We herewith enclose a copy of an automatic fire sprinkler system check report for the
following facility:
Bakersfield College
1801 Panorama Dr.
Bakersfield, CA. 93305
to the party checked below:
Owner:
k' Fire Dept:
Thank You
RLH Fire Protection
File:7499
Bakersfield College
1801 Panorama Dr.
Bakersfield, CA. 93305
(DU -,?Jq s - u� a l
Bakersfield City Fire Department
1501 Truxtun Ave
Bakersfield, CA. 93301
IIIIIIIIVIIIIIIIIII 66
IE
RLH Fire Protection
3430 Unicorn Rd. Bakersfield, CA 93308 Voice:661.322.9344 Fax:661.322.6816 Lic.# 777717
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended bV CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
System Riser ID: 7499
Property Information:
- -
Type Of System: OF C44
Name: Bakersfield College- Science /Enginerrinc
Wet Pipe
Address: 1801 Panorama Dr
❑ Dry Pipe �' a
A -O = After Operation
❑ Preaction Y
MI = Per Manufacturer's Instructions
❑ DelugeiE M
City: Bakersfield
Frequency
Main Drain Test Results:
Abbreviation Key:
Initial Static Pressure: (psi)
I = Inspection
T =Test
Residual Pressure: (psi)
M = Maintenance
A -O = After Operation
Restored Static Pressure: (psi)
MI = Per Manufacturer's Instructions
Item
Activity
Frequency
Description
NFPA 25
Fail
N/A
Pass
Reference
1.1
I
Daily
Preaction /Deluge Valves - Enclosure
12.4.3.1
X
Weekly
temperature
1.2
I
Daily
Dry Pipe Valves - Enclosure
12.4.4.1.1
X
Weekly
tem erature
1.3
I
Quarterly
Gauges - (Dry, Preaction, Deluge
5.2.4.2
X
Systems)
5.2.4.3
1.4
I
Quarterly
Control Valves
12.3.2.1
X
1.5
1
Quarterly
Alarm Devices
5.2.6
X
1.6
I
Quarterly
Gauges (Wet Pipe Systems)
5.2.4.1
X
1.7
1
Quarterly
Hydraulic nameplate
5.2.7
X
1.8
1
Quarterly
Pipe and Fittings
5.2.2
X
1.9
1
Quarterly
Sprinklers
5.2.1
X
1.10
1
Quarterly
Spare Sprinklers
5.2.1.3
X
1.11
1
Quarterly
Fire Department Connections
12.7.1
X
1.12
I
Quarterly
Alarm Valves - Exterior Inspection
12.4.1.1
X
1.13
I
Quarterly
Preaction /Deluge Valves - Exterior
12.4.3.1.6
X
Inspection
1.14
1
Quarterly
Pressure Reducing Valves
12.5.1.1
X
1.15
1
Quarterly
Dry Pipe Valves- Exterior Inspection
12.4.4.1.4
X
1.16
1
Quarterly
Backflow Preventers
12.6.1
X
1.17
1
Annual
Buildings
5.2.5
X
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 1 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Activity
Date Of Inspection, Testing, Maintenance: 01/05/2011
Description
System Riser ID: 7499
Fail
Property Information:
Pass
Type Of System:
_
o f FAQ
Name: Bakersfield College- Science /Enginerrinc
Hangers
❑x Wet Pipe
+�'�� 0 ,9
Address: 1801 Panorama Dr
❑ Dry Pipe
co n
Annually
Seismic Braces
❑ Preaction
X
1.20
1
5 Years
Hangers (Accessible concealed spaces)
❑ DelugeE
City: Ba ersfield
1.21
I
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.18
1
Annually
Hangers
5.2.3
X
1.19
1
Annually
Seismic Braces
5.2.3
X
1.20
1
5 Years
Hangers (Accessible concealed spaces)
5.2.3.3
X
1.21
I
5 Years
Seismic Braces (Accessible concealed
s aces
5.2.3.3
X
1.22
1
5 Years
Pipe and Fittings (Accessible concealed
spaces)
5.2.2.3
X
1.23
1
5 Years
Sprinklers (Accessible concealed spaces)
5.2.1.1.4
X
1.24
1
5 Years
Alarm Valves - Interior Inspection
12.4.1.2
X
1.25
1
5 Years
Alarm Valves - Strainers, filters, orifices
12.4.1.2
X
1.26
1
5 Years
Check Valves - Interior Inspection
12.4.2.1
X
1.27
I
5 Years
Preaction /Deluge Valves - Interior
Inspection
12.4.3.1.7
X
1.28
1
5 Years
Preaction /Deluge Valves - Strainers,
filters, orifices
12.4.3.1.8
X
1.29
1
5 Years
Dry Pipe Valves - Interior Inspection
12.4.4.1.5
X
1.30
1
5 Years
Dry Pipe Valves - Strainers, filters, orifices
12.4.4.1.6
X
2.1
T
Annually
Alarm Devices (90 Sec)
5.3.3
12.2.7
X
2.2
T
Annually
Main Drain Test (Enter data on Page 1)
12.2.6
12.2.6.1
12.3.3.4
X
2.3
T
Annually
Antifreeze Test
5.3.4
X
2.4
T
Annually
Control Valve - Position
12.3.3.1
X
2.5
T
Annually
Control Valve - Operation
12.3.3.1
X
2.6
T
Annually
Supervisory
12.3.3.5
X
2.7
T
Annually
Preaction Valve - Priming Water
12.4.3.2.1
X
2.8
T
Annually
Preaction Valve - Low Air Pressure Alarm
12.4.3.2.10
X
2.9
T
Annually I
Preaction Valve - Full Flow Trip Test
12.4.3.2.2
X
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 2 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended bV CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
Property Information:
Name: Bakersfield College- Science /Enginerrinc
Address: 1801 Panorama Dr
City: Bakersfield
System Riser ID: 7499
Type Of System: F Cq
Wet Pipe
2
❑ Dry Pipe 'v
❑ Preaction �► .,
❑ Deluge ARE M .
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
2.10
T
Annually
Dry Pipe Valve - Priming Water
12.4.4.2.1
X
2.11
T
Annually
y
ry Pipe Valve - Low Air Pressure
Alarm
12.4.4.2.6
X
2.12
T
Annually
y
ry Pipe Valve - Quick- Opening
Device
12.4.4.2.4
X
2.13
T
Annually
Dry Pipe Valve - Trip
12.4.4.2.2
X
2.14
T
Annually
Backflow Preventor Assemblies
12.6.2
X
2.15
T
3 Years
Dry Pipe Valve - Full Flow Trip Test
12.4.4.2.2.2
X
2.16
T
5 Years
Gauges
5.3.2
X
2.17
T
5 Years
Pressure Reducing Valve
12.5.1.2
X
2.18
T
5 Years
Fire Department Connection Backflush
12.7.4
X
2.19
T
5 Years
Sprinklers - Extra High Temperature
5.3.1.1.1.3
X
2.20
T
5 Years
Sprinklers - Corrosive environment or
corrosive water
5.3.1.1.2
X
2.21
T
10 Years
Sprinklers - Dry
5.3.1.1.1.5
X
2.22
T
20 Years
Sprinklers - Fast Response
5.3.1.1.1.2
X
2.23
T
50 Years
Sprinklers
5.3.1.1.1
X
224
T
75 Years
Sprinklers 75 years in service
5.3.1.1.1.4
X
2.25
T
Sprinklers manufactured prior to 1920
- Re lace
5.3.1.1.1.1
X
3.1
M
Annually
Control Valves
12.3.4
X
3.2
M
Annually
Preaction /Deluge Valves
12.4.3.3.2
X
3.3
M
Annually
Dry Pipe Valves /Quick- Opening
Devices
12.4.4.3.2
X
3.4
M
Annually
Dry Pipe Valve - Low Point Drains
12.4.4.3.3
X
3.5
M
5 Years
Obstruction Investigation
Chapter 13
X
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 3 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
Property Information:
Name: Bakersfield College- Science /Enginerrinc
Address: 1801 Panorama Dr
City: Bakersfield
System Riser ID: 7499
Type Of System:
F Cq���o
� Wet Pipe � �
❑ Dry Pipe co y
❑ Preaction
❑ Deluge ARE M�
Item
Deficiencies and Comments:
Deficiencies and Comments Item number must correspond to the Item number
of the activity listed above:
❑ See Continuation Page(s) (Indicate the number of continuation pages)
❑PASS
❑ FAIL 01/05/2011
Signature Date
State Fire Marshal AES 2
March 21, 2006
Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 4 of 5
Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717
Page 5of5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
System Riser ID: 7499
Property Information:;
..
Type Of System: F'C4 C,�C
Name: Bakersfield College -Sam Art & Music
Wet Pipe Quo
-ra
Address: 1801 Panorama Dr
❑ Dry Pipe °� p
A -O = After Operation
❑ Preaction �►
MI = Per Manufacturer's Instructions
❑ Deluge ARE M
City: Bakersfield
Frequency
Main Drain Test Results:
Abbreviation Key:
Initial Static Pressure: (psi)
I = Inspection
T = Test
Residual Pressure: (psi)
M = Maintenance
A -O = After Operation
Restored Static Pressure: (psi)
MI = Per Manufacturer's Instructions
Item
Activity
Frequency
Description
NFPA 25
Fail
N/A
Pass
Reference
1.1
1
Daily
Preaction /Deluge Valves - Enclosure
12.4.3.1
X
Weekly
temperature
1.2
1
Daily
Dry Pipe Valves - Enclosure
12.4.4.1.1
X
Weekly
temperature
1.3
1
Quarterly
Gauges - (Dry, Preaction, Deluge
5.2.4.2
X
Systems)
5.2.4.3
1.4
1
Quarterly
Control Valves
12.3.2.1
X
1.5
1
Quarterly
Alarm Devices
5.2.6
X
1.6
I
Quarterly
Gauges (Wet Pipe Systems)
5.2.4.1
X
1.7
1
Quarterly
Hydraulic nameplate
5.2.7
X
1.8
1
Quarterly
Pipe and Fittings
5.2.2
X
1.9
1
Quarterly
Sprinklers
5.2.1
X
1.10
1
Quarterly
Spare Sprinklers
5.2.1.3
X
1.11
1
Quarterly
Fire Department Connections
12.7.1
X
1.12
1
Quarterly
Alarm Valves - Exterior Inspection
12.4.1.1
X
1.13
1
Quarterly
Quarter)
Preaction /Deluge Valves - Exterior
12.4.3.1.6
X
Inspection
1.14
1
Quarterly
Pressure Reducing Valves
12.5.1.1
X
1.15
1
Quarterly
Dry Pipe Valves- Exterior Inspection
12.4.4.1.4
X
1.16
1
Quarterly
Backflow Preventers
12.6.1
X
1.17
I
Annual
Buildings
5.2.5
X
State Fire Marshal AES 2
March 21, 2006
Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 1 of 5
FAI 01 101 1 WA
Item
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Frequency
Date Of Inspection, Testing, Maintenance: 01/05/2011
System Riser ID: 7499
Fail
Property Information:
Pass
Type Of System:
IF CA(��O
Name: Bakersfield
College -Sam Art & Music
❑x Wet Pipe
,t�0
� .fl
Address: 1801 Panorama
Dr
❑ Dry Pipe
2
n
Annually
Seismic Braces
❑ Preaction°
.,
X
1.20
1
5 Years
Hangers (Accessible concealed spaces)
❑ Deluge
RE Mme`
City: Bakersfield
1.21
1
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.18
1
Annually
Hangers
5.2.3
X
1.19
1
Annually
Seismic Braces
5.2.3
X
1.20
1
5 Years
Hangers (Accessible concealed spaces)
5.2.3.3
X
1.21
1
5 Years
Seismic Braces (Accessible concealed
spaces)
5.2.3.3
X
1.22
1
5 Years
Pipe and Fittings (Accessible concealed
spaces)
5.2.2.3
X
1.23
1
5 Years
Sprinklers (Accessible concealed spaces)
5.2.1.1.4
X
1.24
1
5 Years
Alarm Valves - Interior Inspection
12.4.1.2
X
1.25
1
5 Years
Alarm Valves - Strainers, filters, orifices
12.4.1.2
X
1.26
1
5 Years
Check Valves - Interior Inspection
12.4.2.1
X
1.27
1
5 Years
Preaction /Deluge Valves - Interior
Inspection
12.4.3.1.7
X
1.28
1
5 Years
Preaction /Deluge Valves - Strainers,
filters, orifices
12.4.3.1.8
X
1.29
1
5 Years
Dry Pipe Valves - Interior Inspection
12.4.4.1.5
X
1.30
1
5 Years
Dry Pipe Valves - Strainers, filters, orifices
12.4.4.1.6
X
2.1
T
Annually
Alarm Devices (90 Sec)
5.3.3
12.2.7
X
2.2
T
Annually
Main Drain Test (Enter data on Page 1)
12.2.6
12.2.6.1
12.3.3.4
X
2.3
T
Annually
Antifreeze Test
5.3.4
X
2.4
T
Annually
Control Valve - Position
12.3.3.1
X
2.5
T
Annually
Control Valve - Operation
12.3.3.1
X
2.6
T
Annually
Supervisory
12.3.3.5
X
2.7
T
Annually
Preaction Valve - Priming Water
12.4.3.2.1
X
2.8
T
Annually
Preaction Valve - Low Air Pressure Alarm
12.4.3.2.10
X
2.9
j T
Annually I
Preaction Valve - Full Flow Trip Test
12.4.3.2.2
X
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 2 of 5
F.1
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
System Riser ID: 7499
Property Information:
--
Type Of System:
of C.44.t .
Name: Bakersfield College -Sam Art & Music
❑x Wet Pipe
Address: 1801 Panorama Dr
❑ Dry Pipe a
❑ Preaction► .+
❑ DelugeE M
City: Bakersfield
NFPA 25
Item
Activity
Frequency
Description
Reference
Fail
N/A
Pass
2.10
T
Annually
Dry Pipe Valve - Priming Water
12.4.4.2.1
X
2.11
T
Annually
Dry Pipe Valve - Low Air Pressure
12.4.4.2.6
X
Alarm
2.12
T
Annually
y
ry Pipe Valve - Quick- Opening
12.4.4.2.4
X
Device
2.13
T
Annually
Dry Pipe Valve - Trip
12.4.4.2.2
X
2.14
T
Annually
Backflow Preventor Assemblies
12.6.2
X
2.15
T
3 Years
Dry Pipe Valve - Full Flow Trip Test
12.4.4.2.2.2
X
2.16
T
5 Years
Gauges
5.3.2
X
2.17
T
5 Years
Pressure Reducing Valve
12.5.1.2
X
2.18
T
5 Years
Fire Department Connection Backflush
12.7.4
X
2.19
T
5 Years
Sprinklers - Extra High Temperature
5.3.1.1.1.3
X
2.20
T
5 Years
Sprinklers - Corrosive environment or
5.3.1.1.2
X
corrosive water
2.21
T
10 Years
Sprinklers - Dry
5.3.1.1.1.5
X
2.22
T
20 Years
Sprinklers - Fast Response
5.3.1.1.1.2
X
2.23
T
50 Years
Sprinklers
5.3.1.1.1
X
2.24
T
75 Years
Sprinklers 75 years in service
5.3.1.1.1.4
X
2.25
T
Sprinklers manufactured prior to 1920
5.3.1.1.1.1
X
- Re lace
3.1
M
Annually
Control Valves
12.3.4
X
3.2
M
Annually
Preaction /Deluge Valves
12.4.3.3.2
X
3.3
M
Annually
Dry Pipe Valves /Quick- Opening
12.4.4.3.2
X
Devices
3.4
M
Annually
Dry Pipe Valve - Low Point Drains
12.4.4.3.3
X
3.5
M
5 Years
Obstruction Investigation
Chapter 13
X
State Fire Marshal AES 2
March 21, 2006
Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 3 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
Property Information:
Name: Bakersfield College -Sam Art & Music
Address: 1801 Panorama Dr
City: Bakersfield
System Riser ID: 7499
Type Of System:
OF Cq���C
❑x Wet Pipe Q ,p
❑ Dry Pipe �' y
❑ Preaction
E] Deluge
SAE Mt`
Item
Deficiencies and Comments:
Deficiencies and Comments Item number must correspond to the Item number
of the activity listed above:
❑ See Continuation Page(s) (Indicate the number of continuation pages)
❑x PASS
01/05/2011 01/05/2011
F-1
Signature Date
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 4 of 5
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717
Page 5 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
System Riser ID: 7499
Property Information:
Type Of System: F, -
C,�Cp
Name: Bakersfield College - Library
❑x Wet Pipe
Address: 1801 Panorama Dr
a y
E] Dry Pipe y q
A -O = After Operation
❑ Preaction �► v
MI = Per Manufacturer's Instructions
❑ Deluge "ARE Mp
City: Bakersfield
-- ... - --
Main Drain Test Results:
Abbreviation Key:
Initial Static Pressure: (psi)
I =Inspection
T =Test
Residual Pressure: (psi)
M = Maintenance
A -O = After Operation
Restored Static Pressure: (psi)
MI = Per Manufacturer's Instructions
Item
Activity
Frequency
Description
NFPA 25
Fail
N/A
Pass
Reference
1.1
1
Daily
Preaction /Deluge Valves - Enclosure
12.4.3.1
X
Weekly
temperature
1.2
I
Daily
Dry Pipe Valves - Enclosure
12.4.4.1.1
X
Weeklv
temperature
1.3
1
Quarterly
Gauges - (Dry, Preaction, Deluge
5.2.4.2
X
Systems)
5.2.4.3
1.4
1
Quarterly
Control Valves
12.3.2.1
X
1.5
1
Quarterly
Alarm Devices
5.2.6
X
1.6
1
Quarterly
Gauges (Wet Pipe Systems)
5.2.4.1
X
1.7
1
Quarterly
Hydraulic nameplate
5,2.7
X
1.8
1
Quarterly
Pipe and Fittings
5.2.2.
X
1.9
1
Quarterly
Sprinklers
5.2.1
X
1.10
1
Quarterly
Spare Sprinklers
5.2.1.3
X
1.11
1
Quarterly
Fire Department Connections
12.7.1
X
1.12
1
Quarterly
Alarm Valves - Exterior Inspection
12.4.1.1
X
1.13
1
Quarterly
Quarter)
Preaction /Deluge Valves - Exterior
12.4.3.1.6
X
Inspection
1.14
1
Quarterly
Pressure Reducing Valves
12.5.1.1
X
1.15
1
Quarterly
Dry Pipe Valves- Exterior Inspection
12.4.4.1.4
X
1.16
1
Quarterly
Backflow Preventers
12.6.1
X
1.17
1
Annual
Buildings
5.2.5
X
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 1 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Activity
Date Of Inspection, Testing, Maintenance: 01/0512011
Description
System Riser ID: 7499
Fail
Property Information:
Pass
Type Of System:
F CA(��p
Name: Bakersfield Colleae- Library
Hangers
❑x Wet Pipe
cr A
Address: 18Q1 Panorama Dr
❑ Dry Pipe
1
Annually
Seismic Braces
❑ Preaction
r:.
X
❑ Deluge
RE M
City: Bakersfield
Hangers (Accessible concealed spaces)
5.2.3.3
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.18
1
Annually
Hangers
5.2.3
X
1.19
1
Annually
Seismic Braces
5.2.3
X
1.20
1
5 Years
Hangers (Accessible concealed spaces)
5.2.3.3
X
1.21
1
5 Years
Seismic Braces (Accessible concealed
spaces)
5.2.3.3
X
1.22
1
5 Years
Pipe and Fittings (Accessible concealed
spaces)
5.2.2.3
X
1.23
1
5 Years
Sprinklers (Accessible concealed spaces)
5.2.1.1.4
X
1.24
1
5 Years
Alarm Valves - Interior Inspection
12.4.1.2
X
1.25
1
5 Years
Alarm Valves - Strainers, filters, orifices
12.4.1.2
X
1.26
1
5 Years
Check Valves - Interior Inspection
12.4.2.1
X
1.27
I
5 Years
Preaction /Deluge Valves - Interior
Inspection
12.4.3.1.7
X
1.28
1
5 Years
Preaction /Deluge Valves - Strainers,
filters, orifices
12.4.3.1.8
X
1.29
1
5 Years
Dry Pipe Valves - Interior Inspection
12.4.4.1.5
X
1.30
1
5 Years
Dry Pipe Valves - Strainers, filters, orifices
12.4.4.1.6
X
2.1
T
Annually
Alarm Devices (90 Sec)
5.3.3
12.2.7
X
2.2
T
Annually
Main Drain Test (Enter data on Page 1)
12.2.6
12.2.6.1
12.3.3.4
X
2.3
T
Annually
Antifreeze Test
5.3.4
X
2.4
T
Annually
Control Valve - Position
12.3.3.1
X
2.5
T
Annually
Control Valve - Operation
12.3.3.1
X
2.6
T
Annually
Supervisory
12.3.3.5
X
2.7
T
Annually
Preaction Valve - Priming Water
12.4.3.2.1
X
2.8
T
Annually
Preaction Valve - Low Air Pressure Alarm
12.4.3.2.10
X
2.9
T
Annually
Preaction Valve - Full Flow Trip Test
12.4.3.2.2
X
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 2 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
System Riser ID: 7499
Property Information:
-. - --
Type Of System:
F C4
C,Dp
Name: Bakersfield College- Library
Wet Pipe o
Address: 1801 Panorama Dr
❑ Dry Pipe
❑ Preaction �►
E] Delu e
g
City: Bakersfield
NFPA 25
Item
Activity
Frequency
Description
Reference
Fail
N/A
Pass
2.10
T
Annually
Dry Pipe Valve - Priming Water
12.4.4.2.1
X
2.11
T
Annually
Dry Pipe Valve - Low Air Pressure
12.4.4.2.6
X
Alarm
2.12
T
Annually
y
ry Pipe Valve - Quick- Opening
12.4.4.2.4
X
Device
2.13
T
Annually
Dry Pipe Valve - Trip
12.4.4.2.2
X
2.14
T
Annually
Backflow Preventor Assemblies
12.6.2
X
2.15
T
3 Years
Dry Pipe Valve - Full Flow Trip Test
12.4.4.2.2.2
X
2.16
T
5 Years
Gauges
5.3.2
X
2.17
T
5 Years
Pressure Reducing Valve
12.5.1.2
X
2.18
T
5 Years
Fire Department Connection Backflush
12.7.4
X
2.19
T
5 Years
Sprinklers - Extra High Temperature
5.3.1.1.1.3
X
2.20
T
5 Years
Sprinklers - Corrosive environment or
5.3.1.1.2
X
corrosive water
2.21
T
10 Years
Sprinklers - Dry
5.3.1.1.1.5
X
2.22
T
20 Years
Sprinklers - Fast Response
5.3.1.1.1.2
X
2.23
T
50 Years
Sprinklers
5.3.1.1.1
X
2.24
T
75 Years
Sprinklers 75 years in service
5.3.1.1.1.4
X
2.25
T
Sprinklers manufactured prior to 1920
5.3.1.1.1.1
X
- Replace
3.1
M
Annually
Control Valves
12.3.4
X
32
M
Annually
Preaction /Deluge Valves
12.4.3.3.2
X
3.3
M
Annually
Dry Pipe Valves /Quick- Opening
12.4.4.3.2
X
Devices
3.4
M
Annually
Dry Pipe Valve - Low Point Drains
12.4.4.3.3
X
3.5
M
5 Years
Obstruction Investigation
Chapter 13
X
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 3 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
Property Information:
Name: Bakersfield College- Library
Address: 1801 Panorama Dr
City: Bakersfield
System Riser ID: 7499
Type Of System:
f C&I�o
❑x Wet Pipe 9
� Z
❑ Dry Pipe n
❑ Preaction ;
❑ Deluge ARE M�
Item
Deficiencies and Comments:
Deficiencies and Comments Item number must correspond to the Item number
of the activity listed above:
❑ See Continuation Page(s) (Indicate the number of continuation pages)
❑PASS _.
❑ FAIL 01/05/2011
Signature Date
State Fire Marshal AES 2
March 21, 2006.
Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 4 of 5
inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717
Page 5 of 5
0,04 10 10.14
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
System Riser ID: 7499
Property Information:
Type Of System: F �A �i�o9
Name: Bakersfield College- Language Arts
❑x Wet Pipe �tio
Address: 1801 Panorama Dr
a y
❑ Dry Pipe 07 a
A -O = After Operation
❑ Preaction �► �,
MI = Per Manufacturer's Instructions
❑ Deluge M
City: Bakersfield
Frequency
Main Drain Test Results:
Abbreviation Key:
Initial Static Pressure: (psi)
I = Inspection
T =Test
Residual Pressure: (psi)
M = Maintenance
A -O = After Operation
Restored Static Pressure: (psi)
MI = Per Manufacturer's Instructions
Item
Activity
Frequency
Description
NFPA 25
Fail
N/A
Pass
Reference
1.1
1
Daily
Preaction /Deluge Valves - Enclosure
12.4.3.1
X
Weekly
temperature
1.2
1
Daily
Dry Pipe Valves - Enclosure
12.4.4.1.1
X
Week)
tem erature
1.3
1
Quarterly
Gauges - (Dry, Preaction, Deluge
5.2.4.2
X
Systems)
5.2.4.3
1.4
1
Quarterly
Control Valves
12.3.2.1
X
1.5
1
Quarterly
Alarm Devices
5.2.6
X
1.6
1
Quarterly
Gauges (Wet Pipe Systems)
5.2.4.1
X
1.7
1
Quarterly
Hydraulic nameplate
5.2.7
X
1.8
1
Quarterly
Pipe and Fittings
5.2.2
X
1.9
1
Quarterly
Sprinklers
5.2.1
X
1.10
1
Quarterly
Spare Sprinklers
5.2.1.3
X
1.11
1
Quarterly
Fire Department Connections
12.7.1
X
1.12
1
Quarterly
Alarm Valves - Exterior Inspection
12.4.1.1
X
1.13
1
Quarterly
Quarter)
Preaction /Deluge Valves - Exterior
12.4.3.1.6
X
Inspection
1.14
1
Quarterly
Pressure Reducing Valves
12.5.1.1
X
1.15
1
Quarterly
Dry Pipe Valves- Exterior Inspection
12.4.4.1.4
X
1.16
I
Quarterly
Backflow Preventers
12.6.1
X
1.17
1
Annual
Buildings
5.2.5
X
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 1 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Activity
Date Of Inspection, Testing, Maintenance: 01/05/2011
Description
System Riser ID: 7499
Fail
Property Information:
Pass
Type Of System:
CAC ��O
Name: Bakersfield College - Language Arts
Hangers
❑x Wet Pipe
��pF
tt 9
Address: 1801 Panorama Dr
E] Dry Pipe
c' y
Annually
Seismic Braces
❑ Preaction
�% J
X
1.20
P
5 Years
Hangers (Accessible concealed spaces)
❑ Deluge
M
City: Bakersfield
1.21
I
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.18
1
Annually
Hangers
5.2.3
X
1.19
1
Annually
Seismic Braces
5.2.3
X
1.20
1
5 Years
Hangers (Accessible concealed spaces)
5.2.3.3
X
1.21
I
5 Years
Seismic Braces (Accessible concealed
s aces
5.2.3.3
X
1.22
1
5 Years
Pipe and Fittings (Accessible concealed
spaces
5.2.2.3
X
1.23
1
5 Years
Sprinklers (Accessible concealed spaces)
5.2.1.1.4
X
1.24
1
5 Years
Alarm Valves - Interior Inspection
12.4.1.2
X
1.25
1
5 Years
Alarm Valves - Strainers, filters, orifices
12.4.1.2
X
1.26
1
5 Years
Check Valves - Interior Inspection
12.4.2.1
X
1.27
I
5 Years
Preaction /Deluge Valves - Interior
Inspection
12.4.3.1.7
X
1.28
1
5 Years
Preaction /Deluge Valves - Strainers,
filters, orifices
12.4.3.1.8
X
1.29
1
5 Years
Dry Pipe Valves - Interior Inspection
12.4.4.1.5
X
1.30
1
5 Years
Dry Pipe Valves - Strainers, filters, orifices
12.4.4.1.6
X
2.1
T
Annually
Alarm Devices (90 Sec)
5.3.3
12.2.7
X
2.2
T
Annually
Main Drain Test (Enter data on Page 1)
12.2.6
12.2.6.1
12.3.3.4
X
2.3
T
Annually
Antifreeze Test
5.3.4
X
2.4
T
Annually
Control Valve - Position
12.3.3.1
X
2.5
T
Annually
Control Valve - Operation
12.3.3.1
X
2.6
T
Annually
Supervisory
12.3.3.5
X
2.7
T
Annually
Preaction Valve - Priming Water
12.4.3.2.1
X
2.8
T
Annually
Preaction Valve - Low Air Pressure Alarm
12.4.3.2.10
X
2.9
T
Annually
Preaction Valve - Full Flow Trip Test
12.4.3.2.2
X
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 2 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended bV CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
System Riser ID: 7499
Property Information:
- - - --
Type Of System:
F Cq ��'t`p
Name: Bakersfield College - Language Arts
mow.
❑x Wet Pipe
Address: 1801 Panorama Dr
❑ Dry Pipe °p v
❑ Preaction �y►�,
F` M
❑ Deluge AR EE M
City: Bakersfield
NFPA 25
Item
Activity
Frequency
Description
Reference
Fail
N/A
Pass
2.10
T
Annually
Dry Pipe Valve - Priming Water
12.4.4.2.1
X
2.11
T
Annually
Dry Pipe Valve - Low Air Pressure
12.4.4.2.6
X
Alarm
2.12
T
Annual/
Annually
Dry Pipe Valve - Quick- Opening
12.4.4.2.4
X
Device
2.13
T
Annually
Dry Pipe Valve - Trip
12.4.4.2.2
X
2.14
T
Annually
Backflow Preventor Assemblies
12.6.2
X
2.15
T
3 Years
Dry Pipe Valve - Full Flow Trip Test
12.4.4.2.2.2
X
2.16
T
5 Years
Gauges
5.3.2
X
2.17
T
5 Years
Pressure Reducing Valve
12.5.1.2
X
2.18
T
5 Years
Fire Department Connection Backflush
12.7.4
X
2.19
T
5 Years
Sprinklers - Extra High Temperature
5.3.1.1.1.3
X
2.20
T
5 Years
Sprinklers - Corrosive environment or
5.3.1.1.2
X
corrosive water
2.21
T
10 Years
Sprinklers - Dry
5.3.1.1.1.5
X
2.22
T
20 Years
Sprinklers - Fast Response
5.3.1.1.1.2
X
2.23
T
50 Years
Sprinklers
5.3.1.1.1
X
224
T
75 Years
Sprinklers 75 years in service
5.3.1.1.1.4
X
2.25
T
Sprinklers manufactured prior to 1920
5.3.1.1.1.1
X
- Re lace
3.1
M
Annually
Control Valves
12.3.4
X
3.2
M
Annually
Preaction /Deluge Valves
12.4.3.3.2
X
3.3
M
Annually
Dry Pipe Valves /Quick- Opening
12.4.4.3.2
X
Devices
3.4
M
Annually
Dry Pipe Valve - Low Point Drains
12.4.4.3.3
X
3.5
M
5 Years I
Obstruction Investigation
Chapter 13
X
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 3 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
Property Information:
Name: Bakersfield College- Language Arts
Address: 1801 Panorama Dr
City: Bakersfield
System Riser ID: 7499
Type Of System:
OF CAL��Q
Wet Pipe a 9
j6` Z
❑ Dry Pipe y
❑ Preaction
❑ Deluge t
Item
Deficiencies and Comments:
Deficiencies and Comments Item number must correspond to the Item number
of the activity listed above:
❑ See Continuation Page(s) (Indicate the number of continuation pages)
❑x PASS
❑ FAIL 01/05/2011
Signature Date
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 4 of 5
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717
Page 5 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
System Riser ID: 7499
Property Information:
Type Of System: OF C'4'
Name: Bakersfield College- Industrial Tech.
Wet Pipe
M = Maintenance
co
Address: 1801 Panorama Dr
❑ Dry Pipe
MI = Per Manufacturer's Instructions
❑ Preaction► v
Activity
❑ Deluge qE p't�
City: Bakersfield
NFPA 25
Main Drain Test Results:
Abbreviation Key:
Initial Static Pressure: (psi)
I = Inspection
T =Test
Residual Pressure: (psi)
M = Maintenance
A -O = After Operation
Restored Static Pressure: (psi)
MI = Per Manufacturer's Instructions
Item
Activity
Frequency
Description
NFPA 25
Fail
N/A
Pass
Reference
1.1
1
Daily
Preaction /Deluge Valves - Enclosure
12.4.3.1
X
Weekly
tem erature
1.2
1
Daily
Dry Pipe Valves - Enclosure
12.4.4.1.1
X
Weekly
tem erature
1.3
1
Quarterly
Gauges - (Dry, Preaction, Deluge
5.2.4.2
X
S stems )
5.2.4.3
1.4
1
Quarterly
Control Valves
12.3.2.1
X
1.5
1
Quarterly
Alarm Devices
5.2.6
X
1.6
1
Quarterly
Gauges (Wet Pipe Systems)
5.2.4.1
X
1.7
1
Quarterly
Hydraulic nameplate
5.2.7
X
1.8
1
Quarterly
Pipe and Fittings
5.2.2
X
1.9
1
Quarterly
Sprinklers
5.2.1
X
1.10
1
Quarterly
Spare Sprinklers
5.2.1.3
X
1.11
1
Quarterly
Fire Department Connections
12.7.1
X
1.12
1
Quarterly
Alarm Valves - Exterior Inspection
12.4.1.1
X
1.13
1
Quarter)
Quarterly
Preaction /Deluge Valves - Exterior
12.4.3.1.6
X
Inspection
1.14
1
Quarterly
Pressure Reducing Valves
12.5.1.1
X
1.15
1
Quarterly
Dry Pipe Valves- Exterior Inspection
12.4.4.1.4
X
1.16
1
Quarterly
Backflow Preventers
12.6.1
X
1.17
1
Annual
Buildings
5.2.5
X
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 1 of 5
ANNEX B
Item
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Frequency
Date Of Inspection, Testing, Maintenance: 01/05/2011
System Riser ID: 7499
Fail
Property Information:
Pass
Type Of System:
1
Annually
Hangers
5.2.3
Name: Bakersfield
College- Industrial Tech.
� Wet Pipe
a �
Address: 1801 Panorama
Dr
❑ Dry Pipe
co y
X
❑ Preaction
N% 4
5 Years
Hangers (Accessible concealed spaces)
❑ Deluge
SAE
City: Bakersfield
1.21
_
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.18
1
Annually
Hangers
5.2.3
X
1.19
1
Annually
Seismic Braces
5.2.3
X
1.20
1
5 Years
Hangers (Accessible concealed spaces)
5.2.3.3
X
1.21
1
5 Years
Seismic Braces (Accessible concealed
spaces)
5.2.3.3
X
1.22
1
5 Years
Pipe and Fittings (Accessible concealed
spaces)
5.2.2.3
X
1.23
1
5 Years
Sprinklers (Accessible concealed spaces)
5.2.1.1.4
X
1.24
1
5 Years
Alarm Valves - Interior Inspection
12.4.1.2
X
1.25
1
5 Years
Alarm Valves - Strainers, filters, orifices
12.4.1.2
X
1.26
1
5 Years
Check Valves - Interior Inspection
12.4.2.1
X
1.27
1
5 Years
Preaction /Deluge Valves - Interior
Inspection
12.4.3.1.7
X
1.28
1
5 Years
Preaction /Deluge Valves - Strainers,
filters, orifices
12.4.3.1.8
X
1.29
1
5 Years
Dry Pipe Valves - Interior Inspection
12.4.4.1.5
X
1.30
1
5 Years
Dry Pipe Valves - Strainers, filters, orifices
12.4.4.1.6
X
2.1
T
Annually
Alarm Devices (90 Sec)
5.3.3
12.2.7
X
2.2
T
Annually
Main Drain Test (Enter data on Page 1)
12.2.6
12.2.6.1
12.3.3.4
X
2.3
T
Annually
Antifreeze Test
5.3.4
X
2.4
T
Annually
Control Valve - Position
12.3.3.1
X
2.5
T
Annually
Control Valve - Operation
12.3.3.1
X
2.6
T
Annually
Supervisory
12.3.3.5
X
2.7
T
Annually
Preaction Valve - Priming Water
12.4.3.2.1
X
2.8
T
Annually
Preaction Valve - Low Air Pressure Alarm
12.4.3.2.10
X
2.9
T
Annually I
Preaction Valve - Full Flow Trip Test
12.4.3.2.2
X
State Fire Marshal AES 2
March 21, 2006
Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 2 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
System Riser ID: 7499
Property Information:
- - -- - - - --
Type Of System:
-or-,
Name: Bakersfield College- Industrial Tech.
❑x Wet Pipe o�Z
�Q�
Address: 1801 Panorama Dr
❑ Dry Pipe °D ` q
❑ Preaction �► ��
❑ Deluge �4E M
City: Bakersfield
NFPA 25
Item
Activity
Frequency
Description
Reference
Fail
N/A
Pass
2.10
T
Annually
Dry Pipe Valve - Priming Water
12.4.4.2.1
X
2.11
T
Annually
Dry Pipe Valve - Low Air Pressure
12.4.4.2.6
X
Alarm
2.12
T
Annually
Dry Pipe Valve - Quick- Opening
12.4.4.2.4
X
Device
2.13
T
Annually
Dry Pipe Valve - Trip
12.4.4.2.2
X
2.14
T
Annually
Backflow Preventor Assemblies
12.6.2
X
2.15
T
3 Years
Dry Pipe Valve - Full Flow Trip Test
12.4.4.2.2.2
X
2.16
T
5 Years
Gauges
5.3.2
X
2.17
T
5 Years
Pressure Reducing Valve
12.5.1.2
X
2.18
T
5 Years
Fire Department Connection Backflush
12.7.4
X
2.19
T
5 Years
Sprinklers - Extra High Temperature
5.3.1.1.1.3
X
2.20
T
5 Years
Sprinklers - Corrosive environment or
5.3.1.1.2
X
corrosive water
2.21
T
10 Years
Sprinklers - Dry
5.3.1.1.1.5
X
2.22
T
20 Years
Sprinklers - Fast Response
5.3.1.1.1.2
X
2.23
T
50 Years
Sprinklers
5.3.1.1.1
X
2.24
T
75 Years
Sprinklers 75 years in service
5.3.1.1.1.4
X
2.25
T
Sprinklers manufactured prior to 1920
5.3.1.1.1.1
X
- Re lace
3.1
M
Annually
Control Valves
12.3.4
X
3.2
M
Annually
Preaction /Deluge Valves
12.4.3.3.2
X
3.3
M
Annually
Dry Pipe Valves /Quick- Opening
12.4.4.3.2
X
Devices
3.4
M
Annually
Dry Pipe Valve - Low Point Drains
12.4.4.3.3
X
3.5
M
5 Years
Obstruction Investigation
Chapter 13
X
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 3 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
Property Information:
Name: Bakersfield College- Industrial Tech.
Address: 1801 Panorama Dr
City: Bakersfield
System Riser ID: 7499
Type Of System:
of: CAC/�d.
❑x Wet Pipe .
❑ Dry Pipe y
❑ Preaction
❑ Deluge
ARE Mp
Item
Deficiencies and Comments:
Deficiencies and Comments Item number must correspond to the Item number
of the activity listed above:
❑ See Continuation Page(s) (Indicate the number of continuation pages)
❑x PASS
❑ FAIL 01/05/2011
Signature Date
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 4 of 5
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717
Page 5of5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
System Riser ID: 7499
Property Information:--
- - -<,.
Type Of System: of CAL�,�
Name: Bakersfield College -Gym
Wet Pipe
Address: 1801 Panorama Dr
❑ Dry Pipe y a
A -O = After Operation
❑ Preaction .i
MI = Per Manufacturer's Instructions
❑ Deluge ARE M.
City: Bakersfield
Frequency
Main Drain Test Results:
Abbreviation Key:
Initial Static Pressure: (psi)
I = Inspection
T =Test
Residual Pressure: (psi)
M = Maintenance
A -O = After Operation
Restored Static Pressure: (psi)
MI = Per Manufacturer's Instructions
Item
Activity
Frequency
Description
NFPA 25
Fail
N/A
Pass
Reference
1.1
1
Daily
Preaction /Deluge Valves - Enclosure
12.4.3.1
X
Weekly
temperature
1.2
1
Daily
Dry Pipe Valves - Enclosure
12.4.4.1.1
X
Weekly
tem erature
1.3
1
Quarterly
Gauges - (Dry, Preaction, Deluge
5.2.4.2
X
S stems )
5.2.4.3
1.4
1
Quarterly
Control Valves
12.3.2.1
X
1.5
1
Quarterly
Alarm Devices
5.2.6
X
1.6
1
Quarterly
Gauges (Wet Pipe Systems)
5.2.4.1
X
1.7
1
Quarterly
Hydraulic nameplate
5.2.7
X
1.8
1
Quarterly
Pipe and Fittings
5.2.2
X
1.9
1
Quarterly
Sprinklers
5.2.1
X
1.10
1
Quarterly
Spare Sprinklers
5.2.1.3
X
1.11
1
Quarterly
Fire Department Connections
12.7.1
X
1.12
1
Quarterly
Alarm Valves - Exterior Inspection
12.4.1.1
X
1.13
1
Quarterly
Quarter)
Preaction /Deluge Valves - Exterior
12.4.3.1.6
X
Inspection
1.14
1
Quarterly
Pressure Reducing Valves
12.5.1.1
X
1.15
1
Quarterly
Dry Pipe Valves- Exterior Inspection
12.4.4.1.4
X
1.16
1
Quarterly
Backflow Preventers
12.6.1
X
1.17
1
Annual
Buildings
5.2.5
X
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 1 of 5
ANNEX B
Item
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Frequency
Date Of Inspection, Testing, Maintenance: 01105/2011
System Riser ID: 7499
Fail
Property Information:
Pass
Type Of System:
Cq���O
Name: Bakersfield
College -Gym
❑X Wet Pipe
/C�pF
Q 9
Address: 1801 Panorama
Dr
❑ Dry Pipe
1
Annually
Seismic Braces
❑ Preaction
4
X
❑ Deluge
-F
M
City: Bakersfield
Hangers (Accessible concealed spaces)
5.2.3.3
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.18
1
Annually
Hangers
5.2.3
X
1.19
1
Annually
Seismic Braces
5.2.3
X
1.20
1
5 Years
Hangers (Accessible concealed spaces)
5.2.3.3
X
1.21
1
5 Years
Seismic Braces (Accessible concealed
spaces)
5.2.3.3
X
1.22
1
5 Years
Pipe and Fittings (Accessible concealed
spaces
5.2.2.3
X
1.23
1
5 Years
Sprinklers (Accessible concealed spaces)
5.2.1.1.4
X
1.24
1
5 Years
Alarm Valves - Interior Inspection
12.4.1.2
X
1.25
1
5 Years
Alarm Valves - Strainers, filters, orifices
12.4.1.2
X
1.26
1
5 Years
Check Valves - Interior Inspection
12.4.2.1
X
1.27
1
5 Years
Preaction /Deluge Valves - Interior
Inspection
12.4.3.1.7
X
1.28
1
5 Years
Preaction /Deluge Valves - Strainers,
filters, orifices
12.4.3.1.8
X
1.29
1
5 Years
Dry Pipe Valves - Interior Inspection
12.4.4.1.5
X
1.30
1
5 Years
Dry Pipe Valves - Strainers, filters, orifices
12.4.4.1.6
X
2.1
T
Annually
Alarm Devices (90 Sec)
5.3.3
12.2.7
X
2.2
T
Annually
Main Drain Test (Enter data on Page 1)
12.2.6
12.2.6.1
12.3.3.4
X
2.3
T
Annually
Antifreeze Test
5.3.4
X
2.4
T
Annually
Control Valve - Position
12.3.3.1
X
2.5
T
Annually
Control Valve - Operation
12.3.3.1
X
2.6
T
Annually
Supervisory
12.3.3.5
X
2.7
T
Annually
Preaction Valve - Priming Water
12.4.3.2.1
X
2.8
T
Annually
Preaction Valve - Low Air Pressure Alarm
12.4.3.2.10
X
2.9 j
T j
Annually j
Preaction Valve - Full Flow Trip Test
12.4.3.2.2
X
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 2 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended bV CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
System Riser ID: 7499
Property Information:
-
Type Of System: F CA
Name: Bakersfield College -Gym
❑x Wet Pipe
Address: 1801 Panorama Dr
❑ Dry Pipe °' v
❑ Preaction �►
❑ Deluge SAE p
City: Bakersfield
NFPA 25
Item
Activity
Frequency
Description
Reference
Fail
N/A
Pass
2.10
T
Annually
Dry Pipe Valve - Priming Water
12.4.4.2.1
X
2.11
T
Annually
Annual/
Dry Pipe Valve - Low Air Pressure
12.4.4.2.6
X
Alarm
2.12
T
Annual/
Annually
Dry Pipe Valve - Quick- Opening
12.4.4.2.4
X
Device
2.13
T
Annually
Dry Pipe Valve - Trip
12.4.4.2.2
X
2.14
T
Annually
Backflow Preventor Assemblies
12.6.2
X
2.15
T
3 Years
Dry Pipe Valve - Full Flow Trip Test
12.4.4.2.2.2
X
2.16
T
5 Years
Gauges
5.3.2
X
2.17
T
5 Years
Pressure Reducing Valve
12.5.1.2
X
2.18
T
5 Years
Fire Department Connection Backflush
12.7.4
X
2.19
T
5 Years
Sprinklers - Extra High Temperature
5.3.1.1.1.3
X
2.20
T
5 Years
Sprinklers - Corrosive environment or
5.3.1.1.2
X
corrosive water
2.21
T
10 Years
Sprinklers - Dry
5.3.1.1.1.5
X
2.22
T
20 Years
Sprinklers - Fast Response
5.3.1.1.1.2
X
223
T
50 Years
Sprinklers
5.3.1.1.1
X
2.24
T
75 Years
Sprinklers 75 years in service
5.3.1.1.1.4
X
2.25
T
Sprinklers manufactured prior to 1920
5.3.1.1.1.1
X
- Replace
3.1
M
Annually
Control Valves
12.3.4
X
32
M
Annually
Preaction /Deluge Valves
12.4.3.3.2
X
3.3
M
Annually
Dry Pipe Valves /Quick- Opening
12.4.4.3.2
X
Devices
3.4
M
Annually
Dry Pipe Valve - Low Point Drains
12.4.4.3.3
X
3.5
M
5 Years
Obstruction Investigation
Chapter 13
X
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 3 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
Property Information:
Name: Bakersfield College -Gym
Address: 1801 Panorama Dr
City: Bakersfield
System Riser ID: 7499
Type Of System:
of Cqt/��
❑x Wet Pipe �Q
❑ Dry Pipe y
❑ Preaction �► .,
❑ Deluge f
ARE
Item
Deficiencies and Comments:
Deficiencies and Comments Item number must correspond to the Item number
of the activity listed above:
❑ See Continuation Page(s) (Indicate the number of continuation pages)
❑x PASS
❑ FAIL 01/05/2011
Signature Date
State Fire Marshal AES 2
March 21, 2006
Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 4 of 5
Inspection performed by: RLH Fire Protection - Bakersfield, CA -777717
Page 5 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
System Riser ID: 7499
Property Information:
-- - - -.
Type Of System: of C44j
Name: Bakersfield College -Field House
Wet Pipe ti
Address: 1801 Panorama Dr
y
❑ Dry Pipe r" a
A -O = After Operation
❑ Preaction►
MI = Per Manufacturer's Instructions
❑ DelugegE`Mp
City: Bakersfield
Frequency
Main Drain Test Results:
Abbreviation Key:
Initial Static Pressure: (psi)
I = Inspection
T =Test
Residual Pressure: (psi)
M = Maintenance
A -O = After Operation
Restored Static Pressure: (psi)
MI = Per Manufacturer's Instructions
Item
Activity
Frequency
Description
NFPA 25
Fail
N/A
Pass
Reference
1.1
1
Daily
Preaction /Deluge Valves - Enclosure
12.4.3.1
X
Weekly
temperature
1.2
1
Daily
Dry Pipe Valves - Enclosure
12.4.4.1.1
X
Week/
tem erature
1.3
1
Quarterly
Gauges - (Dry, Preaction, Deluge
5.2.4.2
X
Systems)
5.2.4.3
1.4
1
Quarterly
Control Valves
12.3.2.1
X
1.5
1
Quarterly
Alarm Devices
5.2.6
X
1.6
I
Quarterly
Gauges (Wet Pipe Systems)
5.2.4.1
X
1.7
1
Quarterly
Hydraulic nameplate
5.2.7
X
1.8
1
Quarterly
Pipe and Fittings
5.2.2
X
1.9
1
Quarterly
Sprinklers
5.2.1
X
1.10
1
Quarterly
Spare Sprinklers
5.2.1.3
X
1.11
1
Quarterly
Fire Department Connections
12.7.1
X
1.12
1
Quarterly
Alarm Valves - Exterior Inspection
12.4.1.1
X
1.13
1
Quarterly
Quarter/
Preaction /Deluge Valves - Exterior
12.4.3.1.6
X
Inspection
1.14
1
Quarterly
Pressure Reducing Valves
12.5.1.1
X
1.15
1
Quarterly
Dry Pipe Valves- Exterior Inspection
12.4.4.1.4
X
1.16
1
Quarterly
Backflow Preventers
12.6.1
X
1.17
1
Annual
Buildings
5.2.5
X
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 1 of 5
ANNEX B
Item
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Frequency
Date Of Inspection, Testing, Maintenance: 01/05/2011
System Riser ID: 7499
Fail
Property Information:
Pass
Type Of System:
1
Name: Bakersfield
College -Field House
Q Wet Pipe
of CaC�,�.
,� p
v 9
Address: 1801 Panorama
Dr
❑ Dry Pipe
�' a
Annually
Seismic Braces
❑ Preaction
X
❑ Deluges
M
City: Bakersfield�AE
Hangers (Accessible concealed spaces)
5.2.3.3
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.18
1
Annually
Hangers
5.2.3
X
1.19
1
Annually
Seismic Braces
5.2.3
X
1.20
1
5 Years
Hangers (Accessible concealed spaces)
5.2.3.3
X
1.21
1
5 Years
Seismic Braces (Accessible concealed
s aces
5.2.3.3
X
1.22
1
5 Years
Pipe and Fittings (Accessible concealed
spaces)
5.2.2.3
X
1.23
1
5 Years
Sprinklers (Accessible concealed spaces)
5.2.1.1.4
X
1.24
1
5 Years
Alarm Valves - Interior Inspection
12.4.1.2
X
1.25
1
5 Years
Alarm Valves - Strainers, filters, orifices
12.4.1.2
X
1.26
1
5 Years
Check Valves - Interior Inspection
12.4.2.1
X
1.27
1
5 Years
Preaction /Deluge Valves - Interior
Inspection
12.4.3.1.7
X
1.28
1
5 Years
Preaction /Deluge Valves - Strainers,
filters, orifices
12.4.3.1.8
X
1.29
1
5 Years
Dry Pipe Valves - Interior Inspection
12.4.4.1.5
X
1.30
1
5 Years
Dry Pipe Valves - Strainers, filters, orifices
12.4.4.1.6
X
2.1
T
Annually
Alarm Devices (90 Sec)
5.3.3
12.2.7
X
2.2
T
Annually
Main Drain Test (Enter data on Page 1)
12.2.6
12.2.6.1
12.3.3.4
X
2.3
T
Annually
Antifreeze Test
5.3.4
X
2.4
T
Annually
Control Valve - Position
12.3.3.1
X
2.5
T
Annually
Control Valve - Operation
12.3.3.1
X
2.6
T
Annually
Supervisory
12.3.3.5
X
2.7
T
Annually
Preaction Valve - Priming Water
12.4.3.2.1
X
2.8
T
Annually
Preaction Valve - Low Air Pressure Alarm
12.4.3.2.10
X
2.9
T
Annually I
Preaction Valve - Full Flow Trip Test
12.4.3.2.2
X
State Fire Marshal AES 2
March 21, 2006
Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 2 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
Property Information:
Name: Bakersfield College -Field House
Address: 1801 Panorama Dr
City: Bakersfield
System Riser ID: 7499
Type Of System: F CAC,�o9
Wet Pipe -01f
❑ Dry Pipe °� a
❑ Preaction �y►,
❑ Deluge ARE M '
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
2.10
T
Annually
Dry Pipe Valve - Priming Water
12.4.4.2.1
X
2.11
T
Annually
Dry Pipe Valve - Low Air Pressure
Alarm
12.4.4.2.6
X
2.12
T
Annually
y
ry Pipe Valve - Quick- Opening
Device
12.4.4.2.4
X
2.13
T
Annually
Dry Pipe Valve - Trip
12.4.4.2.2
X
2.14
T
Annually
Backflow Preventor Assemblies
12.6.2
X
2.15
T
3 Years
Dry Pipe Valve - Full Flow Trip Test
12.4.4.2.2.2
X
2.16
T
5 Years
Gauges
5.3.2
X
2.17
T
5 Years
Pressure Reducing Valve
12.5.1.2
X
2.18
T
5 Years
Fire Department Connection Backflush
12.7.4
X
2.19
T
5 Years
Sprinklers - Extra High Temperature
5.3.1.1.1.3
X
2.20
T
5 Years
Sprinklers - Corrosive environment or
corrosive water
5.3.1.1.2
X
2.21
T
10 Years
Sprinklers - Dry
5.3.1.1.1.5
X
2.22
T
20 Years
Sprinklers - Fast Response
5.3.1.1.1.2
X
2.23
T
50 Years
Sprinklers
5.3.1.1.1
X
2.24
T
75 Years
Sprinklers 75 years in service
5.3.1.1.1.4
X
2.25
T
Sprinklers manufactured prior to 1920
- Replace
5.3.1.1.1.1
X
3.1
M
Annually
Control Valves
12.3.4
X
3.2
M
Annually
Preaction /Deluge Valves
12.4.3.3.2
X
3.3
M
Annually
y
ry Pipe Valves /Quick- Opening
Devices
12.4.4.3.2
X
3.4
M
Annually
Dry Pipe Valve - Low Point Drains
12.4.4.3.3
X
3.5
M
5 Years
Obstruction Investigation
Chapter 13
X
State Fire Marshal AES 2
March 21, 2006
Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 3 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
Property Information:
Name: Bakersfield College-Field House
Address: 1801 Panorama Dr
City: Bakersfield
System Riser ID: 7499
. _..... .
Type Of System:
O�;Cat,��9
Fxj Wet Pipe
❑ Dry Pipe °� y
❑ Preaction �f
❑ Deluge ARE M�
Item
Deficiencies and Comments:
Deficiencies and Comments Item number must correspond to the Item number
of the activity listed above:
❑ See Continuation Page(s) (Indicate the number of continuation pages)
❑x PASS
❑ FAIL 01/05/2011
Signature Date
State Fire Marshal AES 2
March 21, 2006
Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 4 of 5
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717
Page 5 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
System Riser ID: 7499
Property Information:
-. -
Type Of System: F Cq
C�,NO,A
Name: Bakersfield College -Child Care 400
Wet Pipe
Address: 1801 Panorama Dr
❑ Dry Pipe a
A -O = After Operation
❑ Preaction �►
MI = Per Manufacturer's Instructions
❑ DelugepE Mp
City: Bakersfield
Frequency
Main Drain Test Results:
Abbreviation Key:
Initial Static Pressure: (psi)
I = Inspection
T =Test
Residual Pressure: (psi)
M = Maintenance
A -O = After Operation
Restored Static Pressure: (psi)
MI = Per Manufacturer's Instructions
Item
Activity
Frequency
Description
NFPA 25
Fail
N/A
Pass
Reference
1.1
1
Daily
Preaction /Deluge Valves - Enclosure
12.4.3.1
X
Weekly
temperature
1.2
I
Daily
Dry Pipe Valves - Enclosure
12.4.4.1.1
X
Weeklv
temperature
1.3
1
Quarterly
Gauges - (Dry, Preaction, Deluge
5.2.4.2
X
Systems)
5.2.4.3
1.4
1
Quarterly
Control Valves
12.3.2.1
X
1.5
1
Quarterly
Alarm Devices
5.2.6
X
1.6
1
Quarterly
Gauges (Wet Pipe Systems)
5.2.4.1
X
1.7
1
Quarterly
Hydraulic nameplate
5.2.7
X
1.8
1
Quarterly
Pipe and Fittings
5.2.2
X
1.9
1
Quarterly
Sprinklers
5.2.1
X
1.10
1
Quarterly
Spare Sprinklers
5.2.1.3
X
1.11
1
Quarterly
Fire Department Connections
12.7.1
X
1.12
I
Quarterly
Alarm Valves - Exterior Inspection
12.4.1.1
X
1.13
I
Quarterly
Quarter)
Preaction /Deluge Valves - Exterior
12.4.3.1.6
X
Inspection
1.14
1
Quarterly
Pressure Reducing Valves
12.5.1.1
X
1.15
1
Quarterly
Dry Pipe Valves- Exterior Inspection
12.4.4.1.4
X
1.16
1
Quarterly
Backflow Preventers
12.6.1
X
1.17
1
Annual
Buildings
5.2.5
X
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 1 of 5
ANNEX B
Item
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Frequency
Date Of Inspection, Testing, Maintenance: 01/05/2011
System Riser ID: 7499
Fail
Property Information:
Pass
Type Of System:
1
Annually
Hangers
5.2.3
of Cq�,�
Name: Bakersfield
College -Child Care 400
Wet Pipe
Q�� . �q
Address: 1801 Panorama
Dr
❑ Dry Pipe
°q D
X
❑ Preaction
.,
5 Years
Hangers (Accessible concealed spaces)
5.2.3.3
4
X
❑ Deluge
-F
SAE M�
City: Bakersfield
Seismic Braces (Accessible concealed
spaces)
5.2.3.3
_..
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.18
1
Annually
Hangers
5.2.3
X
1.19
I
Annually
Seismic Braces
5.2.3
X
1.20
1
5 Years
Hangers (Accessible concealed spaces)
5.2.3.3
X
1.21
1
5 Years
Seismic Braces (Accessible concealed
spaces)
5.2.3.3
X
1.22
1
5 Years
Pipe and Fittings (Accessible concealed
spaces
5.2.2.3
X
1.23
1
5 Years
Sprinklers (Accessible concealed spaces)
5.2.1.1.4
X
1.24
1
5 Years
Alarm Valves - Interior Inspection
12.4.1.2
X
1.25
1
5 Years
Alarm Valves - Strainers, filters, orifices
12.4.1.2
X
1.26
1
5 Years
Check Valves - Interior Inspection
12.4.2.1
X
1.27
1
5 Years
Preaction /Deluge Valves - Interior
Inspection
12.4.3.1.7
X
1.28
1
5 Years
Preaction /Deluge Valves - Strainers,
filters, orifices
12.4.3.1.8
X
1.29
1
5 Years
Dry Pipe Valves - Interior Inspection
12.4.4.1.5
X
1.30
1
5 Years
Dry Pipe Valves - Strainers, filters, orifices
12.4.4.1.6
X
2.1
T
Annually
Alarm Devices (90 Sec)
5.3.3
12.2.7
X
2.2
T
Annually
Main Drain Test (Enter data on Page 1)
12.2.6
12.2.6.1
12.3.3.4
X
2.3
T
Annually
Antifreeze Test
5.3.4
X
2.4
T
Annually
Control Valve - Position
12.3.3.1
X
2.5
T
Annually
. Control Valve - Operation
12.3.3.1
X
2.6
T
Annually
Supervisory
12.3.3.5
X
2.7
T
Annually
Preaction Valve - Priming Water
12.4.3.2.1
X
2.8
T
Annually
Preaction Valve - Low Air Pressure Alarm
12.4.3.2.10
X
2.9
T
Annually
Preaction Valve - Full Flow Trip Test
12.4.3.2.2
X
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 2 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
Property Information:
Name: Bakersfield College -Child Care 400
Address: 1801 Panorama Dr
City: Bakersfield
System Riser ID: 7499
Type Of System: F Ga
O &,
Wet Pipe a Z .
❑ Dry Pipe °p a
❑ Preaction �►
❑ DelugeAgE Mp
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
2.10
T
Annually
Dry Pipe Valve - Priming Water
12.4.4.2.1
X
2.11
T
Annually
y
ry Pipe Valve - Low Air Pressure
Alarm
12.4.4.2.6
X
2.12
T
Annually
Dry Pipe Valve - Quick- Opening
Device
12.4.4.2.4
X
2.13
T
Annually
Dry Pipe Valve - Trip
12.4.4.2.2
X
2.14
T
Annually
Backflow Preventor Assemblies
12.6.2
X
2.15
T
3 Years
Dry Pipe Valve - Full Flow Trip Test
12.4.4.2.2.2
X
2.16
T
5 Years
Gauges
5.3.2
X
2.17
T
5 Years
Pressure Reducing Valve
12.5.1.2
X
2.18
T
5 Years
Fire Department Connection Backflush
12.7.4
X
2.19
T
5 Years
Sprinklers - Extra High Temperature
5.3.1.1.1.3
X
2.20
T
5 Years
Sprinklers - Corrosive environment or
corrosive water
5.3.1.1.2
X
2.21
T
10 Years
Sprinklers - Dry
5.3.1.1.1.5
X
2.22
T
20 Years
Sprinklers - Fast Response
5.3.1.1.1.2
X
2.23
T
50 Years
Sprinklers
5.3.1.1.1
X
2.24
T
75 Years
Sprinklers 75 years in service
5.3.1.1.1.4
X
2.25
T
Sprinklers manufactured prior to 1920
- Re lace
5.3.1.1.1.1
X
3.1
M
Annually
Control Valves
12.3.4
X
3.2
M
Annually
Preaction /Deluge Valves
12.4.3.3.2
X
3.3
M
Annually
Dry Pipe Valves /Quick- Opening
Devices
12.4.4.3.2
X
3.4
M
Annually
Dry Pipe Valve - Low Point Drains
12.4.4.3.3
X
3.5
M
5 Years
Obstruction Investigation
Chapter 13
X
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 3 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
Property Information:
Name: Bakersfield College -Child Care 400
Address: 1801 Panorama Dr
City: Bakersfield
System Riser ID: 7499
Type Of System: F CA
D
❑x Wet Pipe
❑ Dry Pipe co r:
❑ Preaction
E] Deluge .cam P
�'
Item
Deficiencies and Comments:
Deficiencies and Comments Item number must correspond to the Item number
of the activity listed above:
❑ See Continuation Page(s) (Indicate the number of continuation pages)
❑x PASS —
❑ FAIL ✓ / 01/05/2011
Signature Date
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 4 of 5
inspection performed by: RLH Fire Protection - Bakersfield, CA - 777797
Page 5 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended bv CCR Title 19
Date Of Inspection, Testing, Maintenance: 01105/2011
System Riser ID: 7499
Property Information:
- -- -
Type Of System:
of CAC'�Cp
Name: Bakersfield College -Child Care 300
Wet Pipe
Address: 1801 Panorama Dr
❑ Dry Pipe ti �►
A -O = After Operation
❑ Preaction �g►�, �P.
MI = Per Manufacturer's Instructions
❑ DelugeiE M ":
City: Bakersfield
Frequency
Main Drain Test Results:
Abbreviation Key:
Initial Static Pressure: (psi)
I = Inspection
T =Test
Residual Pressure: (psi)
M = Maintenance
A -O = After Operation
Restored Static Pressure: (psi)
MI = Per Manufacturer's Instructions
Item
Activity
Frequency
Description
NFPA 25
Fail
N/A
Pass
Reference
1.1
1
Daily
Preaction /Deluge Valves - Enclosure
12.4.3.1
X
Weekly
tem erature
1.2
I
Daily
Dry Pipe Valves - Enclosure
12.4.4.1.1
X
Weeklv
tem erature
1.3
1
Quarterly
Gauges - (Dry, Preaction, Deluge
5.2.4.2
X
S stems )
5.2.4.3
1.4
1
Quarterly
Control Valves
12.3.2.1
X
1.5
1
Quarterly
Alarm Devices
5.2.6
X
1.6
1
Quarterly
Gauges (Wet Pipe Systems)
5.2.4.1
X
1.7
1
Quarterly
Hydraulic nameplate
5.2.7
X
1.8
1
Quarterly
Pipe and Fittings
5.2.2
X
1.9
1
Quarterly
Sprinklers
5.2.1
X
1.10
1
Quarterly
Spare Sprinklers
5.2.1.3
X
1.11
1
Quarterly
Fire Department Connections
12.7.1
X
1.12
1
Quarterly
Alarm Valves - Exterior Inspection
12.4.1.1
X
1.13
1
Quarterly
Quarter)
Preaction /Deluge Valves - Exterior
12.4.3.1.6
X
Inspection
1.14
1
Quarterly
Pressure Reducing Valves
12.5.1.1
X
1.15
1
Quarterly
Dry Pipe Valves- Exterior Inspection
12.4.4.1.4
X
1.16
1
Quarterly
Backflow Preventers
12.6.1
X
1.17
1
Annual
Buildings
5.2.5
X
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 1 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Activity
Date Of Inspection, Testing, Maintenance: 01105/2011
Description
System Riser ID: 7499
Fail
Property Information:
Pass
Type Of System:
OF CAL,
Name: Bakersfield College -Child Care 300
Hangers
❑x Wet Pipe
,�� p
� .p
Address: 1801 Panorama Dr
E] Dry Pipe
`9 y
Annually
Seismic Braces
❑ Preaction
.,
X
1.20
1
5 Years
Hangers (Accessible concealed spaces)
❑ Deluge�iE.M
City: Bakersfield
1.21
I
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.18
1
Annually
Hangers
5.2.3
X
1.19
1
Annually
Seismic Braces
5.2.3
X
1.20
1
5 Years
Hangers (Accessible concealed spaces)
5.2.3.3
X
1.21
I
5 Years
Seismic Braces (Accessible concealed
spaces)
5.2.3.3
X
1.22
1
5 Years
Pipe and Fittings (Accessible concealed
spaces
5.2.2.3
X
1.23
1
5 Years
Sprinklers (Accessible concealed spaces)
5.2.1.1.4
X
1.24
1
5 Years
Alarm Valves - Interior Inspection
12.4.1.2
X
1.25
1
5 Years
Alarm Valves - Strainers, filters, orifices
12.4.1.2
X
1.26
1
5 Years
Check Valves - Interior Inspection
12.4.2.1
X
1.27
1
5 Years
Preaction /Deluge Valves - Interior
Inspection
12.4.3.1.7
X
1.28
1
5 Years
Preaction /Deluge Valves - Strainers,
filters, orifices
12.4.3.1.8
X
1.29
1
5 Years
Dry Pipe Valves - Interior Inspection
12.4.4.1.5
X
1.30
1
5 Years
Dry Pipe Valves - Strainers, filters, orifices
12.4.4.1.6
X
2.1
T
Annually
Alarm Devices (90 Sec)
5.3.3
12.2.7
X
2.2
T
Annually
Main Drain Test (Enter data on Page 1)
12.2.6
12.2.6.1
12.3.3.4
X
2.3
T
Annually
Antifreeze Test
5.3.4
X
2.4
T
Annually
Control Valve - Position
12.3.3.1
X
2.5
T
Annually
Control Valve - Operation
12.3.3.1
X
2.6
T
Annually
Supervisory
12.3.3.5
X
2.7
T
Annually
Preaction Valve - Priming Water
12.4.3.2.1
X
2.8
T
Annually
Preaction Valve - Low Air Pressure Alarm
12.4.3.2.10
X
2.9
T
Annually
Preaction Valve - Full Flow Trip Test
12.4.3.2.2
X
State Fire Marshal AES 2
March 21, 2006
Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 2 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
Property Information:
Name: Bakersfield College -Child Care 300
Address: 1801 Panorama Dr
City: Bakersfield
System Riser ID: 7499
— -
Type Of System: F CA ��'�p
❑x Wet Pipe
❑ Dry Pipe °� a
❑ Preaction �►
Deluge
❑ 9 E "M
--- . -. -..-
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
2.10
T
Annually
Dry Pipe Valve - Priming Water
12.4.4.2.1
X
2.11
T
Annually
Dry Pipe Valve - Low Air Pressure
Alarm
12.4.4.2.6
X
2.12
T
Annually
Dry Pipe Valve - Quick- Opening
Device
12.4.4.2.4
X
2.13
T
Annually
Dry Pipe Valve - Trip
12.4.4.2.2
X
2.14
T
Annually
Backflow Preventor Assemblies
12.6.2
X
2.15
T
3 Years
Dry Pipe Valve - Full Flow Trip Test
12.4.4.2.2.2
X
2.16
T
5 Years
Gauges
5.3.2
X
2.17
T
5 Years
Pressure Reducing Valve
12.5.1.2
X
2.18
T
5 Years
Fire Department Connection Backflush
12.7.4
X
2.19
T
5 Years
Sprinklers - Extra High Temperature
5.3.1.1.1.3
X
2.20
T
5 Years
Sprinklers - Corrosive environment or
corrosive water
5.3.1.1.2
X
2.21
T
10 Years
Sprinklers - Dry
5.3.1.1.1.5
X
2.22
T
20 Years
Sprinklers - Fast Response
5.3.1.1.1.2
X
2.23
T
50 Years
Sprinklers
5.3.1.1.1
X
2.24
T
75 Years
Sprinklers 75 years in service
5.3.1.1.1.4
X
2.25
T
Sprinklers manufactured prior to 1920
- Re lace
5.3.1.1.1.1
X
3.1
M
Annually
Control Valves
12.3.4
X
3.2
M
Annually
Preaction /Deluge Valves
12.4.3.3.2
X
3.3
M
Annually
Dry Pipe Valves /Quick- Opening
Devices
12.4.4.3.2
X
3.4
M
Annually
Dry Pipe Valve - Low Point Drains
12.4.4.3.3
X
3.5
M
5 Years
Obstruction Investigation
Chapter 13
X
State Fire Marshal AES 2
March 21, 2006
Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 3 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
Property Information:
Name: Bakersfield College -Child Care 300
Address: 1801 Panorama Dr
City: Bakersfield
System Riser ID: 7499
_.
Type Of System: f CA'
ticQ
❑X Wet Pipe
❑ Dry Pipe y
❑ Preaction �► �,
❑ Deluge
E M
Item
Deficiencies and Comments:
Deficiencies and Comments Item number must correspond to the Item number
of the activity listed above:
❑ See Continuation Page(s) (Indicate the number of continuation pages)
x PASS ,,n -
❑
❑ FAIL 1) 01 /05/2011
Signature Date
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 4 of 5
inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717
Page 5 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
System Riser ID: 7499
Property Information:
Type Of System: p Cq
o C,�p
Name: Bakersfield College -Book Store
❑x Wet Pipe
Address: 1801 Panorama Dr
❑ Dry Pipe a
A -O = After Operation
❑ Preaction
MI = Per Manufacturer's Instructions
❑ Deluge
City: Bakersfield
Frequency
Main Drain Test Results:
Abbreviation Key:
Initial Static Pressure: (psi)
I = Inspection
T = Test
Residual Pressure: (psi)
M = Maintenance
A -O = After Operation
Restored Static Pressure: (psi)
MI = Per Manufacturer's Instructions
Item
Activity
Frequency
Description
NFPA 25
Fail
N/A
Pass
Reference
1.1
1
Daily
Preaction /Deluge Valves - Enclosure
12.4.3.1
X
Weekly
terniperature
1.2
I
Daily
Dry Pipe Valves - Enclosure
12.4.4.1.1
X
WeekIv
tem erature
1.3
1
Quarterly
Gauges - (Dry, Preaction, Deluge
5.2.4.2
X
S stems )
5.2.4.3
1.4
1
Quarterly
Control Valves
12.3.2.1
X
1.5
1
Quarterly
Alarm Devices
5.2.6
X
1.6
I
Quarterly
Gauges (Wet Pipe Systems)
5.2.4.1
X
1.7
1
Quarterly
Hydraulic nameplate
5.2.7
X
1.8
1
Quarterly
Pipe and Fittings
5.2.2
X
1.9
1
Quarterly
Sprinklers
5.2.1
X
1.10
1
Quarterly
Spare Sprinklers
5.2.1.3
X
1.11
1
Quarterly
Fire Department Connections
12.7.1
X
1.12
I
Quarterly
Alarm Valves - Exterior Inspection
12.4.1.1
X
1.13
I
Quarterly
Quarter)
Preaction /Deluge Valves - Exterior
12.4.3.1.6
X
Inspection
1.14
1
Quarterly
Pressure Reducing Valves
12.5.1.1
X
1.15
1
Quarterly
Dry Pipe Valves- Exterior Inspection
12.4.4.1.4
X
1.16
1
Quarterly
Backflow Preventers
12.6.1
X
1.17
I
Annual
Buildings
5.2.5
X
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 1 of 5
ANNEX B
Item
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Frequency
Date Of Inspection, Testing, Maintenance: 01/05/2011
System Riser ID: 7499
Fail
Property Information:
Pass
Type Of System:
1
Annually
Hangers
5.2.3
Cqt,��o
Name: Bakersfield
College -Book Store
❑x Wet Pipe
I
Address: 1801 Panorama
Dr
❑ Dry Pipe
�' y
X
❑ Preaction
.,
5 Years
Hangers (Accessible concealed spaces)
5.2.3.3
X
Deluge
❑ 9
ARE p
City: Bakersfield
Seismic Braces (Accessible concealed
spaces)
5.2.3.3
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.18
1
Annually
Hangers
5.2.3
X
1.19
I
Annually
Seismic Braces
5.2.3
X
1.20
1
5 Years
Hangers (Accessible concealed spaces)
5.2.3.3
X
1.21
1
5 Years
Seismic Braces (Accessible concealed
spaces)
5.2.3.3
X
1.22
1
5 Years
Pipe and Fittings (Accessible concealed
spaces)
5.2.2.3
X
1.23
1
5 Years
Sprinklers (Accessible concealed spaces)
5.2.1.1.4
X
1.24
1
5 Years
Alarm Valves - Interior Inspection
12.4.1.2
X
1.25
1
5 Years
Alarm Valves - Strainers, filters, orifices
12.4.1.2
X
1.26
1
5 Years
Check Valves - Interior Inspection
12.4.2.1
X
1.27
1
5 Years
Preaction /Deluge Valves - Interior
Inspection
12.4.3.1.7
X
1.28
1
5 Years
Preaction /Deluge Valves - Strainers,
filters, orifices
12.4.3.1.8
X
1.29
1
5 Years
Dry Pipe Valves - Interior Inspection
12.4.4.1.5
X
1.30
1
5 Years
Dry Pipe Valves - Strainers, filters, orifices
12.4.4.1.6
X
2.1
T
Annually
Alarm Devices (90 Sec)
5.3.3
12.2.7
X
2.2
T
Annually
Main Drain Test (Enter data on Page 1)
12.2.6
12.2.6.1
12.3.3.4
X
2.3
T
Annually
Antifreeze Test
5.3.4
X
2.4
T
Annually
Control Valve - Position
12.3.3.1
X
2.5
T
Annually
Control Valve - Operation
12.3.3.1
X
2.6
T
Annually
Supervisory
12.3.3.5
X
2.7
T
Annually
Preaction Valve - Priming Water
12.4.3.2.1
X
2.8
T
Annually
Preaction Valve - Low Air Pressure Alarm
12.4.3.2.10
X
F2.9
T
Annually I
Preaction Valve - Full Flow Trip Test
12.4.3.2.2
X
State Fire Marshal AES 2
March 21, 2006
Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 2 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
System Riser ID: 7499
Property Information:
Type Of System: of
cqt,'
Name: Bakersfield College -Book Store
Wet Pipe
Z
Address: 1801 Panorama Dr
❑ Dry Pipe _ a.
❑ Preaction .r
❑ Deluge E M
City: Bakersfield
NFPA 25
Item
Activity
Frequency
Description
Reference
Fail
N/A
Pass
2.10
T
Annually
Dry Pipe Valve - Priming Water
12.4.4.2.1
X
2.11
T
Annually
Dry Pipe Valve - Low Air Pressure
12.4.4.2.6
X
Alarm
2.12
T
Annually
y
ry Pipe Valve - Quick- Opening
12.4.4.2.4
X
Device
2.13
T
Annually
Dry Pipe Valve - Trip
12.4.4.2.2
X
2.14
T
Annually
Backflow Preventor Assemblies
12.6.2
X
2.15
T
3 Years
Dry Pipe Valve - Full Flow Trip Test
12.4.4.2.2.2
X
2.16
T
5 Years
Gauges
5.3.2
X
2.17
T
5 Years
Pressure Reducing Valve
12.5.1.2
X
2.18
T
5 Years
Fire Department Connection Backflush
12.7.4
X
2.19
T
5 Years
Sprinklers - Extra High Temperature
5.3.1.1.1.3
X
2.20
T
5 Years
Sprinklers - Corrosive environment or
5.3.1.1.2
X
corrosive water
2.21
T
10 Years
Sprinklers - Dry
5.3.1.1.1.5
X
2.22
T
20 Years
Sprinklers - Fast Response
5.3.1.1.1.2
X
2.23
T
50 Years
Sprinklers
5.3.1.1.1
X
2.24
T
75 Years
Sprinklers 75 years in service
5.3.1.1.1.4
X
2.25
T
Sprinklers manufactured prior to 1920
5.3.1.1.1.1
X
- Replace
3.1
M
Annually
Control Valves
12.3.4
X
3.2
M
Annually
Preaction /Deluge Valves
12.4.3.3.2
X
3.3
Annuall
Dry Pipe Valves /Quick- Opening
12.4.4.3.2
X
Devices
3.4
M
Annually
Dry Pipe Valve - Low Point Drains
12.4.4.3.3
X
3.5
M
5 Years
Obstruction Investigation
Chapter 13
X
State Fire Marshal AES 2
March 21, 2006
Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 3 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
Property Information:
Name: Bakersfield College -Book Store
Address: 1801 Panorama Dr
City: Bakersfield
System Riser ID: 7499
Type Of System:
���f CAC�,�o
❑x Wet Pipe Q
❑ Dry Pipe GD y
❑ Preaction
❑ DelugeRF'Mp,
Item
Deficiencies and Comments:
Deficiencies and Comments Item number must correspond to the Item number
of the activity listed above:
❑ See Continuation Page(s) (Indicate the number of continuation pages)
❑x PASS _
F1 FAIL 01/05/2011
Signature Date
State Fire Marshal AES 2
March 21, 2006
Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 4 of 5
inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717
Page 5 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
System Riser ID: 7499
Property Information:
-
Type Of System:
Name: Bakersfield College -Child Care 200
Wet Pipe
Address: 1801 Panorama Dr
❑ Dry Pipe a
A -O = After Operation
❑ Preaction �►'' �+:
MI = Per Manufacturer's Instructions
❑ Deluge ARE M
City: Bakersfield
Frequency
Main Drain Test Results:
Abbreviation Key:
Initial Static Pressure: (psi)
I = Inspection
T = Test
Residual Pressure: (psi)
M = Maintenance
A -O = After Operation
Restored Static Pressure: (psi)
MI = Per Manufacturer's Instructions
Item
Activity
Frequency
Description
NFPA 25
Fail
N/A
Pass
Reference
1.1
1
Daily
Preaction /Deluge Valves - Enclosure
12:4.3.1
X
Weekly
temperature
1.2
I
Daily
Dry Pipe Valves - Enclosure
12.4.4.1.1
X
Week/
tem erature
1.3
1
Quarterly
Gauges - (Dry, Preaction, Deluge
5.2.4.2
X
Systems)
5.2.4.3
1.4
1
Quarterly
Control Valves
12.3.2.1
X
1.5
1
Quarterly
Alarm Devices
5.2.6
X
1.6
I
Quarterly
Gauges (Wet Pipe Systems)
5.2.4.1
X
1.7
1
Quarterly
Hydraulic nameplate
5.2.7
X
1.8
1
Quarterly
Pipe and Fittings
5.2.2
X
1.9
1
Quarterly
Sprinklers
5.2.1
X
1.10
1
Quarterly
Spare Sprinklers
5.2.1.3
X
1.11
1
Quarterly
Fire Department Connections
12.7.1
X
1.12
I
Quarterly
Alarm Valves - Exterior Inspection
12.4.1.1
X
1.13
I
Quarterly
Preaction /Deluge Valves - Exterior
12.4. 3.1.6
X
Inspection
1.14
1
Quarterly
Pressure Reducing Valves
12.5.1.1
X
1.15
1
Quarterly
Dry Pipe Valves- Exterior Inspection
12.4.4.1.4
X
1.16
1
Quarterly
Backflow Preventers
12.6.1
X
1.17
I
Annual
Buildings
5.2.5
X
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 1 of 5
ANNEX B
Item
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Frequency
Date Of Inspection, Testing, Maintenance: 01/05/2011
System Riser ID: 7499
Fail
Property Information:
Pass
Type Of System:
_
Name: Bakersfield
College -Child Care 200
❑x Wet Pipe
of: Cqt��O
Address: 1801 Panorama
Dr
❑ Dry Pipe
1
Annually
Seismic Braces
❑ Preaction.,
X
1.20
4
5 Years
Hangers (Accessible concealed spaces)
❑ Deluge
SAE M
City: Bakersfield
1.21
_..
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.18
1
Annually
Hangers
5.2.3
X
1.19
1
Annually
Seismic Braces
5.2.3
X
1.20
1
5 Years
Hangers (Accessible concealed spaces)
5.2.3.3
X
1.21
1
5 Years
Seismic Braces (Accessible concealed
spaces)
5.2.3.3
X
1.22
I
5 Years
Pipe and Fittings (Accessible concealed
spaces
5.2.2.3
X
1.23
1
5 Years
Sprinklers (Accessible concealed spaces)
5.2.1.1.4
X
1.24
1
5 Years
Alarm Valves - Interior Inspection
12.4.1.2
X
1.25
1
5 Years
Alarm Valves - Strainers, filters, orifices
12.4.1.2
X
1.26
1
5 Years
Check Valves - Interior Inspection
12.4.2.1
X
1.27
1
5 Years
Preaction /Deluge Valves - Interior
Inspection
12.4.3.1.7
X
1.28
1
5 Years
Preaction /Deluge Valves - Strainers,
filters, orifices
12.4.3.1.8
X
1.29
1
5 Years
Dry Pipe Valves - Interior Inspection
12.4.4.1.5
X
1.30
1
5 Years
Dry Pipe Valves - Strainers, filters, orifices
12.4.4.1.6
X
2.1
T
Annually
Alarm Devices (90 Sec)
5.3.3
12.2.7
X
2.2
T
Annually
Main Drain Test (Enter data on Page 1)
12.2.6
12.2.6.1
12.3.3.4
X
2.3
T
Annually
Antifreeze Test
5.3.4
X
2.4
T
Annually
Control Valve - Position
12.3.3.1
X
2.5
T
Annually
Control Valve - Operation
12.3.3.1
X
2.6
T
Annually
Supervisory
12.3.3.5
X
2.7
T
Annually
Preaction Valve - Priming Water
12.4.3.2.1
X
2.8
T
Annually
Preaction Valve - Low Air Pressure Alarm
12.4.3.2.10
X
2.9
T
Annually
Preaction Valve - Full Flow Trip Test
12.4.3.2.2
X
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717. Page 2 of 5
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
System Riser ID: 7499
Property Information:
-
Type Of System: OF Cq��� -
Name: Bakersfield College -Child Care 200
❑x Wet Pipe q� �p
Address: 1801 Panorama Dr
❑ Dry Pipe °� a
❑ Preaction .r
❑ Deluge EM
City: Bakersfield
NFPA 25
Item
Activity
Frequency
Description
Reference
Fail
N/A
Pass
2.10
T
Annually
Dry Pipe Valve - Priming Water
12.4.4.2.1
X
2.11
T
Annually
y
ry Pipe Valve - Low Air Pressure
12.4.4.2.6
X
Alarm
2.12
T
Annually
Dry Pipe Valve - Quick- Opening
12.4.4.2.4
X
Device
2.13
T
Annually
Dry Pipe Valve - Trip
12.4.4.2.2
X
2.14
T
Annually
Backflow Preventor Assemblies
12.6.2
X
2.15
T
3 Years
Dry Pipe Valve - Full Flow Trip Test
12.4.4.2.2.2
X
2.16
T
5 Years
Gauges
5.3.2
X
2.17
T
5 Years
Pressure Reducing Valve
12.5.1.2
X
2.18
T
5 Years
Fire Department Connection Backflush
12.7.4
X
2.19
T
5 Years
Sprinklers - Extra High Temperature
5.3.1.1.1.3
X
2.20
T
5 Years
Sprinklers - Corrosive environment or
5.3.1.1.2
X
corrosive water
2.21
T
10 Years
Sprinklers - Dry
5.3.1.1.1.5
X
2.22
T
20 Years
Sprinklers - Fast Response
5.3.1.1.1.2
X
2.23
T
50 Years
Sprinklers
5.3.1.1.1
X
2.24
T
75 Years
Sprinklers 75 years in service
5.3.1.1.1.4
X
2.25
T
Sprinklers manufactured prior to 1920
5.3.1.1.1.1
X
- Replace
3.1
M
Annually
Control Valves
12.3.4
X
3.2
M
Annually
Preaction /Deluge Valves
12.4.3.3.2
X
3.3
M
Annually
Dry Pipe Valves /Quick- Opening
12.4.4.3.2
X
Devices
3.4
M
Annually
Dry Pipe Valve - Low Point Drains
12.4.4.3.3
X
3.5
M
5 Years
Obstruction Investigation
Chapter 13
X
State Fire Marshal AES 2
March 21, 2006
Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 3 of 5
U 1141 104 10.14
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25 Chapter 5 as amended by CCR Title 19
Date Of Inspection, Testing, Maintenance: 01/05/2011
Property Information:
Name: Bakersfield College -Child Care 200
Address: 1801 Panorama Dr
City: Bakersfield
System Riser ID: 7499
Type Of System:
�F CA�p�o
Wet Pipe �a : • .
❑ Dry Pipe �' a
❑ Preaction
❑ Deluge M
Item
Deficiencies and Comments:
Deficiencies and Comments Item number must correspond to the Item number
of the activity listed above:
❑ See Continuation Page(s) (Indicate the number of continuation pages)
❑X PASS
F1 FAIL 01/05/2011
Signature Date
State Fire Marshal AES 2
March 21, 2006
Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 4 of 5
Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 5 of 5