HomeMy WebLinkAboutSPRINKLERS INSP 1/5/2011i Design, Installation, Inspection, & Repair of Fire Sprinkler Systems Bakersfield San Francisco Livermore DATE: January 2011 We herewith enclose a copy of an automatic fire sprinkler system check report for the following facility: Bakersfield College 1801 Panorama Dr. Bakersfield, CA. 93305 to the party checked below: Owner: k' Fire Dept: Thank You RLH Fire Protection File:7499 Bakersfield College 1801 Panorama Dr. Bakersfield, CA. 93305 (DU -,?Jq s - u� a l Bakersfield City Fire Department 1501 Truxtun Ave Bakersfield, CA. 93301 IIIIIIIIVIIIIIIIIII 66 IE RLH Fire Protection 3430 Unicorn Rd. Bakersfield, CA 93308 Voice:661.322.9344 Fax:661.322.6816 Lic.# 777717 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended bV CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 System Riser ID: 7499 Property Information: - - Type Of System: OF C44 Name: Bakersfield College- Science /Enginerrinc Wet Pipe Address: 1801 Panorama Dr ❑ Dry Pipe �' a A -O = After Operation ❑ Preaction Y MI = Per Manufacturer's Instructions ❑ DelugeiE M City: Bakersfield Frequency Main Drain Test Results: Abbreviation Key: Initial Static Pressure: (psi) I = Inspection T =Test Residual Pressure: (psi) M = Maintenance A -O = After Operation Restored Static Pressure: (psi) MI = Per Manufacturer's Instructions Item Activity Frequency Description NFPA 25 Fail N/A Pass Reference 1.1 I Daily Preaction /Deluge Valves - Enclosure 12.4.3.1 X Weekly temperature 1.2 I Daily Dry Pipe Valves - Enclosure 12.4.4.1.1 X Weekly tem erature 1.3 I Quarterly Gauges - (Dry, Preaction, Deluge 5.2.4.2 X Systems) 5.2.4.3 1.4 I Quarterly Control Valves 12.3.2.1 X 1.5 1 Quarterly Alarm Devices 5.2.6 X 1.6 I Quarterly Gauges (Wet Pipe Systems) 5.2.4.1 X 1.7 1 Quarterly Hydraulic nameplate 5.2.7 X 1.8 1 Quarterly Pipe and Fittings 5.2.2 X 1.9 1 Quarterly Sprinklers 5.2.1 X 1.10 1 Quarterly Spare Sprinklers 5.2.1.3 X 1.11 1 Quarterly Fire Department Connections 12.7.1 X 1.12 I Quarterly Alarm Valves - Exterior Inspection 12.4.1.1 X 1.13 I Quarterly Preaction /Deluge Valves - Exterior 12.4.3.1.6 X Inspection 1.14 1 Quarterly Pressure Reducing Valves 12.5.1.1 X 1.15 1 Quarterly Dry Pipe Valves- Exterior Inspection 12.4.4.1.4 X 1.16 1 Quarterly Backflow Preventers 12.6.1 X 1.17 1 Annual Buildings 5.2.5 X State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 1 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Activity Date Of Inspection, Testing, Maintenance: 01/05/2011 Description System Riser ID: 7499 Fail Property Information: Pass Type Of System: _ o f FAQ Name: Bakersfield College- Science /Enginerrinc Hangers ❑x Wet Pipe +�'�� 0 ,9 Address: 1801 Panorama Dr ❑ Dry Pipe co n Annually Seismic Braces ❑ Preaction X 1.20 1 5 Years Hangers (Accessible concealed spaces) ❑ DelugeE City: Ba ersfield 1.21 I Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass 1.18 1 Annually Hangers 5.2.3 X 1.19 1 Annually Seismic Braces 5.2.3 X 1.20 1 5 Years Hangers (Accessible concealed spaces) 5.2.3.3 X 1.21 I 5 Years Seismic Braces (Accessible concealed s aces 5.2.3.3 X 1.22 1 5 Years Pipe and Fittings (Accessible concealed spaces) 5.2.2.3 X 1.23 1 5 Years Sprinklers (Accessible concealed spaces) 5.2.1.1.4 X 1.24 1 5 Years Alarm Valves - Interior Inspection 12.4.1.2 X 1.25 1 5 Years Alarm Valves - Strainers, filters, orifices 12.4.1.2 X 1.26 1 5 Years Check Valves - Interior Inspection 12.4.2.1 X 1.27 I 5 Years Preaction /Deluge Valves - Interior Inspection 12.4.3.1.7 X 1.28 1 5 Years Preaction /Deluge Valves - Strainers, filters, orifices 12.4.3.1.8 X 1.29 1 5 Years Dry Pipe Valves - Interior Inspection 12.4.4.1.5 X 1.30 1 5 Years Dry Pipe Valves - Strainers, filters, orifices 12.4.4.1.6 X 2.1 T Annually Alarm Devices (90 Sec) 5.3.3 12.2.7 X 2.2 T Annually Main Drain Test (Enter data on Page 1) 12.2.6 12.2.6.1 12.3.3.4 X 2.3 T Annually Antifreeze Test 5.3.4 X 2.4 T Annually Control Valve - Position 12.3.3.1 X 2.5 T Annually Control Valve - Operation 12.3.3.1 X 2.6 T Annually Supervisory 12.3.3.5 X 2.7 T Annually Preaction Valve - Priming Water 12.4.3.2.1 X 2.8 T Annually Preaction Valve - Low Air Pressure Alarm 12.4.3.2.10 X 2.9 T Annually I Preaction Valve - Full Flow Trip Test 12.4.3.2.2 X State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 2 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended bV CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 Property Information: Name: Bakersfield College- Science /Enginerrinc Address: 1801 Panorama Dr City: Bakersfield System Riser ID: 7499 Type Of System: F Cq Wet Pipe 2 ❑ Dry Pipe 'v ❑ Preaction �► ., ❑ Deluge ARE M . Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass 2.10 T Annually Dry Pipe Valve - Priming Water 12.4.4.2.1 X 2.11 T Annually y ry Pipe Valve - Low Air Pressure Alarm 12.4.4.2.6 X 2.12 T Annually y ry Pipe Valve - Quick- Opening Device 12.4.4.2.4 X 2.13 T Annually Dry Pipe Valve - Trip 12.4.4.2.2 X 2.14 T Annually Backflow Preventor Assemblies 12.6.2 X 2.15 T 3 Years Dry Pipe Valve - Full Flow Trip Test 12.4.4.2.2.2 X 2.16 T 5 Years Gauges 5.3.2 X 2.17 T 5 Years Pressure Reducing Valve 12.5.1.2 X 2.18 T 5 Years Fire Department Connection Backflush 12.7.4 X 2.19 T 5 Years Sprinklers - Extra High Temperature 5.3.1.1.1.3 X 2.20 T 5 Years Sprinklers - Corrosive environment or corrosive water 5.3.1.1.2 X 2.21 T 10 Years Sprinklers - Dry 5.3.1.1.1.5 X 2.22 T 20 Years Sprinklers - Fast Response 5.3.1.1.1.2 X 2.23 T 50 Years Sprinklers 5.3.1.1.1 X 224 T 75 Years Sprinklers 75 years in service 5.3.1.1.1.4 X 2.25 T Sprinklers manufactured prior to 1920 - Re lace 5.3.1.1.1.1 X 3.1 M Annually Control Valves 12.3.4 X 3.2 M Annually Preaction /Deluge Valves 12.4.3.3.2 X 3.3 M Annually Dry Pipe Valves /Quick- Opening Devices 12.4.4.3.2 X 3.4 M Annually Dry Pipe Valve - Low Point Drains 12.4.4.3.3 X 3.5 M 5 Years Obstruction Investigation Chapter 13 X State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 3 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 Property Information: Name: Bakersfield College- Science /Enginerrinc Address: 1801 Panorama Dr City: Bakersfield System Riser ID: 7499 Type Of System: F Cq���o � Wet Pipe � � ❑ Dry Pipe co y ❑ Preaction ❑ Deluge ARE M� Item Deficiencies and Comments: Deficiencies and Comments Item number must correspond to the Item number of the activity listed above: ❑ See Continuation Page(s) (Indicate the number of continuation pages) ❑PASS ❑ FAIL 01/05/2011 Signature Date State Fire Marshal AES 2 March 21, 2006 Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 4 of 5 Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 5of5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 System Riser ID: 7499 Property Information:; .. Type Of System: F'C4 C,�C Name: Bakersfield College -Sam Art & Music Wet Pipe Quo -ra Address: 1801 Panorama Dr ❑ Dry Pipe °� p A -O = After Operation ❑ Preaction �► MI = Per Manufacturer's Instructions ❑ Deluge ARE M City: Bakersfield Frequency Main Drain Test Results: Abbreviation Key: Initial Static Pressure: (psi) I = Inspection T = Test Residual Pressure: (psi) M = Maintenance A -O = After Operation Restored Static Pressure: (psi) MI = Per Manufacturer's Instructions Item Activity Frequency Description NFPA 25 Fail N/A Pass Reference 1.1 1 Daily Preaction /Deluge Valves - Enclosure 12.4.3.1 X Weekly temperature 1.2 1 Daily Dry Pipe Valves - Enclosure 12.4.4.1.1 X Weekly temperature 1.3 1 Quarterly Gauges - (Dry, Preaction, Deluge 5.2.4.2 X Systems) 5.2.4.3 1.4 1 Quarterly Control Valves 12.3.2.1 X 1.5 1 Quarterly Alarm Devices 5.2.6 X 1.6 I Quarterly Gauges (Wet Pipe Systems) 5.2.4.1 X 1.7 1 Quarterly Hydraulic nameplate 5.2.7 X 1.8 1 Quarterly Pipe and Fittings 5.2.2 X 1.9 1 Quarterly Sprinklers 5.2.1 X 1.10 1 Quarterly Spare Sprinklers 5.2.1.3 X 1.11 1 Quarterly Fire Department Connections 12.7.1 X 1.12 1 Quarterly Alarm Valves - Exterior Inspection 12.4.1.1 X 1.13 1 Quarterly Quarter) Preaction /Deluge Valves - Exterior 12.4.3.1.6 X Inspection 1.14 1 Quarterly Pressure Reducing Valves 12.5.1.1 X 1.15 1 Quarterly Dry Pipe Valves- Exterior Inspection 12.4.4.1.4 X 1.16 1 Quarterly Backflow Preventers 12.6.1 X 1.17 I Annual Buildings 5.2.5 X State Fire Marshal AES 2 March 21, 2006 Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 1 of 5 FAI 01 101 1 WA Item Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Frequency Date Of Inspection, Testing, Maintenance: 01/05/2011 System Riser ID: 7499 Fail Property Information: Pass Type Of System: IF CA(��O Name: Bakersfield College -Sam Art & Music ❑x Wet Pipe ,t�0 � .fl Address: 1801 Panorama Dr ❑ Dry Pipe 2 n Annually Seismic Braces ❑ Preaction° ., X 1.20 1 5 Years Hangers (Accessible concealed spaces) ❑ Deluge RE Mme` City: Bakersfield 1.21 1 Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass 1.18 1 Annually Hangers 5.2.3 X 1.19 1 Annually Seismic Braces 5.2.3 X 1.20 1 5 Years Hangers (Accessible concealed spaces) 5.2.3.3 X 1.21 1 5 Years Seismic Braces (Accessible concealed spaces) 5.2.3.3 X 1.22 1 5 Years Pipe and Fittings (Accessible concealed spaces) 5.2.2.3 X 1.23 1 5 Years Sprinklers (Accessible concealed spaces) 5.2.1.1.4 X 1.24 1 5 Years Alarm Valves - Interior Inspection 12.4.1.2 X 1.25 1 5 Years Alarm Valves - Strainers, filters, orifices 12.4.1.2 X 1.26 1 5 Years Check Valves - Interior Inspection 12.4.2.1 X 1.27 1 5 Years Preaction /Deluge Valves - Interior Inspection 12.4.3.1.7 X 1.28 1 5 Years Preaction /Deluge Valves - Strainers, filters, orifices 12.4.3.1.8 X 1.29 1 5 Years Dry Pipe Valves - Interior Inspection 12.4.4.1.5 X 1.30 1 5 Years Dry Pipe Valves - Strainers, filters, orifices 12.4.4.1.6 X 2.1 T Annually Alarm Devices (90 Sec) 5.3.3 12.2.7 X 2.2 T Annually Main Drain Test (Enter data on Page 1) 12.2.6 12.2.6.1 12.3.3.4 X 2.3 T Annually Antifreeze Test 5.3.4 X 2.4 T Annually Control Valve - Position 12.3.3.1 X 2.5 T Annually Control Valve - Operation 12.3.3.1 X 2.6 T Annually Supervisory 12.3.3.5 X 2.7 T Annually Preaction Valve - Priming Water 12.4.3.2.1 X 2.8 T Annually Preaction Valve - Low Air Pressure Alarm 12.4.3.2.10 X 2.9 j T Annually I Preaction Valve - Full Flow Trip Test 12.4.3.2.2 X State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 2 of 5 F.1 Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 System Riser ID: 7499 Property Information: -- Type Of System: of C.44.t . Name: Bakersfield College -Sam Art & Music ❑x Wet Pipe Address: 1801 Panorama Dr ❑ Dry Pipe a ❑ Preaction► .+ ❑ DelugeE M City: Bakersfield NFPA 25 Item Activity Frequency Description Reference Fail N/A Pass 2.10 T Annually Dry Pipe Valve - Priming Water 12.4.4.2.1 X 2.11 T Annually Dry Pipe Valve - Low Air Pressure 12.4.4.2.6 X Alarm 2.12 T Annually y ry Pipe Valve - Quick- Opening 12.4.4.2.4 X Device 2.13 T Annually Dry Pipe Valve - Trip 12.4.4.2.2 X 2.14 T Annually Backflow Preventor Assemblies 12.6.2 X 2.15 T 3 Years Dry Pipe Valve - Full Flow Trip Test 12.4.4.2.2.2 X 2.16 T 5 Years Gauges 5.3.2 X 2.17 T 5 Years Pressure Reducing Valve 12.5.1.2 X 2.18 T 5 Years Fire Department Connection Backflush 12.7.4 X 2.19 T 5 Years Sprinklers - Extra High Temperature 5.3.1.1.1.3 X 2.20 T 5 Years Sprinklers - Corrosive environment or 5.3.1.1.2 X corrosive water 2.21 T 10 Years Sprinklers - Dry 5.3.1.1.1.5 X 2.22 T 20 Years Sprinklers - Fast Response 5.3.1.1.1.2 X 2.23 T 50 Years Sprinklers 5.3.1.1.1 X 2.24 T 75 Years Sprinklers 75 years in service 5.3.1.1.1.4 X 2.25 T Sprinklers manufactured prior to 1920 5.3.1.1.1.1 X - Re lace 3.1 M Annually Control Valves 12.3.4 X 3.2 M Annually Preaction /Deluge Valves 12.4.3.3.2 X 3.3 M Annually Dry Pipe Valves /Quick- Opening 12.4.4.3.2 X Devices 3.4 M Annually Dry Pipe Valve - Low Point Drains 12.4.4.3.3 X 3.5 M 5 Years Obstruction Investigation Chapter 13 X State Fire Marshal AES 2 March 21, 2006 Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 3 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 Property Information: Name: Bakersfield College -Sam Art & Music Address: 1801 Panorama Dr City: Bakersfield System Riser ID: 7499 Type Of System: OF Cq���C ❑x Wet Pipe Q ,p ❑ Dry Pipe �' y ❑ Preaction E] Deluge SAE Mt` Item Deficiencies and Comments: Deficiencies and Comments Item number must correspond to the Item number of the activity listed above: ❑ See Continuation Page(s) (Indicate the number of continuation pages) ❑x PASS 01/05/2011 01/05/2011 F-1 Signature Date State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 4 of 5 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 5 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 System Riser ID: 7499 Property Information: Type Of System: F, - C,�Cp Name: Bakersfield College - Library ❑x Wet Pipe Address: 1801 Panorama Dr a y E] Dry Pipe y q A -O = After Operation ❑ Preaction �► v MI = Per Manufacturer's Instructions ❑ Deluge "ARE Mp City: Bakersfield -- ... - -- Main Drain Test Results: Abbreviation Key: Initial Static Pressure: (psi) I =Inspection T =Test Residual Pressure: (psi) M = Maintenance A -O = After Operation Restored Static Pressure: (psi) MI = Per Manufacturer's Instructions Item Activity Frequency Description NFPA 25 Fail N/A Pass Reference 1.1 1 Daily Preaction /Deluge Valves - Enclosure 12.4.3.1 X Weekly temperature 1.2 I Daily Dry Pipe Valves - Enclosure 12.4.4.1.1 X Weeklv temperature 1.3 1 Quarterly Gauges - (Dry, Preaction, Deluge 5.2.4.2 X Systems) 5.2.4.3 1.4 1 Quarterly Control Valves 12.3.2.1 X 1.5 1 Quarterly Alarm Devices 5.2.6 X 1.6 1 Quarterly Gauges (Wet Pipe Systems) 5.2.4.1 X 1.7 1 Quarterly Hydraulic nameplate 5,2.7 X 1.8 1 Quarterly Pipe and Fittings 5.2.2. X 1.9 1 Quarterly Sprinklers 5.2.1 X 1.10 1 Quarterly Spare Sprinklers 5.2.1.3 X 1.11 1 Quarterly Fire Department Connections 12.7.1 X 1.12 1 Quarterly Alarm Valves - Exterior Inspection 12.4.1.1 X 1.13 1 Quarterly Quarter) Preaction /Deluge Valves - Exterior 12.4.3.1.6 X Inspection 1.14 1 Quarterly Pressure Reducing Valves 12.5.1.1 X 1.15 1 Quarterly Dry Pipe Valves- Exterior Inspection 12.4.4.1.4 X 1.16 1 Quarterly Backflow Preventers 12.6.1 X 1.17 1 Annual Buildings 5.2.5 X State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 1 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Activity Date Of Inspection, Testing, Maintenance: 01/0512011 Description System Riser ID: 7499 Fail Property Information: Pass Type Of System: F CA(��p Name: Bakersfield Colleae- Library Hangers ❑x Wet Pipe cr A Address: 18Q1 Panorama Dr ❑ Dry Pipe 1 Annually Seismic Braces ❑ Preaction r:. X ❑ Deluge RE M City: Bakersfield Hangers (Accessible concealed spaces) 5.2.3.3 Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass 1.18 1 Annually Hangers 5.2.3 X 1.19 1 Annually Seismic Braces 5.2.3 X 1.20 1 5 Years Hangers (Accessible concealed spaces) 5.2.3.3 X 1.21 1 5 Years Seismic Braces (Accessible concealed spaces) 5.2.3.3 X 1.22 1 5 Years Pipe and Fittings (Accessible concealed spaces) 5.2.2.3 X 1.23 1 5 Years Sprinklers (Accessible concealed spaces) 5.2.1.1.4 X 1.24 1 5 Years Alarm Valves - Interior Inspection 12.4.1.2 X 1.25 1 5 Years Alarm Valves - Strainers, filters, orifices 12.4.1.2 X 1.26 1 5 Years Check Valves - Interior Inspection 12.4.2.1 X 1.27 I 5 Years Preaction /Deluge Valves - Interior Inspection 12.4.3.1.7 X 1.28 1 5 Years Preaction /Deluge Valves - Strainers, filters, orifices 12.4.3.1.8 X 1.29 1 5 Years Dry Pipe Valves - Interior Inspection 12.4.4.1.5 X 1.30 1 5 Years Dry Pipe Valves - Strainers, filters, orifices 12.4.4.1.6 X 2.1 T Annually Alarm Devices (90 Sec) 5.3.3 12.2.7 X 2.2 T Annually Main Drain Test (Enter data on Page 1) 12.2.6 12.2.6.1 12.3.3.4 X 2.3 T Annually Antifreeze Test 5.3.4 X 2.4 T Annually Control Valve - Position 12.3.3.1 X 2.5 T Annually Control Valve - Operation 12.3.3.1 X 2.6 T Annually Supervisory 12.3.3.5 X 2.7 T Annually Preaction Valve - Priming Water 12.4.3.2.1 X 2.8 T Annually Preaction Valve - Low Air Pressure Alarm 12.4.3.2.10 X 2.9 T Annually Preaction Valve - Full Flow Trip Test 12.4.3.2.2 X State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 2 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 System Riser ID: 7499 Property Information: -. - -- Type Of System: F C4 C,Dp Name: Bakersfield College- Library Wet Pipe o Address: 1801 Panorama Dr ❑ Dry Pipe ❑ Preaction �► E] Delu e g City: Bakersfield NFPA 25 Item Activity Frequency Description Reference Fail N/A Pass 2.10 T Annually Dry Pipe Valve - Priming Water 12.4.4.2.1 X 2.11 T Annually Dry Pipe Valve - Low Air Pressure 12.4.4.2.6 X Alarm 2.12 T Annually y ry Pipe Valve - Quick- Opening 12.4.4.2.4 X Device 2.13 T Annually Dry Pipe Valve - Trip 12.4.4.2.2 X 2.14 T Annually Backflow Preventor Assemblies 12.6.2 X 2.15 T 3 Years Dry Pipe Valve - Full Flow Trip Test 12.4.4.2.2.2 X 2.16 T 5 Years Gauges 5.3.2 X 2.17 T 5 Years Pressure Reducing Valve 12.5.1.2 X 2.18 T 5 Years Fire Department Connection Backflush 12.7.4 X 2.19 T 5 Years Sprinklers - Extra High Temperature 5.3.1.1.1.3 X 2.20 T 5 Years Sprinklers - Corrosive environment or 5.3.1.1.2 X corrosive water 2.21 T 10 Years Sprinklers - Dry 5.3.1.1.1.5 X 2.22 T 20 Years Sprinklers - Fast Response 5.3.1.1.1.2 X 2.23 T 50 Years Sprinklers 5.3.1.1.1 X 2.24 T 75 Years Sprinklers 75 years in service 5.3.1.1.1.4 X 2.25 T Sprinklers manufactured prior to 1920 5.3.1.1.1.1 X - Replace 3.1 M Annually Control Valves 12.3.4 X 32 M Annually Preaction /Deluge Valves 12.4.3.3.2 X 3.3 M Annually Dry Pipe Valves /Quick- Opening 12.4.4.3.2 X Devices 3.4 M Annually Dry Pipe Valve - Low Point Drains 12.4.4.3.3 X 3.5 M 5 Years Obstruction Investigation Chapter 13 X State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 3 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 Property Information: Name: Bakersfield College- Library Address: 1801 Panorama Dr City: Bakersfield System Riser ID: 7499 Type Of System: f C&I�o ❑x Wet Pipe 9 � Z ❑ Dry Pipe n ❑ Preaction ; ❑ Deluge ARE M� Item Deficiencies and Comments: Deficiencies and Comments Item number must correspond to the Item number of the activity listed above: ❑ See Continuation Page(s) (Indicate the number of continuation pages) ❑PASS _. ❑ FAIL 01/05/2011 Signature Date State Fire Marshal AES 2 March 21, 2006. Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 4 of 5 inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 5 of 5 0,04 10 10.14 Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 System Riser ID: 7499 Property Information: Type Of System: F �A �i�o9 Name: Bakersfield College- Language Arts ❑x Wet Pipe �tio Address: 1801 Panorama Dr a y ❑ Dry Pipe 07 a A -O = After Operation ❑ Preaction �► �, MI = Per Manufacturer's Instructions ❑ Deluge M City: Bakersfield Frequency Main Drain Test Results: Abbreviation Key: Initial Static Pressure: (psi) I = Inspection T =Test Residual Pressure: (psi) M = Maintenance A -O = After Operation Restored Static Pressure: (psi) MI = Per Manufacturer's Instructions Item Activity Frequency Description NFPA 25 Fail N/A Pass Reference 1.1 1 Daily Preaction /Deluge Valves - Enclosure 12.4.3.1 X Weekly temperature 1.2 1 Daily Dry Pipe Valves - Enclosure 12.4.4.1.1 X Week) tem erature 1.3 1 Quarterly Gauges - (Dry, Preaction, Deluge 5.2.4.2 X Systems) 5.2.4.3 1.4 1 Quarterly Control Valves 12.3.2.1 X 1.5 1 Quarterly Alarm Devices 5.2.6 X 1.6 1 Quarterly Gauges (Wet Pipe Systems) 5.2.4.1 X 1.7 1 Quarterly Hydraulic nameplate 5.2.7 X 1.8 1 Quarterly Pipe and Fittings 5.2.2 X 1.9 1 Quarterly Sprinklers 5.2.1 X 1.10 1 Quarterly Spare Sprinklers 5.2.1.3 X 1.11 1 Quarterly Fire Department Connections 12.7.1 X 1.12 1 Quarterly Alarm Valves - Exterior Inspection 12.4.1.1 X 1.13 1 Quarterly Quarter) Preaction /Deluge Valves - Exterior 12.4.3.1.6 X Inspection 1.14 1 Quarterly Pressure Reducing Valves 12.5.1.1 X 1.15 1 Quarterly Dry Pipe Valves- Exterior Inspection 12.4.4.1.4 X 1.16 I Quarterly Backflow Preventers 12.6.1 X 1.17 1 Annual Buildings 5.2.5 X State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 1 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Activity Date Of Inspection, Testing, Maintenance: 01/05/2011 Description System Riser ID: 7499 Fail Property Information: Pass Type Of System: CAC ��O Name: Bakersfield College - Language Arts Hangers ❑x Wet Pipe ��pF tt 9 Address: 1801 Panorama Dr E] Dry Pipe c' y Annually Seismic Braces ❑ Preaction �% J X 1.20 P 5 Years Hangers (Accessible concealed spaces) ❑ Deluge M City: Bakersfield 1.21 I Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass 1.18 1 Annually Hangers 5.2.3 X 1.19 1 Annually Seismic Braces 5.2.3 X 1.20 1 5 Years Hangers (Accessible concealed spaces) 5.2.3.3 X 1.21 I 5 Years Seismic Braces (Accessible concealed s aces 5.2.3.3 X 1.22 1 5 Years Pipe and Fittings (Accessible concealed spaces 5.2.2.3 X 1.23 1 5 Years Sprinklers (Accessible concealed spaces) 5.2.1.1.4 X 1.24 1 5 Years Alarm Valves - Interior Inspection 12.4.1.2 X 1.25 1 5 Years Alarm Valves - Strainers, filters, orifices 12.4.1.2 X 1.26 1 5 Years Check Valves - Interior Inspection 12.4.2.1 X 1.27 I 5 Years Preaction /Deluge Valves - Interior Inspection 12.4.3.1.7 X 1.28 1 5 Years Preaction /Deluge Valves - Strainers, filters, orifices 12.4.3.1.8 X 1.29 1 5 Years Dry Pipe Valves - Interior Inspection 12.4.4.1.5 X 1.30 1 5 Years Dry Pipe Valves - Strainers, filters, orifices 12.4.4.1.6 X 2.1 T Annually Alarm Devices (90 Sec) 5.3.3 12.2.7 X 2.2 T Annually Main Drain Test (Enter data on Page 1) 12.2.6 12.2.6.1 12.3.3.4 X 2.3 T Annually Antifreeze Test 5.3.4 X 2.4 T Annually Control Valve - Position 12.3.3.1 X 2.5 T Annually Control Valve - Operation 12.3.3.1 X 2.6 T Annually Supervisory 12.3.3.5 X 2.7 T Annually Preaction Valve - Priming Water 12.4.3.2.1 X 2.8 T Annually Preaction Valve - Low Air Pressure Alarm 12.4.3.2.10 X 2.9 T Annually Preaction Valve - Full Flow Trip Test 12.4.3.2.2 X State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 2 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended bV CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 System Riser ID: 7499 Property Information: - - - -- Type Of System: F Cq ��'t`p Name: Bakersfield College - Language Arts mow. ❑x Wet Pipe Address: 1801 Panorama Dr ❑ Dry Pipe °p v ❑ Preaction �y►�, F` M ❑ Deluge AR EE M City: Bakersfield NFPA 25 Item Activity Frequency Description Reference Fail N/A Pass 2.10 T Annually Dry Pipe Valve - Priming Water 12.4.4.2.1 X 2.11 T Annually Dry Pipe Valve - Low Air Pressure 12.4.4.2.6 X Alarm 2.12 T Annual/ Annually Dry Pipe Valve - Quick- Opening 12.4.4.2.4 X Device 2.13 T Annually Dry Pipe Valve - Trip 12.4.4.2.2 X 2.14 T Annually Backflow Preventor Assemblies 12.6.2 X 2.15 T 3 Years Dry Pipe Valve - Full Flow Trip Test 12.4.4.2.2.2 X 2.16 T 5 Years Gauges 5.3.2 X 2.17 T 5 Years Pressure Reducing Valve 12.5.1.2 X 2.18 T 5 Years Fire Department Connection Backflush 12.7.4 X 2.19 T 5 Years Sprinklers - Extra High Temperature 5.3.1.1.1.3 X 2.20 T 5 Years Sprinklers - Corrosive environment or 5.3.1.1.2 X corrosive water 2.21 T 10 Years Sprinklers - Dry 5.3.1.1.1.5 X 2.22 T 20 Years Sprinklers - Fast Response 5.3.1.1.1.2 X 2.23 T 50 Years Sprinklers 5.3.1.1.1 X 224 T 75 Years Sprinklers 75 years in service 5.3.1.1.1.4 X 2.25 T Sprinklers manufactured prior to 1920 5.3.1.1.1.1 X - Re lace 3.1 M Annually Control Valves 12.3.4 X 3.2 M Annually Preaction /Deluge Valves 12.4.3.3.2 X 3.3 M Annually Dry Pipe Valves /Quick- Opening 12.4.4.3.2 X Devices 3.4 M Annually Dry Pipe Valve - Low Point Drains 12.4.4.3.3 X 3.5 M 5 Years I Obstruction Investigation Chapter 13 X State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 3 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 Property Information: Name: Bakersfield College- Language Arts Address: 1801 Panorama Dr City: Bakersfield System Riser ID: 7499 Type Of System: OF CAL��Q Wet Pipe a 9 j6` Z ❑ Dry Pipe y ❑ Preaction ❑ Deluge t Item Deficiencies and Comments: Deficiencies and Comments Item number must correspond to the Item number of the activity listed above: ❑ See Continuation Page(s) (Indicate the number of continuation pages) ❑x PASS ❑ FAIL 01/05/2011 Signature Date State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 4 of 5 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 5 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 System Riser ID: 7499 Property Information: Type Of System: OF C'4' Name: Bakersfield College- Industrial Tech. Wet Pipe M = Maintenance co Address: 1801 Panorama Dr ❑ Dry Pipe MI = Per Manufacturer's Instructions ❑ Preaction► v Activity ❑ Deluge qE p't� City: Bakersfield NFPA 25 Main Drain Test Results: Abbreviation Key: Initial Static Pressure: (psi) I = Inspection T =Test Residual Pressure: (psi) M = Maintenance A -O = After Operation Restored Static Pressure: (psi) MI = Per Manufacturer's Instructions Item Activity Frequency Description NFPA 25 Fail N/A Pass Reference 1.1 1 Daily Preaction /Deluge Valves - Enclosure 12.4.3.1 X Weekly tem erature 1.2 1 Daily Dry Pipe Valves - Enclosure 12.4.4.1.1 X Weekly tem erature 1.3 1 Quarterly Gauges - (Dry, Preaction, Deluge 5.2.4.2 X S stems ) 5.2.4.3 1.4 1 Quarterly Control Valves 12.3.2.1 X 1.5 1 Quarterly Alarm Devices 5.2.6 X 1.6 1 Quarterly Gauges (Wet Pipe Systems) 5.2.4.1 X 1.7 1 Quarterly Hydraulic nameplate 5.2.7 X 1.8 1 Quarterly Pipe and Fittings 5.2.2 X 1.9 1 Quarterly Sprinklers 5.2.1 X 1.10 1 Quarterly Spare Sprinklers 5.2.1.3 X 1.11 1 Quarterly Fire Department Connections 12.7.1 X 1.12 1 Quarterly Alarm Valves - Exterior Inspection 12.4.1.1 X 1.13 1 Quarter) Quarterly Preaction /Deluge Valves - Exterior 12.4.3.1.6 X Inspection 1.14 1 Quarterly Pressure Reducing Valves 12.5.1.1 X 1.15 1 Quarterly Dry Pipe Valves- Exterior Inspection 12.4.4.1.4 X 1.16 1 Quarterly Backflow Preventers 12.6.1 X 1.17 1 Annual Buildings 5.2.5 X State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 1 of 5 ANNEX B Item Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Frequency Date Of Inspection, Testing, Maintenance: 01/05/2011 System Riser ID: 7499 Fail Property Information: Pass Type Of System: 1 Annually Hangers 5.2.3 Name: Bakersfield College- Industrial Tech. � Wet Pipe a � Address: 1801 Panorama Dr ❑ Dry Pipe co y X ❑ Preaction N% 4 5 Years Hangers (Accessible concealed spaces) ❑ Deluge SAE City: Bakersfield 1.21 _ Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass 1.18 1 Annually Hangers 5.2.3 X 1.19 1 Annually Seismic Braces 5.2.3 X 1.20 1 5 Years Hangers (Accessible concealed spaces) 5.2.3.3 X 1.21 1 5 Years Seismic Braces (Accessible concealed spaces) 5.2.3.3 X 1.22 1 5 Years Pipe and Fittings (Accessible concealed spaces) 5.2.2.3 X 1.23 1 5 Years Sprinklers (Accessible concealed spaces) 5.2.1.1.4 X 1.24 1 5 Years Alarm Valves - Interior Inspection 12.4.1.2 X 1.25 1 5 Years Alarm Valves - Strainers, filters, orifices 12.4.1.2 X 1.26 1 5 Years Check Valves - Interior Inspection 12.4.2.1 X 1.27 1 5 Years Preaction /Deluge Valves - Interior Inspection 12.4.3.1.7 X 1.28 1 5 Years Preaction /Deluge Valves - Strainers, filters, orifices 12.4.3.1.8 X 1.29 1 5 Years Dry Pipe Valves - Interior Inspection 12.4.4.1.5 X 1.30 1 5 Years Dry Pipe Valves - Strainers, filters, orifices 12.4.4.1.6 X 2.1 T Annually Alarm Devices (90 Sec) 5.3.3 12.2.7 X 2.2 T Annually Main Drain Test (Enter data on Page 1) 12.2.6 12.2.6.1 12.3.3.4 X 2.3 T Annually Antifreeze Test 5.3.4 X 2.4 T Annually Control Valve - Position 12.3.3.1 X 2.5 T Annually Control Valve - Operation 12.3.3.1 X 2.6 T Annually Supervisory 12.3.3.5 X 2.7 T Annually Preaction Valve - Priming Water 12.4.3.2.1 X 2.8 T Annually Preaction Valve - Low Air Pressure Alarm 12.4.3.2.10 X 2.9 T Annually I Preaction Valve - Full Flow Trip Test 12.4.3.2.2 X State Fire Marshal AES 2 March 21, 2006 Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 2 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 System Riser ID: 7499 Property Information: - - -- - - - -- Type Of System: -or-, Name: Bakersfield College- Industrial Tech. ❑x Wet Pipe o�Z �Q� Address: 1801 Panorama Dr ❑ Dry Pipe °D ` q ❑ Preaction �► �� ❑ Deluge �4E M City: Bakersfield NFPA 25 Item Activity Frequency Description Reference Fail N/A Pass 2.10 T Annually Dry Pipe Valve - Priming Water 12.4.4.2.1 X 2.11 T Annually Dry Pipe Valve - Low Air Pressure 12.4.4.2.6 X Alarm 2.12 T Annually Dry Pipe Valve - Quick- Opening 12.4.4.2.4 X Device 2.13 T Annually Dry Pipe Valve - Trip 12.4.4.2.2 X 2.14 T Annually Backflow Preventor Assemblies 12.6.2 X 2.15 T 3 Years Dry Pipe Valve - Full Flow Trip Test 12.4.4.2.2.2 X 2.16 T 5 Years Gauges 5.3.2 X 2.17 T 5 Years Pressure Reducing Valve 12.5.1.2 X 2.18 T 5 Years Fire Department Connection Backflush 12.7.4 X 2.19 T 5 Years Sprinklers - Extra High Temperature 5.3.1.1.1.3 X 2.20 T 5 Years Sprinklers - Corrosive environment or 5.3.1.1.2 X corrosive water 2.21 T 10 Years Sprinklers - Dry 5.3.1.1.1.5 X 2.22 T 20 Years Sprinklers - Fast Response 5.3.1.1.1.2 X 2.23 T 50 Years Sprinklers 5.3.1.1.1 X 2.24 T 75 Years Sprinklers 75 years in service 5.3.1.1.1.4 X 2.25 T Sprinklers manufactured prior to 1920 5.3.1.1.1.1 X - Re lace 3.1 M Annually Control Valves 12.3.4 X 3.2 M Annually Preaction /Deluge Valves 12.4.3.3.2 X 3.3 M Annually Dry Pipe Valves /Quick- Opening 12.4.4.3.2 X Devices 3.4 M Annually Dry Pipe Valve - Low Point Drains 12.4.4.3.3 X 3.5 M 5 Years Obstruction Investigation Chapter 13 X State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 3 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 Property Information: Name: Bakersfield College- Industrial Tech. Address: 1801 Panorama Dr City: Bakersfield System Riser ID: 7499 Type Of System: of: CAC/�d. ❑x Wet Pipe . ❑ Dry Pipe y ❑ Preaction ❑ Deluge ARE Mp Item Deficiencies and Comments: Deficiencies and Comments Item number must correspond to the Item number of the activity listed above: ❑ See Continuation Page(s) (Indicate the number of continuation pages) ❑x PASS ❑ FAIL 01/05/2011 Signature Date State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 4 of 5 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 5of5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 System Riser ID: 7499 Property Information:-- - - -<,. Type Of System: of CAL�,� Name: Bakersfield College -Gym Wet Pipe Address: 1801 Panorama Dr ❑ Dry Pipe y a A -O = After Operation ❑ Preaction .i MI = Per Manufacturer's Instructions ❑ Deluge ARE M. City: Bakersfield Frequency Main Drain Test Results: Abbreviation Key: Initial Static Pressure: (psi) I = Inspection T =Test Residual Pressure: (psi) M = Maintenance A -O = After Operation Restored Static Pressure: (psi) MI = Per Manufacturer's Instructions Item Activity Frequency Description NFPA 25 Fail N/A Pass Reference 1.1 1 Daily Preaction /Deluge Valves - Enclosure 12.4.3.1 X Weekly temperature 1.2 1 Daily Dry Pipe Valves - Enclosure 12.4.4.1.1 X Weekly tem erature 1.3 1 Quarterly Gauges - (Dry, Preaction, Deluge 5.2.4.2 X S stems ) 5.2.4.3 1.4 1 Quarterly Control Valves 12.3.2.1 X 1.5 1 Quarterly Alarm Devices 5.2.6 X 1.6 1 Quarterly Gauges (Wet Pipe Systems) 5.2.4.1 X 1.7 1 Quarterly Hydraulic nameplate 5.2.7 X 1.8 1 Quarterly Pipe and Fittings 5.2.2 X 1.9 1 Quarterly Sprinklers 5.2.1 X 1.10 1 Quarterly Spare Sprinklers 5.2.1.3 X 1.11 1 Quarterly Fire Department Connections 12.7.1 X 1.12 1 Quarterly Alarm Valves - Exterior Inspection 12.4.1.1 X 1.13 1 Quarterly Quarter) Preaction /Deluge Valves - Exterior 12.4.3.1.6 X Inspection 1.14 1 Quarterly Pressure Reducing Valves 12.5.1.1 X 1.15 1 Quarterly Dry Pipe Valves- Exterior Inspection 12.4.4.1.4 X 1.16 1 Quarterly Backflow Preventers 12.6.1 X 1.17 1 Annual Buildings 5.2.5 X State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 1 of 5 ANNEX B Item Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Frequency Date Of Inspection, Testing, Maintenance: 01105/2011 System Riser ID: 7499 Fail Property Information: Pass Type Of System: Cq���O Name: Bakersfield College -Gym ❑X Wet Pipe /C�pF Q 9 Address: 1801 Panorama Dr ❑ Dry Pipe 1 Annually Seismic Braces ❑ Preaction 4 X ❑ Deluge -F M City: Bakersfield Hangers (Accessible concealed spaces) 5.2.3.3 Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass 1.18 1 Annually Hangers 5.2.3 X 1.19 1 Annually Seismic Braces 5.2.3 X 1.20 1 5 Years Hangers (Accessible concealed spaces) 5.2.3.3 X 1.21 1 5 Years Seismic Braces (Accessible concealed spaces) 5.2.3.3 X 1.22 1 5 Years Pipe and Fittings (Accessible concealed spaces 5.2.2.3 X 1.23 1 5 Years Sprinklers (Accessible concealed spaces) 5.2.1.1.4 X 1.24 1 5 Years Alarm Valves - Interior Inspection 12.4.1.2 X 1.25 1 5 Years Alarm Valves - Strainers, filters, orifices 12.4.1.2 X 1.26 1 5 Years Check Valves - Interior Inspection 12.4.2.1 X 1.27 1 5 Years Preaction /Deluge Valves - Interior Inspection 12.4.3.1.7 X 1.28 1 5 Years Preaction /Deluge Valves - Strainers, filters, orifices 12.4.3.1.8 X 1.29 1 5 Years Dry Pipe Valves - Interior Inspection 12.4.4.1.5 X 1.30 1 5 Years Dry Pipe Valves - Strainers, filters, orifices 12.4.4.1.6 X 2.1 T Annually Alarm Devices (90 Sec) 5.3.3 12.2.7 X 2.2 T Annually Main Drain Test (Enter data on Page 1) 12.2.6 12.2.6.1 12.3.3.4 X 2.3 T Annually Antifreeze Test 5.3.4 X 2.4 T Annually Control Valve - Position 12.3.3.1 X 2.5 T Annually Control Valve - Operation 12.3.3.1 X 2.6 T Annually Supervisory 12.3.3.5 X 2.7 T Annually Preaction Valve - Priming Water 12.4.3.2.1 X 2.8 T Annually Preaction Valve - Low Air Pressure Alarm 12.4.3.2.10 X 2.9 j T j Annually j Preaction Valve - Full Flow Trip Test 12.4.3.2.2 X State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 2 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended bV CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 System Riser ID: 7499 Property Information: - Type Of System: F CA Name: Bakersfield College -Gym ❑x Wet Pipe Address: 1801 Panorama Dr ❑ Dry Pipe °' v ❑ Preaction �► ❑ Deluge SAE p City: Bakersfield NFPA 25 Item Activity Frequency Description Reference Fail N/A Pass 2.10 T Annually Dry Pipe Valve - Priming Water 12.4.4.2.1 X 2.11 T Annually Annual/ Dry Pipe Valve - Low Air Pressure 12.4.4.2.6 X Alarm 2.12 T Annual/ Annually Dry Pipe Valve - Quick- Opening 12.4.4.2.4 X Device 2.13 T Annually Dry Pipe Valve - Trip 12.4.4.2.2 X 2.14 T Annually Backflow Preventor Assemblies 12.6.2 X 2.15 T 3 Years Dry Pipe Valve - Full Flow Trip Test 12.4.4.2.2.2 X 2.16 T 5 Years Gauges 5.3.2 X 2.17 T 5 Years Pressure Reducing Valve 12.5.1.2 X 2.18 T 5 Years Fire Department Connection Backflush 12.7.4 X 2.19 T 5 Years Sprinklers - Extra High Temperature 5.3.1.1.1.3 X 2.20 T 5 Years Sprinklers - Corrosive environment or 5.3.1.1.2 X corrosive water 2.21 T 10 Years Sprinklers - Dry 5.3.1.1.1.5 X 2.22 T 20 Years Sprinklers - Fast Response 5.3.1.1.1.2 X 223 T 50 Years Sprinklers 5.3.1.1.1 X 2.24 T 75 Years Sprinklers 75 years in service 5.3.1.1.1.4 X 2.25 T Sprinklers manufactured prior to 1920 5.3.1.1.1.1 X - Replace 3.1 M Annually Control Valves 12.3.4 X 32 M Annually Preaction /Deluge Valves 12.4.3.3.2 X 3.3 M Annually Dry Pipe Valves /Quick- Opening 12.4.4.3.2 X Devices 3.4 M Annually Dry Pipe Valve - Low Point Drains 12.4.4.3.3 X 3.5 M 5 Years Obstruction Investigation Chapter 13 X State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 3 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 Property Information: Name: Bakersfield College -Gym Address: 1801 Panorama Dr City: Bakersfield System Riser ID: 7499 Type Of System: of Cqt/�� ❑x Wet Pipe �Q ❑ Dry Pipe y ❑ Preaction �► ., ❑ Deluge f ARE Item Deficiencies and Comments: Deficiencies and Comments Item number must correspond to the Item number of the activity listed above: ❑ See Continuation Page(s) (Indicate the number of continuation pages) ❑x PASS ❑ FAIL 01/05/2011 Signature Date State Fire Marshal AES 2 March 21, 2006 Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 4 of 5 Inspection performed by: RLH Fire Protection - Bakersfield, CA -777717 Page 5 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 System Riser ID: 7499 Property Information: -- - - -. Type Of System: of C44j Name: Bakersfield College -Field House Wet Pipe ti Address: 1801 Panorama Dr y ❑ Dry Pipe r" a A -O = After Operation ❑ Preaction► MI = Per Manufacturer's Instructions ❑ DelugegE`Mp City: Bakersfield Frequency Main Drain Test Results: Abbreviation Key: Initial Static Pressure: (psi) I = Inspection T =Test Residual Pressure: (psi) M = Maintenance A -O = After Operation Restored Static Pressure: (psi) MI = Per Manufacturer's Instructions Item Activity Frequency Description NFPA 25 Fail N/A Pass Reference 1.1 1 Daily Preaction /Deluge Valves - Enclosure 12.4.3.1 X Weekly temperature 1.2 1 Daily Dry Pipe Valves - Enclosure 12.4.4.1.1 X Week/ tem erature 1.3 1 Quarterly Gauges - (Dry, Preaction, Deluge 5.2.4.2 X Systems) 5.2.4.3 1.4 1 Quarterly Control Valves 12.3.2.1 X 1.5 1 Quarterly Alarm Devices 5.2.6 X 1.6 I Quarterly Gauges (Wet Pipe Systems) 5.2.4.1 X 1.7 1 Quarterly Hydraulic nameplate 5.2.7 X 1.8 1 Quarterly Pipe and Fittings 5.2.2 X 1.9 1 Quarterly Sprinklers 5.2.1 X 1.10 1 Quarterly Spare Sprinklers 5.2.1.3 X 1.11 1 Quarterly Fire Department Connections 12.7.1 X 1.12 1 Quarterly Alarm Valves - Exterior Inspection 12.4.1.1 X 1.13 1 Quarterly Quarter/ Preaction /Deluge Valves - Exterior 12.4.3.1.6 X Inspection 1.14 1 Quarterly Pressure Reducing Valves 12.5.1.1 X 1.15 1 Quarterly Dry Pipe Valves- Exterior Inspection 12.4.4.1.4 X 1.16 1 Quarterly Backflow Preventers 12.6.1 X 1.17 1 Annual Buildings 5.2.5 X State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 1 of 5 ANNEX B Item Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Frequency Date Of Inspection, Testing, Maintenance: 01/05/2011 System Riser ID: 7499 Fail Property Information: Pass Type Of System: 1 Name: Bakersfield College -Field House Q Wet Pipe of CaC�,�. ,� p v 9 Address: 1801 Panorama Dr ❑ Dry Pipe �' a Annually Seismic Braces ❑ Preaction X ❑ Deluges M City: Bakersfield�AE Hangers (Accessible concealed spaces) 5.2.3.3 Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass 1.18 1 Annually Hangers 5.2.3 X 1.19 1 Annually Seismic Braces 5.2.3 X 1.20 1 5 Years Hangers (Accessible concealed spaces) 5.2.3.3 X 1.21 1 5 Years Seismic Braces (Accessible concealed s aces 5.2.3.3 X 1.22 1 5 Years Pipe and Fittings (Accessible concealed spaces) 5.2.2.3 X 1.23 1 5 Years Sprinklers (Accessible concealed spaces) 5.2.1.1.4 X 1.24 1 5 Years Alarm Valves - Interior Inspection 12.4.1.2 X 1.25 1 5 Years Alarm Valves - Strainers, filters, orifices 12.4.1.2 X 1.26 1 5 Years Check Valves - Interior Inspection 12.4.2.1 X 1.27 1 5 Years Preaction /Deluge Valves - Interior Inspection 12.4.3.1.7 X 1.28 1 5 Years Preaction /Deluge Valves - Strainers, filters, orifices 12.4.3.1.8 X 1.29 1 5 Years Dry Pipe Valves - Interior Inspection 12.4.4.1.5 X 1.30 1 5 Years Dry Pipe Valves - Strainers, filters, orifices 12.4.4.1.6 X 2.1 T Annually Alarm Devices (90 Sec) 5.3.3 12.2.7 X 2.2 T Annually Main Drain Test (Enter data on Page 1) 12.2.6 12.2.6.1 12.3.3.4 X 2.3 T Annually Antifreeze Test 5.3.4 X 2.4 T Annually Control Valve - Position 12.3.3.1 X 2.5 T Annually Control Valve - Operation 12.3.3.1 X 2.6 T Annually Supervisory 12.3.3.5 X 2.7 T Annually Preaction Valve - Priming Water 12.4.3.2.1 X 2.8 T Annually Preaction Valve - Low Air Pressure Alarm 12.4.3.2.10 X 2.9 T Annually I Preaction Valve - Full Flow Trip Test 12.4.3.2.2 X State Fire Marshal AES 2 March 21, 2006 Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 2 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 Property Information: Name: Bakersfield College -Field House Address: 1801 Panorama Dr City: Bakersfield System Riser ID: 7499 Type Of System: F CAC,�o9 Wet Pipe -01f ❑ Dry Pipe °� a ❑ Preaction �y►, ❑ Deluge ARE M ' Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass 2.10 T Annually Dry Pipe Valve - Priming Water 12.4.4.2.1 X 2.11 T Annually Dry Pipe Valve - Low Air Pressure Alarm 12.4.4.2.6 X 2.12 T Annually y ry Pipe Valve - Quick- Opening Device 12.4.4.2.4 X 2.13 T Annually Dry Pipe Valve - Trip 12.4.4.2.2 X 2.14 T Annually Backflow Preventor Assemblies 12.6.2 X 2.15 T 3 Years Dry Pipe Valve - Full Flow Trip Test 12.4.4.2.2.2 X 2.16 T 5 Years Gauges 5.3.2 X 2.17 T 5 Years Pressure Reducing Valve 12.5.1.2 X 2.18 T 5 Years Fire Department Connection Backflush 12.7.4 X 2.19 T 5 Years Sprinklers - Extra High Temperature 5.3.1.1.1.3 X 2.20 T 5 Years Sprinklers - Corrosive environment or corrosive water 5.3.1.1.2 X 2.21 T 10 Years Sprinklers - Dry 5.3.1.1.1.5 X 2.22 T 20 Years Sprinklers - Fast Response 5.3.1.1.1.2 X 2.23 T 50 Years Sprinklers 5.3.1.1.1 X 2.24 T 75 Years Sprinklers 75 years in service 5.3.1.1.1.4 X 2.25 T Sprinklers manufactured prior to 1920 - Replace 5.3.1.1.1.1 X 3.1 M Annually Control Valves 12.3.4 X 3.2 M Annually Preaction /Deluge Valves 12.4.3.3.2 X 3.3 M Annually y ry Pipe Valves /Quick- Opening Devices 12.4.4.3.2 X 3.4 M Annually Dry Pipe Valve - Low Point Drains 12.4.4.3.3 X 3.5 M 5 Years Obstruction Investigation Chapter 13 X State Fire Marshal AES 2 March 21, 2006 Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 3 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 Property Information: Name: Bakersfield College-Field House Address: 1801 Panorama Dr City: Bakersfield System Riser ID: 7499 . _..... . Type Of System: O�;Cat,��9 Fxj Wet Pipe ❑ Dry Pipe °� y ❑ Preaction �f ❑ Deluge ARE M� Item Deficiencies and Comments: Deficiencies and Comments Item number must correspond to the Item number of the activity listed above: ❑ See Continuation Page(s) (Indicate the number of continuation pages) ❑x PASS ❑ FAIL 01/05/2011 Signature Date State Fire Marshal AES 2 March 21, 2006 Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 4 of 5 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 5 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 System Riser ID: 7499 Property Information: -. - Type Of System: F Cq C�,NO,A Name: Bakersfield College -Child Care 400 Wet Pipe Address: 1801 Panorama Dr ❑ Dry Pipe a A -O = After Operation ❑ Preaction �► MI = Per Manufacturer's Instructions ❑ DelugepE Mp City: Bakersfield Frequency Main Drain Test Results: Abbreviation Key: Initial Static Pressure: (psi) I = Inspection T =Test Residual Pressure: (psi) M = Maintenance A -O = After Operation Restored Static Pressure: (psi) MI = Per Manufacturer's Instructions Item Activity Frequency Description NFPA 25 Fail N/A Pass Reference 1.1 1 Daily Preaction /Deluge Valves - Enclosure 12.4.3.1 X Weekly temperature 1.2 I Daily Dry Pipe Valves - Enclosure 12.4.4.1.1 X Weeklv temperature 1.3 1 Quarterly Gauges - (Dry, Preaction, Deluge 5.2.4.2 X Systems) 5.2.4.3 1.4 1 Quarterly Control Valves 12.3.2.1 X 1.5 1 Quarterly Alarm Devices 5.2.6 X 1.6 1 Quarterly Gauges (Wet Pipe Systems) 5.2.4.1 X 1.7 1 Quarterly Hydraulic nameplate 5.2.7 X 1.8 1 Quarterly Pipe and Fittings 5.2.2 X 1.9 1 Quarterly Sprinklers 5.2.1 X 1.10 1 Quarterly Spare Sprinklers 5.2.1.3 X 1.11 1 Quarterly Fire Department Connections 12.7.1 X 1.12 I Quarterly Alarm Valves - Exterior Inspection 12.4.1.1 X 1.13 I Quarterly Quarter) Preaction /Deluge Valves - Exterior 12.4.3.1.6 X Inspection 1.14 1 Quarterly Pressure Reducing Valves 12.5.1.1 X 1.15 1 Quarterly Dry Pipe Valves- Exterior Inspection 12.4.4.1.4 X 1.16 1 Quarterly Backflow Preventers 12.6.1 X 1.17 1 Annual Buildings 5.2.5 X State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 1 of 5 ANNEX B Item Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Frequency Date Of Inspection, Testing, Maintenance: 01/05/2011 System Riser ID: 7499 Fail Property Information: Pass Type Of System: 1 Annually Hangers 5.2.3 of Cq�,� Name: Bakersfield College -Child Care 400 Wet Pipe Q�� . �q Address: 1801 Panorama Dr ❑ Dry Pipe °q D X ❑ Preaction ., 5 Years Hangers (Accessible concealed spaces) 5.2.3.3 4 X ❑ Deluge -F SAE M� City: Bakersfield Seismic Braces (Accessible concealed spaces) 5.2.3.3 _.. Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass 1.18 1 Annually Hangers 5.2.3 X 1.19 I Annually Seismic Braces 5.2.3 X 1.20 1 5 Years Hangers (Accessible concealed spaces) 5.2.3.3 X 1.21 1 5 Years Seismic Braces (Accessible concealed spaces) 5.2.3.3 X 1.22 1 5 Years Pipe and Fittings (Accessible concealed spaces 5.2.2.3 X 1.23 1 5 Years Sprinklers (Accessible concealed spaces) 5.2.1.1.4 X 1.24 1 5 Years Alarm Valves - Interior Inspection 12.4.1.2 X 1.25 1 5 Years Alarm Valves - Strainers, filters, orifices 12.4.1.2 X 1.26 1 5 Years Check Valves - Interior Inspection 12.4.2.1 X 1.27 1 5 Years Preaction /Deluge Valves - Interior Inspection 12.4.3.1.7 X 1.28 1 5 Years Preaction /Deluge Valves - Strainers, filters, orifices 12.4.3.1.8 X 1.29 1 5 Years Dry Pipe Valves - Interior Inspection 12.4.4.1.5 X 1.30 1 5 Years Dry Pipe Valves - Strainers, filters, orifices 12.4.4.1.6 X 2.1 T Annually Alarm Devices (90 Sec) 5.3.3 12.2.7 X 2.2 T Annually Main Drain Test (Enter data on Page 1) 12.2.6 12.2.6.1 12.3.3.4 X 2.3 T Annually Antifreeze Test 5.3.4 X 2.4 T Annually Control Valve - Position 12.3.3.1 X 2.5 T Annually . Control Valve - Operation 12.3.3.1 X 2.6 T Annually Supervisory 12.3.3.5 X 2.7 T Annually Preaction Valve - Priming Water 12.4.3.2.1 X 2.8 T Annually Preaction Valve - Low Air Pressure Alarm 12.4.3.2.10 X 2.9 T Annually Preaction Valve - Full Flow Trip Test 12.4.3.2.2 X State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 2 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 Property Information: Name: Bakersfield College -Child Care 400 Address: 1801 Panorama Dr City: Bakersfield System Riser ID: 7499 Type Of System: F Ga O &, Wet Pipe a Z . ❑ Dry Pipe °p a ❑ Preaction �► ❑ DelugeAgE Mp Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass 2.10 T Annually Dry Pipe Valve - Priming Water 12.4.4.2.1 X 2.11 T Annually y ry Pipe Valve - Low Air Pressure Alarm 12.4.4.2.6 X 2.12 T Annually Dry Pipe Valve - Quick- Opening Device 12.4.4.2.4 X 2.13 T Annually Dry Pipe Valve - Trip 12.4.4.2.2 X 2.14 T Annually Backflow Preventor Assemblies 12.6.2 X 2.15 T 3 Years Dry Pipe Valve - Full Flow Trip Test 12.4.4.2.2.2 X 2.16 T 5 Years Gauges 5.3.2 X 2.17 T 5 Years Pressure Reducing Valve 12.5.1.2 X 2.18 T 5 Years Fire Department Connection Backflush 12.7.4 X 2.19 T 5 Years Sprinklers - Extra High Temperature 5.3.1.1.1.3 X 2.20 T 5 Years Sprinklers - Corrosive environment or corrosive water 5.3.1.1.2 X 2.21 T 10 Years Sprinklers - Dry 5.3.1.1.1.5 X 2.22 T 20 Years Sprinklers - Fast Response 5.3.1.1.1.2 X 2.23 T 50 Years Sprinklers 5.3.1.1.1 X 2.24 T 75 Years Sprinklers 75 years in service 5.3.1.1.1.4 X 2.25 T Sprinklers manufactured prior to 1920 - Re lace 5.3.1.1.1.1 X 3.1 M Annually Control Valves 12.3.4 X 3.2 M Annually Preaction /Deluge Valves 12.4.3.3.2 X 3.3 M Annually Dry Pipe Valves /Quick- Opening Devices 12.4.4.3.2 X 3.4 M Annually Dry Pipe Valve - Low Point Drains 12.4.4.3.3 X 3.5 M 5 Years Obstruction Investigation Chapter 13 X State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 3 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 Property Information: Name: Bakersfield College -Child Care 400 Address: 1801 Panorama Dr City: Bakersfield System Riser ID: 7499 Type Of System: F CA D ❑x Wet Pipe ❑ Dry Pipe co r: ❑ Preaction E] Deluge .cam P �' Item Deficiencies and Comments: Deficiencies and Comments Item number must correspond to the Item number of the activity listed above: ❑ See Continuation Page(s) (Indicate the number of continuation pages) ❑x PASS — ❑ FAIL ✓ / 01/05/2011 Signature Date State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 4 of 5 inspection performed by: RLH Fire Protection - Bakersfield, CA - 777797 Page 5 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended bv CCR Title 19 Date Of Inspection, Testing, Maintenance: 01105/2011 System Riser ID: 7499 Property Information: - -- - Type Of System: of CAC'�Cp Name: Bakersfield College -Child Care 300 Wet Pipe Address: 1801 Panorama Dr ❑ Dry Pipe ti �► A -O = After Operation ❑ Preaction �g►�, �P. MI = Per Manufacturer's Instructions ❑ DelugeiE M ": City: Bakersfield Frequency Main Drain Test Results: Abbreviation Key: Initial Static Pressure: (psi) I = Inspection T =Test Residual Pressure: (psi) M = Maintenance A -O = After Operation Restored Static Pressure: (psi) MI = Per Manufacturer's Instructions Item Activity Frequency Description NFPA 25 Fail N/A Pass Reference 1.1 1 Daily Preaction /Deluge Valves - Enclosure 12.4.3.1 X Weekly tem erature 1.2 I Daily Dry Pipe Valves - Enclosure 12.4.4.1.1 X Weeklv tem erature 1.3 1 Quarterly Gauges - (Dry, Preaction, Deluge 5.2.4.2 X S stems ) 5.2.4.3 1.4 1 Quarterly Control Valves 12.3.2.1 X 1.5 1 Quarterly Alarm Devices 5.2.6 X 1.6 1 Quarterly Gauges (Wet Pipe Systems) 5.2.4.1 X 1.7 1 Quarterly Hydraulic nameplate 5.2.7 X 1.8 1 Quarterly Pipe and Fittings 5.2.2 X 1.9 1 Quarterly Sprinklers 5.2.1 X 1.10 1 Quarterly Spare Sprinklers 5.2.1.3 X 1.11 1 Quarterly Fire Department Connections 12.7.1 X 1.12 1 Quarterly Alarm Valves - Exterior Inspection 12.4.1.1 X 1.13 1 Quarterly Quarter) Preaction /Deluge Valves - Exterior 12.4.3.1.6 X Inspection 1.14 1 Quarterly Pressure Reducing Valves 12.5.1.1 X 1.15 1 Quarterly Dry Pipe Valves- Exterior Inspection 12.4.4.1.4 X 1.16 1 Quarterly Backflow Preventers 12.6.1 X 1.17 1 Annual Buildings 5.2.5 X State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 1 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Activity Date Of Inspection, Testing, Maintenance: 01105/2011 Description System Riser ID: 7499 Fail Property Information: Pass Type Of System: OF CAL, Name: Bakersfield College -Child Care 300 Hangers ❑x Wet Pipe ,�� p � .p Address: 1801 Panorama Dr E] Dry Pipe `9 y Annually Seismic Braces ❑ Preaction ., X 1.20 1 5 Years Hangers (Accessible concealed spaces) ❑ Deluge�iE.M City: Bakersfield 1.21 I Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass 1.18 1 Annually Hangers 5.2.3 X 1.19 1 Annually Seismic Braces 5.2.3 X 1.20 1 5 Years Hangers (Accessible concealed spaces) 5.2.3.3 X 1.21 I 5 Years Seismic Braces (Accessible concealed spaces) 5.2.3.3 X 1.22 1 5 Years Pipe and Fittings (Accessible concealed spaces 5.2.2.3 X 1.23 1 5 Years Sprinklers (Accessible concealed spaces) 5.2.1.1.4 X 1.24 1 5 Years Alarm Valves - Interior Inspection 12.4.1.2 X 1.25 1 5 Years Alarm Valves - Strainers, filters, orifices 12.4.1.2 X 1.26 1 5 Years Check Valves - Interior Inspection 12.4.2.1 X 1.27 1 5 Years Preaction /Deluge Valves - Interior Inspection 12.4.3.1.7 X 1.28 1 5 Years Preaction /Deluge Valves - Strainers, filters, orifices 12.4.3.1.8 X 1.29 1 5 Years Dry Pipe Valves - Interior Inspection 12.4.4.1.5 X 1.30 1 5 Years Dry Pipe Valves - Strainers, filters, orifices 12.4.4.1.6 X 2.1 T Annually Alarm Devices (90 Sec) 5.3.3 12.2.7 X 2.2 T Annually Main Drain Test (Enter data on Page 1) 12.2.6 12.2.6.1 12.3.3.4 X 2.3 T Annually Antifreeze Test 5.3.4 X 2.4 T Annually Control Valve - Position 12.3.3.1 X 2.5 T Annually Control Valve - Operation 12.3.3.1 X 2.6 T Annually Supervisory 12.3.3.5 X 2.7 T Annually Preaction Valve - Priming Water 12.4.3.2.1 X 2.8 T Annually Preaction Valve - Low Air Pressure Alarm 12.4.3.2.10 X 2.9 T Annually Preaction Valve - Full Flow Trip Test 12.4.3.2.2 X State Fire Marshal AES 2 March 21, 2006 Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 2 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 Property Information: Name: Bakersfield College -Child Care 300 Address: 1801 Panorama Dr City: Bakersfield System Riser ID: 7499 — - Type Of System: F CA ��'�p ❑x Wet Pipe ❑ Dry Pipe °� a ❑ Preaction �► Deluge ❑ 9 E "M --- . -. -..- Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass 2.10 T Annually Dry Pipe Valve - Priming Water 12.4.4.2.1 X 2.11 T Annually Dry Pipe Valve - Low Air Pressure Alarm 12.4.4.2.6 X 2.12 T Annually Dry Pipe Valve - Quick- Opening Device 12.4.4.2.4 X 2.13 T Annually Dry Pipe Valve - Trip 12.4.4.2.2 X 2.14 T Annually Backflow Preventor Assemblies 12.6.2 X 2.15 T 3 Years Dry Pipe Valve - Full Flow Trip Test 12.4.4.2.2.2 X 2.16 T 5 Years Gauges 5.3.2 X 2.17 T 5 Years Pressure Reducing Valve 12.5.1.2 X 2.18 T 5 Years Fire Department Connection Backflush 12.7.4 X 2.19 T 5 Years Sprinklers - Extra High Temperature 5.3.1.1.1.3 X 2.20 T 5 Years Sprinklers - Corrosive environment or corrosive water 5.3.1.1.2 X 2.21 T 10 Years Sprinklers - Dry 5.3.1.1.1.5 X 2.22 T 20 Years Sprinklers - Fast Response 5.3.1.1.1.2 X 2.23 T 50 Years Sprinklers 5.3.1.1.1 X 2.24 T 75 Years Sprinklers 75 years in service 5.3.1.1.1.4 X 2.25 T Sprinklers manufactured prior to 1920 - Re lace 5.3.1.1.1.1 X 3.1 M Annually Control Valves 12.3.4 X 3.2 M Annually Preaction /Deluge Valves 12.4.3.3.2 X 3.3 M Annually Dry Pipe Valves /Quick- Opening Devices 12.4.4.3.2 X 3.4 M Annually Dry Pipe Valve - Low Point Drains 12.4.4.3.3 X 3.5 M 5 Years Obstruction Investigation Chapter 13 X State Fire Marshal AES 2 March 21, 2006 Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 3 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 Property Information: Name: Bakersfield College -Child Care 300 Address: 1801 Panorama Dr City: Bakersfield System Riser ID: 7499 _. Type Of System: f CA' ticQ ❑X Wet Pipe ❑ Dry Pipe y ❑ Preaction �► �, ❑ Deluge E M Item Deficiencies and Comments: Deficiencies and Comments Item number must correspond to the Item number of the activity listed above: ❑ See Continuation Page(s) (Indicate the number of continuation pages) x PASS ,,n - ❑ ❑ FAIL 1) 01 /05/2011 Signature Date State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 4 of 5 inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 5 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 System Riser ID: 7499 Property Information: Type Of System: p Cq o C,�p Name: Bakersfield College -Book Store ❑x Wet Pipe Address: 1801 Panorama Dr ❑ Dry Pipe a A -O = After Operation ❑ Preaction MI = Per Manufacturer's Instructions ❑ Deluge City: Bakersfield Frequency Main Drain Test Results: Abbreviation Key: Initial Static Pressure: (psi) I = Inspection T = Test Residual Pressure: (psi) M = Maintenance A -O = After Operation Restored Static Pressure: (psi) MI = Per Manufacturer's Instructions Item Activity Frequency Description NFPA 25 Fail N/A Pass Reference 1.1 1 Daily Preaction /Deluge Valves - Enclosure 12.4.3.1 X Weekly terniperature 1.2 I Daily Dry Pipe Valves - Enclosure 12.4.4.1.1 X WeekIv tem erature 1.3 1 Quarterly Gauges - (Dry, Preaction, Deluge 5.2.4.2 X S stems ) 5.2.4.3 1.4 1 Quarterly Control Valves 12.3.2.1 X 1.5 1 Quarterly Alarm Devices 5.2.6 X 1.6 I Quarterly Gauges (Wet Pipe Systems) 5.2.4.1 X 1.7 1 Quarterly Hydraulic nameplate 5.2.7 X 1.8 1 Quarterly Pipe and Fittings 5.2.2 X 1.9 1 Quarterly Sprinklers 5.2.1 X 1.10 1 Quarterly Spare Sprinklers 5.2.1.3 X 1.11 1 Quarterly Fire Department Connections 12.7.1 X 1.12 I Quarterly Alarm Valves - Exterior Inspection 12.4.1.1 X 1.13 I Quarterly Quarter) Preaction /Deluge Valves - Exterior 12.4.3.1.6 X Inspection 1.14 1 Quarterly Pressure Reducing Valves 12.5.1.1 X 1.15 1 Quarterly Dry Pipe Valves- Exterior Inspection 12.4.4.1.4 X 1.16 1 Quarterly Backflow Preventers 12.6.1 X 1.17 I Annual Buildings 5.2.5 X State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 1 of 5 ANNEX B Item Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Frequency Date Of Inspection, Testing, Maintenance: 01/05/2011 System Riser ID: 7499 Fail Property Information: Pass Type Of System: 1 Annually Hangers 5.2.3 Cqt,��o Name: Bakersfield College -Book Store ❑x Wet Pipe I Address: 1801 Panorama Dr ❑ Dry Pipe �' y X ❑ Preaction ., 5 Years Hangers (Accessible concealed spaces) 5.2.3.3 X Deluge ❑ 9 ARE p City: Bakersfield Seismic Braces (Accessible concealed spaces) 5.2.3.3 Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass 1.18 1 Annually Hangers 5.2.3 X 1.19 I Annually Seismic Braces 5.2.3 X 1.20 1 5 Years Hangers (Accessible concealed spaces) 5.2.3.3 X 1.21 1 5 Years Seismic Braces (Accessible concealed spaces) 5.2.3.3 X 1.22 1 5 Years Pipe and Fittings (Accessible concealed spaces) 5.2.2.3 X 1.23 1 5 Years Sprinklers (Accessible concealed spaces) 5.2.1.1.4 X 1.24 1 5 Years Alarm Valves - Interior Inspection 12.4.1.2 X 1.25 1 5 Years Alarm Valves - Strainers, filters, orifices 12.4.1.2 X 1.26 1 5 Years Check Valves - Interior Inspection 12.4.2.1 X 1.27 1 5 Years Preaction /Deluge Valves - Interior Inspection 12.4.3.1.7 X 1.28 1 5 Years Preaction /Deluge Valves - Strainers, filters, orifices 12.4.3.1.8 X 1.29 1 5 Years Dry Pipe Valves - Interior Inspection 12.4.4.1.5 X 1.30 1 5 Years Dry Pipe Valves - Strainers, filters, orifices 12.4.4.1.6 X 2.1 T Annually Alarm Devices (90 Sec) 5.3.3 12.2.7 X 2.2 T Annually Main Drain Test (Enter data on Page 1) 12.2.6 12.2.6.1 12.3.3.4 X 2.3 T Annually Antifreeze Test 5.3.4 X 2.4 T Annually Control Valve - Position 12.3.3.1 X 2.5 T Annually Control Valve - Operation 12.3.3.1 X 2.6 T Annually Supervisory 12.3.3.5 X 2.7 T Annually Preaction Valve - Priming Water 12.4.3.2.1 X 2.8 T Annually Preaction Valve - Low Air Pressure Alarm 12.4.3.2.10 X F2.9 T Annually I Preaction Valve - Full Flow Trip Test 12.4.3.2.2 X State Fire Marshal AES 2 March 21, 2006 Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 2 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 System Riser ID: 7499 Property Information: Type Of System: of cqt,' Name: Bakersfield College -Book Store Wet Pipe Z Address: 1801 Panorama Dr ❑ Dry Pipe _ a. ❑ Preaction .r ❑ Deluge E M City: Bakersfield NFPA 25 Item Activity Frequency Description Reference Fail N/A Pass 2.10 T Annually Dry Pipe Valve - Priming Water 12.4.4.2.1 X 2.11 T Annually Dry Pipe Valve - Low Air Pressure 12.4.4.2.6 X Alarm 2.12 T Annually y ry Pipe Valve - Quick- Opening 12.4.4.2.4 X Device 2.13 T Annually Dry Pipe Valve - Trip 12.4.4.2.2 X 2.14 T Annually Backflow Preventor Assemblies 12.6.2 X 2.15 T 3 Years Dry Pipe Valve - Full Flow Trip Test 12.4.4.2.2.2 X 2.16 T 5 Years Gauges 5.3.2 X 2.17 T 5 Years Pressure Reducing Valve 12.5.1.2 X 2.18 T 5 Years Fire Department Connection Backflush 12.7.4 X 2.19 T 5 Years Sprinklers - Extra High Temperature 5.3.1.1.1.3 X 2.20 T 5 Years Sprinklers - Corrosive environment or 5.3.1.1.2 X corrosive water 2.21 T 10 Years Sprinklers - Dry 5.3.1.1.1.5 X 2.22 T 20 Years Sprinklers - Fast Response 5.3.1.1.1.2 X 2.23 T 50 Years Sprinklers 5.3.1.1.1 X 2.24 T 75 Years Sprinklers 75 years in service 5.3.1.1.1.4 X 2.25 T Sprinklers manufactured prior to 1920 5.3.1.1.1.1 X - Replace 3.1 M Annually Control Valves 12.3.4 X 3.2 M Annually Preaction /Deluge Valves 12.4.3.3.2 X 3.3 Annuall Dry Pipe Valves /Quick- Opening 12.4.4.3.2 X Devices 3.4 M Annually Dry Pipe Valve - Low Point Drains 12.4.4.3.3 X 3.5 M 5 Years Obstruction Investigation Chapter 13 X State Fire Marshal AES 2 March 21, 2006 Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 3 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 Property Information: Name: Bakersfield College -Book Store Address: 1801 Panorama Dr City: Bakersfield System Riser ID: 7499 Type Of System: ���f CAC�,�o ❑x Wet Pipe Q ❑ Dry Pipe GD y ❑ Preaction ❑ DelugeRF'Mp, Item Deficiencies and Comments: Deficiencies and Comments Item number must correspond to the Item number of the activity listed above: ❑ See Continuation Page(s) (Indicate the number of continuation pages) ❑x PASS _ F1 FAIL 01/05/2011 Signature Date State Fire Marshal AES 2 March 21, 2006 Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 4 of 5 inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 5 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 System Riser ID: 7499 Property Information: - Type Of System: Name: Bakersfield College -Child Care 200 Wet Pipe Address: 1801 Panorama Dr ❑ Dry Pipe a A -O = After Operation ❑ Preaction �►'' �+: MI = Per Manufacturer's Instructions ❑ Deluge ARE M City: Bakersfield Frequency Main Drain Test Results: Abbreviation Key: Initial Static Pressure: (psi) I = Inspection T = Test Residual Pressure: (psi) M = Maintenance A -O = After Operation Restored Static Pressure: (psi) MI = Per Manufacturer's Instructions Item Activity Frequency Description NFPA 25 Fail N/A Pass Reference 1.1 1 Daily Preaction /Deluge Valves - Enclosure 12:4.3.1 X Weekly temperature 1.2 I Daily Dry Pipe Valves - Enclosure 12.4.4.1.1 X Week/ tem erature 1.3 1 Quarterly Gauges - (Dry, Preaction, Deluge 5.2.4.2 X Systems) 5.2.4.3 1.4 1 Quarterly Control Valves 12.3.2.1 X 1.5 1 Quarterly Alarm Devices 5.2.6 X 1.6 I Quarterly Gauges (Wet Pipe Systems) 5.2.4.1 X 1.7 1 Quarterly Hydraulic nameplate 5.2.7 X 1.8 1 Quarterly Pipe and Fittings 5.2.2 X 1.9 1 Quarterly Sprinklers 5.2.1 X 1.10 1 Quarterly Spare Sprinklers 5.2.1.3 X 1.11 1 Quarterly Fire Department Connections 12.7.1 X 1.12 I Quarterly Alarm Valves - Exterior Inspection 12.4.1.1 X 1.13 I Quarterly Preaction /Deluge Valves - Exterior 12.4. 3.1.6 X Inspection 1.14 1 Quarterly Pressure Reducing Valves 12.5.1.1 X 1.15 1 Quarterly Dry Pipe Valves- Exterior Inspection 12.4.4.1.4 X 1.16 1 Quarterly Backflow Preventers 12.6.1 X 1.17 I Annual Buildings 5.2.5 X State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 1 of 5 ANNEX B Item Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Frequency Date Of Inspection, Testing, Maintenance: 01/05/2011 System Riser ID: 7499 Fail Property Information: Pass Type Of System: _ Name: Bakersfield College -Child Care 200 ❑x Wet Pipe of: Cqt��O Address: 1801 Panorama Dr ❑ Dry Pipe 1 Annually Seismic Braces ❑ Preaction., X 1.20 4 5 Years Hangers (Accessible concealed spaces) ❑ Deluge SAE M City: Bakersfield 1.21 _.. Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass 1.18 1 Annually Hangers 5.2.3 X 1.19 1 Annually Seismic Braces 5.2.3 X 1.20 1 5 Years Hangers (Accessible concealed spaces) 5.2.3.3 X 1.21 1 5 Years Seismic Braces (Accessible concealed spaces) 5.2.3.3 X 1.22 I 5 Years Pipe and Fittings (Accessible concealed spaces 5.2.2.3 X 1.23 1 5 Years Sprinklers (Accessible concealed spaces) 5.2.1.1.4 X 1.24 1 5 Years Alarm Valves - Interior Inspection 12.4.1.2 X 1.25 1 5 Years Alarm Valves - Strainers, filters, orifices 12.4.1.2 X 1.26 1 5 Years Check Valves - Interior Inspection 12.4.2.1 X 1.27 1 5 Years Preaction /Deluge Valves - Interior Inspection 12.4.3.1.7 X 1.28 1 5 Years Preaction /Deluge Valves - Strainers, filters, orifices 12.4.3.1.8 X 1.29 1 5 Years Dry Pipe Valves - Interior Inspection 12.4.4.1.5 X 1.30 1 5 Years Dry Pipe Valves - Strainers, filters, orifices 12.4.4.1.6 X 2.1 T Annually Alarm Devices (90 Sec) 5.3.3 12.2.7 X 2.2 T Annually Main Drain Test (Enter data on Page 1) 12.2.6 12.2.6.1 12.3.3.4 X 2.3 T Annually Antifreeze Test 5.3.4 X 2.4 T Annually Control Valve - Position 12.3.3.1 X 2.5 T Annually Control Valve - Operation 12.3.3.1 X 2.6 T Annually Supervisory 12.3.3.5 X 2.7 T Annually Preaction Valve - Priming Water 12.4.3.2.1 X 2.8 T Annually Preaction Valve - Low Air Pressure Alarm 12.4.3.2.10 X 2.9 T Annually Preaction Valve - Full Flow Trip Test 12.4.3.2.2 X State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717. Page 2 of 5 ANNEX B Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 System Riser ID: 7499 Property Information: - Type Of System: OF Cq��� - Name: Bakersfield College -Child Care 200 ❑x Wet Pipe q� �p Address: 1801 Panorama Dr ❑ Dry Pipe °� a ❑ Preaction .r ❑ Deluge EM City: Bakersfield NFPA 25 Item Activity Frequency Description Reference Fail N/A Pass 2.10 T Annually Dry Pipe Valve - Priming Water 12.4.4.2.1 X 2.11 T Annually y ry Pipe Valve - Low Air Pressure 12.4.4.2.6 X Alarm 2.12 T Annually Dry Pipe Valve - Quick- Opening 12.4.4.2.4 X Device 2.13 T Annually Dry Pipe Valve - Trip 12.4.4.2.2 X 2.14 T Annually Backflow Preventor Assemblies 12.6.2 X 2.15 T 3 Years Dry Pipe Valve - Full Flow Trip Test 12.4.4.2.2.2 X 2.16 T 5 Years Gauges 5.3.2 X 2.17 T 5 Years Pressure Reducing Valve 12.5.1.2 X 2.18 T 5 Years Fire Department Connection Backflush 12.7.4 X 2.19 T 5 Years Sprinklers - Extra High Temperature 5.3.1.1.1.3 X 2.20 T 5 Years Sprinklers - Corrosive environment or 5.3.1.1.2 X corrosive water 2.21 T 10 Years Sprinklers - Dry 5.3.1.1.1.5 X 2.22 T 20 Years Sprinklers - Fast Response 5.3.1.1.1.2 X 2.23 T 50 Years Sprinklers 5.3.1.1.1 X 2.24 T 75 Years Sprinklers 75 years in service 5.3.1.1.1.4 X 2.25 T Sprinklers manufactured prior to 1920 5.3.1.1.1.1 X - Replace 3.1 M Annually Control Valves 12.3.4 X 3.2 M Annually Preaction /Deluge Valves 12.4.3.3.2 X 3.3 M Annually Dry Pipe Valves /Quick- Opening 12.4.4.3.2 X Devices 3.4 M Annually Dry Pipe Valve - Low Point Drains 12.4.4.3.3 X 3.5 M 5 Years Obstruction Investigation Chapter 13 X State Fire Marshal AES 2 March 21, 2006 Inspection performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 3 of 5 U 1141 104 10.14 Inspection, Testing, and Maintenance Fire Sprinkler System NFPA 25 Chapter 5 as amended by CCR Title 19 Date Of Inspection, Testing, Maintenance: 01/05/2011 Property Information: Name: Bakersfield College -Child Care 200 Address: 1801 Panorama Dr City: Bakersfield System Riser ID: 7499 Type Of System: �F CA�p�o Wet Pipe �a : • . ❑ Dry Pipe �' a ❑ Preaction ❑ Deluge M Item Deficiencies and Comments: Deficiencies and Comments Item number must correspond to the Item number of the activity listed above: ❑ See Continuation Page(s) (Indicate the number of continuation pages) ❑X PASS F1 FAIL 01/05/2011 Signature Date State Fire Marshal AES 2 March 21, 2006 Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 4 of 5 Inspection Performed by: RLH Fire Protection - Bakersfield, CA - 777717 Page 5 of 5