRODUCT 10855 5 % HIGH PRODUCT 10955"
10855
HIGH PRODUCT 95% DELIVERY LIMIT 11159 DELIVERY LIMIT 1115%
11459 1809 1809
DELIVERY LIMIT 1809
LOW PRODUCT 500 LOW PRODUCT 500
LOW PRODUCT 500 LEAK ALARM LIMIT: 99 LEAK ALARM LIMIT: 99
LEAK ALARM LIMIT: 99 SUDDEN LOSS LIMIT: 99 SUDDEN LOSS LIMIT: 99
SUDDEN LOSS LIMIT: 99 TANK TILT 0.00 TANK TILT 1 .40
TANK TILT 2.50 PROBE OFFSET 0.00 PROBE OFFSET 0.00
-PROBE OFFSET 0.00
SIPHON MANIFOLDED TANKS SIPHON MANIFOLDED TANKS
SIPHON MANIFOLDED TANKS T#: NONE ' TI: NONE
LINE MANIFOLDED TANKS LINE MANIFOLDED TANKS
TO NONE TO: 01 TO: NONE
LINE MANIFOLDED TANKS
TO: 02
LEAK MIN PERIODIC: 1% LEAK MIN PERIODIC: i%
120 120
LEAK MIN PERIODIC: 120 PERIODIC TEST TYPE PERIODIC TEST TYPE
PERIODIC TEST TYPE STANDARD STANDARD
STANDARD PERIODIC TEST FAIL PERIODIC TEST FAIL
PERIODIC TEST FAIL ALARM DISABLED ALARM DISABLED
ALARM DISABLED GROSS TEST FAIL GROSS TEST FAIL
GROSS TEST FAIL ALARM DISABLED ALARM DISABLED
ALARM DISABLED PER TEST AVERAGING: OFF PER TEST AVERAGING: OFF
PER TEST AVERAGING: OFF TANK TEST NOTIFY: OFF TANK TEST NOTIFY: OFF
TANK TEST NOTIFY: OFF TNK TST SIPHON BREAK:OFF TNK TST SIPHON BREAK:OFF
TNK TST SIPHON BREAK:OFF DELIVERY DELAY 1 MIN DELIVERY DELAY I MIN t
DELIVERY DELAY 1 MIN PUMP THRESHOLD 10.00 PUMP THRESHOLD 10.00%
PUMP THRESHOLD 10.00%
T 4:DIESEL -LIQUID SENSOR SETUP --- - --� -_
PRODUCT CODE 4 - - - - - - - - - - - -
THERMAL COEFF : .000450 PUMP SENSOR SETUP
TANK DIAMETER 111 .50 L I :UNL 1 STP - - - - - - - - - -
TANK PROFILE 1 PT TRI-STATE -(SINGLE FLOAT)
FULL VOL 12062 CATEGORY STP SUMP• S>-I-:UNL-EADED 1
TANK 0: 1
DISPENSE MODE:
FLOAT SIZE: 4.0 IN. L 2:UNL 1 ANN MANIFOLDED: ALTERNATE
TRI-STATE' (SINGLE FLOAT)
WATER WARNING 2.0 CATEGORY ANNULAR-SPACE S 2:PREMIUM
HIGH WATER LIMIT: 3.0 TANK #: 3
MAX OR LABEL VOL: 12062 DISPENSE MODE:
OVERFILL LIMIT 90% L 3:UNL 2 STP STANDARD
10855 TRI-STATE. .(SINGLE ,FLOAT),.
HIGH PRODUCT 95% CATEGORY- 'STP-SUMP `_
11459
DELIVERY LIMIT 151%
. 1809 L 4:UNL 2 ANN
NORMALLY CLOSED
LOW PRODUCT 500 CATEGORY :. ANNULAR- SPACE
LEAK ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 99
TANK TILT 0.20
PROBE OFFSET 0.00 L 5:PNL STP OUTPUT RELAY SETUP
- TRI-STATE (SINGLE FLOAT) - - - - - - - - - - _ -
CATEGORY :. STP SUMP
SIPHON MANIFOLDED TANKS R 1 :UNL 1
TO: NONE TYPE:
LINE MHNIFOLDED TANKS L 6:PNL ANN PUMP CONTROL-OUTPUT
T#: NONE TRI-STATE (SINGLE FLOAT) TANK 0: 1
CATEGORY : ANNULAR SPACE
LEAK MIN PERIODIC: 0% LIQUID SENSOR ALMS
0 L 1 :FUEL ALARM
PERIODIC TEST TYPE L 7:DSL STP L 3:FUEL ALARM
STANDARD TRI-STATE (SINGLE FLOAT) L 9:FUEL ALARM
E CATEGORY : STP SUMP
L10:FUEL ALARM
PERIODIC TEST FAIL Lll :FUEL ALARM
ALARM DISABLED L12:FUEL ALARM
L B:DSL ANN L I :SENSOR OUT ALARM
GROSS TEST FAIL TRI-STATE '(SINGLE FLOAT) L 3:SENSOR OUT ALARM
ALARM DISABLED CATEGORY ANNULAR SPACE L 9:SENSOR OUT ALARM
PER TEST AVERAGING: OFF L10:SENSOR OUT ALARM
Lll :SENSOR OUT ALARM
L12:SENSOR OUT ALARM
TANK TEST NOTIFY: OFF L 9:DISP 1-2 L 1 :SHORT ALARM
TRI-STATE .(SINGLE FLOAT) L 3:SHORT ALARM
TNK TST SIPHON BREAK:OFF CATEGORY : DISPENSER PAN L 9:SHORT ALARM
N
DELIVERY DELAY 1 MIN LIO:SHORT ALARM
PUMP THRESHOLD : 10.0 Lll :SHORT ALARM
L10:D1SP 3-4 L1.2:SHORT ALARM
TRI-STATE (SI•NGLE FLOAT) ISD SITE ALARMS
CATEGORY : DISPENSER PAN ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL:
ISD VAPOR LEAK FAIL
ISD VP PRES- FAIL
LI-1 :DISP 5-6 ISD VP STATUS FAIL
i CATEGORY :(DISPENSERPAN ISD SETUP FAIL
ISD SENSOR OUT FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
LEAK TEST METHOD L12:DISP 7-8 ALL:DEGRD COLLECT FAIL
TEST ON DATE : ALL TANK CATEGORYE:(SINGLE
DISPENSERFLOAT) ALL:FLOW COLLECT FAIL
PAN
FEB 6. 2007
START TIME : DISABLED
TEST RATE .:0.20 GAL/HR
DURATION 2 HOURS L13:E. TRANS SUMP
TRI-STATE (SINGLE FLOAT)
TST EARLY STOP:DISABLED CATEGORY : PIPING SUMP
LEAK TEST REPORT FORMAT
NORMAL L14:W. TRANS SUMP
TRI-STATE (SINGLE FLOAT)
CATEGORY PIP-ING SUMP
i
R 2:UNL 2 ^R 4:DIESEL" T
TYPE: TYPE:
PUMP CONTROL OUTPUT STANDARD EVR/ISD SETUP
TANK #: 2 NORMALLY CLOSED
TANK #: 4
LIQUID SENSOR ALMS EVR TYPE: VACUUM ASSIST
L I :FUEL ALARM VACUUM ASSIST TYPE
L 3:FUEL ALARM LIQUID SENSOR ALMS HEALY VAC
L 9:FUEL ALARM L 7:FUEL ALARM
L10:FUEL ALARM L10:FUEL ALARM NOZZLE A/L RANGE
L11 :FUEL ALARM L12:FIJEL ALARM MAX: 1 .15 MIN: 0.95
1_12:FUEL ALARM L13 FUEL ALARM
L I :SENSOR OUT ALARM L14:FUEL ALARM VAPOR PROCESSOR TYPE
L 3:SENSOR OUT ALARM L 7:SENSOR OUT ALARM NO VAPOR PROCESSOR
L 9:SENSOR OUT ALA yy� L10:SENSOR OUT ALARM
L10:SENSOR OUT ALARPI 1_1.2:SENSOR OUT ALARM
L 1 1 :SENSOR OUT ALARM L 1-3-:SENSOR OUT -ALARM ANALYSIS TIMES
L12:SENSOR OUT 'ALARM L14:SENSOR OUT ALARM TIME:- 10:00 AM
L 1 :SHORT ALARM L '7:SHORT ALARM DELAY MINUTES: 1 i
L 3:SHORT ALARM LIO:SHORT ALARM
L 9:SHORT ALARM r. L12:SHORT ALARM
L10:SHORT ALARM L13:SHORT ALARM ACCEPT HIGH ORVR:
L11 :SHORT ALARM L14:SHORT ALARM DISABLED
L12:SHORT ALARM
R 5:OVERFILL,ALARM ISD HOSE TABLE
ISD SITE ALARMS TYPE: ID FP FL HL AA RR
ISD GROSS PRES FAIL. STANDARD `-
ISD DEGRD PRES FAIL NORMALLY OPEN O1- O1 -01 -02-y0I- �UU
ISD VAPOR LEAK. FAIL 02 02 02 02 01 UU
ISD VP PRES FAIL TANK #: "NONE 03 03 03 '02 02 :UU
ISD VP STATUS FAIL 04 04 04 . 02 02 UU
ISD SETUP FAIL 05 05 05 02 03 UU
ISD SENSOR OUT FAIL IN-TANK ALARMS 06 06 06 02 03 'UU
ALL:OVERFILL ALARM-' 07 07 07. 02 0.4 UU
ISD HOSE ALARMS ALL:HIGH PRODUCT•ALARM 08 08 08 02 04 UU
ALL:GROSS COLLECT FAIL ALL:MAX PRODUCT ALARM
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL - ISD AIRFLOW METER MAP
ID SERIAL NUM LABEL
R 3:PREr1 ----------------=---:----
TYPE: ( 1 8448 FM .1-2
PUMP CONTROL OUTPUT 2 8409 FM 3-.4
TANK #: 3 ; 3 8408 5-B FM
4 8455 FM
LIQUID SENSOR ALMS
L 5:FUEL ALARM ISD FUEL�GRADE H4 E:,MAP
L 9:FUEL ALARM SMARTSENSOR SETUP' 1
L10:FUEL ALARM - -• - - - - - - - - FP MHH MHH MHH-MHH' AA
-
LII :FUEL ALARM ------------ - -7 s
L 12:FUEL ALARM s. 1 :V.P 1-2 DI 201 301 901 U U `.-1
L 5:SENSOR OUT ALARM CATEGORY VAPOR PRESSURE 02 202 302 902 U :U '•1
L 9:SENSOR OUT ALARM t- 03 203 303 903 U U ; 2
L10:SENSOR OUT ALARM s 2:FM, 1-2.. 04 204 304 904 U U. .2
L11 :SENSOR OUT ALARM CATEGORY AIR FLOW METER 05 205 305 905 U U ,.!:3
L12:SENSOR OUT ALARM 06 206 306 906 U U 3
L 5:SHORT ALARM s 3:FM 3-4 07 207 307 907- U U :;;4
L 9:SHORT ALARM CATEGORY 'AIR FLOW METER 08 208 308 908 U U =.';4
L10:SHORT ALARM {
L11 :SHORT ALARM s 4:5-6 FM
L12:SHORT ALARM CATEGORY AIR FLOW METER LABEL TABLE
-------------------
.----
ISD SITE ALARMS s 5:FM 7-8 1 UNASSIGNED i
ISD GROSS PRES FAIL CATEGORY AIR FLOW METER 2: BLEND3
ISD DEGRD PRES FAIL t 3: REGULAR -
ISD VAPOR LEAK FAIL 4: MID GRADE
ISD VP PRES FAIL 5: PREMIUM ,
ISD VP STATUS FAIL 6: GOLD
ISD SETUP FAIL 7 BRONZE
ISD SENSOR OUT FAIL' =8: SILVER
9: BLEND2
ISD HOSE ALARMS . 10: BLEND4
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL '
P F=
FMC SETUP r'
PROCESSOR_CCONTROL L,EVEL:
NONE
SWRCB,January 2006
Spill Bucket Testing Report Form
This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and
printouts from tests (if applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: #346 Fastrip#621 1 Date of Testing: 06/16/2010
Facility Address: 805 34 Street, Bakersfield,CA 93301
Facility Contact: Omero Garcia I Phone: 661-393-7000
Date Local Agency Was Notified of Testing : 5/24/10
Name of Local Agency Inspector(if present during testing): Ernie Medina
2. TESTING CONTRACTOR INFORMATION
Company Name: Confidence UST Services,Inc.
Technician Conducting Test: Garry DiMaggio
Credentials': X CSLB Contractor X ICC Service Tech. ❑SWRCB Tank Tester ❑Other(Spec)
License Number(s): CSLB#804904 ICC#8019607-UT
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: x Hydrostatic ❑Vacuum ❑Other
Test Equipment Used: Lake Test Equipment Resolution: 0.0625"
Identify Spill Bucket(By Tank 1 Regular 1 2 Regular 2 3 Super(Product) 4 Diesel(Product) �
Number, Stored Product, etc. Product Product
Bucket Installation Type: ❑Direct Bury ❑Direct Bury ❑Direct Bury ❑Direct Bury
x Contained in Sump x Contained in Sump x Contained in Sump x Contained in Sum
Bucket Diameter: 12.00" 12.00" 12.00" 12.00"
Bucket Depth. 14.25" 14.50" 13.75" 14.00"
Wait time between applying 5 min. 5 min. 5 min. 5 min.
vacuum/water and start of test:
Test Start Time(Tj): 10:00 am 10:00 am 10:00 am 10:00 am
Initial Reading(Rj): 9.75" 9.50" 9.50" 9.75"
Test End Time(TF): 11:00 am 11:00 am 11:00 am 11:00 am
Final Reading(RF): 9.75" 9.50" 9.50" 9.75"
Test Duration(TF—Tj): 1 hour 1 hour 1 hour 1 hour
Change in Reading(RF-Rj): 0.00" 0.00" 0.00" 0.00"
Pass/Fail Threshold or 0.0625" 0.0625" 0.0625" 0.0625
Criteria:
Test Result: X Pass ❑ Fail-' =IX Pass -[]Fail X Pass- ❑Fail X- Pass ❑Fail•.
Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true,accurate,and in full compliance with legal requirements.
Technician's Signature: Date: 06/16/2010
' State laws and regulations do not currently require testing to be performed by a qualified contractor. However,local requirements
may be more stringent.
SWRCB,January 2006
Spill Bucket Testing Report Form
This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and
printouts from tests (f applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: 4346 Fastrip#621 1 Date of Testing: 06/16/2010
Facility Address: 805 34` Street,Bakersfield,CA 93301
Facility Contact: Omero Garcia I Phone: 661-393-7000
Date Local Agency Was Notified of Testing : 5/24/10
Name of Local Agency Inspector(rf present during testing): Ernie Medina
2. TESTING CONTRACTOR INFORMATION
Company Name: Confidence UST Services,Inc.
Technician Conducting Test: Garry DiMaggio
Credentials': X CSLB Contractor X ICC Service Tech. ❑SWRC13 Tank Tester ❑Other(Spec)
License Number(s): CSLB#804904 ICC#8019607-UT
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: x Hydrostatic ❑Vacuum ❑Other
Test Equipment Used: Lake Test Equipment Resolution: 0.0625"
Identify Spill Bucket(By Tank 1 Regular 1 (Vapor) 2 Regular 2(Vapor) 3 Super(Vapor) 4
Number, Stored Product, etc.)
Bucket Installation Type: ❑ Direct Bury ❑ Direct Bury ❑Direct Bury ❑Direct Bury
x Contained in Sump x Contained in Sump x Contained in Sump ❑Contained in Sum
Bucket Diameter: 12.00" 12.00" 12.00"
Bucket Depth: 14.25" 14.50" 13.75"
Wait time between applying 5 min. 5 min. 5 min.
vacuum/water and start of test:
Test Start Time(T,): 10:00 am 10:00 am 10:00 am
Initial Reading(Rj): 9.50" 9.75" 9.75"
Test End Time(TO: 11:00 am 11:00 am 11:00 am
Final Reading(RF): 9.50" 8.25" 9.75"
Test Duration(TF—T,): 1 hour 1 hour 1 hour
Change in Reading(RF-R,): 0.00" 1.50" 0.00"
Pass/Fail Threshold or 0,0625" 0.0625" 0.0625"
Criteria:
Test Result: X Pass ❑ Fail 0-Pass X Fail X Pass'. -❑Fail ❑ Pass- ❑Fail
Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests)
Regular #2 (Vapor-OPW) Spill Bucket has been ordered and is scheduled to be
Replaced 7/2/10.
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certto that all the information contained in this report is true,accurate,and in full compliance with legal requirements.
Technician's Signature: Date: 06/16/2010
' State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
�#
I
Txly
-(XWP 1AX[f WITWCGx1U " Invoice No.: 23200
9346 Fastrip #621
80534 1h Street
Bakersfield, CA 93301
Repairs completed:
Veeder-Root would not Re-boot after removing power for fail-safe. Investigation
led to back-up battery. Replaced battery, recovered from archive and performed
mapping for ISD. Finished monitoring system certification and notified Fire
Department of results.
Required Repairs, Still Pending:
Regular#2 (Vapor— OPW) Spill Bucket needs to be replaced. Bucket has been
ordered and is scheduled to be replaced 7/2/10.
Technician Name: Garry DiMaggio
Signature:
Date: 6/28/2010