HomeMy WebLinkAbout1125 CALIFORNIA Avenue25 -79 INSPBCTION, TESTING, AND MAINTENANCE OF WATER -BASED FIRE PROTECTION SYSTEMS
Inspection, Testing, and Maintenance Cover Sheet
NFPA 25 as amended by CCR. Title 19
Property information:
Name: CALIFORNIA SENIOR HOUSING
Address: 1125 CALIFORNIA AVE.
City: BAKERSFIELD
ZIP: 93304
Contact: AMBER
Telephone: 324 -5088
Occupancy /Use: RETIREMENT
HOUING
Construction Type: WOOD
No. Stories: 3
Year Constructed: 2005
Contractor Information:
Name:
CONTROL FIRE PROTECTION CO INC
Address:
1347 OGDEN STREET
City:
BAKERSFIELD
State:
CA
Telephone:
881 -322 -1881
CA License#
534844
Job #
Performed by. ISRAEL GALLEGOS
(Print)
Note: Contractor Information may be
2 Number of System Risers
Copy sent to:
X Owner Date 1117/2011
X Fire AHJ . Date
o Contractor Date
1) For specific Inspection, testing, and
maintenance requirements and information,
am NFPA 25, 2002 Edition as amended by
California Code of Regulations, Title 19, $901
to I908.
2) Inspection Items may be performed by the
Owner In accordance with California Code of
Regulations Title 19 MCI
Forms Included with this report
NFPA 25
hapter
Number of Forms
N/A
FAIL*
PASS
X Automatic Sprinkler System
5
X
❑ Standpipe and Hose Systems
8
❑ Private Water Supply System
7
❑ Fire Pump
8
❑ Water Storage Tank
9
❑ Water Spray System
10
❑ Foam Water Sprinkler System
11
I'See `Deficiencles and Comments° section at and of each respective form.
State Fire Marshal AES 1
ANNEX B 25-79
Inspection, Testing, and Maintenance Fire
NFPA 26 Chapter 5 as amended
Sprinider System Page 1 of 4
b CCR, Title 19
Date of Inspection, Testing, Maintenance: 1/1312011
System Riser ID: BUILDING A&B
Property Information:
T = Test
Type of System: SOP C
Name: CALIFORNIA SENIOR HOUSING
X Wet Pipe �v~
❑ Dry Pipe °q
Address: 1125 CALIFORNIA AVE
❑ Preaction
❑ Deluge
Item
Activity
City: BAKERSFIELD
Description
Main Drain Test Results:
Abbreviation Key:
I = Inspection
Initial Static Pressure: 55 (psi)
T = Test
M = Maintenance
Residual Pressure: 50 (psi)
A-O = After Operation
MI = Per Manufacturer's Instructions
Restored Static Pressure: 50 (psi)
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.1
1
Daily
Preaotion/Deluge Valves — Enclosure
12.4.3.1
Weekly
temperature
1.2
1
Daily
Dry Pipe Valves — Enclosure
12.4.4.1.1
Weekly
temperature
1.3
1
Quarterly
Gauges (Dry, Preaction, Deluge
6.2.4.2
systems)
5.2.4.3
1.4
1
Quarterly
Control Valves
12.3.2.1
15.2.6
1.5
1
Quarterly
Alarm Devices
1.8
j I
Quarterly
Gauges (Wet Pipe Systems)
5.2.4.1
1.7
1
Quarterly
Hydraulic nameplate
6.2.7
1.8
1
Quarterly
Pipe and Fittings
5.2.2
1.9
1
Quarterly
Sprinklers
5.2.1
1.10
1
Quarterly
Spare Sprinklers
5.2.1.3
1.11
1
Quarterly
Fire Department Connections
12.7.1
1.12
1
Quarterly
Alarm Valves — Exterior Inspection
12.4.1.1
1.13
1
Quarterly
Preaction/Delugs Valves — Exterior
12.4.3.1.6
Inspection
1.14
1
Quarterly
Pressure Reducing Valves
12.6.1.1
1.15
f
Quarterly
Dry Pipe Valves — Exterior Inspection
12.4.4.1.4
1.18
1
Quarterly
Backilow Preventen3
12.6.1
1.17
1
Annually
Buildings
5.2.5
State Fire Marshal AES 2 March 21, 2006
-S4O INSPECTION, TESTING, AND MAWMANCE OF WATER - BASED FIRE PROTECTION SYSTEMS
Inspection, Testing, and Maintenance Fire
NFPA 25 Chapter 5 as amended
Sprinkler System Page 2 of 4
b CCR Title 19
Date of Inspection, Testing, Maintenance: 1/1312011
Property Information: "
Name: CALIFORNIA SENIOR HOUSING
Address: 1125 CALIFORNIA AVE
City: BAKERSFIELD
System Riser ID: BUILDING A &B
Type of System: SOP Da4,a
X Wet-Pipe
❑ Dry Pipe
❑ Preaction
❑ Deluge
�e
Item
Activity
Frequency
Description
NFPA25
Reference
Fail
WA
Pass
1.16
1
Annually
Hangers
52.3
1.19
1
Annually
Seismic Braces
52.3
1.20
1
5 Years
Hangers (Accessible concealed spaces)
52.3.3
X
1.21
1
5 Years
Seismic Brame (Accessible concealed
5.2.3.3
X
1.22
1
5 Years
Plpe and Fittings (Accessible concealed
522.3
X
1.23
1
5 Years
Sprinklers (Accessible concealed spaces)
52.1.1.4
X
1.24
1
5 Years
Alarm Valves — Interior Inspection
12.4.12
X
1.25
1
6 Years
Alarm Valves - Strainers, filters, offices
12.4.1.2
X
1.26
1
5 Years
Check Values — Interior Inepecriion
12.4.2.1
X
1.27
1
5 Years
PreebtlorVIDelluos Valves — Interior
Inspection
12.4.3.1.7
X
1.26
1
5 Years
Sbora offioeseluge Vaves -miners,
12.4.3.1.8
X
129
1
6 Years
Dry Pipe Valves— Interior Inspection
12.4.4.1.5
X
1.30
1
5 Years
Dry Pipe Valves - $trainers, filters, ortfioes
12.4.4.1.6
X
2.1
T
Annually
Marm Devices (90 Sec)
5.3.3
12.2.7
2.2
T
Annually
Main Drain Test (Enter date on Pegs 1)
12.2.6
122.8.1
12.3.3.4
2.3
T
Annually
Antifreeme Test
5.3.4
2.4
T
Annually
Control Valle - Position
12.3.3.1
2.5
T
Annually
CmW Valve — Operation
12.3.3.1
2.6
T
Annually
Supervisory
12.3.3.5
2.7
T
Annually
Preaction Valve — PfmingWater
12.4.32.1
2.8
T
Annually
Preactlon Valve — Low Air Pressure Alarm
12.4.32.10
2.9
T
Annudy
Preaction Valve — Full Flow Trip Test
12.4.322
State Fire Marshal AES 2 March 21, 2008
ANNEX B 2541
Inspection, Testing, and Maintenance Fire
NFPA 25 Chapter 6 as amended
Sprinkler System Page 3 of 4
b CCR Title 19
Date of Inspection, Testing, Maintenance: 1/13/2011
Property Information:
Name: CALIFORNIA SENIOR HOUSING
Address: 1125 CALIFORNIA AVE
City: BAKERSFIELD
System Riser ID: BUILDING A&B
Type of System: mpg Cam
X Wet Pipe �~
O Dry Pipe
O Deluge
BEM
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
2.10
T
Annually
Dry Pipe Valve — Priming Water
12.4.4.2.1
2.11
T
Annually
Arm Pipe Valve — Low Air Pressure
12.4.4.2.6
2.12
T
Annually
Dry Pipe Valve — Quick- Opening
Device
12.4.4.2.4
2.13
T
Annually
Dry Pipe Valve — Trip Test
12.4.4.2.2
2.14
T
Annually
Backflow Preventer Assemblies
12.6.2
2.15
T
3 Years
Dry Pipe Valve — Full Flow Trip Test
12.4.4.2.22
2.16
T
6 Years
Gauges
5.3.2
X
2.17
T
5 Years
Pressure Reducing Valve
12.5.1.2
X
2.18
T
5 Years
Fire Department Connection Backflush
12.7.4
X
2.19
T
6 Years
Sprinkler@ — Extra High Temperature
6.3.1.1.1.3
X
2.20
T
5 Years
Sprinklers — Corrosive environment or
corrosive water
5.3.1.1.2
X
2.21
T
10 Years
Sprinklers - Dry
5.3.1.1.1.5
2.22
T
20 Years
Sprinklers - Fast, Response
5.3.1.1.1.2
223
T
60 Years
Sprinklers
6.3.1.1.1
2.24
T
76 Years
Sprinklers 76 years in service
6.3.1.1.1 A
225
T
Sprinklers manufactured prior to 1920
6.3.1.1.1.1
3.1
M
Annually
Control Valves
12.3.4
32
M
Annually
Preacdon/Dsluge Valves
12.4.3.32
3.3
..M
Annually
DDevPes ValveaQuidaOpening
12.4.4.3.2
3.4
M
Annually
Dry Pipe Valve - Low Point Drains
12.4.4.3.3
3.5
M
5 Years
Obstruction Investigation
Chapter 13
X
State Fire Marshal AES 2 March 21, 2006
25-82 INSPECTION, 7MTING, AND MAIRMANCE OF WATBR -BASED FIRE PROTECTION SYSTEMS
inspection, Testing, and Maintenance Fire SprinMer System Page 4 of 4
NFPA 25, Chapter 8 as amended b CCR, Title 19
Date of Inspection, Testing, Maintenance: 1/1312011 System Riser ID: BUILDING A&B
Property Information:
Type of System: F,OP cq�
Name: CALIFORNIA SENIOR HOUSING X Wet Pipe
Address: 1126 CALIFORNIA AVE ❑ Dry Pipe
❑ Preaction
❑ Deluge
City: BAKERSFIELD
Item Deficiencies and Comments Item number must correspond to the Item number
of the Activity listed above:
1.23 2 PAINTED SPRINKLER HEADS ON THE SECOND FLOOR HALLWAY
❑ See Continuation Page(s) (Indicate the number of continuation
PASS
X FAIL
ISRAEL
Date 1/1312011
State Fire Marshal AES 2 , March 21, 2006