Loading...
HomeMy WebLinkAbout2010 SPILL BUCKETS IIIIIII VIII III IIII 39 IE SWRCB,January 2006 Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printouts from tests (f applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: 4346 Fastrip#621 1 Date of Testing: 8/13/2010 Facility Address: 805 34`h Street Bakersfield,CA 93301 Facility Contact: Omero Garcia Phone: (661)393-7000 Date Local Agency Was Notified of Testing: 8/10/2010 Name of Local Agency Inspector(f present during testing): Ernie Medina 2. TESTING CONTRACTOR INFORMATION Company Name: Confidence UST Services INC. Technician Conducting Test: Kristopher Karns Credentials: X CSLB Contractor X ICC Service Tech. X SWRCB Tank Tester ❑Other(Spec) License Number(s): CSLB#804904 ICC Service Tech.#5264406-UT SWRCB#09-1743 3. SPILL BUCKET TESTING INFORMATION Test Method Used: X Hydrostatic ❑Vacuum ❑Other Test Equipment Used: Lake Test Equipment Resolution: 0.0625 Identify Spill Bucket(By Tank 1 Super 2 3 4 Number, Stored Product, etc. Bucket Installation Type: ❑ Direct Bury ❑Direct Bury ❑Direct Bury ❑ Direct Bury X Contained in Sump ❑Contained in Sump ❑Contained in Sump ❑Contained in Sum Bucket Diameter: 12.00" Bucket Depth: 14.25" Wait time between applying 5 minutes vacuum/water and start of test: Test Start Time(Tj): 9:00am Initial Reading(Ri): 11.75" Test End Time(TF): 10:00am Final Reading(RF): 11.75" Test Duration(TF—Ti): 1 hour Change in Reading(RF-Rj): 0.00" Pass/Fail Threshold or 0.0625 Criteria: Test Result: X Pass ❑Fail ❑ Pass ❑Fail ❑ Pass ❑Fail ❑ Pass ❑Fail Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true,accurate,and in full compliance with legal requirements. Technician's Signature: 1w1.! Date:_8/13/2010 State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements may be more stringent. 111111'Jill 40 I