HomeMy WebLinkAbout7.5-140ELECTRICAL SYMBOLS GENERALELECTRICAL NOTES SYMBOL DESCRIPTION SYMBOL DESCRIPTION BASIC MATERIALS AND METHODS ■ FLUORESCENT FIXTURE, RECESSED ® ® BRANCH PANELBOARD, SURFACE, FLUSH SECTION 16100 BASIC ELECTRICAL REQUIREMENTS PART 1 - GENERAL D. ALL ELECTRICAL BOXES SHALL BE SUPPORTED FROM BUILDING STRUCTURAL MEMBERS INDEPENDENTLY OF THE uj M O l() PART 1 - GENERAL 1.1 RELATED DOCUMENTS CONDUIT RACEWAY. MECHANICAL SYSTEMS OF SUSPENDED CEILING SUPPORTS. RECESSED BOXES SHALL BE ■ O FLUSH WITH SURROUNDING SURFACES. ALL BOXES AND CABINETS SHALL BE PROTECTED DURING CONSTRUCTION AND �o FLUORESCENT FIXTURE, SURFACE ® �� DISTRIBUTION PANELBOARD; SURFACE, FLUSH 1.1 RELATED DOCUMENTS A. REFER TO DRAWINGS AND CONTRACT FOR MATERIALS FURNISHED BY OWNER, INSTALLED BY CONTRACTOR OR FURNISHED AND INSTALLED BY OWNER. SHALL BE CLEANED BEFORE PULLING WIRE AND INSTALLING DEVICES. O A. REFER TO DRAWINGS AND CONTRACT FOR MATERIALS FURNISHED BY OWNER, INSTALLED BY CONTRACTOR OR E. UNLESS NOTED OTHERWISE, RECEPTACLES SHALL BE INSTALLED 18" ABOVE THE FINISHED FLOOR AND SWITCHES ^ M FURNISHED AND INSTALLED BY OWNER. 1.2 SCOPE OF WORK SHALL BE 48" ABOVE FINISH FLOOR. RECEPTACLES NOTED ABOVE WORK COUNTER AND CABINETS SHALL 1.2 SUMMARY BE MOUNTED ABOVE THE BACKSPLASH. WEATHERPROOF RECEPTACLES SHALL BE INSTALLED SO THAT THE COVER ^ O r I-O-I FLUORESCENT FIXTURE, OPEN STRIP o TELEPHONE TERM. CABINET; SURFACE, FLUSH A. FURNISH ALL LABOR, SUPERVISION AND EQUIPMENT (UNLESS EQUIPMENT IS SPECIFICALLY NOTED AS 'OWNER A. SECTION 16200 APPLIES TO ALL WORK HERE UNDER AND SHALL INCLUDE CONDUIT, BOXES, WIRE, WIRING DEVICES, PROTECTS THE DEVICE IN THE OPEN POSITION. RECEPTACLES SHALL BE BONDED TO METALLIC BOXES OR TO O O FURNISHED') FOR THE COMPLETE INSTALLATION OF A COMPLETE AND PROPERLY OPERATING ELECTRICAL SYSTEM MOTOR STARTERS, LIGHTING FIXTURES, HEAT TRACE AND RELATED MATERIALS SEPARATE GROUND CONDUCTOR PER NEC. m M O WITH ALL NECESSARY AUXILIARIES AND APPURTENANCES. PART 2 - PRODUCTS F. EQUIPMENT CONNECTIONS: PROVIDE ALL NECESSARY MOTOR STARTERS, DISCONNECT SWITCHES, CONTROLS, Q a,, L O O INCANDESCENT OR HID FIXTURE, SURFACE /PENDANT Ep DISCONNECT SWITCH; FUSED B. NATIONAL ELECTRICAL PACKAGES 1. THE OWNER THROUGH A DESIGNATED NATIONAL ELECTRICAL PACKAGE VENDOR MAY PROVIDE 2.1 RACE WAY CONDUIT, BOXES WIRE ETC AND CONNECT COMPLETE TO EACH PIECE OF EQUIPMENT REQUIRING CONNECTIONS , . INDICATED ON THE DRAWINGS. WHERE EQUIPMENT RATINGS DIFFER FROM THAT INDICATED, CONSULT � � t0 Q 0 LL SWITCHGEAR, PANELBOARDS, AND SPECIFIC LIGHTING FIXTURES. SEE DRAWINGS FOR DETAILS. CONSTRUCTION MANAGER, WHERE EQUIPMENT IS NOTED AS FUTURE, TERMINATE CIRCUIT IN JUNCTION BOX AND 0 U u 2. FURNISH ALL NECESSARY LABOR AND EQUIPMENT TO COMPLETELY INSTALL THE NATIONAL ELECTRICAL A. SHALL BE AS INDICATED ON THE DRAWINGS TAPE ENDS OF THE CONDUCTORS. O ® INCANDESCENT OR HID FIXTURE, RECESSED Dj DISCONNECT SWITCH; UNFUSED PACKAGE AS INDICATED IN THE DRAWINGS. B. FLEXIBLE CONDUIT: UL LISTED LIQUID TIGHT CONDUIT WITH LIQUID TIGHT CONDUCTORS. G. LIGHTING FIXTURES: FIXTURES SUPPORTED IN EXPOSED GRID CEILINGS SHALL BE PROVIDED WITH CLIPS. FIXTURES w, G9 C. PROVIDE ALL EXCAVATION AND TAMP BACKFILL AS REQUIRED TO COMPLETE WORK. CORRECT ANY SETTLING DURING MOUNTED IN OR ON TILE CEILINGS SHALL BE ALIGNED WITH TILES. LIGHTING FIXTURES SHALL BE SUPPORTING WIRE � O QUARANTINE PERIOD TO OWNER'S SATISFACTION. C. RIGID CONDUIT: RIGID GALVANIZED THREADED THICKWALL CONDUIT WITH THREADED FITTINGS SHALL BE PROVIDED SHALL BE PROVIDED AT EACH FIXTURE CORNER. SURFACE MOUNTED LIGHT FIXTURES SHALL BE SECURED PER C *, LU Q-I INCANDESCENT OR HID FIXTURE, WALL MOUNTED ® MOTOR STARTER; MAGNETIC IN SLABS ON GRADE. CONDUITS BELOW SLABS ON GRADE OR IN EARTH OUTSIDE OF BUILDINGS SHALL BE MANUFACTURER'S RECOMMENDATIONS. J V N LL 1.3 QUALITY ASSURANCE SCHEDULE 40 PVC WITH SEPARATE GROUNDING CONDUCTOR PER NEC, WHERE ACCEPTABLE BY LOCAL CODES. � O A. MANUFACTURER'S QUALIFICATIONS ELECTRICAL EQUIPMENT, AS INDICATED IN THE DRAWINGS, IN WHERE THE USE OF PVC CONFLICTS WITH LOCAL CODES, SUBSTITUTE RIGID GALVANIZED THREADED THICKWALL H. CLEANING: ALL EQUIPMENT INCLUDING PANELBOARDS, SWITCHES, WIRING DEVICES, LIGHTING FIXTURES, WALL w O (n O ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS AND REQUIREMENT. PROVIDE RELATED PRODUCTS AND CONDUIT PAINTED WITH 2 COATS OF ASPHALTUM AND WITH 2 COATS APPLIED AT JOINTS AFTER INSTALLATION. PLATES, ETC. SHALL BE FREE OF CORROSION, DIRT, POINT SPATTER OR DAMAGE OF ANY SORT AT FINAL ACCEPTANCE W N 0-0 PARKING LUMINAIRE TRANSFORMER; DISTRIBUTION ACCESSORIES PROTECTING FROM DIRT, MOISTURE, CONTAMINANTS AND WEATHER FROM ONE MANUFACTURER. STORE MATERIALS IN ACCORDANCE WITH MANUFACTURER RECOMMENDATIONS. COMPANY EQUIPMENT D. ELECTRIC METALLIC TUBING: ALL OTHER CONDUIT SHALL BE ELECTRIC METALLIC TUBING WITH COMPRESSION TYPE OF THE WORK. CONTRACTOR SHALL CLEAN, REPAIR OR REPLACE SOME AS INSTRUCTED BY THE CONSTRUCTION MANGER BEFORE FINAL PAYMENT. h o N Y MANUFACTURER'S, OTHER THAN THOSE LISTED, WILL BE ACCEPTABLE UPON WRITTEN APPROVAL OF CONSTRUCTION FITTINGS MANAGER, ALL ELECTRICAL MATERIALS SHALL BE LISTED AND LABELS BY UL AND SHALL CONFORM TO NEMA AND I. CONNECTIONS TO EQUIPMENT SHALL BE MADE WITH A 3' -0" FLEXIBLE LIQUID TIGHT CONDUIT WITH LIQUID TIGHT ~ OTHER INDUSTRY STANDARDS. E. CONCEALED BOXES SHALL BE 4' SQUARE GALVANIZED STEEL WITH GALVANIZIED EXTENSION RINGS, TOTAL DEPTH CONNECTORS. m M M I� SPOT OR FLOODLIGHT MOTOR OUTLET & CONNECTION B. CODES AND STANDARDS: ELECTRICAL SYSTEM SHALL CONFORM TO REQUIREMENTS OF NATIONAL, STATE AND LOCAL OF NOT LESS THAN 2 -1/2'. SURFACE MOUNTED BOXES SHALL BE CAST WEATHERPROOF ALUMINUM. J. CONNECTIONS TO RECESSED LIGHTING FIXTURES SHALL BE MADE WITH 6' -0" OF FLEXIBLE CONDUIT FROM A BOX ♦ ` v ^ 2.2 WIRING WITHIN 2' - . 0" OF THE FIXTURE ELECTRIC CODES, LOCAL AUTHORITIES AND UTILITY COMPANY. � O >-O ROADWAY LUMINAIRE CONDUIT, CONCEALED; WALL OR CEILING C. WORKMANSHIP: EXPERIENCED, WELL - TRAINED WORKERS COMPETENT TO COMPLETE THE WORK AS SPECIFIED A. WIRING: CONDUCTORS SHALL BE 98% CONDUCTIVITY COPPER OF #12 AWG- MINIMUM SIZE. 3.2 INSTALLATION, HEAT TRACE - NOT USED SHALL PERFORM LABOR IN CONFORMANCE WITH GENERALLY ACCEPTED TRADE STANDARDS. INTALL ALL EQUIPMENT SQUARE AND PLUMB ALLOWING ACCESS FOR PROPER OPERATION AND SERVICE. B. INSULATION SHALL BE COLOR CODED, AND RATED FOR 600 VOLTS MINIMUM. TYPE THHN OR THWN SHALL BE i USED WHERE CONDUIT SIZES ARE LIMITED. AT OTHER LOCATIONS, TYPE TW MAY BE USED IN SIZES #10 AND 3.3 INSTALLATION, TIME CLOCK ■ O POST OR WALKWAY LUMINAIRE CONDUIT, CONCEALED; FLOOR OR UNDERGROUND 1.4 STRUCTURAL AND SPACE CONDITIONS #12 AWG AND TYPE THW FOR LARGER SIZES. A. PROVIDE 7 DAY CALENDAR DIAL TIME CLOCK WITH BYPASS PROVISIONS FOR EXTERIOR LIGHTS. uj A. ALL WORK SHALL AVOID ABSTRUCTIONS AND INTERFERENCE WITH OTHER TRADES, PRESERVE HEADROOM AND KEEP C. WIRE CONNECTORS FOR SIZES #10 AWG AND LESS SHALL BE BUCHANAN "PRESS- SHURE ", IDEAL "WRAP -CAP ", OPENINGS AND PASSAGEWAYS CLEAR AND FREE. T &B "STAKONS" OR 3M "SCOTCHLOK . CONNECTORS FOR WIRE SIZE #8 AND LARGER SHALL BE B. UPON COMPLETION OF THE INSTALLATION, SET THE TIME CONTROLS PER THE OWNERS REPRESENTATIVE'S EXIT LIGHT; CEILING, WALL; ARROW INDICATES CONDUIT, EXPOSED T &B OR BURNDY METHODS USING HYDRAULIC PRESSES. SCHEDULE. DIRECTION 1.5 DRAWINGS 2.3 WIRING DEVICES 3.4 INSTALLATION, TELEPHONE SYSTEM A. CONTRACTOR IS RESPONSIBLE FOR EXAMINING THE DRAWINGS, SPECIFICATIONS, SITE AND OTHER BID DOCUMENTS KEYLESS PORCELAIN LAMPHOLDER RATED 550W, PRIOR TO SUBMITTING A PROPOSAL A. WALL SWITCHES SHALL BE COLOR PER ARCH AND SHALL BE AS FOLLOWS OR APPROVED EQUAL. A. FURNISH AND INSTALL THE TELEPHONE EMPTY CONDUIT, PULL WIRE, TERMINAL BOXES, JUNCTION BOXES, AND © 250V, GE #GE5740 -7 OR EQUAL WITH 150W LAMP T CONDUIT, TELEPHONE B. THE DRAWINGS AS PREPARED ARE DIAGRAMMATIC. THE WORK SHALL FOLLOW AS CLOSELY AS ACTUAL 20 A SP, 125/277 V. - -A &H 1991W, BRYANT 4901W, OR HUBBELL 1221W. OUTLET BOXES, IN BUILDING WHERE INDICATED ON THE DRAWINGS. CONSTRUCTION OF THE PROJECT AND THE WORK OF ALL TRADES PERMIT. BRYANT OR HUBBELL 3.5 INSTALLATION, SOUND SYSTEM - NOT USED NL „ �� LIGHT FIXTURE CONNECTED TO SECURITY NL CONDUIT, UP 1.6 CUTTING AND PATCHING 20 A 4W,, 125/277 V - -A&H 11994W,, BRYANT 4904W,. OR HUBBELL 11224W. 20 A. SP, 125/277V WITH PILOT LIGHT -- ARROW- HART #1991 -PL, BRYANT #4901 -PL, OR HUBBELL #1221 -PL U 00 LIGHTING CIRCUIT 20 A, SP, 125//277v, WEATHERPROOF-- ARROW HART #1991/2881 -C OR HUBBELL #1281/1795. O A. CUTTING OR PATCHING NECESSARY TO PERMIT THE INSTALLATION OF ANY WORK UNDER THIS CONTRACT IS THE z co RESPONSIBILITY OF THIS TRADE. CUTTING AND PATCHING SHALL BE COORDINATED WITH OTHER TRADES SO AS NOT TO B. RECEPTACLES SHALL BE WHITE AND SHALL BE AS FOLLOWS OR APPROVED EQUAL. PROVIDE OTHER RECEPTACLES 3.6 INSTALLATION, COMPUTER CASH REGISTER SYSTEM - NOT USED m � O EMERGENCY LIGHTING UNIT CONDUIT, DOWN IMPACT OTHER WORK. AS INDICATED ON THE DRAWINGS. 20A, 125V DUPLEX -- A &H #5362W (1), BRYANT #5362W 20A, 125V w 1.7 TESTING TWISTLOCK -- HUBBELL 2310 30A, 250V, 3W - G - -- A & H #5700, BRYANT 9630FR OR HUBBELL #9430 SECTION 16400 O Z � Q F1 LETTER ADJACENT SUYMBOL INDICATES FIXTURE / BRANCH CIRCUIT HOMERUN, CROSS HATCHING INDICATES NUMBER OF #12 AWG WIRES WHEN A. TESTS: ENTIRE ELECTRICAL SYSTEM SHALL BE FULLY TESTED AND CORRECTED OF ANY SHORT CIRCUITS, OPEN GROUNDS, FAULTY WIRING AND INCORRECT CONNECTIONS. VERIFY FAN MOTOR SPEED AND DIRECTION. 50A, 250V, 3P, 4W - G - -- A & H, P & S OR HUBBELL 8450 WITH 8452 PLUG & 4/C #8 SO CORD. GROUND FAULT -- A & H #53GF62, BRYANT #53GF62 OR HUBBEL #GF 5362. PROVIDE SPRING LOADED SERVICE AND DISTRIBUTION PART 1 - GENERAL LL Q - D z \1±0 TYPE, NUMBER INDICATES INPUT WATTS A -5 MORE THAN TWO, PANEL A, CIRCUIT NO. 5 WEATHERPROOF COYERS WHERE REQUIRED BY CODE. 1.1 RELATED DOCUMENTS Q 0- (j) ry PART 2 - EXECUTION CLOCK & SIGN HANGER - -- A & H #5708, BRYANT #2828 -GS OR HUBBELL #5235. W c LIGHT SWITCH S.P.S.T.; +48" U.O.N. O3 INDICATES NUMBER OF DETAIL NOTE 2.1 ELECTRICAL SYSTEM INSTALLATION, GENERAL C. PROVIDE FACE PLATES FOR ALL DEVICES INCLUDING WALL SWITCHES, RECEPTACLES, AND TELEPHONE OUTLETS AND ALL WALL OUTLETS. FACEPLATES SHALL BE WHITE SATIN FINISHED STAINLESS STEEL. A. REFER TO DRAWINGS AND CONTRACT FOR MATERIALS FURNISHED AND INSTALLED BY CONTRACTOR OR FURNISHED AND INSTALLED BY OWNER. �/ 0L G O LL A. SEQUENCE, COORDINATE, AND INTEGRATE THE VARIOUS ELEMENTS OF ELECTRICAL SYSTEMS, MATERIALS, AND Qn f0, U \W / COMPONENTS. D. DIMMERS SHALL BE WHITE - -- #D -18P. 1.2 SCOPE OF WORK G_ J Q 2 LIGHT SWITCH 2 P.S.T.; +48" U.O.N. EF 1 MECHANICAL EQUIPMENT DESIGNATION 1. COORDINATE ELECTRICAL SYSTEMS, EQUIPMENT, AND MATERIALS INSTALLATION WITH OTHER BUILDING E. PHOTO CELLS SHALL BE RATED 16.6 AMPS 120 VOLTS. LIGHTS SHALL BE 1.5 FOOTCANDLES FOR TURN ON AND 10 A. SECTION 16400 APPLIES TO ALL WORK HERE UNDER AND SHALL INCLUDE WORK REQUIRED FOR METERING, GROUND U U COMPONENTS. FOOTCANDLES FOR TURN OFF. SUITABLE FOR TEMPERATURE RANGES FOR -30 DEGREE'S F TO +140 DEGREES F AND WEATHERPROOF ENCLOSED. LOAD TO REMAIN ON IN CASE OF CELL FAILURE. SHALL HAVE A MINIMUM TIME RODS, PANEL BOARDS, DISCONNECT SWITCHES AND RELATED MATERIALS. PART 2 - PRODUCTS `.J s LIGHT SWITCH 3 -WAY; +48" U.O.N. O � D SUBSCRIPT LETTER ADJACENT SYMBOL 2. VERIFY ALL DIMENSIONS BY FIELD MEASUREMENTS. DELAY OF 15 SECONDS. PROVIDE PARAGON CATALOG #CW201 -00 OF EQUAL. � U W � INDICATES CONTROL 3. ARRANGE FOR CHASES, SLOTS, AND OPENINGS IN OTHER BUILDINGS COMPONENTS DURING PROGRESS OF 2.4 LIGHTING 2.1 SERVICE ENTRANCE rn ) w J J w LIGHT SWITCH 4 -WAY; +48 " U.O.N. O NUMBER ADJACENT SUMBOL INDICATES CIRCUIT NO. CONSTRUCTION, TO ALLOW FOR ELECTRICAL INSTALLATIONS. 4. COORDINATE THE INSTALLATION OF REQUIRED SUPPORTING DEVICES AND SLEEVES TO BE SET IN POURED -IN- A. LIGHTING FIXTURES SHALL BE FURNISHED BY CONTRACTOR AS SCHEDULED ON DRAWINGS EXCEPT FOR THOSE INDICATED TO BE FURNISHED BY OWNER. CONTRACTOR SHALL INSTALLALL LIGHTING FIXTURES AND PROVIDE A. CONTRACTOR SHALL VERIFY SERVICE VOLTAGE AND TYPE OF TERMINATION WITH LOCAL UTILITY COMPANY AND SHALL PROVIDE NECESSARY REVISIONS AND MODIFICATIONS REQUIRED. SERVICE TERMINATION'S MAY EITHER BE v Z J LV - - U) LL 4 2 5 ON PANELBOARD NECESSARY MOUNTING HARDWARE. ALL RECESSED LIGHTING FIXTURES SHALL BE THERMALLY PROTECTED AND IC UNDERGROUND OR OVERHEAD DEPENDING ON THE UTILITY COMPANIES REQUIREMENT AND APPROVAL BY �( PLACE CONCRETE AND OTHER STRUCTURAL COMPONENTS, AS THEY ARE CONSTRUCTED. CONSTRUCTION MANAGER. < CV RATED AS REQUIRED BY CODE. z ® SWITCH, DIMMING, SIZED TO SERVE THE CONNECTED LOAD +24" INDICATES MOUNTING HEIGHT TO CENTER OUTLET A.F.F. 5. SEQUENCE, COORDINATE, AND INTEGRATE INSTALLATIONS OF ELECTRICAL MATERIALS AND EQUIPMENT FOR EFFICIENT FLOW OF THE WORK. GIVE PARTICULAR ATTENTION TO LARGE EQUIPMENT REQUIRING POSITIONING B. CONTRACTOR SHALL FURNISH AND INSTALL ONE COMPLETE SET OF LAMPS FOR ALL LIGHTING FIXTURES SUPPLIED BY 2.2 UTILITY COMPANY METERING n n c) UJ PRIOR TO CLOSING IN THE BUILDING. THE CONTRACTOR. FIXTURES SUPPLIED BY THE OWNER OR OTHERS SHALL BE FURNISHED WITH LAMPS BY EACH Q CO RESPECTIVE FIXTURE SUPPLIER. PROVIDE LABEL IN EACH FIXTURE INDICATING SIZE AND TYPE OF LAMP A. CONTRACTOR SHALL PROVIDE NECESSARY METERING FACILITIES INCLUDING METER SOCKET, CURRENT TRANSFORMER CABINET, CONDUIT AND OTHER WORK FOR METERING REQUIRED BY THE LOCAL UTILITY COMPANY. p "``'"' SWITCH W/ PILOT LIGHT U.O.N. UNLESS OTHERWISE NOTED 6. WHERE MOUNTING HEIGHTS ARE NOT DETAILED OR DIMENSIONED, INSTALL SYSTEMS, MATERIALS, AND EQUIPMENT TO PROVIDE THE MAXIMUM HEADROOM POSSIBLE. CORRESPONDING WITH SCHEDULE ON DRAWING. C. FLUORESCENT LAMPS SHALL BE COLOR SHOWN IN SCHEDULE, ENERGY EFFICIENT, MANUFACTURED BY GENERAL 2.3 GROUNDING m 7. COORDINATE CONNECTION OF ELECTRICAL SYSTEMS WITH EXTERIOR UNDERGROUND AND OVERHEAD UTILITIES AND SERVICES. COMPLY WITH REQUIREMENTS OF GOVERNING REGULATIONS, FRANCHISED SERVICE ELECTRIC WATT MISER II A. ALL EXPOSED NON CURRENT CARRYING METALLIC PARTS OF ELECTRICAL EQUIPMENT, METALLIC RACEME SYSTEMS, a THERMAL OVERLOAD SWITCH A.F.F. ABOVE FINISHED FLOOR COMPANIES, AND CONTROLLING AGENCIES. PROVIDE REQUIRED CONNECTION FOR EACH SERVICE. D. INCANDESCENT LAMPS SHALL BE INSIDE FROSTED WITH 2500 -HOUR LAMP LIFE RATED 130 VOLTS. GROUNDING CONDUCTOR IN RACEWAYS AND NEUTRAL CONDUCTOR OF THE WIRING SYSTEM SHALL BE GROUNDED THE GROUND CONNECTION SHALL EXTEND TO THE POINT 8. INSTALL SYSTEMS, MATERIALS, AND EQUIPMENT TO CONFORM WITH DRAWINGS AND SPECS, TO GREATEST E. FLUORESCENT BALLAST'S SHALL BE ENERGY EFFICIENT. MANUFACTURED BY GENERAL ELECTRIC. MAXI -MISER II OF ENTRANCE OF THE METALLIC WATER SERVICE SHALL BE GROUNDED AS DESCRIBED BY NFPA 70 EXTENT POSSIBLE. CONFORM TO ARRANGEMENTS INDICATED THE CONTRACT DOCUMENTS, RECOGNIZING WHERE THERE ARE NO METALLIC WATER SERVICES TO THE BUILDINGS GROUND CONNECTIONS SHALL BE MADE THAT PORTIONS OF THE WORK ARE DIAGRAMMATIC COORDINATION TCONSTRUCTION IREQUIR 2.5 STARTERS TO DRIVEN GROUND RODS ON THE EXTERIOR OF THE BUILDING. J AB TWO SWITCHES AT LOCATION A.F.G. ABOVE FINISHED GRADE EQUIREMENTS CONFLICT WITH IND VIDUAL' SYSTEM MENTS, REFFER CONFLICT CT MANAGER FOR RESOLUTION PRIOR TO INSTALLATION. A. STARTERS: THREE -PHASE UNITS SHALL BE SQUARE D TYPE 8536 WITH 120 VOLTS COIL, N.O. AUXILIARY B. GROUND RODS SHALL BE OF ZINC - COATED COPPER CLAD STEEL NOT LESS THAN 3/4: IN DIAMETER, 8' LONG O CONTACT, AND WITH RED PILOT (IN COVER) DRIVEN FULL LENGTH INTO THE EARTH. THE MAXIMUM RESISTANCE OF A DRIVEN GROUND ROD SHALL NOT EXCEED rrrYYY111 M HP RATED SWITCH OR MANUAL MOTOR STARTER N.I.C. NOT IN CONTRACT 9. INSTALL SYSTEMS, MATERIALS, AND EQUIPMENT LEVEL AND PLUMB, PARALLEL AND PERPENDICULAR TO OTHER BUILDING SYSTEMS AND COMPONENTS, WHERE INSTALLED EXPOSED IN FINISHED SPACES. 2.6 TIME CLOCK 25 OHMS UNDER NORMALLY DRY CONDITIONS. IF THIS RESISTANCE CANNOT BE OBTAINED WITH A SIGNAL ROD, ADDITIONAL RODS MAY BE COUPLED AND DRIVEN WITH THE FIRST ROD. "`✓'' 10. INSTALL ELECTRICAL EQUIPMENT TO FACILITATE SERVICING, MAINTENANCE, AND REPAIR OR REPLACEMENT OF EQUIPMENT COMPONENTS. AS MUCH AS PRACTICAL, CONNECT EQUIPMENT FOR EASE OF DISCONNECTING, A. PROVIDE TIME CLOCK AS SHOWN ON DRAWINGS. 2.4 PANELBOARDS OUTLET, DUPLEX CONVENIENCE, 20A, 125V; 15" A.F.F. U.O.N. W.P. ADJACENT TO SYMBOL INDICATES WITH MINIMUM OF INTERFERENCE WITH OTHER INSTALLATIONS. B. BRANCH PANELBOARDS WILL BE FURNISHED TO THE CONTRACTOR, UNLESS NOTED AS SUPPLIED BY OWNER, FOR INSTALLATION BY THE ELECTRICAL CONTRACTOR UNLESS INDICATED OTHER ON DRAWINGS. THEY WILL BE U) WEATHERPROOF OUTLET OR DEVICE 11. INSTALL SYSTEMS, MATERIALS, AND EQUIPMENT GIVING RIGHT -OF -WAY PRIORITY TO SYSTEMS REQUIRED TO PART 3 - EXECUTION UNASSEMBLED BOLT ON CIRCUIT BREAKER TYPE, MINIMUM OF 14" WIDE AND 5 3/4: DEEP, RECESSED OR n BE INSTALLED AT A SPECIFIED SLOPE. SURFACE MOUNTED AS INDICATED. PROVIDE TYPEWRITTEN CIRCUIT DIRECTORY ON INSIDE DOOR PROTECTED WITH U 3.1 INSTALLATION, GENERAL h--1 OUTLET, DUPLEX CONVENIENCE MOUNTED ON COUNTER, G.F.I. GROUND FAULT INTERRUPTER 2.2 IDENTIFICATION A. RACEWAY SYSTEM SHALL BE INSTALLED TO MAINTAIN THE MAXIMUM HEADROOM. COMMON SUPPORTS MAY CLEAR PLASTIC SHIELD IN A CARDHOLDER CIRCUIT BREAKERS SHALL BE THERMAL MAGNETIC FULL SIZE, COMMON TRIP ON 2 AND 3 POLE WITH TRIP FREE HANDLES, RATED NOT LESS THAN 10,000 RMS AMPERES. (n W Z SEE ARCHITECT FOR MOUNTING HEIGHT A. PANELBOARD SCHEDULES- INTALL IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND COMPLY BE USED FOR MECHANICAL AND ELECTRICAL EQUIPMENT BY COORDINATING THE WORK WITH ALL TRADES. 2.5 DISCONNECT SWITCHES � 1..� OUTLET, DUPLEX CONVENIENCE, DEDICATED EQUIPMENT BP BATTERY PACK WITH FOLLOWING REQUIREMENTS. PROVIDE TYPEWRITTEN DIRECTORIES IN BRANCH PANELBOARDS WITH CLEAR PLASTIC SHIELDS. B. USE ONLY TYPE WIRE PULLING LUBRICANTS FOR WIRE #4 AWG OR LARGER. SPLICE WIRE ONLY IN ACCESSIBLE BOXES. MAKE WIRE JOINTS MECHANICALLY STRONG BEFORE APPLYING THE CONNECTOR, AND WHERE A. HVAC DISCONNECT SWITCHES SHALL BE FURNISHED BY THE CONTRACTOR, UNLESS NOTED AS SUPPLIED BY O W O �--I l D B. EQUIPMENT LABELS- PROVIDE ENGRAVED PLASTIC NAME PLATES ON ALL DISCONNECT SWITCHES, MOTOR TAPE IS USED, WRAP EACH JOINT TO THE THICKNESS OF THE ORIGINAL INSULATION CLEAN AND POLISH METALLIC SURFACES BEFORE INSTALLING CONDUCTORS. APPLY PRESSURE TYPE LUGS ON STANDARD CONDUCTORS CONNECTED OWNER, FOR INSTALLATION BY THE ELECTRICAL CONTRACTOR UNLESS INDICATED OTHERWISE ON DRAWINGS. ALL DISCONNECT SWITCHES WILL BE NORMAL DUTY TYPE NEMA ND, FUSED UNLESS NOTED OTHERWISE, WAND WITH Z � r1� OPERATOR INTERLOCKED WITH THE DOOR SO DOOR CAN BE OPENED ONLY IN THE "OFF" POSITION. ® I�--I OUTLET, DUPLEX CONVENIENCE, ISOLATED FOR COMPUTERS � LIGHT SWITCH & OUTLET COMBINATION STARTERS. CONTROL DEVICES, AND SWITCHES IN SERVICE ENTRANCE EQUIPMENTS. END OF SECTION TO SCREW OR BOLT TYPE CONNECTIONS. PART 3 - EXECUTION J Z M--I IG WITH SEPARATE GROUND C. ALL WIRE SHALL BE INSTALLED IN A CONDUIT AND SHALL BE CONCEALED. IF UNFORESEEN CONDITION REQUIRES WIRE TO BE EXPOSED TO RACEWAY SHALL BE INSTALLED AS INCONSPICUOUSLY AS POSSIBLE, CUT RACEWAY Q W SQUARES; REAM SMOOTH AND MAKE UP TIGHT. PLUG ENDS OF RACEWAYS DURING CONSTRUCTION AND SWAB 3.1 INSTALLATION, GENERAL U OUTLET, FOURPLEX CONVENIENCE; +12" U.O.N. CLOCK OUTLET, +7' -0" U.O.N. CLEAN BEFORE PULLING WIRE OF CABLE. - rTl A. PANELBOARDS SHALL BE INSTALLED AT HEIGHT INDICATED. DISCONNECT SWITCHES SHALL BE n/ < INSTALLED 4' -0" ABOVE FINISHED FLOOR WHERE POSSIBLE. ALL CABINETS SHALL BE VACUUM CLEANED BEFORE PULLING WIRE. OUTLET, SINGLE, 250V, 3W, CURRENT RATING 3 1/2 z PULLBOX, STATE SPEC. NO. AS NOTED END OF SECTION U w 20A INDICATED ADJACENT SYMBOL; +12" U.O.N. W NN a OUTLET, THERMOSTAT; +60 U.O.N. BP BYPASS TIMER W OJ JUNCTION BOX; CEILING, WALL DI COMB. OUTLET, CAT 5 DATA /PHONE, +12" U.O.N. DATE revision ® OUTLET, FLOOR POWER a DUCT SMOKE DETECTOR Oo OCCUPANCY SENSOR, WATTSTOPPER DUTLET, TELEVISION, AT +12" U.O.N. OR EQUM DATE MARK ISSUED JUNCTION BOX FOR OVERHEAD MEDICAL LIGHT; SWITCH PROVIDED IN FIXTURE; FIXTURE PROVIDED BY OWNER. DWG. BY - -- CHK'D BY DATE - -- JOB NO. 02 -263 FILE NO. �e * NOX8339 ran 9/08 CALIF SHEET E -1 OF SHEET - c,n - rn m p �.0 WNW. _u sn . 1; 66 1 f M 3 Zi L � P CA-i? V _ q I S PLANS PREPARED FOR m I E. MICHAEL LOUDEN, P.E. mw rrJ cr . "9 SAUNDERS PARK BRAUN ELECTRIC COMPANY, INC. IY -� Ti RECREATION FACILITY 3012 SILLECT AVE., SUITE B 2720 Stolle Court RAKERSFIELU. CA 93309 v O�� 189' OF i -�4' -CONDUITS c> P4 _P4 BAKERSFMD CALIFORNIA BAKERSFIELD, CALIFORNIA 93308 _u sn . 1; 66 1 f M 3 Zi L � P CA-i? V q I ELECTRICAL SITE PLAN PLANS PREPARED FOR m I E. MICHAEL LOUDEN, P.E. mw SAUNDERS PARK BRAUN ELECTRIC COMPANY, INC. IY RECREATION FACILITY 3012 SILLECT AVE., SUITE B 2720 Stolle Court RAKERSFIELU. CA 93309 BAKERSFMD CALIFORNIA BAKERSFIELD, CALIFORNIA 93308 Ph (661) 397 -9494 Fa J661) 99'7 -98$3 W M n M Z W y M � d M 0 � v LL J s °w W N� Q o N Y Q M V m ^ W .. QI s a W H1 H1 H1 H1 H1 H1 H1 H1 H1 H1 U o z m a O z Q LL Z (j) ry H1 H1 H1 H1 H1 H1 H1 H1 H1 H1 Lu O O Lu LL � U Q J W U EE � U C) w O U J J () W �_ W Z j U) LL H1 H1 H1 H1 H1 H1 H1 H1 H1 H1 N U) I o W cY) m < QI SCOREBOARD SCOREBOARD QI J NO.1 N0.2 rO LA -24 LA -26 ` H1 H1 H1 H1 H1 H1 H1 H1 H1 H1 Z ry U o Q < Q n- LL ►� Cl) Z H1 H1 H1 H1 H1 H1 H1 H1 H1 H1 W zQ J �w� Q�w U) W llf H1 H1 H1 H1 H1 H1 H1 H1 H1 H1 DATE revision LA -1,3 LA -5,7 LA -9,11 LA -13,15 LA -17,19 LA -2,4 LA -6,8 LA -10,12 LA -14,16 LA -18,20 J Ql DATE MARK ISSUED LA -22 DWG. BY - -- CHK'D BY DATE - -- LIGHTING PLAN 1,8•• -1 9.099 JOB NO. 02 -263 FILE NO. s� * NOX8339 IPA ran 9/08 OF CALF SHEET E =3 OF SHEET W M n M z W y M � d M 0 � v LL J s °w W NN o N W m M V .- s W I U o C) m a O z Q LL Z o a_ U) ry Lu � O w O � U Q J LL W 0 U CF /1B CF /1E w Q F F w —j J jjj z J Lu U) LL Q z N U) I D O LLI Q Cy) �e EXH FAN ONE ROOF) m CIRC FAN �INSIDE) 208v 3ph (TYP -3) CF /1A 1/3hp - .OFLA EF /1A EF /1B EF /1C CF /1F F 208v 1 ph (TYP -6) F F F F LA- 32,34,36 Z ry U o z Q Q CF /1C CF /1D Q 0 L F � F � n LA- 25,27,29 LA- 31,33,35 W W O Q O zQ W Q � w U) w DATE revision L— DATE MARK ISSUED DWG. BY - -- CHK'D BY DATE - -- POWER PLAN 1 /$11 =1 9-099 JOB NO. 02 -263 FILE NO. low * NOX8339 ran 9/08 OF CALF SHEET E =4 OF SHEET i i LIGHT FIXTURE SCHEDULE VOLTAGE: 120V (U.o.N.) 1.) FIXTURES SHALL HAVE APPROPRIATE. UL LABLE, DAMP, OR WET AS REQUIRED BY CODES AND ORDINAGES. 2.) FIXTURES SHALL INCLUDE ALL ACCESSORIES NECESSARY FOR INSTALLATION ACCORDING TO MANUFACTURER'S SHOP DRAWINGS AND AS.REQUIRED BY CODES AND LOCAL ORDINANCES. 3.) PRIOR TO ORDERING ANY LIGHTING EQUIPMENT, THE CONTRACTOR $HALL COORDINATE ALL FIXTURE LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS AND CEILING CAVITY DEPTHS. 4) SPECIFICATIONS. CATIONS. E PROVIDED AND COMPATIBILITY BILIIY BETWEEN ACCORDING FIXTURE, LAMP AND ALLA T(S FIXTURE SCHEDULE AND 5.) CONTRACTOR SHALL. VERIFY FIXTURE VOLTAGES AND CEILING TRIM ,COMPATIBLITY PRIOR TO ORDERING FIXTURE. 6.) PROVIDE APPROVED FIRE -RATED ENCLOSURES FOR ALL LIGHTING FIXTURES LOCATED IN FIRE– RATED CEILINGS. 7.) LIGHTING FIXTURE CATALOG NUMBERS ARE SERIES TYPE ONLY. PROVIDE ALL NECESSARY HARDWARE AS REQUIRED BY THE SPECIFICATIONS, DRAWING, AND PROJECT CONDITIONS FOR A COMPLETE INSTALLATION. 8.) ALL FIXTURES SHALL BE ORDERED WITH APPROPRIATE BALLAST(S) THAT HAVE UL AND CBM LABELS. ALL BALLASTS MUST CONFORM TO TITLE 24REQUIREMENTS FOR PERFORMANCE. PROVIDE MULTIPLE BALLASTS FOR DUAL –LEVEL SWITCHING AND WIRING (i.e. TANDEM) AS INDICATED ON THE PLANS. 9.) UPON INITIAL ENERGIZING OF ALL NEW FLUORESENT LAMPS, A CONTINUOS PERIOD OF 30 HOURS. SHALL OCCUR PRIOR TO DE– ENERGIZING OF LAMPS, FOR. MANUFACTURER REQUIRED LAMP BURN –IN AND MAXIMUM LAMP LIFE. 10.) ALL FLUORESCENT BALLASTS SHALL BE ELECTRONIC TYPE. PROVIDE .END OF LIFE (EOL) SHUT –DOWN PROTECTION FOR COMPACT FLUORESCENT LAMPS. 11.) ENSURE COMPATIBILITY OF ALL LIGHTING SYSTEM COMPONENTS ESPECIALLY DIMMED SYSTEMS. FIXTURES, LAMPS, BALLAST(S), AND DIMMING SYSTEMS /INDIVIDUAL CONTROLS MUST BE FACTORY CERTIFIED COMPATIBLE FOR FULL RANGE OF DIMMING COMPATIBILITY. 12.) PROVIDE CLEARANCES FROM COMBUSTIBLES A MINIMUM OF 1/2- (OTHER THAN AT POINTS OF SUPPORT) AND 3 FROM INSULATION FOR RECESSED LIGHTING FIXTURES WHICH ARE NON –IC RATED. 13.) PROVIDE A MINIMUM OF TWO (2) #12 SUPPORT WIRES ATTACHED'70 BUILDING FRAME IN ADDITION TO T –BAR CLIPS FOR FLUORESCENT FIXTURES RECESSED IN SUSPENDED T –BAR CEILING 14) ALL LIGHTING POLES 15 FEET AND LONGER .SHALL BE COMPLETE WITH INTEGRAL PRE–INSTALLED FACTORY ENGINEERED DAMPING ASSEMBLY TYPE INPUT WATTS DESCRIPTION AND MANUFACURER REMARKS HIGH BAY OPEN ACRYLIC REFLECTOR 26' -MAX HT 22 -1/2 DIA H1 460 VOLTAGE: 120V – LAMP: 400 WATT METAL HALIDE - MANUFACTURER: DAY BRITE`HBO40OPMT�PSG AR 22 – QUARTS FLOOD .ALUMINUM HOUSING BRONZE _ COLOR n� 15n �,� rent. env NEMA 6X6 PANEL "LA" BUS AMPS 200 ___ MFR. MILBANK r –__ LOC. METAL PEDESTAL_ –Y MTG. _OUTDOOR_ MAIN AMPS_ 200A 120/208V SEE 1 –LINE BOTTOM 30K PHASE 3 4 ___ WIRES VOLTS, ____________ FEEDER AT __ AIC RATING, DESCRIPTION VOLT -AMPS OUTLETS BKR. WIRE BUS CONNECTION IR BKR.I OUTLETS VOLT –AMPS DESCRIPTION A B C LTG REC MISC AMP P AWG AWG. P AMP MISC REC LTG A B C LIGHT BK1 1380 6 20.,/. 12 1 3 2 f��4 6 8 10 12 12 20 6 1380 LIGHT BK 7 12 2 1380 1380 2 12 5 7 12 20 6 1380 LIGHT BK 8 LIGHT BK2 1380 6 20 12 12 2 1380 1380 2 12 9 11 12 20 • 6 1380 LIGHT BK 9 LIGHT BK3 1380 6 20 12 12 2 1380 1380 2 12 LIGHT BK4 1380 6 20 12 t 3 15 14 16 18 20 22 —f 24 GFI 26 28 12 20 6 1380 LIGHT BK 10 1380 2 12 12 2 1380 LIGHT BK5 1380 6 20 12 17 19 12 20 6 1380 LIGHT BK 7 1380 2 12 12 2 1380 21 23 25 12 1 20 8 1200 QUARTZ LTS LIGHT BK6 1380 6 20 12 8 1 40 1 3800 SCOREBOARD 1 1380 2 12 8 1 40 1 3800 SCOREBOARD 2 CF /1 A 850 15 1 12 27 12 1 20 • 4 800 WP REC. ON GFI CF/1B 850 15 1 12 29 GFI 30 12 1 20 • 1 1000 TABLE REC. ON GFI CF /1 C 850 15 1 12 31 32 34 36 38 40 42 10 30 3 • 1840 EF/ 1 A,1 B,1 C CF/11) 850 15 1 12 33 35 10 184.0 CF/1E 850 15 1 12 10 3 1840 CF /1 F 850 15 1 12 37 1 20 - SPARE 'CONTROLLER 500 15 1 12 GFI 39 WP REC. ON GFI 800 4 20 1 12 41 SPARE — 20 1 CONNECTED LOAD 3720 4020 3220 11100 7980 9780 CONNECTED LOAD LOAD DATA BY PHASE DEMAND CALCULATIONS PHASE VOLT -AMPS: PHASE TOTAL— AMPS: PHASE A TOTAL : 14820 VA. PHASE A TOTAL _ 23 _ A• PHASE B TOTAL : 12OQQ _ VA. PHASE B TOTAL _ 100 =_ A. PHASE C TOTAL : -13000 VA. PHASE C TOTAL _109 _ A. . TOTAL CONNECTED VOLT -AMPS 39820 VA. LONG CONTINUOUS LOADING (LCL) _ A4%O VA. TOTAL DEMAND _ 4829MO VA. \ 4ZA A\lMC• I TOTAL DEMAND AMPS = x$284 VOLTS –AMPS — (V3 * Irl'1A= VULIAht __1.ys___VULi. ._ – =� -- AS- BUIILT — Relay Can Diagram p �--� �•--� TB 2 m -3] 51 d-7 LC to 3 zy �-L4 If y y3 S3 5`I T5t w Ox 2(v z9 3a 7 GC g ors Mu cl= �c /iD ig '1 h `i 8 �ss s� s7 f 3, SY59Go tit S-6 c� 00 iIr ra y bS' 4G 33 3y 3 zz /d H y6 (e9 a. d- -Trbnz �nC to su r� aH x3o �S uj M � M Z � Lu M 0 0 K � r o LL 0 �.0'� cJ U) W 0 N t0 W C4 o • N w a>' m M \+ T 1L W U o Z m M 0 z W � �•.._ Q LL < D Z lij 0 Ow�_ U Q J w 11 U 1- V IL �••- w o V J J fo J w Q w cv U) J Z V_ c� C� Q m m W � z I-=- J � J U O z L-- Q W Z U J IL Q J L LJ -- ►� Q p U Z Q w 0 DC W _j W w DC DA`fE revision DATE I MARK I ISSUED DWG. BY — CHKD BY D 10/1710 JOB NO. 02 -263 FILE NO. cr. CA1.\1 SHEET E =5 OF 5 SHEET